CA650046EN
Effective May 2015
Supersedes I550-60 April 2012
•
•
•
•
•
For connection of polymeric cable to transformers, switchgear, motors and other equipment with a premoulded separable connector
For indoor and outdoor installations
System voltage up to 42 kV
Continuous current rating up to 1250 A when installed on an appropriate equipment bushing
Cable particulars:
•
Polymeric cable (XLPE, EPR, etc.)
•
•
Copper or aluminum conductors
Semiconducting or metallic screens
•
Conductor size: 24 kV 120-800 mm 2
36 kV 95-800 mm 2
•
•
•
•
•
•
Provides a fully screened and fully submersible separable connection when mated with the proper bushing or plug
Built-in capacitive test point allows for an easy check of the circuit status
Available with either DIN compression lugs or mechanical (shear bolt) lugs
No minimum phase clearance requirements
Mounting can be vertical, horizontal, or any angle in between
100% factory tested
•
Meets the requirements of IEC 60502-4 and
CENELEC HD 629.1 S2
•
•
•
Our manufacturing facility is registered to ISO
9001 by third party audit
Required Production Tests
Periodic X-Ray Analysis
•
•
•
No special tools, heating, taping, or potting are required
Connector may be energized immediately after installation on its mating part
Mates with bushings, plugs, and junction devices complying with CENELEC EN 50180 and 50181
Catalog Data CA650046EN
Effective May 2015
1
3
4
7
5
8
6
DTS1242 bolted tee connector - interface C
9
10
11
12
2
1. Clamping Screw
Tin-plated brass screw and brass nut secures the bolted tee conductor contact with the bushing
2. Insulation
Moulded EPDM insulating rubber is formulated and mixed in-house to ensure high quality
3. Basic Insulating Plug
Moulded epoxy part has a threaded metal insert to accept the clamping screw
4. Capacitive Test Point
Capacitive test point provides means to check circuit status.
5. Rubber Cap
Moulded EPDM conducting rubber cap protects and earths the test point during normal operation
6. Internal Screen
Moulded EPDM conducting rubber screen controls electrical stress
7. Capacitive Test Point (Optional)
Capacitive Test point provides a means to check circuit status. A moulded EPDM conducting rubber cap provides a watertight seal.
8. Stress Relief
The configuration of the outer screen and the cable adapter provide cable stress relief
9. Cable Adapter
The sized opening provides an interference fit to maintain a watertight seal and provides the initial cable stress relief
10. Earthing Eyes
Moulded into the external screen for connection of an earthing wire
11. External Screen
Moulded EPDM conducting rubber provides protective deadfront shield.
12. Conductor Contact
Inertia welded bimetallic compression or mechanical (shear bolt) lug accepts copper or aluminum conductors.
Figure 1. 1250 A, 42 kV Class DTS1242 bolted tee connector.
Table 1. Electrical Ratings
DTS1242
Max. Rated System Voltage (U m
)
Basic Impulse Level
AC Voltage Withstand (5 min.)
42 kV
200 kV
93.5 kV
125 kV DC Voltage Withstand (15 min.)
Continuous Current
Thermal Short Circuit, 3 sec.
1250 A
45 kA
Dynamic Short Circuit 100 kA
N otee: Ratings are based on IEC Standards and do not reflect maximum capability.
2 www.eaton.com/cooperpowerseries
DTS1242 bolted tee connector - interface C
54 mm
103 mm
96 mm
205 mm
152 mm
350 mm
75 mm
Figure 2. DTS1250 bolted tee connector dimensional information.
Catalog Data CA650046EN
Effective May 2015
The complete kit includes: moulded tee housing, cable adapter, conductor contact, insulating plug, rubber cap, clamping screw, lubricant, wipers and installation instructions.
To order a 42 kV bolted tee connector, use the Catalog Number
Section Guide, on page 4 and select the cable insulation range from Table 2, which gives you the best centering of the insulation diameter and then select the conductor size from Table 3.
Ordering Examplee: For a 36 kV drain wire shielded cable with a 500 mm2 aluminum conductor, 44 mm core insulation diameter and a DIN style crimp connector in a single-phase kit with a test point, including the cable sealing kit, specify
DTS1242FU500N1T1 .
Table 2. Cable Range
Insulation Range
Designation
C
D
E
A
B
F
G
H
Cable Insulation Range Dia. (mm)
Min.
28.2
31.1
35.0
37.2
40.1
42.9
46.5
50.0
Max.
32.3
35.7
39.1
41.6
44.8
47.9
51.9
56.0
Table 3. Conductor Size
Conductor
Size (mm2) DIN Type
185
240
300
95
120
150
400
500
630
800
U095
U120
U150
U185
U240
U300
U400
U500
-
U630
Mechanical Type
S300
S800
S630
www.eaton.com/cooperpowerseries 3
Catalog Data CA650046EN
Effective May 201
D T S 1 2 4 2
DTS1242 bolted tee connector - interface C
F U 5 0 0 N 1 T 1
Basic Catalog Number Insulation Range Table 2
Connector Size Table 3
T = Test Point
N = No Test Point
1 = 1-phase kit
3 = 3-phase kit
Cable Sealing Kit
See Table 4
Table 4. Cable Sealing Kits
Description
T1 Basic tape kit with sealing mastic and tape for one single core cable with copper screen wires (3 tape kits included with 3-phase kit)
N otee: For other cable sealing kits, please contact your Eaton representative.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122