THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I DIVISION 2 GROUPS A,B,C AND D HAZARDOUS LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY. 915U-D20-900/2400 Serial Data Radio FCC Notice Antenna connection (SMA Female) This device complies with Part 15.247 of the FCC Rules. Operation is subject to the following two conditions: · · This device may not cause harmful interference and This device must accept any interference received, including interference that may cause undesired operation 9-30V DC Supply Antenna Installation SURGE ARRESTOR (OPTIONAL) Power Source 1 Wavelength minimum Wavelengths 900 MHz = 33 cm 2.4GHz = 13 cm RF Link Fail COLINEAR ANTENNA RS232 (DB9) connections WEATHERPROOF CONNECTORS WITH “3M 23” TAPE DTE Device (Computer) RxD (Pin 2) TxD (Pin 3) GND (Pin 5) RTS (Pin 7) CTS (Pin 8) STRESS RELIEF LOOP COAXIAL CABLE MAST MODULE PROVIDE GOOD GROUND CONNECTION TO MAST, MODULE AND SURGE ARRESTOR INSTALL ANTENNA ABOVE LOCAL OBSTRUCTIONS FOR MAXIMUM RADIO DISTANCE EARTH terminal on bottom of module · · · · · · · · · Notes WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS. WARNING - EXPLOSION HAZARD - SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2. Module can be powered using either an external Listed Power Supply with LPS Outputs or a Listed Battery Pack with LPS Outputs. Only one power source can be used at a time. Single Point „EARTH‟ termination on bottom plate of module for surge protection RS485 End Point Termination is configured via Webpage interface X - The device as shipped provides IP20 protection only. For the higher protection levels the device must be installed in the adequate enclosure. "THE USB CONNECTOR IS FOR TEMPORARY CONNECTION ONLY. DO NOT USE, CONNECT, OR DISCONNECT UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS. CONNECTION OR DISCONNECTION IN AN EXPLOSIVE ATMOSPHERE COULD RESULT IN AN EXPLOSION." DIN Rail Mounting Clip To mount Clip – insert the two keyed tabs into the available slots on the back of the module (Clip can only be mounted one way). Press firmly until the Clip clicks into place. To remove Clip - Insert a flat blade screwdriver into the slotted holes on each side of the module so that the screwdriver is perpendicular to the slot. Press lightly to release the Clip. DCE Device (PLC) RxD (Pin 3) TxD (Pin 2) GND (Pin 5) RTS (Pin 8) CTS (Pin 7) 915U-D Terminals 232 TX (Term 7) 232 RX (Term 8) GND (Term 9) CTS (Term 5) RTS (Term 6) RS485 connections IF GROUND CONDITIONS ARE POOR, INSTALL MORE THAN ONE STAKE inst_Elpro_915U-D_1.1.3.vsd Lamp Enclosure Chassis Protective Surge Earth # Name 1 PWR 2 CMN 3 RLY A 4 RLY B 5 CTS 6 RTS 7 232 TX 8 232 RX 9 GND 10 485 (+) 11 485 (-) 12 GND 915U-D Terminals # Name 1 PWR 2 CMN 3 RLY A 4 RLY B 5 CTS 6 RTS 7 232 TX 8 232 RX 9 GND 10 485 (+) 11 485 (-) 12 GND 915U-D Terminals # Name 1 PWR 2 CMN 3 RLY A 4 RLY B 5 CTS 6 RTS 7 232 TX 8 232 RX 9 GND 10 485 (+) 11 485 (-) 12 GND 915U-D Terminals RS485 (+) 915U-D-900/2400 RSSI RS485 (-) * * GND Voltage Fade Margin * Cable lengths over 10m should only be grounded at one end only. 3.25 40dB 3.00 35dB Sealed Relay 2.75 30dB WARNING – Exposure to some chemicals may 2.5 25dB degrade the sealing properties of materials USB Mini-B 2.25 20dB used in the Sealed Relay Device. 2.0 15dB Programming RECOMMENDATION - It is recommended to 1.75 10dB port inspect the sealed relay device periodically and 1.5 5dB to check for any degradation of the materials 1.25 0dB and to replace the complete product, not the Connect Volt Meter across RSSI and GND Pins. sealed device, if any degradation is found. Recommended minimum is 2.0v which is equivalent to a 15dB Fade Margin