2-Lamp Specification-grade 0-10V Dimming Ballast Specifications COOPER LIGHTING EL E C T R O N I C D I MM ING BA LLA ST S WIT H A NA LOG DIMMING CONTR OL (0-10V) FOR TWO (2) LAMP FIXTUR ES Cooper Controls Electronic Dimming Ballasts, powered by Fifth Light Technology, offer cost-effective, reliable dimming control for linear fluorescent lamps, down to 3% for T5/T5HO and T8 lamps. These multi-lamp ballasts cover two-lamp fixtures over a range of lamp types and lengths installed in Cooper Lighting fluorescent lighting fixtures. All of the ballasts have tightly regulated current control to the lamp, quick programmed rapid start circuits, active power factor correction and lamp end-of-life protection. When used in two-lamp fixtures, the ballast operates in parallel-lamp mode, where if one lamp fails, the other stays lit. In addition, the Specification Grade ballasts perform true parallel-lamp dimming, ensuring start-up, dimming, and cut-off of the lamps are tightly coordinated and regulated. The ballasts are ideal for direct integration with Cooper Controls solutions and compatible with a wide variety of analog controls and photocells. F E AT U R E S Ideal for use with 0-10V energy-management systems, daylight harvesting and local controls Programmed Rapid Start maximizes lamp life Helps meet energy codes, including ASHRAE 90.1 and California Title 24, when applied properly End-of-lamp-life Shutdown circuit with Auto-reset for safe, long-term operation Compatible with Energy-Saving and Low-Mercury Lamps Active Power-factor Correction for maximum energy savings 120-277V input for easy ordering and universal application Control inputs protected against mis-wiring with built-in line voltage protection Dimming Range: 3% for T5/T5HO and T8 Starts at any dimmed level without flashing S TA N D A R D S A N D LIST ING S cULus Listed (Class P, Type 1 Outdoor, Type CC) National Electrical Manufacturers Association (NEMA) Premium Rated Meets ANSI Standard C82.11 Meets FCC CFR 47 Part 18 for EMI and RFI Non-consumer limits Meets ANSI Standard C62.41 No PCBs Restriction of Hazardous Substances Directive (RoHS) Compliant Sound Rated, Class A Ballast must be grounded in accordance with national and local electrical codes Control can be wired as Class I or Class II Complies with Consortium for Energy Efficiency (CEE) standards P E R F O R M A N C E A ND ELECT RICA L CHA RA CT ERISTICS FOR ALL SINGLE-LAMP BALLASTS Minimum Dimming Temperature: 50°F (10°C). Energy Saving Lamps: 60°F (16°C) Minimum Starting Temp: 0°F (-18°C) Maximum Ambient Temperature: 104°F (40°C) Maximum Case Temperature: 167°F (75°C) Ballast Factor: 1.0 Power Factor: > .98 Crest Factor: < 1.7 Total Harmonic Distortion (THD): < 10% Start time: less than 700ms P E R F O R M A N C E A ND ELECT RICA L CHA RA CT ERISTICS BY LAMP TYP E Cooper Part Number FLT-232PSUNVS010-R1-C FLT-228PSUNVS010-R1-C FLT-254PSUNVS010-R1-C Lamp Type T8 T5 T5HO Specific Lamp Lamp Watt Lamp Length Lamp Operation Voltage Input Amps -120V Input Amps -277V BEF 120V BEF 277V T8 40 4 0.59 0.25 1.24 1.24 T8 32 4 0.47 0.2 1.53 1.53 T8 28 4 0.4 0.17 1.81 1.81 T8 25 3 0.36 0.15 2.02 2.02 T8 17 2 0.25 0.11 2.81 2.81 T8U 32 U 0.49 0.21 1.50 1.50 T8ES 32 (30) 4 0.44 0.19 1.61 1.61 T8ES 32 (25) 4 0.37 0.16 1.98 1.98 T5 28 4 0.55 0.23 1.59 1.59 T5 21 3 0.42 0.17 2.13 2.13 T5 14 2 0.29 0.12 3.03 3.03 T5ES 28 (26) 4 0.52 0.22 1.75 1.75 Parallel Parallel 120-277 120-277 T5ES 28 (25) 4 0.51 0.21 1.75 1.75 T5HO 54 4 0.94 0.41 0.89 0.89 FT55W 55 4 0.88 0.38 0.86 0.86 FC55T5HO 55 4 0.83 0.38 0.87 0.87 T5HOES 54 (49) 4 0.89 0.37 0.99 0.99 Parallel 120-277 Dimming Performance 3% 3% 3% ACF130942 8/5/14 2-Lamp Specification-grade 0-10V Dimming Ballast Specifications COOPER LIGHTING D I MMI N G C O N T R O L A P PLICAT IONS A ND SPECIFICAT IONS Use Purple (+) and Gray (-) for connection to 0-10VDC 0V = Minimum Light Output Wiring Purple and Gray together provides 3% light output Can be wired Class I or Class II Capping Purple and Gray separately provides 100% light output Ballast will source a maximum of 250µA for control needs Built-in line voltage protection: Minimum Light Output level will occur if line voltage is applied Control must be capable of sinking current supplied by ballast 10VDC = Maximum Light Output W I RI N G D I A G R A M Green (ground) Red White (neutral) Red Black (line) Yellow Ballast Yellow Purple (control +) Blue Gray (control -) Blue B ALLAS T D R AWI N G S 1.71 16.88 8.58 16.28 1.18 1.18 9.50 .26 8.90 14.58 1.25 1.00 ‘A’ BALLAST 1.18 ‘D’ BALLAST D I MMI N G C U R V E S Power 120% Light Output Power 120% Light Output 100% 100% 100% 80% 80% 80% 60% 60% 60% 40% 40% 40% 20% 20% 20% 0% 0% 0 1 2 3 4 5 6 7 8 9 10 Power 120% Light Output 0% 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 Control Voltage (VDC) Control Voltage (VDC) Control Voltage (VDC) T5 Dimming Curve T5HO Dimming Curve T8 Dimming Curve 7 8 9 10 WARRAN T Y A N D SU P P O RT INFORM AT ION Cooper Lighting warrants to the purchaser that each factory-installed electronic ballast will be free from defects in material or workmanship for a period of five (5) years from the date of manufacture when properly installed and under normal conditions of use. Call (800) 955-4946 or email ballast@cooperindustries.com for warranty information and support. Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Lighting Business 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.cooperlighting.com Specifications and dimensions subject to change without notice. ACF130942 8/5/14