Padmounted Switchgear Service Information Type PST-9 Automatic Source Transfer Switchgear Installation, Operation & Maintenance Instructions Figure 1. Kyle® Type PST-9 Automatic Source Transfer Switchgear. S285-60-1 911053KM Contents Safety Information ..................................................... 2 Installation Procedures .............................................16 Product Information .................................................. 3 Initial Mechanical Operation Check .......................17 Introduction ............................................................ 3 Initial Electrical Operation Check ...........................18 Acceptance and Initial Inspection .......................... 3 Initial S Control Operation Check............................19 Handling and Storage ............................................. 3 Maintenance Information...........................................20 ANSI Standards ...................................................... 3 Maintenance Inspection Procedures ......................20 Quality Standards.................................................... 3 Internal Inspection and Repair ...............................20 PST-9 Overall Description ........................................ 4 Insulating Oil Maintenance .....................................21 Ratings and Specifications ...................................... 7 Frequency of Maintenance ....................................21 Load Transfer Functionality ...................................... 8 Types of Oil Samples .............................................21 S-Control Operation ............................................... 8 Oil Sampling Guidelines .........................................21 CI Interrupter Switch Operation ..............................12 Oil Fill Guidelines ...................................................21 Overcurrent Protection Functionality ......................14 Oil Testing ..............................................................22 TPG Electronic Trip Control Operation ...................14 Testing.........................................................................23 VFI Vacuum Fault Interrupter Operation .................15 High Potential Withstand Tests ..............................23 Replacement Parts .....................................................23 December 2002 • NEW Printed in USA 1 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions ! SAFETY FOR LIFE ! SAFETY FOR LIFE SAFETY FOR LIFE Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission. SAFETY INFORMATION The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. • Is thoroughly familiar with these instructions. • Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. • Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. • Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. DANGER: Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high and low voltage lines and equipment. G103.3 ! WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 ! Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. ! WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ! CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. ! CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. 2 WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. ! G102.1 WARNING: Power distribution equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety prodedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain this equipment can result in death, severe personal injury, and equipment damage. G122.2 ! ! S285-60-1 SAFETY FOR LIFE PRODUCT INFORMATION Introduction Handling and Storage Service Information S285-60-1 provides installation instructions, operation information, maintenance procedures and testing information for Kyle Type PST-9 Padmounted Automatic Source Transfer Switchgear. Before installing and operating this control, carefully read and understand the contents of this manual. The switchgear should remain on its shipping pallet until it is installed. When handling the switchgear, always use a fork truck that has adequate lifting capacity and forks that extend the entire length of the pallet. Improper handling can cause damage to the switchgear. For additional information, refer to the following applicable service information bulletins: • S260-75-1 Kyle Type S Automatic Transfer Control Installation, Operating and Maintenance Instructions. • S275-10-1 Kyle Type CI Three-Phase Fault Interrupters Installation and Operation Instructions. • S285-10-1 Kyle Type VFI, Oil Insulated, Vacuum Fault Interrupter; Installation, Operation, and Maintenance Instructions • S285-75-1 Kyle Tri-Phase, TPG, and TPG w/SCADA Electronic Control Instructions. Installation and Operation Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. If the switchgear is to be stored for any appreciable time before installation, provide a clean, dry storage area. Be careful during handling and storage to minimize the possibility of mechanical damage. Do not stack other material on the switchgear cabinet. ANSI Standards Kyle PST-9 Padmounted Switchgear products are designed and tested in accordance with ANSI standards C37.60, C37.72, C37.85, C.57.12.28 and ANSI/EEE Standard 386. Quality Standards The Quality System at the Cooper Power Systems Kyle Distribution Switchgear plant is certified to the ISO 9001 Standard. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described, nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, please contact your Cooper Power Systems representative. Acceptance and Initial Inspection The PST switchgear is completely assembled, tested, and inspected at the factory. The switchgear is filled to the correct level with insulating oil. It is in good condition when accepted by the freight carrier for shipment. 1. Upon receipt, inspect the unit thoroughly for damage and loss of parts or oil incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. 2. Check for oil leakage and tighten any bolts that may have loosened during shipment. 3 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions PST-9 OVERALL DESCRIPTION Type PST-9 Automatic Source Transfer Switchgear provides both loss-of-voltage and overcurrent protection for critical loads for 15-, 25-, and 35 kV underground systems. PST-9 units are self-contained, steel constructed pad mount enclosures containing oil as a dielectric insulator medium. They are shipped fully assembled and filled with oil. PST-9 switchgear is designed for outdoor mounting on a concrete pad. Power is fed to, and from, the switchgear from underground through openings in the pad. Deadfront construction minimizes the high voltage safety hazards for both the operator and the general public. Vacuum Interrupters Load-break switching and fault interruption takes place within sealed vacuum interrupters. Vacuum interrupters provide fast, low energy arc interruption and produce no arcing by-products to contaminate the insulating oil. Use of vacuum interruption significantly reduces the maintenance required of this equipment. Loss-of-voltage protection functionality is provided by a Type S Automatic Load Transfer Control and two 3-phase Type CI motor-operated, source-side vacuum interrupter switches (Figure 2). The Type S Automatic Transfer Control monitors the preferred and alternate line voltages and provides the timing and control logic required to perform the automatic load transfer in the event of a voltage loss. The control commands the operations of the two Type CI vacuum interrupter switches during auto transfer. Manually operated levers enable manual trip and close of source-side CI interrupter switches during power outages. Operational power (120 Vac) for the transfer control and vacuum switches is derived from system line levels via internally mounted potential transformers; no external source of power is required. Kyle Type VFI Interrupters and either Tri-Phase or TriPhase with Ground (TPG) electronic controls provide independent overcurrent protection of the two PST taps. Both taps are independently served by separate controls commanding the operations of a dedicated VFI vacuum fault interrupter on each tap (Figure 2). CI Switch CI Switch S Control S1 Preferred Source Tri-Phase/TPG Control N.O. N.C. VFI VFI T1 T2 S2 Alternate Source Tri-Phase/TPG Control Figure 3. Vacuum Interrupter Assembly. 00015KM Bushings Bushings are mounted horizontally in-line and located a minimum of 24 inches above the pad. Depending on the rating of the PST-9 unit, bushings may be furnished in different configurations and ratings. 200 amp interfaces are provided as either 200-amp bushing wells or 200-amp one-piece loadbreak bushings. 600amp deadbreak aluminum type bushings are furnished for PST-9 units rated for 600 amp continuous current operation. All bushings conform to ANSI/IEEE Standard 386. Standard Cabinet Features Standard features (Figures 4 and 5) include an oil level indicator on each front plate, automatic pressure-relief valve, operation one-line diagrams on the doors, oil fill plug, oil drain and sampler and a standoff bracket for each bushing. Standard grounding provisions include a 1/2-13 UNC stainless steel ground nut for each bushing. Figure 2. PST-9 Functional Diagram. Cabinet Padlocking Provisions Overcurrent sensing, timing and tripping functions are performed by the Tri-Phase/TPG electronic controls. Sensing CT's, mounted internally on each phase, are used by the TPG control to monitor line current. If the current monitored is greater than the phase or ground minimum trip level, the control begins a user selected time-current curve (TCC) delay sequence. At the completion of the programmed TCC delay, a signal is issued to trip the VFI interrupter on the respective load tap. Cabinet Construction 4 Provisions are included for padlocking the cabinet in order to prevent unauthorized door opening. The cabinet must be locked at all times to prevent accidental contact with hazardous voltage. Type PST-9 switchgear features deadfront, tamperresistant, low-profile construction. It is suitable for operation in demanding indoor and outdoor applications. Cabinets meet the enclosure security requirements of ! S285-60-1 SAFETY FOR LIFE CI Interrupter Switch S2 Manual Operating Lever Interrupting Switch Manual Spring Charge Operator CI Interrupter Switch S1 Operation Counter Interrupting Switch Spring Charge Indicator CI Interrupter Switch S1 Status Indicator Nameplate CI Interrupter Switch S1 Manual Operating Lever One-line Diagram Type S Transfer Control Enclosure Source 2 Bushings Source 1 Bushings Potential Transformer Dead-break Disconnect Switch Figure 4. PST-9 Source-Side Features. 00016KM Pressure Relief Valve VFI Interrupter Operating Handle Oil Fill Plug Tri-Phase/TPG Control VFI Interrupter Operating Handle Tri-Phase/TPG Control Oil Level Indicator One-line Diagram Oil Drain Plug and Sampler Tap 1 Bushings Figure 5. PST-9 Tap-Side Features. 1/2 - 13UNC Stainless Steel Ground Nut - Typ. Tap 2 Bushings 02030KM 5 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions ANSI standard C57.12.28. Tank construction is of 10gauge steel, and doors are made of 12-gauge steel. Recessed lifting provisions are provided at each corner of the tank for a balanced lift. Side-hinged, cabinet style doors are provided with door stays and fitted with stainless steel hinges. Both source and tap doors can be fully open at the same time. Each door has a floating lock pocket with padlock provisions and penta-head silicon bronze door bolt. Cabinet Finish PST-9 switchgear is finished in a green color, which conforms to Munsell 7GY 3.29/1.5 Green. The coating conforms to the following specifications: ANSI standard C57.12.28, ASTM B1117 1000-hour 5% salt spray corrosion test, ASTM D2247 1000-hour humidity test, ASTM G53 500-hour ultraviolet accelerated weathering test, and ASTM D2794 impact test. Figure 6. CI Interrupter Switch Trip-Reset Lever. 00018KM Interrupter Duty Cycle The CI and VFI interrupter mechanism conforms to the duty cycle requirements of ANSI C37.60. Switch Test Sequence The VFI operating mechanism conforms to the switch test sequence requirements of ANSI C37.72. Nameplate Prior to installation, check the nameplate ratings. Verify the overall current and voltage ratings, transformer ratings and one-line diagrams are correct for the planned installation. Operating Handles WARNING: Hazardous voltage. Never rely on the open position of the operating handle or the contact position indicator; it does not ensure that the line is de-energized. Follow all locally approved safety practices. Failure to comply can result in contact with high voltage, which will cause death or severe personal injury. G123.1 ! Type PST-9 switchgear is equipped with shotgun stick operable loadbreak switch handles for operation of the CI source-side and VFI tap-side interrupter switches. The operating handle of CI interrupter switches provides incremental travel between the trip, close, and reset positions of the switch (Figure 6). CI interrupter trip-reset levers may be padlocked in the tripped position. The Type VFI interrupters are equipped with hotstickoperable handles that are located on the tap-side of the unit. VFI operating handles are factory configured for either ganged three-phase operation (all three phases operated simultaneously with a single handle) or singlephase operation (each phase operates independently). The operating handle (Figure 7) provides convenient push-to-close and pull-to-open operation. VFI operating handles may be padlocked in the open position. 6 931158KMA Figure 7. VFI operating handle, three-phase ganged operation. Weight The weight of the switchgear is shown on the nameplate. Make sure that lifting equipment used is rated sufficiently to safely handle the switchgear. ! S285-60-1 SAFETY FOR LIFE RATINGS AND SPECIFICATIONS Table 1 Electrical Ratings PST-9 Transfer Switchgear Description Maximum Design Voltage, kV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BIL, kV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-Minute Withstand Voltage (60 Hz) Interrupter and Terminators, kV Continuous Current (max), A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interrupting Current (sym./asym.), kA . . . . . . . . . . . . . . . . . . . . . . . Momentary Current 10 cycles (asym.), kA . . . . . . . . . . . . . . . . . . . . 3 Second Withstand Current (sym.), kA . . . . . . . . . . . . . . . . . . . . . . Making Current (sym.), kA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transformer Magnetizing Interrupting Current, A . . . . . . . . . . . . . . . Cable Charging Interrupting Current, A . . . . . . . . . . . . . . . . . . . . . . Table 2 Interrupting Duty Cycle Percent of Interrupting Current Rating 15 - 20 45 - 55 90 - 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15kV 25kV 35kV 15.5 95 34 600 12/20 20 12 12 21 10 27 125 40 600 12/20 20 12 12 21 25 38 150 50 600 12/20 25 12 12 21 40 Table 3 Switching and Transfer Times Number of Operations Direction of Transfer 88 112 32 232 Total Preferred to Alternate Alternate to Preferred Alternate to Preferred Type of Return Transition First Interrupter Reaction Time * (Cycles) Transition Time** Cycles Non-Parallel Non-Parallel Parallel 2.0 to 3.0 2.0 to 3.0 5.0 to 6.0 5.0 to 6.0 5.0 to 6.0 2.0 to 3.0 * Time from expiration of time delay to first opening (or closing) of high-voltage interrupter. Add about 1 cycle to values shown to allow for S control relay time. * * Time load tap is disconnected or parallel, dependant upon transition used. All Cabinets 48" High Table 4 Overall Dimensions 15/25 kV 35 kV Bushing Rating Source / Tap A B C D 600 A / 200 A 95 70 36 16 600 A / 600 A 101 70 36 22 200 A / 200 A 89 70 30 16 600 A / 200 A 103 70 40 20 600 A / 600 A 109 70 40 26 200 A / 200 A 97 70 34 20 Tap Cabinet Overall Rating Source Cabinet Dimensions (in) Unit Description C 30" 32 A B D 30" 7 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions LOAD TRANSFER FUNCTIONALITY TYPE S Automatic Load Transfer Control Operation The Type S Load Transfer Control monitors the source voltage taps and provides the timing and control logic required to perform the automatic load transfer in the event of a voltage loss. The control commands the operations of the two Type CI interrupter source switches during auto transfer. The three-phase voltage on Source I and Source II is sensed by 6 internal potential transformers (Figures 8 and 10). The control senses and interprets 85 percent of applied voltage and above as normal voltage and 65 percent of applied voltage and below as loss of voltage. When the value of the preferred source drops below 65 percent, the S Control initiates a programmed transfer of the load to the alternate line source. The face of the control (Figure 9) provides visual indication of the status of each Cl interrupter, control settings, and manual operation capabilities. The transfer operation is programmed on the control panel; digital timer settings and switch settings permit complete program flexibility to coordinate with other system operating parameters. The control requires 120 Vac, 50/60 Hz, 500 VA to operate the transfer switches. Quiescent power dissipation at 120 Vac is 18 watts. No external source of power is required for the control as the 120 Vac power requirement is supplied by the B-Phase (Source I) and Y-Phase (Source II) inputs from the internally mounted potential transformers. Preferred Mode Operation The following is a typical Preferred Mode automatic load-transfer sequence (Figure 8): The load is transferred to the alternate source, after completing a preset time delay, when one or more phases of preferred source voltage is lost and normal voltage is present on the alternate source. The load is then transferred back to the preferred source, after completing a preset time delay, when normal voltage is restored to the preferred source. The return transfer can be either non-parallel (NP) in which the alternatesource switch opens before the preferred-source switch closes, or parallel (P) in which the preferred-source switch closes before the alternate-switch opens. With parallel return, the second outage is eliminated; however, both sources must be in phase. The return-transfer mode is selected by setting the Source Preference Switch (S4). CAUTION: Equipment misoperation. Source I and Source II high voltage switches can be paralleled in the manual operation mode even if SOURCE PREFERENCE switch, S4, is set for NP (non-parallel operation). Make sure both sources are in synchronism if a manual parallel operation is to be performed. Failure to comply can result in misoperation (unintended operation) and equipment damage. T304.0 CI Switch CI Switch S Control S1 Preferred Source N.O. N.C. VFI VFI Tri-Phase/TPG Control T1 T2 Sequence 1: Tri-Phase/TPG Control PST-9 Unit during normal operating conditions Closed CI Switch Open CI Switch S Control S1 Preferred Source VFI VFI Tri-Phase/TPG Control T1 T2 Sequence 2: S2 Alternate Source Tri-Phase/TPG Control PST-9 Unit switched to alternate voltage source after loss of preferred voltage source CI Switch CI Switch S Control S1 Preferred Source N.O. N.C. VFI Tri-Phase/TPG Control Sequence 3: VFI T1 T2 S2 Alternate Source Tri-Phase/TPG Control PST-9 Unit after restoration of preferred voltage source Figure 8. PST-9 Load Transfer Functionality. 8 S2 Alternate Source ! S285-60-1 SAFETY FOR LIFE SWITCH I STATUS INDICATOR LAMPS LAMP TEST SWITCH SWITCH II STATUS INDICATOR LAMPS ALTERNATE TO PREFERRED TIMER PREFERRED TO ALTERNATE TIMER MANUAL OPERATION SOURCE I AND SOURCE II SWITCHES (S1, S2) OPERATION SELECTOR SWITCH (S3) SOURCE I ENERGIZED LAMP SOURCE II ENERGIZED LAMP CONTROL MODE SWITCH (S5) SOURCE PREFERENCE-AND-RETURN MODE SELECTOR SWITCH (S4) FUSES Figure 9. Type S Transfer Control Front Panel Details. 00019KM Either Source I or Source II can be selected as the preferred (PREF 1 or PREP II) source by setting the Source Preference-and-Return Mode Selector Switch S4. ferred source. Moving Control Mode switch S5 to the NORMAL position during return sequence inhibition will cause immediate return to the Preferred Source. No Preference Operation Each switch can be independently opened and closed manually by setting Operation Selector Switch S3 to MANUAL and operating MANUAL OPER. SOURCE S1 and MANUAL OPER. SOURCE S2 switches as required. When either source is acceptable for continuous critical load supply, the Source Preference-and-Return Mode Selector Switch S4 may be set to the No Preference Operation (NO PREF) position. Upon loss of Source I voltage, and after a preset time delay, the load is automatically transferred to Source II if normal voltage is present on Source ll. However, the load is not transferred back when Source I voltage is restored, but remains on Source II indefinitely, until a loss of voltage on Source II initiates an automatic transfer to Source 1. Hold on Alternate Operation For some loss-of-voltage protection schemes it may be preferable to inhibit return to the preferred source from the alternate source upon restoration of the preferred source voltage. By placing Control Mode switch S5 into the HOLD ON ALTERNATE position, manual operation of the switches is required to transfer back to the pre- Manual Operation CAUTION: Parallel connection of sources is possible when manually closing CI interrupters. If parallel connection of sources is not desired do not operate the trip-reset levers of both CI interrupters into the closed position. T275.0 IMPORTANT: If Control Mode Switch S3 is placed in the “AUTO” position, the S-control will place the highvoltage Type CI transfer switches into the configuration that is currently selected by the Source Preference Switch S4. This may result in an unintended transfer. Make sure the desired state of the high-voltage Type CI transfer switches match the setting of S4 before returning S3 to the “AUTO” position. 9 Figure 10. PST-9 Automatic Source Transfer Switchgear Schematic. To TPG Control Receptacle "CT 1" To S Control Receptacle "SW" 10 PT SW CT To S Control Receptacle "PT" D H B A C F G E K H G M L J D B A F E C G M L N H B A K J C F D E GRY YEL RED BRN VIO ORG BLU GRN BLK GRY WHT/RED VIO WHT/BRN WHT YEL RED BRN BLU GRN ORG VIO 7 8 6 3 4 5 1 2 TB3 9 10 4 5 6 7 8 3 1 2 TBC2 9 10 6 7 8 5 4 1 2 3 TBC1 C ø F.S.T. (–) C ø F.S.T. (+) WHT/ORG WHT/RED GRY B ø F.S.T. (–) B ø F.S.T. (+) A ø F.S.T. (–) A ø F.S.T. (+) RED BRN WHT/BRN BLK WHT – TC + M CI Interrupter #1 BLU C. T. PROT R (NO) LS3 CC (NC) (NO) (NO) (NC) LS2 LS4 LS2 LS3 – TC + R (NO) LS3 CC (NC) (NO) (NO) (NC) LS2 LS4 LS2 LS3 M LS1 (NC) (NC) (NC) (NC) LS1 LS4 CI Interrupter #2 LS4 BRN RED ORG YEL GRN Aø Bø Cø WHT TB3-2 TB3-1 TB3-7 TB3-6 TB3-5 TB3-4 TB3-3 BLK BLK WHT BLK WHT H1 X1 RED RED RED Aø F.S.T. – X1 Bø F.S.T. – X1 Cø F.S.T. – X2 Phase Current Sensors – Cø F.S.T. – Bø F.S.T. – Aø F.S.T. X1 X2 H2 S1A CI Interrupter #1 X2 Aø VFI Interrupter #2 + H1 + S1B H2 X2 X2 Bø X1 H1 + X1 S1C H2 X2 X2 Cø H2 S2C H1 X1 H2 X2 X2 Cø X1 + S2B H1 X1 H2 X2 X2 Bø X1 + S2A H1 X1 X2 CI Interrupter #2 VFI Interrupter #1 Aø X1 + WHT BLK BLK WHT BLK WHT RED RED RED C. T. PROT Aø Bø Cø BLU BRN RED ORG YEL GRN WHT/RED WHT/ORG WHT GRY WHT/BRN BLK RED BRN ORG BLK BLK BLK BLK ORG GRN T1A BLU YEL T1B BLK T1C BLK T2C GRN T2B BLU YEL T2A VIO C ø F.S.T. (–) C ø F.S.T. (+) B ø F.S.T. (–) B ø F.S.T. (+) A ø F.S.T. (–) A ø F.S.T. (+) G M L N H B A K J C E F D CT Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions To TPG Control Receptacle "CT 2" ! S285-60-1 SAFETY FOR LIFE Operation of Interval Timer Table 5 Time Ranges of Interval Timer IMPORTANT: Put control in manual mode prior to changing timer setting. There is no loss of voltage protection when in manual mode. Failure to comply can cause unintended operation. The Type S automatic load transfer control features two digital timers with automatic reset. One timer controls the time required to transfer from the preferred source to the alternate source, the other timer controls the time to transfer from the alternate source to the preferred source. Each timer can be set for a minimum delay setting ranging from .01 seconds to 99.9 hours. The time-delay setting for preferred-to-alternate-source transfer must be long enough to allow discrimination between permanent loss of voltage and temporary loss of voltage due to transient effects or reclosing intervals of backup protective reclosers or breakers. The time delay for return from alternate to preferred source upon restoration of preferred-source voltage should be set for an interval long enough to assure that service on the preferred source has been permanently restored. When the S load-transfer control is programmed to operate in the no-preference mode, there are no preferred or alternate sources. Time-delay intervals for transfer from Source I to Source ll are governed by the left preferred-toalternate timer and for transfer from Source ll to Source I by the right alternate-to-preferred timer. The two digital timers used on the S Control feature the following informational indicators and adjustment controls: OUT Indicator OUT Digital Time Display 3.45 39 4 9 5 999 S Thumbwheel Time Setting 9.99 99.9 999 99.9 999 99.9 Indication S S S M M H Time Range 0.01 to 9.99 sec 0.1 to 99.9 sec 0.1 to 999 sec 0.1 to 99.9 min 1 to 999 min 0.1 to 99.9 hour Adjustment of Time Delay Settings IMPORTANT: Care must be taken while making adjustments to the thumbwheel time selector switches. Incomplete setting may cause timer malfunction and control misoperation. Time delay settings are made by rotating the thumbwheel selector switches to the desired numeric time setting (Figure 11). For example, if the thumbwheel time setting is 345 the timer will time out in 34.5 seconds based off the time range selector setting of 0.1 to 99.9 seconds. After setting the desired time setting, re-check the time range and decimal point position to verify that the time setting you have entered is correct. Note: The thumbwheel time setting, which does not turn infinitely, should not be turned beyond the limit. Out Indicator Function The out indicator briefly lights to signal completion of a timing interval and confirm that the timer has operated. For additional information regarding the operation and adjustment Kyle S Control refer to Service Information Bulletin S260-75-1, Kyle Type S Automatic Transfer Control Installation, Operating and Maintenance Instructions. Decimal Point Indicator Time Range Selector Figure 11. S Control Timer Details. Digital Time Display LED display of timer operation. Displays time count. Timer counts up until it reaches the time delay setting that was programmed with the thumbwheel switches. Time Range Selector The time range selector is used to select the range and the units of time (Figure 11). Use a small flat blade screwdriver to rotate the selector to the desired setting. For a specific unit of time (seconds, minutes, or hours) the range selected is indicated by the position of the decimal point indicator just above the selector window. The available ranges are shown in Table 5. 11 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions CI Interrupter Switch Type CI three-phase motor-operated source transfer interrupter switches (Figure 12) employ long-life vacuum interrupters. The vacuum interrupter contacts are opened and closed by a mechanism that releases stored spring energy. The separate opening and closing springs are automatically charged by a 120-Vac motor. The load transfer interrupter switches are electrically operated, receiving trip or close signals from the S automatic load transfer control. Solenoids receive the command signals and release the charged springs to effect a quick open or quick close operation of the vacuum contacts. Figure 14. Manual Push-Pull Spring Charging Operator. 00023KM Operating Modes The Cl switches can be tripped automatically, electrically, or manually operated; they can be closed electrically or manually provided the springs are charged. CI switch operating modes are: AUTOMATIC Figure 12. CI Interrupter Switches. 00022KM CI interrupting switches can be manually operated for test purposes or if operating power is lost. A hotstick operable, external trip-reset lever (Figure 13) allows switches to be opened and closed manually. An external push-pull operator is provided for manually charging the springs (Figure 14). The push-pull operator is easily operated with a shotgun stick. The CI Interrupter Switch Trip-Reset Levers (S1 and S2) must be in the RESET position for automatic load transfer control operation to occur. Tripping and closing of the CI transfer switches is initiated by a signal from the Type S Transfer Control. An opening signal briefly energizes the opening solenoid, releasing a latch and thus tripping the opening springs. A closing signal energizes the closing solenoid, tripping the closing spring. Closing is not permitted until the limit switch closes to indicate that the springs are charged. Automatic closing provision is not included. ELECTRICAL Non-automated opening and closing are initiated by operation of the open-close toggle switches SW1 and SW 2 (Figure 9) on the S Transfer Control front panel. Non-automated electrical opening and closing is permitted only when the S Transfer Control is operating in the manual mode. MANUAL Tripping and closing are initiated by operation of the manual trip-reset handles located on the source-side padmount tank. CI Interrupter Operating Sequences Figure 13. CI Interrupter Switch Trip-Reset Lever. 00018KM When the interrupter contacts are open and the 120 Vac supply to the spring charging motor is energized, the spring charging motor will charge the closing and opening springs. The CI Interrupters Trip-Reset Levers (S1 and S2) must be in the RESET position for this operation to occur. Upon receipt of a closing signal, a solenoidoperated latch releases the closing spring which drives the three vacuum interrupter contacts to their closed position. As the contacts are closed, the closing spring energy is 12 ! S285-60-1 SAFETY FOR LIFE fully discharged while the opening spring remains charged and latched. Upon receipt of an opening signal, a solenoid releases the opening-spring latch and the contacts of all three vacuum interrupters are simultaneously driven to their open position as the opening spring fully discharges. Immediately after the contacts reach full open, the spring charging cycle is repeated as the spring charging motor runs to recharge the springs. Recharging is completed in 20 seconds and both closing and opening springs are then latched and ready for future operations. Should the 120-volt motor power be lost while the interrupter contacts are open but after the springs have been charged, one contact closing operation can still be achieved through use of the trip-close handle on the mechanism tank. Likewise, after the interrupter has been closed, energy for one trip operation remains stored in the mechanism. Manual Operation of CI Interrupters With its manual spring-charging capability the Cl interrupter switches can be operated without the presence of the low-voltage motor supply from the S Control. WARNING: Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high and low voltage lines and equipment. G103.3 ! WARNING: Hazardous voltage. Never rely on the open position of the operating handle or the contact position indicator; it does not ensure that the line is de-energized. Follow all locally approved safety practices. Failure to comply can result in contact with high voltage, which will cause death or severe personG123.1 al injury. ! CAUTION: Equipment misoperation. Source I and Source II high voltage switches can be paralleled in the manual operation mode even if SOURCE PREFERENCE switch, S4, is set for NP (non-parallel operation). Make sure both sources are in synchronism if a manual parallel operation is to be performed. Failure to comply can result in misoperation (unintended operation) and equipment damage. T304.0 Manual Closing Of CI Interrupter CAUTION: Parallel connection of sources is possible when manually closing CI interrupters. If parallel connection of sources is not desired, do not operate the trip-reset levers of both CI interrupters into the closed position. T275.0 2. Observe the CI interrupter spring status indicator. If the indicator shows the springs are discharged, proceed with step 3. If the indicator shows springs are charged, proceed to step 5. 3. Move the CI Transfer Switch Trip-Reset lever to the TRIP position and then to the RESET position. 4. Using a shotgun stick, pull the spring charging handle approximately 30 times, or until the spring charging indicator switches from the white, "spring discharged" to the yellow, "springs charged" position. 5. Move the Trip-Reset lever to CLOSE. Interrupter contacts will close and handle will spring back to the RESET Position. IMPORTANT: Return of the S-Control Mode Switch S3 to the “AUTO” position, upon completion of manual CI switching operations, will place the high-voltage transfer switches into the configuration presently selected by Source Preference Switch S4. This may result in an unintended transfer. Make sure the desired state of the high-voltage CI transfer switches match the setting of S4 before returning S3 to the “AUTO” position. Manual Tripping of CI Interrupter 1. If the S control is in service, move the S Control Operation Selector toggle switch S3 to the MANUAL position to eliminate any unanticipated opening and closing of the CI source switches when Vac supply is restored. 2. Move the CI interrupter switch lever to the TRIP position. This action will release a trip in the operating mechanism, allowing the charging springs to drive the contacts to their open position. The trip-reset lever will remain in the TRIP position. The interrupter can not be closed by the S Control while the Trip-Reset Lever is in the TRIP position. IMPORTANT: Return of the S-Control Mode Switch S3 to the “AUTO” position, upon completion of manual CI switching operations, will place the high-voltage transfer switches into the configuration presently selected by Source Preference Switch S4. This may result in an unintended transfer. Make sure the desired state of the high-voltage CI transfer switches match the setting of S4 before returning S3 to the “AUTO” position. For additional information regarding the operation and adjustment of Type CI Vacuum Interrupters Switches refer to Service Information Bulletin S275-10-1, Kyle Type CI Three-Phase Fault Interrupters Installation and Operation Instructions. Manual closing during loss of 120 Vac supply can be accomplished by using the following procedure: 1. If the S Control is in service, move the S Control Operation Selector toggle switch S3 to the MANUAL position to eliminate any unexpected opening and closing of the CI source switches when Vac supply is restored. 13 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions OVERCURRENT PROTECTION FUNCTIONALITY Tri-Phase/TPG Electronic Trip Control The Tri-Phase Control and Tri-Phase with Ground Trip Control (TPG) (see Figures 15 and 16) are comprised of solid-state circuit boards and “plug-in” type time current curve (TCC) cards. Controls include DIP switches on the control circuit board and provide means to program control operation. Tri-Phase Control settings include unique minimum trip levels for each phase, activation and programming of the instantaneous trip feature, and selection between single and three-phase tripping. TPG Control Settings include unique minimum trip levels for each phase and minimum trip levels for ground, a ground trip block ON/OFF switch, activation and programming of the instantaneous trip feature for both phase and ground, and selection between independent or three-phase ganged tripping. On both controls, independent trip operation is only possible when operating a Kyle VFI or PST-9 that is equipped with three individual single-phase trip handles. When line current, on any phase, exceeds the programmed minimum trip level, the Tri-Phase or TPG electronic control issues a trip signal, which causes the switchgear to trip open. Ground Trip Block Switch S7 Figure 15. TPG Control (Tri-Phase Control not shown). 98009KM In VFI applications with three single-phase trip handles, the control can be switched for single-phase operation. This mode allows independent interruption of the faulted phase(s). When switched for three-phase operation, a fault detected on any phase causes the simultaneous interruption of all three phases. Both controls make use of internally mounted 1000:1 ratio current sensing transformers (CT) to monitor line current. If the current sensed is greater than the programmed minimum trip level, the control will begin a user-selectable TCC delay. At the completion of the time delay, a signal is issued which causes the fault interrupting switchgear to trip. Controls are powered by system current, via the CTs. The controls require no external voltage supply or battery backup and are not affected by system voltage conditions (such as overvoltage transients). TPG controls make use of the same internally mounted 1000:1 ratio current-sensing transformers (CTs) on each phase to monitor line current used for phase tripping. Additional CTs are not required. If the Ground Trip feature is activated when phase imbalance exceeds the programmed minimum trip level, the TPG electronic control issues a trip signal, causing the VFI mechanism to trip OPEN. The Ground trip feature of the TPG control may be blocked by setting Ground Trip Block Switch S7 (Figure 15), located on the TPG board, to the “On” position. If the Ground Trip feature is not blocked, then a permanent phase current imbalance that exceeds the programmed minimum trip level will cause the control to time-out and issue a trip signal. 14 01082KM Figure 16. TPG Control Enclosure on Inside of Tap-Side Door. For additional information regarding the operation and adjustment of Kyle Tri-Phase and TPG Controls refer to Service Information Bulletin S285-75-1, Kyle Tri-Phase, TPG, and TPG w/SCADA Electronic Control Installation and Operation Instructions. ! S285-60-1 SAFETY FOR LIFE VFI Vacuum Fault Interrupters Type VFI vacuum interrupters provide fault current interruption and load make/break switching capabilities. Shotgun stick operable operating handles are located on the front plate of the unit. VFI operating mechanisms can be factory configured for either single- or ganged threephase operation. WARNING: Hazardous Voltage. Always use a shotgun stick when working with this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. ! G108A.0 The VFI operating handles (Figures 5 and 18) are located on the tap-side, front plate of the PST-9 unit. The VFI operating handles must be operated with a shotgun stick. Opening VFI Interrupters Flux Shift Tripper The VFI vacuum fault interrupter is opened by pulling the operation handle down to the open position. The handle may be padlocked in the open position to prevent accidental closure. Vacuum Interrupter Figure 17. Vacuum interrupter assembly. 911072KMA Current sensing transformers, located inside the switchgear tank, provide line current information to the TriPhase or TPG control. When line current exceeds the minimum trip setting the control initiates a signal, which causes the VFI to interrupt the circuit. Interruption may be single- or three-phase, depending upon the configuration of the control and VFI interrupter. Manual VFI Operation 931158KMA Figure 18. VFI operating handle, three-phase ganged operation. Resetting VFI Interrupters WARNING: Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high and low voltage lines and equipment. G103.3 After the VFI mechanism has tripped, as the result of a fault condition, the mechanism must be reset before it can be closed. To reset the mechanism, firmly pull the operating handle down toward the ground until the latch resets. After the latch has been successfully reset, the VFI interrupter mechanism can be closed normally. WARNING: Hazardous voltage. Never rely on the open position of the operating handle or the contact position indicator; it does not ensure that the line is de-energized. Follow all locally approved safety practices. Failure to comply can result in contact with high voltage, which will cause death or severe personal injury. G123.1 Closing VFI Interrupters ! ! WARNING: Do not operate this equipment out of oil. Oil is the electrical insulating medium within this equipment; operation out of oil will result in internal flashovers that will damage the equipment and can cause death or severe personal injury. G104.2 ! The VFI vacuum fault interrupter is closed by briskly pushing the handle up, into the closed position. For additional information regarding the operation of Kyle Type VFI Vacuum Fault Interrupters, refer to: Service Information Bulletin S285-10-1, Kyle Type VFI, Oil Insulated, Vacuum Fault Interrupter; Installation, Operation, and Maintenance Instructions. 15 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions INSTALLATION PROCEDURES WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury, and equipment damage. ! CAUTION: Follow all locally approved safety practices when lifting and mounting the equipment. Use the lifting lugs provided. Lift the unit smoothly and do not allow the unit to shift. Improper lifting can result in equipment damage. G106.2 G102.1 1. Check oil level. Make sure the oil in switchgear tank is at the proper level by checking the oil level indicator on the source-side and tap-side panels; both indicators should be at the proper level. CAUTION: Equipment damage. Never place jacks, tackle or other attachments under the unit for the purpose of lifting. Failure to comply will result in damage to the equipment. T240.0 2. Test oil dielectric strength. If the switchgear has been stored for some time, or is being relocated, perform a dielectric test on the oil in accordance with ASTMapproved testing procedures. 4. Mount switchgear on concrete pad. NOTE: R-TEMP® or Envirotemp® FR3™ dielectric fluid may be provided instead of insulating oil, if specified at the time of order. Refer to manufacturer’s instructions for specifications and ASTM-approved testing procedures. CAUTION: The use of R-TEMP® and Envirotemp® FR3™ dielectric fluids is limited to a minimum operating temperature of 0 C°(32° F). T307 .0 CAUTION: This equipment relies on oil to provide electrical insulation between components. The dielectric strength of the oil must be checked on a regular basis, as part of the routine maintenance inspection, to ensure that it is at or above minimum dielectric requirements. Use of this equipment with insulating oil that does not meet minimum requirements can result in internal flashovers that will damage the equipment and can cause personal injury. G107.2 A. The switchgear must be installed on a level concrete pad or structure that has been designed to support the size and weight of the unit. B. The switchgear must be hoisted only by the recessed lifting provisions provided at the four corners of the tank. Suitable lifting straps must be used to prevent damaging the switchgear housing. WARNING: Hazardous voltage. Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. ! T223.2 ! A. In new equipment, the oil must have a minimum dielectric strength of 26 kV. If the dielectric strength of the oil is less than 26 kV, filter the oil to restore its dielectric strength to acceptable minimum level. B. For additional information on oil specifications and tests, refer to Reference Data R280-90-1 and to the oil testing procedures detailed on pages 20-22 of this manual. 3. Check the nameplate ratings. Verify the overall current and voltage ratings, transformer ratings and one-line diagrams are correct for the planned installation. 5. Ground switchgear. Switchgear must be adequately grounded. Make a permanent, low-resistance, ground connection at the 1/2”-13 UNC connectors located at the bottom of the switchgear front plates (refer to Figure 5). The Type S automatic load transfer control is grounded to the source-side front plate of the switchgear tank with a woven grounding cable. 6. Make high-voltage line connections. A. Prior to making connections, verify the source-side preferred and alternate elbows, and tap-side elbows are correctly identified. Verify the PST-9 unit is oriented correctly for the installation; the source leads must connect to the source bushings, tap leads must connect to the tap bushings of the unit. B. Refer to the operation one-line diagram located inside the doors of the switchgear and make only those elbow connections shown. The voltage and current ratings shown on the nameplate must be correct for the planned installation. C. All cables or bushings not in use must be properly isolated from all other leads. Unused leads must be parked on standoff insulators, or properly grounded using an elbow grounding kit 7. Close and lock switchgear doors. Switchgear doors must be closed and locked in order to prevent unauthorized access and accidental contact with high voltage. 16 ! S285-60-1 SAFETY FOR LIFE Initial Mechanical Operation Check 2. Verify CI interrupter springs are discharged by moving both yellow Trip-Reset levers to the CLOSE position. WARNING: Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high and low voltage lines and equipment. G103.3 ! WARNING: Hazardous voltage. Never rely on the open position of the operating handle or the contact position indicator; it does not ensure that the line is de-energized. Follow all locally approved safety practices. Failure to comply can result in contact with high voltage, which will cause death or severe personal injury. G123.1 ! 3. If CI interrupter switch S1 is closed, open it by operating the yellow trip-reset lever above the S1 bushing to the TRIP position. Position indicator will show a green OPEN flag (Figure 13). 4. Move the yellow trip trip-reset lever to the RESET position. 5. Pull the spring charging operator handle approximately 30 times, or until the spring charging indicator switches from the white, "spring discharged" to the yellow, "springs charged" position (Figure 20). WARNING: Do not operate this equipment out of oil. Oil is the electrical insulating medium within this equipment; operation out of oil will result in internal flashovers that will damage the equipment and can cause death or severe personal injury. G104.2 ! WARNING: Hazardous Voltage. Always use a shotgun stick when working with this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. ! G108A.0 With the PST-9 unit out of service and completely deenergized conduct the following test: 1. At the SW receptacle of the S-Control disconnect the cable connecting to the corresponding SW receptacle located on the source-side front plate of the tank (Figure 19). Figure 20. Push-Pull Charge Spring Operator Indicator before and after manual charging of CI Interrupter Switch. 6. Move the yellow trip-reset lever to the CLOSE position. 7. Switch S1 should close with an audible "thunk" and position indicator should switch to a red "closed" flag. 9. Repeat steps 2-6 for CI interrupter switch S2. PT 10. Re-connect the cable previously disconnected between source-side tank receptacle SW and S Control enclosure receptacle SW. SAFETY INSTRUCTIONS PT 00023KM 8. Move the yellow trip-reset lever to the TRIP position. Unit should trip open and position indicator should read open. SW S Control Enclosure Panel 00024KM SAFETY INSTRUCTIONS SAFETY INSTRUCTIONS SW Figure 19. Disconnection of CI Interrrupter Switch Cable at SW receptacle of S Control enclosure. 17 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions Initial Electrical Operation Check Terminal Strip TB2 WARNING: Hazardous voltage caused by backfeeding of transformers. Isolate potential transformers from source bushings using potential transformer dead-break disconnect switches located on the source-side panel. Failure to do will result in risk of possible contact with high voltage at the source bushings, which may cause death or severe personal injury. ! T273.0 With the PST-9 out of service and de-energized, isolate the potential transformers to eliminate risk of contact with hazardous voltage caused by transformer backfeeding during testing operations. Isolate the transformers with the following procedure. Figure 22. Location of terminal strip TB2 behind face panel of Type S Transfer Control. 1. At the PT receptacle of the S Control disconnect the cable connecting to the corresponding PT receptacle located on the source-side front plate of the tank (Figure 21). A B C G G X Y Z SW 120 VAC PT S Control Enclosure Panel Figure 23. Connection of AC power for initial electrical operation testing of the PST-9 unit. SAFETY INSTRUCTIONS PT SAFETY INSTRUCTIONS 3. Jumper terminal Z to Y to X, and C to B to A. SAFETY INSTRUCTIONS SW Figure 21. Disconnection of Potential Transformer Cable at PT receptacle of S Control enclosure panel. 2. Disconnect the switchgear’s internal potential transformer via the six manually operated dead break switches located below each source bushing (Figure 4). 3. Install insulating caps on all source and tap bushings. Verify proper electrical operation using the following procedure: 1. Place the yellow CI Interrupter Switch Trip-Reset levers, located on the source side panel, into the RESET position. 2. Connect 120 Vac, 60 Hz power supply to terminals B and Y of Terminal Strip TB2 of the S Transfer Control. Connect the grounded side of the power supply to terminal G (Figures 22 and 23). 18 4. The spring charging motor of one or both CI interrupter switches, depending on whether the respective interrupter springs are charged or discharged, should begin to operate after completion of steps 1-3. Motor spring charging takes approximately 30 seconds. ! SAFETY FOR LIFE S285-60-1 Initial S Control Operation Check CAUTION: Equipment misoperation. Source I and Source II high voltage switches can be paralleled in the manual operation mode even if SOURCE PREFERENCE switch, S4, is set for NP (non-parallel operation). Make sure both sources are in synchronism if a manual parallel operation is to be performed. Failure to comply can result in misoperation (unintended operation) and equipment damage. T304.0 To place the Type S Transfer Control into service, proceed as follows: 1. The switches on the S-Control front panel should be positioned as follows: A. S1 (MANUAL OPER. SOURCE 1)— OFF B. S2 (MANUAL OPER. SOURCE ll)— OFF C. S3 (OPERATION SELECTOR) — MANUAL D. S4 (SOURCE PREFERENCE AND RETURN MODE)—set to the desired mode of operation. E. S5 (CONTROL MODE)—NORMAL 2. Set the PREFERRED TO ALTERNATE TIMER and ALTERNATE TO PREFERRED TIMER as required. 3. Make sure both high-voltage CI transfer switches are open. 4. With all six fuses in place, energize both power sources to the control. A. SOURCE I ENERGIZED lamp should be on. B. SOURCE ll ENERGIZED lamp should be on. C. SWITCH I OPEN lamp should be on. D. SWITCH ll OPEN lamp should be on. 5. Depending upon which source is the preferred source, momentarily operate either S1 or S2 to the CLOSE position. The appropriate switch will close to energize the load and its status indicating lights will transfer from OPEN to CLOSED. 6. Place the OPERATION SELECTOR SWITCH (S3) to AUTO. The S control is in service. No further operation will occur until the preferred source voltage is lost. 7. To simulate loss of voltage on any phase of either source, simply unscrew the appropriate fuse "FU" from the preferred source, per S4 switch position, and wait for the digital timer to time out and initiate transfer to the alternate source. For additional information regarding the operation and adjustment Kyle S Control Refer to Service Information Bulletin S260-75-1, Kyle Type S Automatic Transfer Control Installation, Operating and Maintenance Instructions. 19 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions MAINTENANCE CAUTION: This equipment requires routine inspection and maintenance to ensure proper operation. If it is not maintained, it can fail to operate properly. Improper operation can cause equipment damage and possible personal injury. G105.1 ! CAUTION: This equipment relies on oil to provide electrical insulation between components. The dielectric strength of the oil must be checked on a regular basis, as part of the routine maintenance inspection, to ensure that it is at or above minimum dielectric requirements. Use of this equipment with insulating oil that does not meet minimum requirements can result in internal flashovers that will damage the equipment and can cause personal injury. G107.2 ! The Type PST switchgear is a deadfront design. All live parts are contained within the sealed tank enclosure. A routine maintenance inspection program is required to ensure proper operation. It is necessary to establish and maintain a regular schedule for sampling and testing the insulating oil to ensure proper dielectric strength and to maintain the proper oil level in the switchgear. Maintenance Inspection Procedure The Type PST switchgear must be de-energized, grounded and removed from service before conducting any maintenance, oil sampling or oil-filling procedures. WARNING: Hazardous voltage. This equipment must be de-energized and grounded prior to conducting any maintenance, oil sampling or oil filling procedures. Failure to comply can result in death or severe personal injury. T239.1 ! 1. De-energize and ground switchgear. 2. Reduce internal tank pressure to 0 PSIG. The switchgear is equipped with a pressure relief valve that opens at 5 PSIG and closes at 3 PSIG. To relieve internal tank pressure pull the ring on the pressure relief valve. 3. Check oil level. Make sure the oil in the switchgear tank is at the proper level by checking the oil level indicators located on the source and tap sides of the PST unit. NOTE: Refer to Insulating Oil Maintenance, on page 21, for additional information regarding oil maintenance and testing requirements. 4. Inspect for damage. Check for unusual wear to the paint finish. Check bushings and elbows. Make sure connections are secure. Check for oil leaks or other unusual or abnormal indications of wear or abuse. Make sure that cabinet doors will lock securely. Record any unusual conditions. 20 Internal Inspection and Repair If internal damage is suspected, or if the switchgear must be opened for inspection, the following procedure is recommended. 1. De-energize and ground switchgear. 2. Draw an oil sample. Use the drain plug with sampler at the bottom of the tank. If moisture is found in the tank, re-fill with clean, dry insulating oil. 3. Clean off tank cover. Take appropriate precautions to keep dirt, moisture and other foreign matter from entering tank and contaminate the insulating oil. 4. Remove tank cover. 5. Inspect for internal damage. Check inside the switchgear for broken leads or loose parts. If any bushings or interrupters are damaged repair as required. 6. Bushing repairs. The bushings can be changed with the tank cover removed. A. Lower the oil level as needed to make repairs. Store the drained oil according to locally approved procedures. B. Disconnect the internal cables and leads. C. Unbolt external steel clamps from the front plate and replace any damaged bushings, or bushing wells, with new parts and a new gasket. Be sure to position gasket so it will seal properly. 7. Interrupter repairs. Contact your local Cooper Power Systems Division sales representative for additional information and ordering procedures. 8. Replace tank cover. Secure with original hardware. The cover gasket may be reused if it is not damaged. 9. Re-fill with insulating oil. Refer to the Oil Sampling and Testing Procedures in this manual and make sure that the unit is properly filled to the 77° F (25° C) oil fill level with clean, dry insulating oil. 10. Close and lock doors. After repairs are completed close and lock switchgear doors, in order to prevent unauthorized access and accidental contact with high voltage lines. ! S285-60-1 SAFETY FOR LIFE Insulating Oil Maintenance Oil Sampling Guidelines To assure trouble-free operation of this equipment, a regular schedule of oil testing and oil maintenance is required. A routine oil testing and maintenance schedule is necessary to monitor changes that occur in the oil as a result of normal operation and to detect abnormal conditions that may occur. Use the following oil sampling guidelines in order to prevent contamination of the samples taken: Maintaining a record of this test data will help in assessing the condition of the oil over time. Note: R-Temp® or Envirotemp® FR3™ dielectric fluid may be provided instead of oil, if specified at time of order. Refer to manufacturer’s instructions for specifications and ASTM-approved testing procedures. Frequency of Maintenance The insulating oil should be initially tested within two years after the installation of the equipment. That test will yield information required to establish a benchmark reference for observing trends in the unit’s normal operation and to diagnose any fault conditions that may be present. After the initial oil testing and inspection, vacuum switchgear should be maintained every six years. Each scheduled padmounted switchgear maintenance activity should include a physical inspection of the unit, an oil level check and oil testing as described in the Oil Testing section of this manual. Types of Oil Samples The unit must be de-energized before collecting an oil sample. Collecting an oil sample from a unit that has critically low oil level could result in flashover and unit failure when the unit is re-energized. Never energize this equipment without ensuring that it is filled to the proper oil level with clean, dry insulating oil. 1. De-energize and ground the switchgear prior to sampling oil. 2. Never collect an oil sample immediately after oil has been added. A stabilization period of 96 hours is required prior to sampling. 3. Never sample oil during inclement weather (rain, sleet, or snow). The oil sample could be contaminated by moisture. 4. Always use the drain plug and sampler, located near the bottom of the front plate of the tank, to collect oil samples. 5. Use only approved oil-resistant materials, such as nitrile rubber or silicone tubing, for sampling the oil. Use of other materials can result in contamination of the oil sample. 6. Be careful to prevent contamination of the oil sample from foreign material such as dirt, dust, chemicals, etc., in oil carrying and holding apparatus such as oil cans, transfer tubes, syringes, etc. 7. Upon completion of the sampling, recheck the oil level, and add oil if required. Oil Fill Guidelines The oil level indicator sight gauge on the front plate of the switchgear provides a convenient method to check oil level. The indicator provides the correct level for oil at 77° F (25° C). If the oil level is low, use the following procedure to add dry mineral insulating oil to fill the unit to the correct level: The oil sampling procedure requires that two types of oil samples be taken. 1. De-energize and ground the switchgear prior to oil filling. 1. A bulk oil sample to be used for general oil tests. Approximately one quart (one liter), taken in accordance with ASTM D923 (latest revision), is required. 2. Use only insulating oil that complies with ASTM D3487 (latest revision). The oil must have a minimum dielectric strength of 30 kV when tested per ASTM D877. Never use oil that contains PCB’s (Polychlorinated Biphenyls). 2. A "gas-tight" oil sample taken in accordance with ASTM D3613 (latest revision), for diagnosis and fault gas analysis. 3. Use only transfer equipment that uses oil resistant materials for hoses, seals, valves, pumps, etc. Failure to use proper transfer equipment can result in contamination of the oil. 4. When adding oil, use the oil fill plug located on the front plate of the unit. 21 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions 5. Avoid getting gas bubbles in the oil during filling. Gas bubbles in the oil can reduce the dielectric strength. 6. When filling is complete, check the oil level gauge to verify that the oil is filled to the correct level. Allow at least one hour for gas bubbles to dissipate prior to energizing the unit. 7. Replace oil fill plug and energize the unit. 8. Record the date and the amount of oil needed to refill the unit; retain information with the permanent maintenance record of the unit. Table 7 Dissolved Gas In Insulating Oil Maintenance Chart Total Acetylene Level CombustC2H2 ible Gas Required Action Less than 35 ppm Less than 500 ppm Normal Level Resample per routine maintenance schedule 35–50 ppm 500 – 1000 ppm Caution Level Resample at 3–6 months to establish trend; main tain oil if gas levels increase to hazardous level. More than 50 ppm More than 1000 ppm Hazardous Level Remove unit from service and maintain the oil. Oil Testing The insulating oil in this equipment has been tested to meet the requirements of ASTM D3487, and it has been processed to remove moisture and dissolved gases. It must be tested on a regular basis in order to ensure that it meets those requirements. Two types of oil tests are required to evaluate and maintain the quality of the insulating oil. They are general oil tests and dissolved gas analysis. General Oil Tests The general oil test requirements are taken from IEEE Standard C57.106-1991, IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment. The required oil tests and acceptable limits for service-aged oil are shown in Table 6. Oil test results that do not meet the requirements may indicate a problem with either the oil or the unit. Contact your Cooper Power Systems representative for technical assistance. Table 6 Test Limits for Service-Aged Oil Oil Test Dielectric Strength Acid Number Dissipation Factor Interfacial Tension Moisture Content Method Requirement D877 D974 26 kV minimum 0.20 mg KOH/g maximum D924 D971 D1533 1.0% maximum 24 mN/m minimum 35 ppm maximum Dissolved Gas Analysis Dissolved gas analysis is a useful technique for diagnosing abnormal conditions and assessing the “normal” condition of oil in oil-filled equipment. The method employed is ASTM D3612, which is used in conjunction with ANSI/IEEE C57.104-1987, IEEE Guide for the Detection and Determination of Generated Gases in Oil-Immersed Transformers and their Relations to the Serviceability of the Equipment. Table 7 provides recommendations on dissolved gas levels in oil-insulated switchgear. 22 ! S285-60-1 SAFETY FOR LIFE TESTING All padmounted switchgear is carefully tested and adjusted at the factory to operate according to published data. Well-equipped test facilities, a detailed testing procedure, and thoroughly trained personnel assure accurately calibrated equipment. Each unit leaves the factory ready for installation. Trip Test The Kyle KSCE11 Tri-Phase Tripper Tester can be used to verify the operation the VFI trip mechanisms. Contact your local Cooper Power Systems representative for tester ordering information. To perform test: Pre-installation testing is not necessary. However, should verification of switchgear operation prior to installation be required, the vacuum interrupters can be tested using the following procedures 1. De-energize and ground switchgear. High-Potential Withstand Testing of Vacuum Interrupters 4. Close VFI trip handles. High-potential withstand tests can be performed to check the vacuum integrity of the interrupters used in VFI switchgear. Safety Requirements To prevent accidental contact with high-voltage parts, the switchgear and high-voltage transformer must be placed in a suitable test cage and all proper grounding procedures must be observed. 2. Open TPG control enclosure door. 3. Remove cable harness from control circuit board and attach to tripper tester. 5. Press button for desired phase for one second, VFI mechanism should trip. Allow two seconds between tests. Repeat test with other phases, as applicable. If a VFI interrupter(s) fails to trip properly, check battery in tester and repeat test. If the mechanism still fails to trip properly, contact your local Cooper Power Systems representative for additional information and repair information. 6. Reconnect cable to control circuit board, and close TPG enclosure door. WARNING: Hazardous voltage. The switchgear and high voltage transformer must be in a test cage or similar protective device to prevent accidental contact with the high voltage parts. Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. T221.3 7. Close and lock switchgear doors, in order to prevent unauthorized access and accidental contact with high-voltage lines. CAUTION: Radiation. At voltages up to the specified test voltages, the radiation emitted by the vacuum interrupter is negligible. However, above these voltages, radiation injurious to personnel can be emitted. See Service Information S280-90-1, Vacuum Interrupter Withstand Test Voltage Ratings Information G109.2 for further information. Only factory-authorized replacement parts are to be used for Kyle Distribution Switchgear products. Replacement parts are available through the factory Service Department. To order replacement parts, refer to the nameplate and provide the product type, serial number, catalog number, voltage rating, and a description of the part. Contact your Cooper Power Systems representative for additional information and ordering procedures. ! ! With the vacuum interrupters open (manual operating handle(s) in the Open position), perform a high-potential test for one minute/ac (or 15 minutes/dc) across each open vacuum interrupter assembly at the voltages shown in Table 8. The interrupter should withstand the test voltage and should not load down the source. REPLACEMENT PARTS Table 8 High-Potential Withstand Test Voltages VFI Voltage Rating (kV) 15 25 35 High-Potential Test Voltages 25.5 kV ac RMS or 37.1 kV dc 30. kV ac RMS or 42.4 kV dc 37.5 kV ac RMS or 74.2 kV dc 23 Type PST-9 Automatic Source Transfer Switchgear Installation, Operation and Maintenance Instructions ! SAFETY FOR LIFE ©2002 Cooper Industries, Inc. Kyle®, R-Temp®, and Envirotemp® are registered trademarks of Cooper Industries, Inc. KA2048-0398 Rev: 01 P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com KBS 12/02