Switchgear Technical Data TD280015EN Effective July 2015 Supersedes R280-90-18 8/2012 COOPER POWER SERIES Communications Point Data Base for Serial and Ethernet Communications Protocol DNP3 For use with Eaton’s Cooper Power series Form 6 Recloser Control Form 6 DNP3 Device Profile Data Dictionary Form 6 DNP3 Map Points July 1, 2015 v3.00 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 1.01 Date 5/30/2001 5/30/2001 1.02 1.03 1.04 1.05 5/8/2002 10/30/2002 11/20/2002 8/29/2003 1.06 1.07 2.00 3.00 3/10/2004 10/28/2005 8/24/2012 7/1/2015 Description Initial release. Changed wording on SGF "enable" to "block" Made hot line tag CROBs self-resetting. Added Binary Input 59 as "CCI:Control Circuit Interrupted" Added CROBs 18 (Combined Trip / Close) and 19 (Sync-Check Enable) Changed nomenclature of binary inputs and outputs. Added TS crob definitions, updated counter & binary input definitions match the 'DNP Tables at last compilation' file Added TS binary input and counter definitions Minor edits in the Class 0 - 3, Binarys tab. Updates and re-release for ProView 5.0 Updates and re-release for ProView 5.1 Page 1 Cover Page Form 6 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs Description Recloser Closed Recloser Open Control is Locked Out Any Control or System Alarm Above Minimum Trip Supervisory Off Non-Reclosing Ground Trip Blocked SEF Blocked CLPU Blocked Fast Trips Blocked Profile Selected (Normal) Profile Selected (Alt1) Profile Selected (Alt2) Profile Selected (Alt3) Hot Line Tag Bus Voltage Present (Phase A) Bus Voltage Present (Phase B) Bus Voltage Present (Phase C) Reverse Power Flow Battery Test in Progress No AC Power Battery Alarm ci8:Alt1 (TB3:9-10) ci9:Alt2 (TB3:11-12) ci10:Alt3 (TB3:13-14) ci11:Nrml (TB3:15-16) co1:aux (TB1:11-12,13) co2:ok (TB1:14-15) co3:hlt (TB1:16-17) co4:gtb (TB1:18-19) ss1:lo (TB1:9-10) co5:nr (TB3:17-18) co6:alm (TB3:19-20,21) co7:nrm (TB4:1-2) co8:alt1 (TB4:3-4) co9:alt2 (TB4:5-6) co10:alt3 (TB4:7-8) co11:frq (TB4:9-10) co12:vlt (TB4:11-12,13) Reclose Retry Enabled Default Static Variation Obj 01 Var 01 Binary input w/o status Index 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Default Event Variation Obj 02 Var 2 Binary input with time Default Hex Index Event Class 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Page 2 Class 0 - 3, Binarys Form 6 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs Description A Phase Fault Trip B Phase Fault Trip C Phase Fault Trip Ground Fault Trip SEF Trip ci1:RTrip (TB1:3-4) ci2:SClose (TB1:5-6) ci3:STrip (TB1:7-8) ci4:GTB (TB3:1-2) ci5:NRecl (TB3:3-4) ci6:TargR (TB3:5-6) ci7 (TB3:7-8) Ground Overcurrent Alarm Phase Overcurrent Alarm Negative Sequence Overcurrent Alarm Hot Line Tag On from Workbench Hot Line Tag On from Communications Hot Line Tag On from Front Panel Switch Control Circuit Interrupted Default Static Variation Obj 01 Var 01 Binary input w/o status Index 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 Default Event Variation Obj 02 Var 2 Binary input with time Default Hex Index Event Class 29 1 2A 1 2B 1 2C 1 2D 1 2E 1 2F 1 30 1 31 1 32 1 33 1 34 1 35 1 36 1 37 1 38 1 39 1 3A 1 3B 1 Page 3 Class 0 - 3, Binarys Form 6 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs (Triple-Single) Description Recloser Closed (Phase A) Recloser Open (Phase A) Control is Locked Out Any Control or System Alarm Above Minimum Trip Supervisory Off Non-Reclosing Ground Trip Blocked SEF Blocked CLPU Blocked Fast Trips Blocked Profile Selected (Normal) Profile Selected (Alt1) Profile Selected (Alt2) Profile Selected (Alt3) Hot Line Tag Bus Voltage Present (Phase A) Bus Voltage Present (Phase B) Bus Voltage Present (Phase C) Reverse Power Flow Battery Test in Progress No AC Power Battery Alarm ci8:Alt1 (TB3:9-10) ci9:Alt2 (TB3:11-12) ci10:Alt3 (TB3:13-14) ci11:Nrml (TB3:15-16) co1:aux (TB1:11-12,13) co2:ok (TB1:14-15) co3:hlt (TB1:16-17) co4:gtb (TB1:18-19) ss1:lo (TB1:9-10) co5:nr (TB3:17-18) co6:alm (TB3:19-20,21) co7:nrm (TB4:1-2) co8:alt1 (TB4:3-4) co9:alt2 (TB4:5-6) co10:alt3 (TB4:7-8) co11:frq (TB4:9-10) co12:vlt (TB4:11-12,13) Reclose Retry Enabled Default Static Variation Obj 01 Var 01 Binary input w/o status Index 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Default Event Variation Obj 02 Var 2 Binary input with time Default Hex Index Event Class 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Page 4 Class 0 - 3, Binarys (TS) Form 6 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs (Triple-Single) Description A Phase Fault Trip B Phase Fault Trip C Phase Fault Trip Ground Fault Trip SEF Trip ci1:RTrip (TB1:3-4) ci2:SClose (TB1:5-6) ci3:STrip (TB1:7-8) ci4:GTB (TB3:1-2) ci5:NRecl (TB3:3-4) ci6:TargR (TB3:5-6) ci7 (TB3:7-8) Ground Overcurrent Alarm Phase A Overcurrent Alarm Negative Sequence Overcurrent Alarm Hot Line Tag On from Workbench Hot Line Tag On from Communications Hot Line Tag On from Front Panel Switch Control Circuit Interrupted (Phase A) Recloser Closed (Phase B) Recloser Open (Phase B) Control is Locked Out (Phase B) Control Circuit Interrupted (Phase B) Recloser Closed (Phase C) Recloser Open (Phase C) Control is Locked Out (Phase C) Control Circuit Interrupted (Phase C) Phase B Overcurrent Alarm Phase C Overcurrent Alarm Ganged Mode 1-3 Mode 1-1 Mode USEF Blocked Profile Selected (Alt 4) Profile Selected (Alt 5) Default Static Variation Obj 01 Var 01 Binary input w/o status Index 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 Default Event Variation Obj 02 Var 2 Binary input with time Default Hex Index Event Class 29 1 2A 1 2B 1 2C 1 2D 1 2E 1 2F 1 30 1 31 1 32 1 33 1 34 1 35 1 36 1 37 1 38 1 39 1 3A 1 3B 1 3C 1 3D 1 3E 1 3F 1 40 1 41 1 42 1 43 1 44 1 45 1 46 1 47 1 48 1 49 1 4A 1 4B 1 Page 5 Class 0 - 3, Binarys (TS) Form 6 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Counters Description Trip Counter (Phase A) Trip Counter (Phase B) Trip Counter (Phase C) Trip Counter (Ground) Trip Counter (SEF) Total Trip Counter Default Static Variation Obj 20 Var 2 16 bit Counter Index 00 01 02 03 04 05 Default Event Variation Obj 22 Var 2 16 bit Counter w/o time Default Hex Index Event Deadband Class 00 01 02 03 04 05 1 1 1 1 1 1 10000 10000 10000 10000 10000 10000 Page 6 Class 0 - 3, Counters Form 6 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Counters (Triple-Single) Description Trip Counter (Phase A) Trip Counter (Phase B) Trip Counter (Phase C) Trip Counter (Ground) Trip Counter (SEF) Total Trip Counter Operations Counter (Phase A) Operations Counter (Phase B) Operations Counter (Phase C) Default Static Variation Obj 20 Var 2 16 bit Counter Index 00 01 02 03 04 05 06 07 08 Default Event Variation Obj 22 Var 2 16 bit Counter w/o time Default Hex Index Event Deadband Class 00 01 02 03 04 05 06 07 08 1 1 1 1 1 1 1 1 1 10000 10000 10000 10000 10000 10000 10000 10000 10000 Page 7 Class 0 - 3, Counters (TS) Form 6 DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Analog Inputs Description Default Static Variation Obj 30 Var 2 16 bit Index Default Event Variation Obj 32 Var 2 16 bit w/o time Default Division Hex Index Event Scale Factor Class Units Deadband Low High Threshold Threshold A Phase Primary Current Magnitude B Phase Primary Current Magnitude C Phase Primary Current Magnitude 3I0 Primary Current Magnitude 00 01 02 03 00 01 02 03 2 2 2 2 10 10 10 10 Amps Amps Amps Amps 100 100 100 100 10 10 10 10 10000 10000 10000 10000 A Phase Primary Voltage Magnitude B Phase Primary Voltage Magnitude C Phase Primary Voltage Magnitude 04 05 06 04 05 06 2 2 2 1 1 1 Volts Volts Volts 1000 1000 1000 10 10 10 10000 10000 10000 A Phase Power Factor B Phase Power Factor C Phase Power Factor 07 08 09 07 08 09 2 2 2 10000 10000 10000 1 1 1 10 10 10 10000 10000 10000 A Phase Primary Apparent Power B Phase Primary Apparent Power C Phase Primary Apparent Power 10 11 12 0A 0B 0C 2 2 2 1 1 1 kVA kVA kVA 1000 1000 1000 10 10 10 10000 10000 10000 A Phase Primary Real Power B Phase Primary Real Power C Phase Primary Real Power 13 14 15 0D 0E 0F 2 2 2 1 1 1 kW kW kW 1000 1000 1000 10 10 10 10000 10000 10000 A Phase Primary Reactive Power B Phase Primary Reactive Power C Phase Primary Reactive Power 16 17 18 10 11 12 2 2 2 1 1 1 kvar kvar kvar 1000 1000 1000 10 10 10 10000 10000 10000 Line Frequency 19 13 1 100 Hz 10 10 10000 A Phase Primary Demand Currents B Phase Primary Demand Currents C Phase Primary Demand Currents 20 21 22 14 15 16 2 2 2 10 10 10 Amps Amps Amps 100 100 100 10 10 10 10000 10000 10000 Battery Voltage Battery Current 23 24 17 18 3 3 100 1000 Volts Amps 5 1 10 10 10000 10000 Page 8 Class 0 - 3, Analog Inputs Form 6 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status Default Static Variation Description Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Index Hex Index Obj Var 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 Desc Operation Type Operation (Support) Mask CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB Self-Resetting Self-Resetting Latched Latched Latched Latched Latched Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Latched Self-Resetting Latched Latched Self-Resetting Self-Resetting Latched Latched Latched Latched Latched Latched Latched Latched Latched 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff Default Condition Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Conditioned by Supervisory State Description (Factory Default) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes * Close Mechanism * Trip Mechanism Block Reclosing Block Ground Trip Block SEF Block CLPU Block Fast Trips * Profile - Normal * Profile - Alt1 * Profile - Alt2 * Profile - Alt3 * Reset Targets * Reset Demand Meters * Reset Alarms * Test Battery *, *** Hot Line Tag Set *, *** Hot Line Tag Reset Enable Reclose Retry Combined Trip and Close Enable Sync Check Block USEF * Profile - Alt4 * Profile - Alt5 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used * Momentary/Self Resetting, always read FALSE *** Hot Line Tag activates a latching relay in the control "close" circuit. Crosshatch indicates point is supervised regardless of setting Binary Output Binary Output Binary Output 00 01 02 00 01 02 10 02 10 02 10 02 Status Status Status * Close Mechanism * Trip Mechanism Block Reclosing Page 9 CROB Form 6 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status Default Static Variation Description Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Index Hex Index Obj Var 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 Desc Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Operation Type Operation (Support) Mask Default Condition Conditioned by Supervisory State Description (Factory Default) Block Ground Trip Block SEF Block CLPU Block Fast Trips * Profile - Normal * Profile - Alt1 * Profile - Alt2 * Profile - Alt3 * Reset Targets * Reset Demand Meters * Reset Alarms * Test Battery *, *** Hot Line Tag Set *, *** Hot Line Tag Reset Enable Reclose Retry Combined Trip and Close Enable Sync Check Block USEF * Profile - Alt4 * Profile - Alt5 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used * Momentary/Self Resetting, always read FALSE *** Hot Line Tag activates a latching relay in the control "close" circuit. Page 10 CROB Form 6 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status (Triple-Single) Default Static Variation Description Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Index Hex Index Obj Var 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 Desc Operation Type Operation (Support) Mask CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB Self-Resetting Self-Resetting Latched Latched Latched Latched Latched Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Latched Self-Resetting Latched Latched Latched Latched Latched Latched Latched Latched Latched Latched Self-Resetting Self-Resetting Latched Self-Resetting Self-Resetting 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff Default Condition Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Off Conditioned by Supervisory State Description (Factory Default) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes * Close Mechanism (Phase A) * Trip Mechanism (Phase A) Block Reclosing Block Ground Trip Block SEF Block CLPU Block Fast Trips * Profile - Normal * Profile - Alt1 * Profile - Alt2 * Profile - Alt3 * Reset Targets * Reset Demand Meters * Reset Alarms * Test Battery *, *** Hot Line Tag Set *, *** Hot Line Tag Reset Enable Reclose Retry Combined Trip and Close (Phase A) Enable Sync Check * Trip Mechanism (Phase B) * Trip Mechanism (Phase C) * Close Mechanism (Phase B) * Close Mechanism (Phase C) * Activate Ganged Mode * Activate 1-3 Mode * Activate 1-1 Mode * Trip All Phases * Close All Phases Combined Trip and Close (Phase B) Combined Trip and Close (Phase C) Block USEF * Profile - Alt4 * Profile - Alt5 * Momentary/Self Resetting, always read FALSE *** Hot Line Tag activates a latching relay in the control "close" circuit. Crosshatch indicates point is supervised regardless of setting Binary Output 00 00 10 02 Status * Close Mechanism (Phase A) Page 11 CROB (TS) Form 6 DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status (Triple-Single) Default Static Variation Description Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Index Hex Index Obj Var 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 Desc Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Status Operation Type Operation (Support) Mask Default Condition Conditioned by Supervisory State Description (Factory Default) * Trip Mechanism (Phase A) Block Reclosing Block Ground Trip Block SEF Block CLPU Block Fast Trips * Profile - Normal * Profile - Alt1 * Profile - Alt2 * Profile - Alt3 * Reset Targets * Reset Demand Meters * Reset Alarms * Test Battery *, *** Hot Line Tag Set *, *** Hot Line Tag Reset Enable Reclose Retry Combined Trip and Close Enable Sync Check * Trip Mechanism (Phase B) * Trip Mechanism (Phase C) * Close Mechanism (Phase B) * Close Mechanism (Phase C) * Activate Ganged Mode * Activate 1-3 Mode * Activate 1-1 Mode * Trip All Phases * Close All Phases Combined Trip and Close (Phase B) Combined Trip and Close (Phase C) Block USEF * Profile - Alt4 * Profile - Alt5 * Momentary/Self Resetting, always read FALSE *** Hot Line Tag activates a latching relay in the control "close" circuit. Page 12 CROB (TS) Technical Data TD280015EN Communications Point Data Base Effective July 2015 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries © 2015 Eaton All Rights Reserved Printed in USA Publication No. TD280015EN July 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners. For Eaton's Cooper Power series Form 6 recloser control information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.