REGF Constant Current Regulators - Ferroresonant

advertisement
Power & Control Equipment
REGF
Constant Current Regulators - Ferroresonant
Compliances:
FAA AC 150/5345-10: L-828
ICAO Aerodrome Design Manual, Part 5
Medium/15-20kW Unit
Applications
Ordering Information
The REGF Constant Current Regulator is designed to provide precision
control of runway lighting circuits.
The Ferroresonant core design runs
more efficienctly. The Ferroresonant
design also creates a cleaner sine
wave that functions to improve
communication on the power lines
and helps to prolong the life of the
lamps on the circuit. The equipment
can be supplied with a wide range
of control and monitoring options.
Regulator Type:
F = Ferroresonant
These regulators are air cooled and
designed for indoor service.
Cabinet Size:
1 = Mid-Size
Features
Input Voltage:
208 = 208 V, 60 Hz
220 = 220 V, 60 Hz
240 = 240 V, 60 Hz
480 = 480 V, 60 Hz
ƒ ETL Certified
ƒ Low Total Harmonic Distortion
(THD)<10%
ƒ Clean output sinusodial wave form
ƒ Stackable design (2 High Max)
ƒ Soft On/Off
ƒ Air cooled
ƒ Ferroresonant Design
ƒ Built-in digital ammeter
(0.5% accuracy)
ƒ Regulation ±1% over 0 to 100%
load and +10% to -5% line
voltage with no tap changes
ƒ On-off switching under load
ƒ Lightning and transient protection:
input and output lines
ƒ Efficiency – 90% minimum
(High step, fully loaded)
ƒ High power factor .99
(High step, fully loaded)
ƒ Remote reset capability
ƒ Output current maintained
with 30% open isolation
transformer secondaries
ƒ Open circuit protection
ƒ Over current protection
ƒ 10,000 feet remote control
@ 120V
ƒ Temperature – 40°C to +55°C
ƒ Single control board for all sizes
ƒ Rotary switch for step-control
ƒ Field selectable brightness
steps (1, 3, 5)
ƒ Hinged front door with handle
4.4
8 2 8 6 0 F 1 -
-
-
-
CCR Type:
8 = L - 828
Frequency:
60 = 60Hz
Kilowatt Rating:
15 = 15 kW, 6.6A
20 = 20 kW, 6.6A
16 = 15 kW, 20A
21 = 20 kW, 20A
Output Brightness Steps:
1 = 1 Step (5.5A) - 6.6A units only
3 = 3 Step
5 = 5 Step
Options:
B = Integral circuit breaker
C = Computer ready interface*
CA = Intergral S-1 Cutout, Integral circuit breaker, Green/Yellow Grounding
Wires per Canadian Electrical Standards
D = Digitrac™ computerized control and monitoring system
(Includes option C)
M2 = Integral Megatrac earth leak detector (includes option S2)**
S2 = Integral S-1 Cutout
S506A = Load Volts Metering**
V = DC Remote Control, internally supplied (24, 48 & 60 VDC)
* Includes potential and current transformers and relay contacts for indication of
loss of input power and local/remote control.
** Regulator cannot be ordered with both M2 and S506A options.
Standard remote control voltage is 120 VAC.
www.crouse-hinds.com/airportlighting
Outline Drawing
CONSTANT CURRENT REGULATOR
SINGLE PHASE
PowerTrac
IDENTIFICATION:
INPUT:
FAA L-829
Hz,
VOLTS,
OUTPUT:
A@
KW
Hz
KW @ 6.6A
BRIGHTNESS STEPS
OFF
TM
FAA L-828
VOLTS,
CONTROL:
REMOTE
OUTPUT CURRENT
3
5
4.8, 5.5, 6.6A
2.8, 3.4, 4.1, 5.2, 6.6A
1
PART NUMBER
2
LOCAL
CONTROL
SWITCH
WINDSOR, CT U.S.A.
SERIAL NUMBER
3
5
4
!
DANGER
HIGH VOLTAGE PRESENT INSIDE CABINET
WHEN THE REGULATOR IS ENERGIZED
39.75
(1009.6)
30.0
(762)
25.0
(635)
Technical Data
Power Factor/Efficiency Data
(100% load/20kw)
Dimensions:
Inches
(mm)
Instruction Manual:
2334
Shipping Weight:
15kW
860 lbs.
390 kg.
20kW
1070 lbs.
485 kg.
13.8 cu.ft.
0.39 cu.m.
13.8 cu.ft.
0.39 cu.m.
5 - Brightness Step CCR
Step (output)
Power Factor
Efficiency%
B5 (6.6A)
0.99
91%
B4 (5.2A)
0.98
90%
B3 (4.1A)
0.98
89%
B2 (3.4A)
0.91
87%
B1 (2.8 A)
0.71
84%
Shipping Volume:
Renewal Parts
Description
Part Number
Description
Part Number
15 PIN Cable Assembly
Capacitor, 50uF, 660 VAC
Kl Contactor, 95A
Kl Contactor, 120A
Switch Display printed circuit card
Fuse 1A, 5 x 50 mm
Fuse 125MA, 5 x 20 mm
Fuse 2A, 5 x 20 mm
Interconnect P.C. Board
LA1 Lighting Arrestor
34070
32990
32084
32085
32752
10047-2890
10047-2889
10047-2920
34054-1
10047-885
Lighting Arrestor, 3kv (6.6A CCR)
Lighting Arrestor, 6kv (6.6A CCR)
Main printed circuit card, 120 VAC internal
control voltage
Main printed circuit card,
for use with Option V
Display/Switch Ribbon Cable
K2 Solid State Relay & Thermal Pad
Switch knob
RVI Varistor
10053-703
10053-704
Home Office: United States – +1 860-683-4300
International Offices: Canada • China • Dubai • Mexico • Brazil
34031-1
34031-1V
10047-2826
34207
10041-31
10047-1297
4.5