Relaying 230 kV, 100 Mvar C-Type Filter Capacitor Banks Randy Horton, Ted Warren Alabama Power Company Timothy Day, Jack McCall, Arvind Chaudhary Cooper Power Systems These levels guidelines. Abstract: Shunt capacitor banks are considered an economical source of reactive power and are installed in many locations throughout the power system. The addition of a capacitor bank creates a new, and lower resonant frequency as the capacitance interacts with the inherent system inductance. Recent years have seen greater numbers of large industrial customers, with their nonlinear loads, connected to high-voltage portions of the power system. If the harmonic current injected by these nonlinear loads has appreciable components at the resonant frequency of the power system, a severe overvoltage situation can occur. As a result, the ability to filter harmonic current with adequate damping over a selected frequency range has become a necessity in some shunt capacitor bank designs. The C-type harmonic filter can be designed to meet these requirements. This paper describes the design, application, and novel protection of a C-type harmonic filter bank. were obviously outside IEEE-519 Following a preliminary analysis, it was concluded that the harmonic currents would need to be filtered by converting the capacitors into tuned harmonic filters. A single-tuned filter design was considered along with its disadvantages when connected to a transmission system. As the system changes; i.e. new lines are built, other capacitor banks are installed, etc., the resonant frequency will shift. Changes to the filter would need to be made in order for it to work properly. Since the main goal of this project was to provide var support to the system, it was decided to find a method that would allow the bank to be connected to the system without causing a resonance condition. The C-type filter, which has a flat frequency response over the frequency range of interest, is capable of performing this function and was selected as the design of choice. Frequency scans of the considered options are shown below. 5 10 Introduction: Southern Company Services Transmission Planning Department determined that 200 Mvars of capacitors needed to be installed at a 230 kV substation on the Southern System to provide voltage support. The 200 Mvar was split into two equal 100 Mvar banks. Both banks were originally designed to be split-wye grounded banks. Harmonics were monitored at the station bus for one week. With the collected data, it was determined that there was an appreciable magnitude of current at the 5th, 7th and 11th harmonics. Preliminary calculations indicated that the application of 100 Mvars and/or 200 Mvars of capacitors at this particular location would create a harmonic resonance near the 7th harmonic. Both present and future short-circuit strengths were considered. Calculated voltage THD levels at this particular location without filtered capacitor banks ranged from 7.1 – 23.2%, depending on system strength and how many area capacitor banks were on line. Bus Voltage (per Amp Injected Harm. Current) 4 10 Single-tuned Filter 3 Capacitor Only 10 2 C-Type Filter 10 1 10 0 10 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Harmonic (60 Hz base) Figure 1. Frequency Scans of Various Filters The plot shows the amount of voltage appearing at the 230 kV bus for each Ampere of harmonic current injected. Peaks indicate undesirable parallel-resonance conditions, and the 7th harmonic resonance for the capacitor only design is clearly seen. The single-tuned filter permits a shift of the resonance to a non-offensive Page 1 resonant combination results in a net impedance of zero Ohms. Therefore, under normal 60 Hz operation, the damping resistor is effectively shunted thus preventing costly losses. Under these conditions, the only circuit element effectively in service is the main capacitor section. It is this element which provides the needed var support. When the bank is subjected to harmonics, the tuning section no longer presents a zero impedance branch within the network, and harmonic currents are “spilled” into the resistor where they are dissipated. frequency, but this resonance point may vary somewhat depending on system conditions. The C-Type filter relies upon resistive damping to yield the favorable scan characteristics of essentially no problematic resonance across the frequencies of interest. The figure below shows the main components of this type of filter. Main Capacitor Tuning Capacitor Filter Bank Design and Protection Damping Resistor Tuning Reactor As is the norm with high-voltage capacitor banks, system voltage and var requirements typically exceed the ratings of individual capacitor units. The design therefore involves connection of individual units in a matrix array in which the connectivity compliments both capacitor unit and system requirements. Figure 3 shows the single-phase connectivity for the 100 Mvar filter bank. Complete bank protection is also shown comprising the numerous voltage and current transducers placed within the bank as well as the protective elements indicated by their device numbers. Figure 2. Simplified 1-Line Diagram of the C-Type Filter The operation of the C-Type harmonic filter is quite different than a typical tuned filter bank. At 60 Hz, the reactance of the tuning capacitor will cancel the inductive reactance of the tuning reactor. This series- Each Unit: 577 kvar, 17465 V 8 Series Sections 123 kV CT Main Capacitor 51 (CM) Each Unit: 401 kvar, 6072 V 3 Series Sections 360 Ω (x 2) 36 kV CT Tuning Section 51 (CT) 37 (L) 49 (L) 51 (L) 59 (L) 36 kV CT 49 (R1) 51 (R1) 49 (R2) 51 (R2) 21 (L) 60.98 mH 34.5 kV PT Sta. Class Arrester 15 kV CT Figure 3. 230 kV 100 Mvar C-Type Harmonic Filter Bank: Design and Protection Detail Page 2 87 (R) Main Capacitor Section (51-CM) Ze = Protection for the main capacitor section is provided by a definite-time over current relay (51-CM) that monitors the unbalance in the H-connected main capacitor section. The intent is to utilize an indirect measurement, in this case the fundamental frequency bridge current, to yield an indication of bank imbalance, i.e., failure of individual capacitor sections. Ideally, no bridge current flows when the healthy capacitors produce a perfect balance. Bridge current flows when a section fails and the balance is lost. The main concern in the unbalanced case is the voltage impressed upon the remaining capacitor sections. The altered capacitive voltage divider of the bank yields elevated voltages across some remaining sections. Calculations can relate this internal voltage stress to the amount of bridge current. Two levels of definite time over current protection were utilized. One element was designated as the alarm set point, while the other was designated as the trip set point. Both over current elements were biased to accept a steady state vectorial correction current to compensate for inherent unbalance within the capacitor section. This nulling of the unbalance allows for a more sensitive setting. The capacitor units that made up the main capacitor section were fuseless. The internal construction of the capacitor unit (the can) with its 8 series sections is shown below. 1 of 8 Series Sections Total Unit (can) Rating: 577 kvar 17,465 V Figure 4. Internal Series Section Construction of the Main Capacitor Unit The anticipated failure mode of a capacitor section is a short-circuit. The unbalance current flowing in the current transformer shown in Figure 3 for “N” failed capacitor sections can be calculated using (1– 10). Zc = (Vc )2 Qc (1) Page 3 Zc Nc (2) Z f = Z e (N c ⋅ N u − N s ) (3) Z s = Nu Zc (4) Z top = Zs ⋅ Z f (5) Z f (N str − 1) + Z s Z bottom = Zs N str Z top Vtop = Vmax Z top + Z bottom (6) Z bottom Vbottom = Vmax Z top + Z bottom (7) Vtop N str V ⋅ I unbalance = bottom − Z s 2 Zs Vtop ⋅ N c %OV = ⋅ 100 Vc [( N c ⋅ N u ) − N s ] (8) (9) (10) where, Zc = Impedance of capacitor can, Ω Ze = Impedance of capacitor element, Ω Zf = Impedance of string with failed capacitor element, Ω Vc = Rated voltage of each capacitor unit, kV Qc = Reactive power rating of capacitor unit, Mvars Nc = Number of series sections per capacitor unit Ns = Number of shorted series sections in one string Nu = Number of series-connected capacitor units per string Zs = Impedance of healthy string, Ω Ztop = Impedance of top half of main capacitor section, Ω Zbottom = Impedance of bottom half of main capacitor section, Ω Vtop = Voltage across top half of main capacitor section, kV Vbottom = Voltage across bottom half of main capacitor section, kV Vmax = Maximum line-to-neutral system voltage, kV Iunbalance = Unbalance current flowing through current transformer, A %OV = Percent overvoltage on remaining series sections, % Typically, a table is developed to show the unbalance current and %OV for multiple series section failures. Table 1 includes the calculation results for the main section of a 242 kV – 100 Mvar C-Type harmonic filter bank. A detailed example calculation for the main section unbalance current is included in the Appendix. # Failed Series Sections Zf Zs Ztop Zbottom Vtop Vbottom Unbalance Current Elements 0 1 2 3 4 5 6 7 (Ω) 2114.6 2048.5 1982.4 1916.3 1850.2 1784.2 1718.1 1652.0 (Ω) 2114.6 2114.6 2114.6 2114.6 2114.6 2114.6 2114.6 2114.6 (Ω) 264.4 263.3 262.1 260.9 259.7 258.3 256.9 255.4 (Ω) 264.4 264.3 264.3 264.3 264.3 264.3 264.3 264.3 (V) 69859.4 69718.8 69571.6 69412.6 69243.2 69062.1 68868.1 68659.9 (V) 69859.4 69999.9 70151.3 70310.2 70479.7 70660.8 70854.7 71063.0 (A) 0.00 0.53 1.10 1.70 2.34 3.02 3.76 4.55 %OV (% of rated) 100.0% 103.0% 106.2% 109.6% 113.3% 117.2% 121.3% 125.8% Table 1. Main Capacitor Section Unbalance Calculation Results The alarm setting was chosen to detect a single series section failure. A setting of 80% of the calculated value will provide adequate margin. Thus a setting of 0.4 A primary was used. The trip setting was chosen to detect multiple series section failures. The bank should be taken off line before the remaining capacitor sections are subjected to a voltage greater than 110% of their rating. Typically, a string is rated at nominal system voltage; however for a filter bank the string is rated at a voltage higher than nominal. To account for possible overvoltage due to harmonics, a setting that correlated to two series section failures was chosen. From Table 1 it can be seen that the bank would still be operating below 110% of its rating for two series section failures. However, it was decided to go with the more conservative approach due to the unknown voltage developed by harmonics. Thus a setting of 0.8 A primary was selected. Zc = Ze = (Vc )2 Zc 1000 ⋅ N c Page 4 (12) Z f = Z e (N c ⋅ N u − N s ) (13) Z s = Nu Zc (14) Z top _ tune = I main = I tune = Zs ⋅ Z f (15) Z f ⋅ (N str − 1) + Z s Z bottom _ tune = Tuning Capacitor Section (51-CT) A capacitor unit failure is detected in the tuning section of the filter bank in the same manner as that of the main capacitor section. A separate 51-CT (capacitor, tuning) element is used, one per phase. However, since the tuning section consists of capacitors, reactors and resistors, the equations involved in calculating the unbalance current due to a failed series section is somewhat different than for the main capacitor section. Equations (11-22) may be used to calculate this unbalance current. (11) Qc Zs N str (16) Vmax − jZ main (17) R 2 R − jZ top _ tune − jZ bottom _ tune + jωL 2 ( Vtop _ tune = I tune ⋅ − jZ top _ tune ( (18) ) Vbottom _ tune = I tune ⋅ − jZ bottom _ tune ⋅ I main (19) ) (20) Vbottom _ tune Vtop _ tune − I unbalance = Zs Zs %OV = Vtop _ tune ⋅ N c Vc [(N c ⋅ N u ) − N s ] N str ⋅ 2 (21) ⋅ 100 (22) where, Zs = Impedance of healthy string, Ω Ztop = Impedance of top half of main capacitor section, Ω Zbottom = Impedance of bottom half of main capacitor section, Ω Vtop = Voltage across top half of main capacitor section, kV Zc = Impedance of capacitor can, Ω Ze = Impedance of capacitor element, Ω Zf = Impedance of string with failed capacitor element, Ω Vbottom = Voltage across bottom half of main capacitor section, kV Vmax = Maximum line-to-neutral system voltage, kV Ztop_tune = Impedance of the top half of the tuning section, Ω Iunbalance = Unbalance current flowing through current transformer, A Zbottom_tune = Impedance of the bottom half of the tuning section, Ω %OV = Percent overvoltage on remaining series sections, % Vc = Rated voltage of each capacitor unit, kV Qc = Reactive power rating of capacitor unit, Mvars Nc = Number of series sections per capacitor unit Ns = Number of shorted series sections in one string Nu = Number of series-connected capacitor units per string As with the main capacitor section, a table is developed to analyze the behavior of the string for multiple series section failures. Table 2 shows the %OV and unbalance current produced by multiple series section failures. A detailed calculation for the tuning section is included in the Appendix. Nstr = Number of parallel strings per phase # Failed Series Sections Zf Zs Ztop (tune) Zbottom (tune) Vtop (tune) Vbottom (tune) Unbalance Current Elements 0 1 2 3 (Ω) 91.94 61.30 30.65 0.00 (Ω) 91.94 91.94 91.94 91.94 (Ω) 11.49 10.82 9.19 0.00 (Ω) 11.49 11.49 11.49 11.49 (V) 3037.6 2858.9 2440.5 0.0 (V) 3037.6 3037.6 3050.7 3031.4 (A) 0.00 7.77 26.5 131.88 %OV (% of rated) 50.0 70.6 120.6 0.0 Table 2. Tuning Capacitor Section Unbalance Calculation Results The alarm setting is chosen to detect a single series section failure. A setting of 80% of the calculated value will provide adequate margin. Thus a setting of 6.2 A primary will be used. impact on the tuning of the bank. The tuning section capacitors are un-fused and have a voltage rating of twice nominal voltage. This is evident in the %OV data for zero failed sections. This rating minimizes the probability of a failure and allows operation with one shorted series section. The trip setting is chosen to detect multiple series section failures. Typically, a bank is tripped off line when the voltage across the remaining capacitor cans exceeds 110% of their nominal rating. However, for the case of the tuning section, the bank should be tripped after the second series section failure regardless of the percent overvoltage. This is done because a failure of a series section within the tuning section can have an Page 5 The tuning section bridge current used to indicate capacitor unit failures is ideally zero under healthy bank (balanced) conditions. As discussed above with the Main Capacitor, in practice there will be some small current flow in the bridge circuit due to tolerances in the capacitors that yield bank structures not perfectly balanced. Accommodating this error would require de- sensitizing the protective settings. To increase sensitivity, nulling logic was incorporated into the relay: during bank commissioning, this error signal is measured, committed to relay memory and used to compensate the real-time protective algorithms. Because this compensation process involves both the magnitude and phase angle of the inherent error signal, a reference phasor is required for coherent phase accounting. The relay uses the reactor current, of the associated phase, as that reference. +XL Impedance Plane Alarm Radius Nominal Impedance Trip Radius Alarm Impedance Trip Impedance R Figure 5. Tuning Reactor Impedance Protection (21-L) Tuning Reactor (L) The tuning reactor protection consists of an undercurrent relay (37-L); a fundamental frequency definite time over current relay (51-L); thermal image protection (49-L), employing harmonics and thermal time constants; fundamental frequency impedance protection (21-L); and a summed harmonic over voltage element (59-L). When the reactor begins to fail (short turns, etc.), the total impedance of the filter bank begins to increase. Assuming a nearly constant bus voltage, this increase in bank impedance will cause a decrease in the amount of current flowing through the reactor. As a result, an undercurrent relay (37-L) monitoring reactor current is required to detect this particular failure mode of the tuning reactor. Additional protection based upon the reactor impedance is used to enhance the detection of reactor failures. The impedance-based reactor relay monitors the fundamental frequency voltage across the reactor and fundamental frequency reactor currents to determine the actual reactor impedance on a per-phase basis. Although the bus work and CTs contribute some resistance, this value is neglected by the real-time measurement via a compensation set when the unit is commissioned. Figure 5 shows the manner in which the impedance-based method works. The offset mho elements are inward looking. That is, the elements only operate when the reactor impedance falls outside of a given mho circle. Essentially, the sensitivity of the protection is such that a single shorted series section can be detected and an alarm issued with identification of phase-involvement. If the number of shorted series sections is large enough to cause an impedance range shift beyond the alarm region, then a trip command is issued. Figure 5 illustrates the concept of offset impedance circles of normal range and of the alarm zone and the trip zone. Note that during the commissioning process, any errors due to the CTs and VTs are included in the initial measured impedance and are compensated. This error-nulling process allows the setting of a smaller, more sensitive, radius impedance circle around the initial measured impedance. To protect the tuning reactor from a possible overload condition caused by excessive exposure to harmonic current, thermal image relays are provided. A 100 Mvar filter bank at the 230 kV level is an effective sink for system harmonics. Harmonics can cause thermal damage to the reactors. By nature, harmonic overloads are not constant over time: rising and falling over a fixed detection window. Therefore, a thermal protection algorithm is employed that estimated the temperature of both the reactor’s insulator cap and winding hot-spot. The ambient temperature, an important input to this algorithm, is measured via a conventional thermo-couple and a 4-20 mA transducer circuit. The relay’s 49-L (inductor) thermal element is based upon the following equation: TL= 0.00069 (IL 2+ -t 47 2 2 (ILo - IL )e ) + Tambient (°C) which estimates the inductor winding temperature where, IL = ∑αi Ii2 . ILo = IL calculated at the previous iteration. I = rms inductor current of the ith harmonic. t = calculation iteration time (minutes). i = harmonic index (1, 3, 5, 7). α1,3,5,7 = 1.0, 1.12, 1.35, 1.69. The reactor manufacturer provided the above analytic expression along with the conversion factors, time constant and harmonic gains. Response from the relay Page 6 is recommended when a calculated inductor winding temperature of 150 °C is reached. This calculated temperature is considered an absolute value, not a temperature rise. In addition to the above, the manufacturer recommends estimating the temperature of the critical insulating cap of the inductor assembly. The relay included this via its 49-C (cap) element by using the following expression. TC= 0.00037 (IC2 + -t 24 2 2 (ICo - IC )e ) + Tambient (°C) which estimates the inductor insulation cap temperature where, IC = 2∑i2 Ii2 . ICo = IC calculated at the previous iteration. I = rms inductor current of the ith harmonic. t = calculation iteration time (minutes). i = harmonic index (1, 3, 5, 7). The inductor manufacturer recommends relay response when calculated insulation cap temperature reaches 120 °C Harmonic reactor currents cause instantaneous harmonic reactor voltages which can stress the turn-toturn insulation of the reactor. Note that higher harmonics of same magnitude produce a higher voltage due to the higher angular frequency (ω). The harmonic voltage is summed arithmetically and compared to a set value which provides sufficient turn-to-turn overvoltage protection. The analytic expression used in this over voltage element is as follows: VL= 0.377 L ∑i Ii which estimates the instantaneous inductor harmonic voltage stress where, L = inductance (mH) I = rms inductor current. i = harmonic index (1, 3, 5, 7). The inductor manufacturer recommends relay response when calculated voltages reach 20 kV. Although a single device would suffice, two parallelconnected resistors for damping out harmonics are used in order to provide redundancy and create a quasidifferential zone of protection. Note that in a situation of perfect resonance between the tuning L and the tuning C, there will be only harmonic current in the two resistors. The currents that flow through each resistor are measured and the rms current computed. The protection provided is a simple rms (harmonics included) definite time over current element on a perresistor and per-phase basis: the 51-R. However, the possibility of short-term (below the time-delay setting of the 51 elements) repeated rms current overloads necessitates the use of thermal tracking elements (49-R), employing thermal time constants of the resistors and permissible temperature rise allowed. The ambient thermal temperature is also used in the resistor thermal model. The analytic expression for the thermal model of the resistors follows a form similar to that discussed above for the filter bank inductor. One component of the protection problem involves detecting either an opened or shorted resistor when typically only very small harmonic current flows through the component. Normally, differential (87) protection is applied for unit protection, where the current in is equal to the current out. In this particular case it is applied to protect two separate resistors, since currents in the two resistors are expected to be identical as identically rated resistors and CTs are used. The objective is to detect a difference of resistor currents which may indicate failure of either unit. The relay calculates a restraint current, which is an average of the two resistor currents and the differential current, which is the difference between the two resistor currents. RMS sensing is utilized to incorporate the harmonicrich signals. Figure 6 depicts the slope characteristic of this differential element. Differential Current IR1− IR2 Slope Setting Operate Region Non-Operate Region Damping Resistors The two damping resistors are protected using a rms definite time overcurrent relay (51), thermal image protection (49) employing rms currents and resistor thermal time constants, and a unique rms percentage restraint biased differential protection (87). Page 7 Restraint Current IR1+ IR2 2 Figure 6. Differential Slope Characteristic During the commissioning process the inherent differential current is determined and input into the relay. This inherent differential current is subtracted from the calculated differential current which nulls out all the measurement errors and permits a tighter setting for the differential current element operation. Classical differential protection is applied, where the differential current pickup is a percentage of the average current. This unique method provides for greater security in the event of a large temporary over current and consequent CT saturation. Also both resistors are protected by this one differential (87) element employing only two CTs. Traditional differential protection would have required two CTs to protect one resistor. Conclusions The C-Type filter bank provides an economical means of applying shunt capacitor banks in harmonic rich environments with confidence that resonance conditions will be avoided. The protection of such a filter bank can be complex due to the fact that the filter is comprised of many components. The schemes shown in this paper provide a reliable and cost effective means of thoroughly protecting a C-Type harmonic filter bank. The availability of a flexible protection hardware platform, in terms of graphical programmability and expandable voltage/current inputs, permitted the incorporation of all protective elements within a single relay device. Bibliography 1. IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std. 519-1992 2. IEEE Guide For The Protection Of Shunt Capacitor Banks, IEEE Std. C37.99-2000 3. Horton, et al “Unbalance Protection of Fuseless, Split-Wye, Grounded, Shunt Capacitor Banks” IEEE Transaction on Power Delivery July 2002 pp. 698-701 L. Fendrick, et. Al., “Complete Relay 4. Protection for Multi-String Fuseless Capacitor Banks” Georgia Tech Protective Relaying Conference, May 2002. 5. ANSI/IEEE C37.015-1993, IEEE Application Guide for Shunt Reactor Switching Randy Horton received the B.S.E.E. degree from the University of Alabama at Birmingham and the M.E.E. degree from Auburn University all with specialization in electric power systems. He is currently employed at Alabama Power Company as a Senior Engineer in the Protective Equipment Page 8 Application group. Randy is a member of several IEEE PSRC working groups and is a registered professional engineer in the state of Alabama. Ted Warren is currently employed as a Senior Engineer in the Protective Equipment Application group at Alabama Power Company in Birmingham, Alabama. He has also worked as a protection engineer with Alabama Electric Cooperative and has worked in the industrial automation field. He received a B.E.E. degree from Auburn University in 1993. Ted is a registered professional engineer in the State of Alabama. Timothy R. Day is a Senior Relay Application Engineer in the Protective Relay Group of Cooper Power Systems, Franksville, Wisconsin. His present professional endeavors include modeling and analysis of electrical power systems to assess and optimize protection schemes. Timothy enhances existing protective algorithms and develops customized schemes for the Edison Idea line of relays and incorporates Cooper’s power system simulator to verify scheme modifications. He received a M.S.E.E. from Washington State University in 1991. Jack McCall is currently the director for Cooper Power Systems’ Protective Relay Group, located in South Milwaukee, WI. He has an MS in Electric Power Engineering from Rensselaer Polytechnic Institute and a BSEE from Gannon University. Previous positions within Cooper include Marketing Manager for Cooper’s Power Capacitor Group and Power Systems Engineer for Cooper’s Systems Engineering Group. He is a Member of the IEEE Power Engineering Society and has authored numerous papers on transients, harmonics, and capacitor applications in power systems. Arvind Chaudhary received the B.S.E.E. degree from the Indian Institute of Science, Bangalore, India; the M.S.E.E. degree from North Carolina State University, Raleigh; and the Ph.D. degree with a concentration in electric power engineering from Virginia Polytechnic Institute and State University, Blacksburg. He is a Staff Engineer with the Protective Relays, Cooper Power Systems, South Milwaukee, WI. He is responsible for relay applications for the Cooper line of relays and relay settings for power system equipment. He is the recipient of the 2000 IEEE PES Chicago Chapter Outstanding Engineer Award. Also, he is a member of the Technical Committee of the International Power Systems Transients Conferences of 1999, 2001, and 2003. His previous experience has included Sargent & Lundy consulting engineers (1991–1998) and Bharat Heavy Electricals Limited, India (1979–1983). APPENDIX Example Main Section Unbalance Current Calculation Given: Vmax = 242 kV 3 Vc = 17.465 kV Qc = 0.577 Mvar N u = 4 Number of capacitors per string N c = 8 Number of series sections per capacitor can N s = 1 Number of failed series sections N str = 8 Number of strings per phase Zc = Ze = (Vc )2 Qc = 528.64 Ω Zc = 66.08 Ω Nc Z f = Z e ( N c ⋅ N u − N s ) = 2048.49 Ω Z s = N u Z c = 2114 .57 Ω Z top = Zs ⋅ Z f Z f (N str − 1) + Z s Z bottom = = 263.26 Ω Zs = 264.32 Ω N str Z top Vtop = Vmax Z top + Z bottom = 69718.82 V Z bottom Vbottom = Vmax Z top + Z bottom = 69999.95 V Vtop N str V ⋅ I unbalance = bottom − 2 = 0.532 A (primary) Z Z s s %OV = Vtop ⋅ N c Vc [(N c ⋅ N u ) − N s ] ⋅ 100 = 103.02 % Page 9 Example Tuning Section Unbalance Current Calculation Given: Vmax = 242 kV 3 Vc = 6.072 kV Tuning capacitor voltage rating Qc = 0.401 Mvar Tuning capacitor Mvar rating L = 60.98 mH Tuning reactor inductance ω = 2π f = 377 rad/s R = 360 Ω Damping resistor N u = 1 Number of capacitors per string N c = 3 Number of series sections per capacitor can N s = 1 Number of failed series sections N str = 8 Number of strings per phase Z main = 528.64 Impedance of entire main capacitor section (from above calculations) Zc = Z s = N u Z c = 91.94 Ω Zs ⋅ Z f Z top _ tune = = 10.82 Ω Z f ⋅ (N str − 1) + Z s − V max ; I main = 264.29 A primary. − jZ main I main = (Vc )2 = 91.94 Ω Z bottom _ tune = Qc Z Z e = c = 30.64 Ω Nc Z f = Z e (N c ⋅ N u − N s ) = 61.29 Ω I tune = R 2 R − jZ top _ tune − jZ bottom _ tune + jωL 2 ( V top _ tune = I tune ⋅ − jZ top _ tune ( ) V bottom _ tune = I tune ⋅ − jZ bottom _ tune Vtop _ tune ⋅ N c Vc [( N c ⋅ N u ) − N s ] I tune = 264.29 A (primary) V top _ tune = 2858.85 V ) V bottom _ tune V top _ tune − I unbalance = Z Zs s %OV = ⋅ I main Zs = 11.49 Ω N str V bottom _ tune = 3037.53 V N str ⋅ 2 I unbalance = 7.77 A (primary) ⋅ 100 = 70.62 % Page 10 Page 11 Relaying 230 kV, 100 Mvar C-Type Filter Capacitor Banks ©2003 Cooper Power Systems, Inc. Bulletin 03019 • June 2003 • New Issue P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com KWP 6/03