Document Revision June 25, 2012 2501 F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Serial Number 300 and Higher Cooper Industries Crouse-Hinds Division Crouse-Hinds Airport Lighting 1200 Kennedy Road Windsor, CT 06095 Copyright © 2012 Cooper Technologies Company For Parts or Technical Service Call (860) 683-4300 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 1 Configuration Record The following information is specific to the equipment describes as shipped from the factory and should be retained. It should be provided when contacting the factory about this equipment for any reason. Constant Current Regulator, FAA Type Manufacturer’s Part Number Serial Number Date of Manufacture Factory Installed Options Option/Part Number Description ii Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 2 Revisions Revision Number A B Issue/Reissue Letter Number A205-33 A206-176 C D A206-243 A207-034 E A207-120 F A212-134 Description Initial Issue Cover page, added copyright; Figure 1, revised V option description & deleted options S & M and added options S2, S3, M2 & M3; 6.2.3.2, added input fuse info and Warning & notice sections; 7.1.5.3, F2 was 1A Slo-Blo; Figure 11 & 11b, 34031 F2 was 1A Slo-Blo; 10.1, item 11, deleted F2 and added items 12 & 13; Figure 8, P/N 10047-2789 was 100472787 and added P/N 10047-2937 6.2.3.1 spec 150/5345-10F was -10E Figure 1, deleted option S3 & M3; title page, revised copyright to 2007 Revised revision on all pages to read E, no other changes Title page, updated copyright; Figures 2, 3 & 7, updated door latch pictorial & P/N, was 10037-831 iii Checked 3-25-05 6/26/06 Approved TB PG 7/11/06 2/12/07 PG PG 2/12/07 PG 6/25/12 PG Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 3 Limited Product Warranty THE FOLLOWING WARRANTY IS EXCLUSIVE AN IN LIEU OF ALL OTHER WARRANTIES, WHETHER EXPRESS, IMPLIED OR STATUTORY, INCLUDING, BUT NOT BY WAY OF LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE. Crouse-Hinds Airport Lighting Products (the “Company”) warrants each original Buyer of Products Manufactured by the Company that such Products are, at the time of delivery to the Buyer free of material and workmanship defects, provided that no warranty is made with respect to: (a) any Product which has been repaired or altered in such a way, in Company’s judgement, as to affect the Product adversely; (b) any Product which has in Company’s judgment, been subject to negligence, accident or improper storage ; (c) any Product which has not been operated and maintained in accordance with normal practice and in conformity with recommendations and published specifications of company; and, (d) any Products, component parts or accessories manufactured by others but supplied by Company (any claims should be submitted directly to the manufacturer thereof). Crouse-Hinds Airport Lighting Products’ obligation under this warranty is limited to use reasonable efforts to repair or, at its option, replace, during normal business hours at any authorized service facility of Company, any Products which in its judgement proved not to be as warranted within the applicable warranty period. All cost of transportation of Products claimed not to be as warranted and of repaired or replacement Products to or from such service facility shall be borne by Purchaser. Company may require the return of any Product claimed not to be as warranted to one of its facilities as designed by Company, transportation prepaid by Purchaser, to establish a claim under this warranty. The cost of labor for installing a repaired or replacement product shall be borne by Purchaser. Replacement parts provided warranty period of the Products upon which they are installed to the same extent as if such parts were original components thereof. Warranty services provided under the Agreement do not assure uninterrupted operations of Products; Company does not assume any liability for damages caused by any delays involving warranty service. The warranty period for the Products is 24 months from date of shipment or 12 months from date of first use whichever occurs first. iv Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 4 Safety Notices This equipment is normally used or connected to circuits that may employ voltages which are dangerous and may be fatal if accidentally contacted by operating or maintenance personnel. Extreme caution should be exercised when working with this equipment. While practical safety precautions have been incorporated in this equipment, the following rules must be strictly observed: 4.1 KEEP AWAY FROM LIVE CIRCUITS Operating and maintenance personnel must at all times observe all safety regulations. DO NOT PERFORM MAINTENANCE ON INTERNAL COMPONENTS FOR RELAMP WITH POWER ON. 4.2 STORED ENGERGY Ensure capacitors are discharged before working on equipment 4.3 RESUSCITATION Maintenance personnel should familiarize themselves with the technique for resuscitation found in widely published manuals of first aid instruction. v Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 4.4 SAFETY SYMBOLS DANGER: DANGER The hazard or unsafe practice will result in severe injury or death. WARNING: WARNING The hazard or unsafe practice could result in severe injury or death. CAUTION: CAUTION The hazard or unsafe practice could result in minor injury or death. NOTICE: NOTICE Possibly dangerous situation, goods might be damaged. IMPORTANT: IMPORTANT Helpful information. vi Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 5 Table of Contents Title Page ......................................................................................................................................... i 1.0 Configuration Record................................................................................................................ ii 2.0 Revisions .................................................................................................................................. iii 3.0 Limited Product Warranty ....................................................................................................... iv 4.0 Safety Notices ............................................................................................................................v 5.0 Table of Contents .................................................................................................................... vii 6.0 General Information ...................................................................................................................1 6.1 Introduction .........................................................................................................................1 6.2 Equipment Description .......................................................................................................1 6.3 Installation Requirements ...................................................................................................4 7.0 Technical Description ................................................................................................................6 7.1 Theory of Operation ...........................................................................................................6 8.0 Installation and Operation ..........................................................................................................9 8.1 Installation ..........................................................................................................................9 8.2 Operation ............................................................................................................................4 9.0 Maintenance .............................................................................................................................25 9.1 Periodic Maintenance .......................................................................................................25 9.2 Corrective Maintenance ...................................................................................................25 9.3 Problem Solving Guide ....................................................................................................26 10.0 Spare Parts List ......................................................................................................................42 10.1 Scope Figures Figure 1 – Catalog Number Breakdown ..........................................................................................5 Figure 2 - CCR Front View ..........................................................................................................15 Figure 3 – CCR right Side Exterior View ......................................................................................16 Figure 4 – CCR Right Side Interior View .....................................................................................17 Figure 5 – CCR Top View .............................................................................................................18 Figure 6 – CCR Rear View ............................................................................................................19 Figure 7 – CCR Stacking ...............................................................................................................20 Figure 8 – Main Transformer with Component Panel ...................................................................21 Figure 9 – CCR Interior Door ........................................................................................................22 Figure 10 – Remote Control Connections by Customer ................................................................23 Figure 11 – CCR Wiring Diagram .................................................................................................28 Figure 11a – CCR Wiring Diagram (Partial Expanded) ................................................................29 Figure 11b – CCR Wiring Diagram (Partial Expanded) ................................................................30 Figure 12 – 34031 S1 DIP Switch Configuration ..........................................................................31 vii Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 6 General Information 6.1 Introduction 6.1.1 Purpose This instruction manual provides information for installing and maintaining FAA Type L-828 Constant Current Regulators manufactured by Crouse-Hinds Airport Lighting Products, Windsor, Connecticut 06095, U.S.A. 6.1.2 Applicability Only 4, 7.5, and 10kW regulators bearing Crouse-Hinds catalog number series 828x0F, serial number 300 and higher are covered by this manual. Refer to Figure 1 for complete part number information. Instructions for standard options are provided as supplements to this manual. 6.2 Equipment Description 6.2.1 Features The Constant Current Regulator is a power supply designed for precision operation of airfield lighting. The output current is regulated within +/-1% at any load and for line voltages from +10% to –5% of nominal. The three or five discrete brightness steps conform to FAA standards. The regulator may be controlled both locally and from a remote location. Protective circuits are provided to sense an overcurrent or an open circuit in the series lighting loop and shutdown the regulator. The front panel display alerts maintenance personnel to the nature of the shutdown. The protective circuitry can be reset by setting the regulator control switch to off for 1 second. Provided no fault condition remains, setting the control switch to the desired brightness step will restore operation. The regulator may be connected directly to an FAA approved load switching device. No regulator malfunction or damage to the series lighting loop will occur. 6.2.2 Options This regulator can be factory supplied with various options. See Figure 1 for a list of options. 1 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 6.2.3 Specification 6.2.3.1 FAA Classification Specification: Constant Current Regulator manufactured and qualified to FAA Advisory Circular 150/5345-10F Type: L-828 Regulator Class: 1 – 6.6 amperes output current Style: 1 – 3 Brightness Steps: 4.8, 5.5, 6.6 amperes 2 – 5 Brightness Steps: 2.8, 3.4, 4.1, 5.2, 6.6 amperes Ratings: Sizes – 4kW, 7.5kW, 10kW Voltages – 208VAC 50/60 Hz, 220VAC 50/60Hz, 240VAC 50/60Hz, 380VAC 50Hz, 480 VAC 60Hz 6.2.3.2 Electrical Characteristics Primary Power: Refer to Table 1 for ampacity information based on regulator size and line voltage. Remote Control Power: (a) Internal Supply – 120VAC, Standard (Other voltages optional) (b) External Supply – 120VAC, Standard (Other voltages optional) Recommended Input Power Fuse Sizes (not provided) CCR Input Voltage CCR kW Rating 4kW 208 VAC 220 VAC 240 VAC 480 VAC 30A, 250V 25A, 250V 25A, 250V 12A, 250V 7.5kW 50A, 250V 50A, 250V 45A, 250V 25A, 250V 10kW 70A, 250v 70A, 250V 60A, 250V 30A, 250V 2 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes NOTICE: Condition Limits NOTICE Total CCR load shall not exceed the rated load on the nameplate, at installation and subsequent load changes. WARNING: WARNING Running the CCR for long periods of time while overloaded may cause damage to the regulator. 3 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 6.2.3.3 Physical Characteristics Dimensions: Refer to Outline Drawings, Figures 2 – 5 Weight 4 kW – 490 lbs. 7.5kW – 581 lbs. 10kW – 711 lbs. Mechanical: The regulator has a vented steel enclosure painted blue. Upon opening the door, locate K1 contactor to make input line connections. Output lighting arrestors located on the right side of the door are used to make load connections. The electronic control board is located on the interior of the door. The remote control terminal block also plugs directly into the control board. The CCR is designed to allow easy access to other customer serviceable parts. The main transformer is an air-cooled ferroresonant type. Environmental: Temperature: 6.3 -40 degrees C to +55 degrees C (-40 degrees F to +131 degrees F) Relative Humidity: 10 percent to 95 percent Altitude: Zero to 6,600 feet (2000 m) Installation Requirements The regulator is shipped from the factory complete and ready to install. The agency responsible for installation must supply all necessary connectors, wire and conduit. The regulator is for indoor use only. It must be floor mounted. If stacked, units need to be bolted together and bottom unit must be bolted to the floor. Caution – Exterior metal surfaces may exceed 120ºF (49ºC) when regulator is operated at full power for more than 10 hours. 4 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes EXAMPLE: 82860-F1-240-10-5 is a 10KW L-828 Regulator with 240V, 60 Hz input and 6.6A output. It has five brightness steps. Ordering Information 8 2 8 0 F - - - - FAA Type: 8 = L-828 Frequency: 5 = 50Hz 6 = 60 Hz Regulator Type: F = Ferroresonant Input Voltage: 208 = 208 V, 50 or 60 Hz 220 = 220 V, 50 or 60 Hz 240 = 240 V, 50 or 60 Hz 380 = 380 V, 50 Hz 480 = 480 V, 60 Hz Kilowatt Rating: 04 = 4kw 07 = 7.5kW 10 = 10kW Output Brightness Steps: * 1 = 1 Step (5.5A) 3 = 3 Step (4.8, 5.5 &6.6A) 5 = 5 Step (2.8, 3.4, 4.1, 5.2, & 6.6A) * = 6.6A Output Units Only Options: B = Integral circuit breaker S2 = Integral Model 2 S-1 cutout C = Computer ready interface** D = Digitrac™ computerized control and monitoring system (Includes option C) M2 = Megatrac™ integral earth leakage detector (includes option S2) V = 24, 48 & 60 VDC control voltage Standard remote control voltage is 120 VAC, 50/60 Hz ** Potential & Current transformer included, circuit board with relay contacts for loss of input power and local /remote control Figure 1 Catalog Number Breakdown 5 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 7 Technical Description 7.1 Theory of Operation (Basic Regulator) The information presented here applies to a standard model Constant Current Regulator (CCR). Regulators supplied with options may have minor operating differences, but the basic operation is the same for all units. Many functions in the CCR are controlled by a custom programmed electronic circuit. This device performs brightness step and digital display control, open circuit and over-current sensing, and handles system fault conditions. Several optional features also use the programmed circuit to reduce the amount of additional circuitry required. Each of the standard functions is discussed in detail in the following paragraphs. Optional functions are discussed in Supplemental sections of this manual. 7.1.1 Current Regulation A power transformer in conjunction with a Solid State Relay (SSR) is used for current regulation. This design provides precise control regardless of the load size or line voltage. For very low loads or low brightness settings, the on-time of the SSR will be large. At increased loads or higher brightness settings, the on-time will be lesser. The SSR is controlled using closed-loop electronic feedback control. Load current is sensed by a current transformer which generates an analog signal. The signal is processed by an electronic circuit and compared to a predetermined reference. The result is a pulse width modulated control signal. This control signal is applied to the coil of the SSR. 7.1.2 Brightness Control Each brightness step has a specific digital reference value store in electronic memory. When the desired step is selected by the rotary switch, the proper memory value is converted to an analog signal. This signal is the reference used for comparison as discussed in paragraph 7.1.1. All remote brightness connections are electrically isolated from the control electronics by optocouplers for transient protection. 6 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 7.1.3 Remote Control Operation The regulator can operate remotely using external switches connected to the remote control terminal block TB1. The exact wiring of these switches depends upon whether control power is obtained from the regulator internal supply or from an external source. The regulator turns on to brightness B1 (or B10 or ON) when control power is applied to terminal CC and B1 (B10). To get a higher brightness, control power is applied to terminal B2, B3, B4 or B5. (For three-step regulators, apply control power to B30 or B100, for one-step regulators, apply control power to on). Only the terminal for the desired step and CC require control power. If two or more steps are energized together, the regulator will operate at the highest brightness step selected. 7.1.4 Digital Display A multi-purpose Digital Display provides system operation data. Under normal conditions, the display shows the output current being supplied by the CCR. Under power-up and the system fault conditions, it displays specific CCR status data. 7.1.5 Protective System 7.1.5.1 Overcurrent Protection Overcurrent protection is triggered by comparison of the value of the feedback signal to predetermined limits. In the event of a minor overcurrent (between 5% and 25% above rated output), the control system responds within 5 seconds. If a major overcurrent (greater than 25% above rated output), occurs, the control system responds immediately. The response consists of de-energizing the load by opening the main contactor and providing status data to the digital display. To reset and re-energize the CCR, the rotary switch or remote brightness control switch must be set to OFF for at least one second. 7.1.5.2 Open –Circuited Load Protection This protection is triggered by comparison of the value of the feedback signal to a minimum current level. If the current remains below 2 amps for about 2 seconds, the control system performs the same shutdown sequence as for overcurrent protection. 7 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 7.1.5.3 Fuses Fuse Designator F1 F2 F3 F4 F201 F202 Location Purpose 34031 Circuit Board Remote Control CC Fuse 34031 Circuit Board Main DC Power Supply Fuse 34031 Circuit Board Reference Voltage Fuse 34031 Circuit Board Remote Control Neutral Fuse 34054 Interface Board 120 VAC Control Fuse 34054 Interface Board 120 VAC Option Fuse See Spare Parts List for details in Section 10. Size 1/8A Slo-Blo 2A Slo-Blo 1/8A Slo-Blo 1/8A Slo-Blo 1A Slo-Blo 1A Slo-Blo 7.1.5.4 Transient Protection Protection against transients from lighting or other sources is provided. Lighting arrestor LA1 protects the regulator power lines. Arrestors LA2 and LA3 protect the regulator load lines. Varistors are provided on the control system assembly to protect it from transients on the power and control lines. The lighting protection provided exceeds the requirements of the applicable Advisory Circular. Lighting is a naturally occurring phenomenon that varies in intensity and frequency based upon geographic location. Therefore, each installation should be evaluated to determine the need for additional lighting protection. 7.1.6 System Status Information The CCR Digital Display is used during power-up and fault conditions to provide data regarding system status. 7.1.6.1 Power-Up When power is applied to the CCR and when resetting from a latched fault mode, the control electronics performs a series of internal checks. If these are completed without incident, the control program number will be displayed for one second. The display will then begin to indicate CCR output current. If any check is not successfully completed, the system will “lock-up” and not allow the regulator to come on in any step. Cycle power to recover. 8 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 7.1.6.2 Fault Status Message If the CCR control circuits detect an abnormal system shutdown, a message will automatically scroll across the display. When two or more fault conditions exist, the most recent occurrence is displayed. Messages are cleared when the system is reset or conditions return to normal. Refer to the Operations Section 8.2 for information on specific messages. 8 Installation and Operation WARNING INSTALLATION, SERVICE, MAINTENANCE OR OPERATION SHOULD BE PERFORMED BY QUALIFIED PERSONNEL ONLY. 8.1 Installation The Constant Current Regulator is supplied ready for operation with all ordered options installed. When properly connected, no electrical adjustment other than noted in this section should be necessary before use. 8.1.1 Location The regulator is designed for indoor locations meeting the environment specified in Section 6.2.3.3. The area should be clean and dry, protected from rain, snow, dust, etc., and have adequate ventilation. The equipment should be accessible to qualified personnel only. 8.1.2 Installation Drawings Typical details and dimensions are provided in Figures 2 thru 10. 9 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 8.1.3 Step Configuration The CCR will be shipped configured the way it was ordered. Three steps are required if the number of steps must be changed in the field. 1. Set switch S1 on the control board 34031 to the settings in Figure 12 corresponding to the desired number of steps. 2. Change the rotary switch label plate as described in Figure 2. Order the correct plate if required. 3. Change the number of rotary switch positions by removing the knob and switch. Be careful not to loose the stop which is just behind the front panel. After removing the switch, change the stop location as follows. Looking at the shaft find the location tab that sticks through the front panel for alignment. Count that location as 1. Count clockwise from the location tab 7 positions for a 1-step regulator, 8 positions for a 3-step regulator, and 11 positions for a 5-step regulator. Place the stop in that position and reinstall switch and knob 8.1.4 Recommended Installation and Maintenance Tools The following tools are recommended for installation and maintenance. 1. True RMS amp meter. This must be a true RMS reading meter such as a Fluke 189 and a Fluke 80I-600A or equivalent. 2. Vacuum cleaner for cleaning debris from installation and during regulator maintenance. Avoid compress air since it can force debris into places where damage can occur. 3. Lock-out/Tag-out as required. 4. Tools to install conduit and cable to supply power to CCR. 5. Airfield wire and connector kits to make connections between CCR output and airfield circuit. 10 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 8.1.5 Power Requirements Table 1 list the line current requirements for the different CCR power and voltage ratings. It is recommended that the distribution circuit breaker or fuses be sized to carry 125% of the rated circuit. Table 1 Power Requirements Rated Input Voltage 208 220 240 380 480 8.1.6 4kW 21 20 18 12 9 Rated Input Current (RMS Amperes) 7.5kW 10kW 40 53 38 50 34 46 22 29 17 23 Cable and Conduit Do not locate line and load cables near sensitive control, radar, or communications lines. For cable entrance locations, see Figure 5. 8.1.7 Installation Check List Read these instructions before attempting installation. 1. Improper installation can damage this regulator and may void the warranty! If the equipment fails to perform properly at any step of this procedure, consult the troubleshooting guide in Section 9. Call Crouse-Hinds Airport Lighting Products (860) 683-4300 if further information is required during installation. 2. Instructions for each equipment option included should also be read before proceeding with installation 3. SUGGESTION: completed. To stay organized, make a check mark next to each step as it is 11 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 8.1.7.1 Mechanical Installation 1. Unpack the Constant Current Regulator, and check for any shipping damage. 2. For handling, a 2” forklift clearance is provided underneath the unit and 2 lifting lugs are provided. The regulator should be in place before lifting. 3. Refer to Figures 2 thru 7 for mechanical installation details. Adequate clearance should be left around the regulator for accessing and cooling. Maintain 1-foot clearance between cabinet and rear wall. 8.1.7.2 Power Wiring and Check out 1. Connect the ground conductor to the equipment ground terminal. It is located on the lower right side toward the front of the regulator. CAUTION: DO NOT CONNECT COUNTERPOISE SYSTEM TO THIS TERMINAL. 2. Verify that the line voltage is the same as the regulator nameplate voltage rating. This is very important. CONNECTION TO THE WRONG LINE VOLTAGE MAY VOID THE WARRANTY. 3. See Figure 5 for conduit knockout locations. 4. Connect the line voltage source K1 contactor line side terminals. Torque lugs to 60in – lbs. (6.78 N-m) 5. Connect the series lighting circuit to the output lighting arrestor, LA2 and LA3. CAUTION: DO NOT MEGGER TEST THE SERIES LIGHTING LOAD WHILE IT IS CONNECTED TO THE REGULAOR. 12 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 6. Before connecting remote control lines, check regulator operation using the rotary switch on the front panel. Follow steps A-C below. NOTICE: The regulator is equipped with a safety interlock switch so that when the door is opened, the regulator will de-energize. Be sure that the interlock switch is in its normal operating position before operating. A. Apply main power to the regulator B. Operate the regulator at all brightness steps and check the load current levels are correct. See regulator nameplate for load current levels. IMPORTANT – ONLY A TRUE RMS INSTRUMENT CAN ACCURATELY MEASURE THE REGULATOR OUTPUT EXTERNALLY. OTHER INSTRUMENTS WILL PROVIDE IMPROPER READINGS. C. Shut off main power to the regulator. 8.1.7.3 Control Wiring and Checkout 1. Connect remote control lines to terminal block TB1 located on the 34031 Control Board using the appropriate wiring diagram. Refer to Figures 9, 10, and 11. The regulator is shipped configured for internally supplied remote control power. Jumpers E4 through E9 must be removed if external control power is used. CAUTION: INCORRECT WIRING CAN CAUSE MALFUNCTION OR DAMAGE TO THE CONTROL SYSTEM AND POSSIBLY VOID THE EQUIPMENT WARRANTY. RECHECK THESE CONNECTIONS BEFORE OPERATING. 2. Make final operation check using local and remote modes. Steps A-C below. A. Apply main power to the regulator B. Operate the regulator in the local mode at all brightness steps and check for the correct current levels. C. Operate the regulator in the Remote mode at all brightness steps and check for correct current levels. 13 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 8.1.7.4 Final Installation Steps 1. Make any option related connections discussed in the option supplements. 2. Check that all cables and wiring are dressed within the cabinet. Reinstall all covers. 14 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes CONSTANT CURRENT REGULATOR SINGLE PHASE PowerTrac IDENTIFICATION: INPUT: FAA L-829 A@ KW Hz KW @ 6.6A BRIGHTNESS STEPS OFF Hz, VOLTS, OUTPUT: REMOTE TM FAA L-828 VOLTS, CONTROL: 3 5 OUTPUT CURRENT 4.8, 5.5, 6.6A 2.8, 3.4, 4.1, 5.2, 6.6A 1 PART NUMBER 2 LOCAL CONTROL SWITCH SERIAL NUMBER WINDSOR, CT U.S.A. 3 5 4 ! DANGER HIGH VOLTAGE PRESENT INSIDE CABINET WHEN THE REGULATOR IS ENERGIZED Figure 2 15 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Figure 3 16 Document 2501 Rev. F C1 WARNING DISCHARGE CAPACITORS BEFORE HANDLING Figure 4 17 TB3 CAP1 CAP2 Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes INT GND Figure 5 18 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Figure 6 19 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Figure 7 20 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes K2 T3 T2 INPUT GND INPUT RV1 E1 LA1 T4 TB2 K1 T5 E2 T6 T1 LA3 LA3 OUTPUT LA2 OUTPUT LA2 Figure 8 21 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 34031-1 TB1 N CCI CC B1/B10/0N B2/B30 B3/B100 B4 B5 B6 10 11 12 REMOTE CONTROL TERMINAL BLOCK DOOR GND Figure 9 22 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Figure 10 23 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 8.2 Operation Figure 2 shows the standard controls and indicators on the front control panel. 8.2.1 Local Control Rotary Switch The local control rotary switch in conjunction with the digital display acts as an interactive control terminal for commanding the regulator into local brightness steps or to place it into remote control mode. 8.2.2 Digital Display During normal operation, the digital display functions as a True RMS ammeter, displaying the regulator load current. During power-up, under system fault conditions the display performs other functions. When these other functions are finished using the display, it automatically returns to reading load current. When power is initially applied to the regulator, the computer performs checks for valid operation. If these checks are completed successfully, the display will read “P-X.X.”, where X.X is the software program version number, for a period of 1 second. The normal display activity will begin. If the regulator should shut down due to system fault, a message will immediately begin to scroll across the display to explain the reason for the shut down. See Section 9 for further information. 8.2.3 System Fault Display If a regulator shutdown occurs, you can find out what happened by reading the display: “HIGH LOAD CURRENT” – Overcurrent protection trip. “LOOP” – Open Load protection trip. 24 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 9 Maintenance WARNING INSTALLATION, SERVICE, MAINTENANCE OR OPERATION SHOULD BE PERFORMED BY QUALIFIED PERSONNEL ONLY. 9.1 Periodic Maintenance The Constant Current Regulator should be inspected periodically as shown below: Interval Procedure 1. Remove main power from the regulator. 2. Open the front door 3. Check all wiring connection for loose connections and tighten as necessary. 4. Check for broker or damaged wires and parts. 6 months 5. Remove dust build – up. 6. Inspect housing for rust or chipped paint. Clean and touch up with paint as required. 7. Close door. 8. Restore primary power to the regulator. Operate the regulator at all brightness steps, first by local control, then by remote control. Check for proper load currents. 9.2 Corrective Maintenance Corrective maintenance is required when the regulator does not work properly. This usually requires the replacement of parts or subassemblies. The use of easily removable subassemblies make repairs a simple task. The removal and replacement method should be obvious to qualified personnel. 25 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes WARNING VOLTAGES ABOVE 1000 VOLTS ARE PRESENT WHEN THE REGULATOR IS OPERATING. DO NOT REPAIR OR SERVICE WITHOUT FIRST REMOVING POWER FROM THE REGULATOR. THE USE OF LOCK-OUT DEVICES IS RECOMMENDED. ENERGY MAY BE STORED IN CAPACITORS. DISCHARGE CAPACITORS BEFORE WORKING ON THEM. REGULATORS WITH REMOTE CONTROL MAY HAVE POWER COMING ON THE REMOTE CONTROL LINES EVEN WHEN THE CCR IS OFF. AIRFIELD CIRCUITS MAY BE ENERGIZED BY OTHER SOURCES. CHECK FOR VOLTAGE BETWEEN OUTPUT TERMINALS AND FROM OUTPUT TERMINALS TO GROUND BEFORE WORKING ON AIRFIELD CIRCUIT. The control assembly contains parts which can be replaced in the field by a service person. If properly trained personnel are not available, replace the entire control assembly. Improper removal and handling can cause damage to the equipment. Particular areas of concern are: A. Remove power from the regulator before disconnecting the connector plugs from the control board. B. Note connections of terminal block connectors when replacing them back onto the control board. CAUTION: THE CIRCUIT CARDS WITHIN THE CONTROL ASSEMBLY ARE STATIC SENSITIVE. DO NOT REMOVE OR HANDLE THEM WITHOUTHT A STATIC CONTROL WRIST STRAP. 9.3 Problem Solving Guide This guide will assist qualified airport maintenance personnel in locating and correcting equipment failures. Problems associated with option functions are addressed in the specific option Supplement. If further assistance is required, contact the Customer Service Department at CrouseHinds Airport Lighting Products, Windsor, Connecticut. (Reference Figure 11 Wiring Diagram) 26 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 9.3.1 Fault Isolation The first step in fault isolation is the preliminary evaluation. Start by checking for disconnected wires, switches in the wrong position, blown or missing fuses, etc. Determine if other equipment on the same circuit is operating properly. Be sure that the equipment is being used properly by checking the operation instructions. Finally, if the digital display is working, use the displayed message to localize the problem. If these checks do not pinpoint the problem, try operating the regulator with a short across the load terminals. OPERATING INTO A SHORT WILL NOT HARM THE REGULATOR. This is the best way to find out if the problem is with the regulator or the load circuit. Once these checks have been made, refer to the checklist for further instructions. 27 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Figure 11 – CCR Wiring Diagram See following pages for expanded view 28 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 29 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 30 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes Figure 12 31 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 9.3.1.2 DISPLAY MESSAGES AND WHAT THEY MEAN DISPLAY MESSAGE WHAT IT MEANS ‘P-X.X’ (where X.X is a number like 1.1) This is the indication that all power up checks are OK. The number is the program version. This should appear for 1 second. ‘High Load Current’ The regulator has tripped off-line due to an over current condition. See the section of protection problems to fix. ‘LOOP’ The regulator has tripped off-line due to an open circuit condition. Try operating the regulator into a short circuit. If it doesn’t trip again, check the field wiring for an open. If no open is found, or the unit trips even with a short circuit see the section on protection problems. Display shows some other readable Message. See the option supplement to find out what the message means. Display shows a bunch of funny things or See the section on display problems. garbage. 32 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes QUICK PROBLEM SOLVING CHECKLIST SYMPTOM 1. 2. System will not turn on. 3. Control display OFF. 4. System will not turn Control display is ON. on. WHAT TO DO Check power source turned on. Check for 120 VAC across X1 and X2 on transformer T2. It is probably bad. Check F2. If good, see the section on power supply problems. Check door interlock switch. 1. If display reads ‘0.00’ see the section on local control problem. 2. See the section on digital problems. System will not turn off 1. See section on local control problems. 2. See section on remote control problems. System turn on for 1 to 5 seconds, then trips out. 1. If display reads ‘LOOP’ or “High load current” see section on protection problems. 2. See section on digital problems. System works fine in Local but 1. See section on remote control problems. does not work in remote. 1. Check for overload. Check for overload by shorting the output terminals either with a shorting wire that will handle the CCR output current or by pulling the S1 handle if installed. If the regulator outputs appropriate step current in Wrong current levels in any or all steps, then the airfield circuit is probably overloading the all steps. CCR. 2. If problem is only in remote see section of remote control problems. 3. Otherwise, see section on regulation problems. Regulator works but display is 1. See section on display problems. out or showing ‘funny’ data. 33 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 9.3.2 Detail Problem Solving Guide On the next few pages are detailed problem solving guides. These guides make use of the digital display and the indicators on the control box circuit card to speed repair. 9.3.2.1 Opening the CCR CAUTION: TURN OFF MAIN POWER TO THE REGULATOR BEFORE STARTING. To open the regulator, turn the door latch to the left. Override the interlock switch by pulling the interlock located in the top right corner of the unit. Turn on main power to the regulator to begin trouble-shooting. DANGER: BE CAREFUL! THE CIRCUITS INSIDE AND AROUND THE CABINET INTERIOR ARE ENERGIZED AND CONTAINED DANGEROUS CURRENT LEVELS. 9.3.2.2 Circuit Card Indicators Before doing any problem solving, take a few minutes to become familiar with the circuit card indicators. They are provided as an aid in deciding what part or subassembly to change. Now go to the detail checklist for the problem being addressed. 34 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes The following is a list of the indicators and their function: Designator DS1 Name +5V Description Indicates +5V is available. DS2 +12V Indicates +12V is available. DS3 -12V Indicates –12V is available. DS4 Unreg Indicates unregulated power is available for 5V and +/-12V regulators DS5 Contactor Indicates contactor is energized DS6 Remote Indicates rotary switch is in remote position. DS7 Run Indicates the CPU is running when on constantly. There is a CPU problem if it is off or flashing. DS8 Halt Indicates the CPU is running when off constantly. There is a CPU problem if it is off or flashing. DS9 Sync Indicates the control is receiving a 60Hz signal from the power transformer. DS10 Feedback Indicates the control is receiving a feedback signal from the output current transformer. The following LEDs indicate the associated relay is energized. DS11 Relay1 Indicates the board is in remote mode. DS12 Relay2 Indicates the CCR has input power. DS13 Relay3 Indicates the CCR is outputting current. DS14 Relay4 Indicates the CCR is outputting current in step 1. DS15 Relay5 Indicates the CCR is outputting current in step 2. DS16 Relay6 Indicates the CCR is outputting current in step 3. DS17 Relay7 Indicates the CCR is outputting current in step 4. DS18 Relay8 Indicates the CCR is outputting current in step 5. 35 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes POWER SUPPLY PROBLEM CHECKLIST SYMPTON All board indicators are OFF 1. 2. 3. One power supply indicator is OFF or it is very dim. 4. 1. WHAT TO DO Check fuse F2 to see if it has failed. If so, replace. If fuses are okay, replace the 34031 board. If the F2 fails again, replace the 34031 board. If the indicators light, but the regulator still does not work got to the next symptom. Check door interlock switch. Replace the 34031 Board For further help contact Crouse-Hinds Airport Lighting Products. CAUTION: TURN OFF MAIN AND CONTROL POWER BEFORE REMOVING OR INSTALLING CIRCUIT CARDS. PROTECTION PROBLEM CHECKLIST WHAT TO DO 1. Observe feedback indicator on the control board. If OFF, check current transformer T3 for an open winding. If T3 is OK, replace 34031 board. 2. While de-energized, check to see if K2 (Solid State Relay) SSR is shorted. If SSR is shorted replace relay. 3. Ensure K1 contactor coil is getting power. Display reads ‘HIGH LOAD CURRENT’ 1. If regulator operates on lower steps but currents are high, replace 34031 board. 2. If regulator trips right away, regardless of step, replace 34031 board. 3. K2 SSR may be open. Check coil connections to K2 SSR. Replace K2 SSR if necessary. For further help contact Crouse-Hinds Airport Lighting Products. SYMPTOMS Display reads ‘LOOP; 36 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes CAUTION: TURN OFF MAIN AND CONTROL POWER BEFORE REMOVING OR INSTALLING CIRCUIT CARDS. REGULATION PROBLEM CHECKLIST SYMPTOM All currents low. WHAT TO DO 1. Check fuse F3 to see if control winding fuse has blown. If okay, replace 34031 board. 2. Check to see if K2 SSR is shorted. 3. Check connections to C1 capacitor bank. Measure capacitance to verify while CAP1 and CAP2 leads of power transformer are disconnected: 4kw, 60Hz = 150uF 7.5kw, 60Hz = 250uF 10kw, 60Hz = 400uF High steps OK, but low steps are high. One-step high or low. Low steps OK, but high steps are low. Current fluctuates over a wide range. 1. Replace 34031 board 1. If in local and remote control replace 34031 board. See section on Remote Control problems. 1. Run regulator in a short. If OK, regulator is over-loaded. 2. Check connections to C1 capacitor bank. Verify capacitance of C1 capacitor bank. 1. Observe +12V indicator. If it blinks, then be sure area temperature is below 130 degrees F. If it is OK, replace the 34031 board. For further help contact Crouse-Hinds Airport Lighting Products. 37 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes CAUTION: TURN OFF MAIN AND CONTROL POWER BEFORE REMOVING OR INSTALLING CIRCUIT CARDS. LOCAL CONTROL PROBLEM CHECKLIST SYMPTOMS System will not turn on. System will not turn off. WHAT TO DO 1. Observe Contactor indicator. It should go on and off when switching from off to a step. If it doesn’t then replace 34031 board. 2. Check K1 coil for open. If open replace K1. If OK replace 34031 board. 1. If system will not turn off when the interlock switch is opened, K1 may be welded closed. 2. Observe Contactor indicator. If on all the time, replace 34031 board. For further help contact Crouse-Hinds Airport Lighting Products. 38 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes CAUTION: TURN OFF MAIN AND CONTROL POWER BEFORE REMOVING OR INSTALLING CIRCUIT CARDS. REMOTE CONTROL PROBLEM CHECKLIST SYMPTOM System will not turn on. WHAT TO DO 1. Check in local control. If not OK, see section on local control problems. 2. Check remote supply and wiring. If OK, replace 34031 board. 3. Check door interlock switch System will not turn off. 1. Check for control lines longer than 10,000 feet in length. Current fluctuates up or down. 1. Check for control lines longer than 10,000 feet in length. For further help contact Crouse-Hinds Airport Lighting Products 39 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes CAUTION: TURN OFF MAIN AND CONTROL POWER BEFORE REMOVING OR INSTALLING CIRCUIT CARDS. DIGITAL PROBLEM CHECKLIST SYMPTOM System will not turn on. WHAT TO DO 1. Observe Run and Halt indicators. If they are blinking, replace control board. If the Run indicator is on all the time, see the section on local control problems. For further help contact Crouse-Hinds Airport Lighting Products. 40 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes CAUTION: TURN OFF MAIN AND CONTROL POWER BEFORE REMOVING OR INSTALLING CIRCUIT CARDS. DISPLAY PROBLEM CHECKLIST SYMPTOM Regulator runs but no display. Regulator runs but Display shows wrong current. Regulator works but display is out or showing “funny” data WHAT TO DO 1. Check for a loose cable from the display to the control board If OK replace32752. Display Card. 1. Check S1 DIP switch settings on the control board. 2. Replace 34031 board. 1. If display reads ‘P-.X.X.’ and does not change, see the section on digital problems. 2. Replace 34031 board. For further help contact Crouse-Hinds Airport Lighting Products. 41 Document 2501 Rev. F Instruction Manual L-828 Constant Current Regulator Series 828X0F 4kW, 7.5kW, 10kW, 6.6 Amperes 10 Spare Parts List 10.1 Scope Parts that are option related are discussed in the respective Drawing for that Option. RECOMMENDED SPARE PARTS Item Number 1 2 Reference Designation LA1 T2 3 K1 3 K1 4 K2 SSR 5 6 Capacitor Bank 7 8 9 T3 LA2, LA3 10 F1, F3, F4 11 F201, F202 12 F2 13 Ref K2 Description Input Lightning Arrestor 36V/120V Control Transformer Contactor, 75A Resistive Contactor, 120A Resistive (20kW Units) Solid State Relay (also requires item 13) Control Board Capacitor, 50uF, 600V Display Board Current Transformer, 6.6A Output Lightning Arrestor, 3kV Fuse, 1/8 A Slo-Blo 5 x 20 mm Fuse, 1A Slo-Blo 5 x 20 mm Fuse, 2A Slo-Blo 5 x 20 mm Solid State Relay Thermal Pad (apply to SSR bas) 42 Crouse-Hinds Part Number 10047-885 32279 10047-1249 Manufacturer Part Number GE 9L15ECB001 Square D 8910-DPA62-V02 32085 10047-2789 34031-1 32990 32752 31329 10053-703 10047-2937 Ronken Industries 91D23506H32 Cooper Power Systems UHS0303-0A0D0A1A Bussman GMD125mA Bussman GMD1A Bussman GMD2A