600 A 35 kV class deadbreak PUSH-OP apparatus bushing COOPER POWER SERIES

Catalog Data
CA800028EN
Effective February 2016
Supersedes 800-48 January 1990
COOPER POWER
SERIES
600 A 35 kV class deadbreak
PUSH-OP apparatus bushing
General
Eaton's Cooper Power™ series 600 A 35 kV Class
dead­break PUSH-OP™ apparatus bushing meets
the full requirements of IEEE Std 386™-2006
standard–separable insulated connector systems
(except for apparatus-terminator connection
dimensions). All 600 A 35 kV PUSH-OP type
connectors will operate with this bushing.
The epoxy bushings are designed for sidewall
mounting in transformers, switches and other
apparatus filled with transformer oil, Envirotemp™
FR3™ fluid or an approved equivalent.
Installation
No special tools are required. The bushing
is mounted through the apparatus sidewall
and clamped externally with a special bracket
assembly. Refer to Service Information
MN800009EN 600 A 15, 25, and 35 kV Class
Deadbreak PUSH-OP Apparatus Bushing
Installation Instructions for details.
Production tests
Test are conducted in accordance with IEEE Std
386™-2006 standard.
•
AC 60 Hz 1 Minute Withstand
• 50 kV
•
Minimum Corona Voltage Level
• 26 kV
Tests are conducted in accordance with Eaton
requirements.
•
Physical Inspection
•
Periodic Fluoroscopic Analysis (X-ray)
Catalog Data CA800028EN
600 A 35 kV class deadbreak PUSH-OP apparatus bushing
Effective February 2016
(S1)
5.85"
(149 mm)
Features and
detailed
description
DEADBREAK
RTE
USH
5.25"
(133 mm)
HERE
1.25"
(32 mm)
EPOXY BODY
High strength epoxy
bushing body provides
high electrical, thermal
and mechanical
reliability.
4.00" Dia.
(102 mm)
5/8 " ––11
UNC 2A THREAD
FEMALE CONTACTS
Silver plated female copper contacts
provides superior electrical transfer.
.75 "
(19 mm)
2.56" Dia. TANK WALL OPENING
(65.0 mm)
SEMICONDUCTIVE
COATING
Allows fully
shielded
connection.
Figure 1. 600 A 35 kV Class deadbreak PUSH-OP apparatus bushing.
Table 1. Voltage Ratings and Characteristics
LATCH
HANDLE
DEADBREAK
LATCH HANDLE
Right Side
(B05 Only)
RTE
PUSH
HERE
HITCH PIN
(Optional)
Description
kV
Standard Voltage Class
35
Maximum Rating Phase-to-Ground
21.1
BAIL BRACKET
AC 60 Hz 1 Minute Withstand
50
PUSH PLATE
DC
15
Minute
Withstand
103
Provides
convenient point to
BIL and Full Wave Crest
150
operate PUSH-OP
connector system
Minimum Corona Voltage Level
26
with standard
hotline tools.
Voltage ratings and characteristics are in accordance with IEEE Std 386™-2006 standard.
Table 2. Current Ratings and Characteristics
BAIL BRACKET
ASSEMBLY
Stainless steel
(series 300)
ratchet latch
assembly and
bail bracket
assembly
facilitates
installation of
600 A
deadbreak
PUSH-OP
connector
without
threading
operation.
11.57 "
(294 mm)
4.82 "
(122 mm)
FRONT VIEW
Figure 2. Bail bracket assembly.
NNote: Dimensions given are for reference only.
2
www.eaton.com/cooperpowerseries
Description
Amperes
Continuous
600 A rms
Short Time
25,000 A rms symmetrical for 0.17 s
10,000 A rms symmetrical for 3.0 s
Current ratings and characteristics are in ac­cor­dance with IEEE Std 386™-2006 standard.
Catalog Data CA800028EN
600 A 35 kV class deadbreak PUSH-OP apparatus bushing
Effective February 2016
5.85 "
(149 mm)
DEADBREAK
RTE
TANK FRONT PLATE
PUSH
HERE
STAINLESS STEEL
RATCHET LATCH
7.07 "
(180 mm)
EPOXY
BUSHING
8.6 "
(218 mm)
BUSHING NOT
INCLUDED
CLAMP
DEADBREAK
SIDE VIEW
PUSH
Figure 3. Bail bracket assembly/side view with bushing installed.
RTE
HERE
Ordering information
4.5 " Sq.
(115 mm)
To order a 600 A 35 kV Class deadbreak PUSH-OP apparatus
bushing, specify bushing, bushing bail bracket assembly, clamp and
gasket separately from Table 3.
Table 3. Bushing, Bail Bracket, Clamp and Gasket.
.44" Dia. Hole
(11.2 mm)
3.25 " Dia.
(83 mm)
3.4 " Typ.
(87 mm)
Description
Catalog Number
35 kV Bushing
DB635B150P
Bail Bracket Assembly with Hitch Pin
2638772B03M
Bail Bracket Assembly with Hitch Pin (Latch Handle Right)
2638772B05M
Clamp
2637023B01
Gasket
0537980C06
Figure 4. Clamp.
NNote: Dimensions given are for reference only.
Table 4. Replacement Part
Description
Catalog Number
Shipping Cap (not for energized operation)
2610082P01
DEADBREAK
RTE
PUSH
HERE
www.eaton.com/cooperpowerseries
3
Catalog Data CA800028EN
600 A 35 kV class deadbreak PUSH-OP apparatus bushing
Effective February 2016
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. CA800028EN
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton's Cooper Power series product
information call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.