Fault Indicators Service Information S.T.A.R. Pathfinder Variable Trip ER Faulted Circuit Indicator Installation Instructions S320-62-1 Contents Product Information �������������������������������������������������� 1 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Installation Procedures���������������������������������������������� 3 Operation���������������������������������������������������������������������� 3 Resetting the Fault Indicator������������������������������������ 4 ! CAUTION: The Cooper Power Systems S.TA.R. Type ER Faulted Circuit Indicator is designed to be operated in accordance with normal safe operating procedures. These instructions are not intended to supersede or replace existing safety and operating procedures. Read all the instructions before installing the faulted circuit indicator. Faulted circuit indicators should be installed and serviced only by personnel familiar with good safety practice and the handling of high-voltage electrical equipment. Improper operation, handling, or maintenance can result in death, severe personal injury, and equipment damage. Product Information Introduction The Cooper Power Systems S.T.A.R. PATHFINDER Electrostatic Reset (ER) Faulted Circuit Indicators are used on overhead conductors and indicate the passage of fault current by showing a “fault” flag in the Fisheye display window or by flashing the optional LED lights located on the sides of the indicator housing. When the fault is cleared from the system and the line is re-energized, the fault indicator will automatically reset after the factoryprogrammed period of time. A minimum of 2.4 kV line-toground is needed in order to reset the fault indicator. The Cooper Power Systems S.T.A.R. Faulted Circuit Indicator (FCI) is weatherproof, submersible and meets or exceeds IEEE Std 495™-1986 standard, IEEE “Guide for Testing Faulted Circuit Indicators”. The Fisheye target display will not change status due to mechanical shock or vibration. The S.T.A.R. Pathfinder ER Faulted Circuit Indicator clamps easily to the overhead conductor by using a standard clamp (shotgun) stick. It is primarily for use on uninsulated, unshielded cable, but may also be used on insulated unshielded cable such as tree wire. The fault indicator clamping mechanism will allow the indicator to be used on cable sizes from 0.25" (6.4 mm) up to 2.0" (51 mm) in diameter. The FCI uses a variable trip design, which senses rate of change in line current and trips based on a rise in current. A minimum of 200 A (load current plus fault current) is required to trip the FCI. April 2009 • Supersedes 09/05 R Figure 1. S.T.A.R. Pathfinder Type ER faulted circuit indicator. ! Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. Acceptance and Initial Inspection Each S.T.A.R. PATHFINDER Faulted Circuit Indicator is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the S.T.A.R. PATHFINDER Faulted Circuit Indicator and inspect it thoroughly for damage incurred during shipment. If damaged is discovered, file a claim with the carrier immediately. Handling and Storage Be careful during handling and storage of the S.T.A.R. PATHFINDER Faulted Circuit Indicator to minimize the possibility of damage. If the S.T.A.R. PATHFINDER Faulted Circuit Indicators are to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001:2000 Certified Quality Management System 1 S.T.A.R. PATHFINDER Variable Trip ER Faulted Circuit Indicator Installation Instructions ! SAFETY FOR LIFE SAFETY FOR LIFE ! SAFETY FOR LIFE Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our “Safety For Life” mission. SAFETY Information The instructions in this manual are not intended as a sub­ stitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: nIs thoroughly familiar with these instructions. nIs trained in industry-accepted high- and low-voltage safe operating practices and procedures. nIs trained and authorized to energize, de-energize, clear, and ground power distribution equipment. nIs trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: ! DANGER: Indicates a hazardous situation which, if not avoided, will result in death or serious injury. ! WARNING: Indicates a hazardous situation which, if not avoided, could result In death or serious injury. ! CAUTION: Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Caution: Indicates a hazardous situation which, if not avoided, could result in equipment damage only. 2 Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. ! DANGER: ! WARNING: Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. ! WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. ! WARNING: Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. ! S320-62-1 SAFETY FOR LIFE Installation Procedures CLAMP ARMS 1.Arm the FCI clamp mechanism by grasping each clamping arm (Figure 2), pulling them apart until the trigger arm latches into place. Stops have been built into the clamping arms such that they will only open to the point where the trigger arm will latch (Figure 3). 2.Attach the FCI to a clamp (shotgun) stick using the pulling eye on the front of the faulted circuit indicator. 3.Push the FCI clamping mechanism against the conductor until the trigger mechanism releases from the latched position. Remove the clamp stick. For cable diameters from 0.25" (6.4 mm) to 1.0" (25 mm), the clamp arm pads are required to properly clamp onto the conductor. For cable diameters from 1.0" up to 2.0" (51 mm), the clamp arm pads are not needed and should be removed. (Figure 4). The S.T.A.R. PATHFINDER Variable Trip ER Type Faulted Circuit Indicator is shipped to the customer in the reset position. It is recommended that the unit be manually tested prior to installation. Refer to page 4, “Resetting the Fault Indicator.” ! 5.06" (128.5 mm) TRIGGER ARM Figure 2. Type ER faulted circuit indicator with clamp in unarmed position. WARNING: 3.66" (93.0 mm) Care should be used when installing the FCI on a de-energized system without the use of a shotgun stick. When the clamping mechanism closes, the trigger arm swiftly swings toward the pulling eye and injury could occur if fingers or hands are in the trigger arm’s path. OPERATION LATCH MECHANISM 5.7" (144 mm) Cooper Power Systems S.T.A.R. PATHFINDER Variable Trip Electrostatic Reset Faulted Circuit Indicators are ready to indicate a fault when installed on an energized system. The FCI can also be tested manually prior to installation. When a fault occurs, the FISHEYE target display will turn from the normal position (black) to the tripped position (orange). After a fault, the FCI remains in the tripped position until the system is re-energized. Following restoration of normal system voltage, the FCI will remain in the tripped position for 4-minutes, 4-hours, or 24-hours, depending on the model chosen. This allows the operators time to interrogate the units after system voltage has been restored. Figure 3. Type ER faulted circuit indicator with clamp in armed position. The unit can also be installed on a de-energized circuit, and can sense fault current that may occur on restoration of system power. Simply reset the FCI using the method described below, before installing the FCI on the overhead cable, or using a hotstick after the unit has been installed. The FCI will then be ready to indicate a fault, if one exists on the system when re-energization is attempted. 3 3 S.T.A.R. PATHFINDER Variable Trip ER Faulted Circuit Indicator Installation Instructions RESETTING THE FAULT INDICATOR The S.T.A.R. PATHFINDER Type ER Fault Circuit Indicator is shipped in the reset position. After a fault with the indicator in the orange position, the FCI will reset automatically on system voltage (above 2.4 kV line-toground), following the factory programmed reset delay. Reset times of 4-minutes, 4-hours (standard) and 24-hours are available. The unit can be reset manually with the SMRT reset tool. This will turn the display to the un-faulted or black position and verify battery operations. This can be done prior to installing the FCI on the conductor, or by using the SMRT on a clamp stick after the FCI has been installed on a live circuit. Figure 4. Remove clamp pads attached to each clamping arm on a mechanism where cable diameter exceeds 1". 1. In order to reset the PATHFINDER ER Type Faulted Circuit Indicator, a manual reset/interrogation tool (SMRT) is required (Figure 5). 2. Reset the FISHEYE display by swiping the reset tool past the FCI housing near the clamp arm lever on the side of the FCI, as indicated by a stamped “R”. (Figure 6). Do not hold the SMRT tool against the housing, this will not initiate the test sequence. Swipe the unit across the stamped "R" on the housing. Figure 5. Manual Reset Tool. R Reset Area Location Figure 6. Reset location on the PATHFINDER Type ER faulted circuit indicator. 4 4 ! SAFETY FOR LIFE S320-62-1 For the standard Electrostatic Reset PATHFINDER (SEVT) and the 4-minute reset unit, the following sequence can be used to test the FCI for positive battery operation: If the Variable Trip ER fault indicator is in the tripped (orange) position, prior to being reset with the SMRT tool, the FISHEYE display will rotate to the normal position (black) within 10-seconds after swiping the reset tool across the FCI housing. If the FCI is in the normal (black) position prior to testing for battery operation using the SMRT tool, the display will rotate to the orange position, remain in that position for approximately 10 seconds, then rotate back to the black position. If the unit is equipped with the optional LED light indication, the above sequence remains the same except the timing delays will be closer to 20-seconds and the LED lights will blink when the ball is in the orange (tripped) position. For the 24-reset Electrostatic PATHFINDER (SEVT24), the following sequence can be used to test for positive battery operation: After swiping the SMRT tool across the stamped "R" on the housing, the unit will initially verify that it is in the orange (tripped) position. After a 5-10 second delay, the FISHEYE target display will rotate to the black (normal) position. After another 5-10 second delay, the ball will rotate to the orange position again, then rotate back to the black position a second time after a 5-10 second delay. This will indicate that the battery is operating correctly and that the unit is a 24-hour reset unit. If the unit is equipped with the optional LED light indication, the above sequence remains the same except the timing delays will be closer to 20-seconds and the LED lights will blink when the ball is in the orange (tripped) position. Removing the FCI 1.Insert the hook end from the shotgun stick into the pulling eye of the FCI and lock the shotgun stick tight against the FCI body. 2.Pull straight back on the hotstick. For quicker/ simpler removal of the FCI, it can be removed with hot-line gloves. 3.If the clamp pads are to be used with the FCI upon re-installation, ensure that the pads are properly attached to the clamp arms. 5 S.T.A.R. PATHFINDER Variable Trip ER Faulted Circuit Indicator Installation Instructions TABLE 1 S.T.A.R. Variable Trip Faulted Circuit Indicator Ordering Information Catalog Number Standard Digits: 1 2 3 SE V Options 4 T 5 6 7 Options Digits 5678 S.T.A.R. FCI Line FCI Type Digit 2 E Type Electrostatic Reset Catalog No. S M R T Manual Reset Tool S R P B Replaceable Battery 24 24-hour reset ND 4-minute reset Trip Rating L LED Light Indication (4-hour reset) Digits 3 4 LB Trip Rating LED Light Indication with Replaceable Battery (std. 4-hour reset) V T Variable Trip 24L 24-hour reset, LED Light Indication 24LB 24-hour reset, LED Light Indication with Replaceable Battery NDL 4-minute reset, LED Light Indication NDLB 4-minute reset, LED Light Indication with Replaceable Battery Notes: 1. The S.T.A.R. FCI catalog number may vary in length from 4 digits to 7 digits. 2. The standard S.T.A.R. FCI catalog number may be truncated after entering digits 1-4. 6 ! S320-62-1 SAFETY FOR LIFE This page intentionally left blank. 7 S.T.A.R. PATHFINDER Variable Trip ER Faulted Circuit Indicator Installation Instructions © 2009 Cooper US, Inc. All Rights Reserved. All Cooper logos, Cooper Power Systems, S.T.A.R, FISHEYE, and Pathfinder are valuable trademarks of Cooper US, Inc. in the U.S. and in other countries. You are not permitted to use the Cooper Trademarks without the prior written permission of Cooper US, Inc. IEEE Std 495™-1986 standard is a trademark of the Institute of Electrical and Electronics Engineers, Inc., (IEEE). This publication/product is not endorsed or approved by the IEEE. S320621 Rev 0 (Replaces 5000050848 Rev. 2) 2300 Badger Drive Waukesha, WI 53188 USA www.cooperpower.com