S280-30-7 Reclosers Types VW, VWV27 and VWV38

advertisement
Reclosers
Service Information
Types VW, VWV27 and VWV38
Maintenance Instructions
S280-30-7
14.4 Kv • 560 Amp (Type VW) (Serial No. 510 and
after or beginning with CP57.)
24.9 Kv • 560 Amp (Type VWV27) (Serial No. 144
and after or beginning with CP57.)
34.5 Kv • 560 Amp (Type VWV38) (Serial No. 101
and after or beginning with CP57.)
RADIATION
WARNING
Before performing electrical tests on types VW and VWV
Reclosers, refer to Service Information S280-90-1.
CAUTION
Do not energize this equipment out of oil.
Figure 1.
Type VW vacumm-interrupting, hydraulicaly controlled, automatic circuit recloser.
CONTENTS
Safety for Life ......................................................................2
Introduction .........................................................................2
Description and Operation ..............................................2
General ..............................................................................2
Manual Operating Handle ...............................................2
Non-Reclosing Lever .......................................................2
Contact Position Indicator ................................................2
Vacuum Interrupters ........................................................3
Closing Solenoid ..............................................................3
Closing Solenoid Contactor .............................................3
Hydraulic Pump and Lockout Piston ..............................3
Series Trip Solenoids .......................................................3
Time Delay Unit ................................................................3
Mechanism Operation ......................................................4
Hydraulic Control System Operation ............................4
Maintenance ........................................................................5
Frequency of Maintenance .............................................5
Periodic Maintenance Inspection ....................................5
Manual Operation of the Recloser ..................................6
Mechanism In Oil ...........................................................6
Mechanism Out of Oil ...................................................7
Insulation Level Withstand Tests ....................................7
Oil Condition ......................................................................8
99001KM
Shop Maintenance Procedures .................................9
Control Lever Overtravel Adjustments ......................9
Bushings ...................................................................9
Type VW Bushings ................................................9
Type VWV27 and VWV38 Bushings ....................10
Vacuum Interrupters ................................................12
Closing Solenoid Contactor .....................................12
Closing Solenoid ......................................................12
Series Trip Solenoid ..................................................13
Solenoid Disassembly .............................................13
Solenoid Replacement ............................................13
Time Delay Unit ..........................................................13
Maintenance .............................................................13
Replacement ............................................................14
Removing Mechanism from Head ...........................14
Reinstalling Mechanism into Head ..........................14
Testing .........................................................................14
Notes............................................................................15
Service Parts List .......................................................15
Bushing Part (Figure 25) ..........................................17
Head and Tank Assembly (Figure 26) .....................19
Trip Coil and Interrupter Mechanisms (Figure 27) ...21
(Figure 28) ...............................................................23
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered
sufficiently
for
the
user’s
purpose,
please
contact
your
Cooper
Power
Systems
sales
engineer.
December 1986 • New Issue
1
Types VW and VWV Maintenance Instructions
!
!
SAFETY
FOR LIFE
SAFETY FOR LIFE
SAFETY
FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively
promote safe practices in the use and maintenance of our products through our service literature, instructional training
programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture,
marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working
around high voltage lines and equipment and support our “Safety For Life” mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a substitute for proper training or adequate experience in the
safe operation of the equipment described. Only competent technicians who are familiar with this equipment
should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage
safe operating practices and procedures.
• Is trained and authorized to energize, de-energize,
clear, and ground power distribution equipment.
• Is trained in the care and use of protective equipment
such as flash clothing, safety glasses, face shield,
hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe installation and operation of this equipment, be sure to read
and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements
that apply to this equipment. Additional statements,
related to specific tasks and procedures, are located
throughout the manual.
DANGER: Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety
procedures when working around high and low voltage
lines and equipment.
G103.3
!
WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read
and understand the contents of this manual. Improper
operation, handling or maintenance can result in death,
severe personal injury, and equipment damage. G101.0
!
Hazard Statement Definitions
This manual may contain four types of hazard
statements:
DANGER: Indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
!
WARNING: This equipment is not intended to
protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death,
severe personal injury and equipment damage.
!
G102.1
WARNING: Indicates a potentially hazardous
situation which, if not avoided, could result in
death or serious injury.
!
CAUTION: Indicates a potentially hazardous
situation which, if not avoided, may result in
minor or moderate injury.
!
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only.
2
WARNING: Power distribution equipment must
be selected for the intended application. It must be
installed and serviced by competent personnel who
have been trained and understand proper safety procedures. These instructions are written for such personnel
and are not a substitute for adequate training and experience in safety procedures. Failure to properly select,
install, or maintain this equipment can result in death,
severe personal injury, and equipment damage. G122.2
!
S280-30-7
INTRODUCTION
Service Information S280-30-7 provides the maintenance
instructions for Type VW, VWV27 and VWV38 three-phase,
hydraulically controlled, vacuum reclosers. Included is a general description of the recloser and its operation, instructions for
periodic inspection and routine maintenance, testing procedures, and instructions for shop repairs. A service parts list,
keyed to exploded-view drawings of the recloser is included at
the back of the manual.
DESCRIPTION AND OPERATION
General
The Type VW, VWV27 and VWV38 reclosers are self-controlled
devices that sense and interrupt distribution system fault currents. They automatically reclose to restore service if the fault is
temporary and then reset for another programmed sequence of
operations. If the fault is permanent the recloser locks open
after one, two, three or four operations, depending upon its
operating settings. All three phases open, close, and lock out
simultaneously.
Opening sequences of these reclosers can be all fast, all
delayed, or any combination of fast followed by delayed operations; up to the maximum of four operations. On coordinated
systems, fast operations clear temporary faults before branchline fuses can be damaged. Delayed openings allow time for
fuses or other downline protective devices to clear so that permanent faults can be confined to smaller sections of line
Closing energy, as well as energy to charge the opening
springs, is supplied by a high-voltage closing solenoid which is
momentariIy connected phase-to-phase through a high-voltage
contactor.
Figure 2.
Untanked Type VW vacuum recloser.
A “trip-free” yellow operating handle, located under the sleet
hood, will manually lock open the recloser. It cannot manually
close the recloser, but must be in the CLOSED position for the
closing solenoid contactor to operate. A red contact position
indicator, linked to the recloser mechanism but independent of
the yellow operating handle, is also located under the sleet
hood.
The location of the major components of a VW recloser are
shown in Figure 2. They are similar for the VWV27 and VWV38
reclosers. Being aware of the location of these components and
their operation will provide a quicker and clearer understanding
of the recloser maintenance and repair procedures that follow.
Manual Operating Handle
When the recloser operates to lockout, the (yellow) manual
operation handle drops down (“trips-free”) from under the sleet
hood, to give a visual indication of recloser lockout. The handle
must be reset manually before the recloser can be closed. Lifting the handle up mechanically closes the closing solenoid contactor, and if power is available to the closing coil circuit, the
closing solenoid will energize, resetting the recloser.
A closed recloser can be manually opened and locked out by
pulling down the yellow handle.
Non-Reclosing Lever
The non-reclosing lever provides the capability for locking out
the recloser on the first trip operation regardless of the programmed number of operations to lockout.
Contact Position Indicator
The red arrow-like contact position indicator flag is coupled to
the recloser mechanism to show the position of the main contacts. When the flag is down, the vacuum interrupter contacts
are open; when the flag is up, the contacts are closed.
84603KMA
3
Types VW and VWV Maintenance Instructions
Vacuum Interrupters
Circuit opening and fault interruption is achieved within the three
sealed vacuum interrupters. The moving contact rod assemblies
are operated by the recloser mechanism to open and close the
vacuum interrupter contacts. Berylium copper garter springs are
used in the current exchange assemblies to provide a multi-point
low resistance current path between the stationary bushing leads
and the moving contact rod of the interrupters.
When the recloser mechanism is sequenced to the delayed
operation phase, the speed of plunger movement is restrained
by a time-delay unit. The restrained plunger movement provides a fixed time delay before the recloser mechanism trips.
Closing Solenoid
The moving contacts of the interrupters are closed by the closing
solenoid, which also extends the opening springs in the head
mechanism. This solenoid is energized for only a few cycles during each closing operation when it is momentarily connected
across phases B and C.
SERIES
TRIP
SOLENOID
Closing Solenoid Contactor
Mechanically operated by the head mechanism, the snap-action
contacts of the closing coil contactor complete the high-voltage
circuit to the closing solenoid for each closing operation.
Hydraulic Pump and Lockout Piston
The hydraulic pump counts the number of times the recloser trips.
With each trip the pump piston is pushed into the pump cylinder,
oil is forced through the lockout cylinder check valve into the lockout cylinder. This causes the lockout piston to be raised one step.
When the recloser resets the pump piston is pulled back to the
top of the pump cylinder and oil is drawn in through the intake
check valve.
If the recloser trips again the pump piston will actuate causing
the lockout piston to be pushed up another step. This cycle will
repeat until the recloser locks out. Once locked out the quick
reset rod is mechanically raised allowing the lockout piston to
quickly resettle. If the recloser does not lockout, the lockout piston will resettle gradually (at a rate of approximately 90 seconds
per accumulated operation at 25°C).
Figure 3.
Series Trip coil.
84612KMA
Time Delay Unit
Series Trip Solenoids
The series trip solenoids (Figure 3) are connected in series with
the vacuum interrupters, each carries full line current. When line
current exceeds the minimum trip rating of a coil, by approximately 200 percent, the plunger is drawn into the solenoid. Near
the end of the plunger stroke the recloser mechanism trips.
DELAY
ARM
When the mechanism is sequenced to a delayed operation the
latch assemblies of the trip solenoid plunger linkages are
engaged with the arms on the sealed time-delay units, Figure 4a
and 4b. Trip solenoid plunger movement is then restrained by the
time-delay unit, which provides a consistent delay action by forcing hydraulic fluid through a calibrated orifice within the unit.
DELAY
ARM
FILLER
PLUG
FILLER
PLUG
MINIMUM
TRIP
SPRING
MINIMUM
TRIP
SPRING
ADJUSTMENT
SCREW
ADJUSTMENT
SCREW
Figure 4a.
Time delay unit (old).
4
82020KMA
Figure 4b.
Time delay unit (new).
86780KMA
S280-30-7
MECHANISM OPERATION
The operating mechanism, mounted in the head, opens and
closes the vacuum interrupter contacts. Contact opening is initiated by a series trip solenoid which triggers the trip mechanism
to release the loaded opening springs. Contact closing is performed by the closing solenoid which also charges the opening
springs and resets the mechanism for the next trip operation.
The basic operation of the mechanism is shown in Figure 5.
With the interrupter contacts closed (a), the opening springs
are fully extended and the mechanism is in the reset state. When
excessive current levels are passing through the series trip coil
the solenoid plunger is actuated. The trip solenoid plunger operates the toggle latch, releasing the toggle. This action releases
the opening springs (b) which starts the contact bar assembly in
motion. The spring-biased reset lever rotates to snap the toggle
closed. This action of the reset lever also pulls the plunger out of
the closing solenoid. At this point the interrupter contacts are
fully open (c) and the mechanism is in the open state. When the
closing solenoid plunger reaches the top of its stroke it mechanically closes the closing coil contactor which energizes the closing solenoid. As the plunger is drawn down into the coil the reset
lever is pulled back and latched in its original position. The interrupter contacts are closed (d) and the opening springs are
extended. The mechanism is now ready for another opening
operation.
QUICK
RESET
ROD
TRIP
PISTON
ROD
HYDRAULIC
PUMP ROD
PUMP
BODY
HYDRAULIC CONTROL SYSTEM OPERATION
The hydraulic pump, associated cam, and linkages regulate the
number of fast and delayed operations, count the operations to
lockout, and initiate lockout after a preset number of operations.
The hydraulic pump (Figure 6) is linked to the closing-solenoid
plunger and is pushed downward with each return operation of
Figure 6.
Hydraulic pump.
86796KMA
Figure 5.
Head mechanism lever arrangement
5
Types VW and VWV Maintenance Instructions
the plunger. With its downward stroke, the pump forces a
measured amount of oil under the lockout piston (Figure
7), causing it to rise one step. When the closing coil is energized, the recloser contacts close and the pump returns to its
normal position.
The lockout piston is linked to the sequence selector cam
and the lockout bar. Upward movement of the lockout piston
causes the cam to rotate counterclockwise and the lockout bar
to advance one step. The number of fast operations is preset
on the cam. After these operations, the cam engages the roller
and pushes it to the right. A mechanism arm attached to the
roller engages the time-delay mechanism on each phase. Subsequent operations are then delayed.
When the lockout bar completes its travel, it trips the lockout
latch. Another set of linkages and springs then lock the recloser
contacts open. The quick reset rod is raised, allowing the
hydraulic pump and lockout piston assembly to reset quickly.
The entire pump and sequencing mechanism is now ready for
the next full sequence of operations. For temporary faults that
are cleared before the recloser mechanism reaches lockout,
the hydraulic pump and lockout piston assembly resettles gradually (at a rate of approximately 90 seconds per operation at
25° C) to reset the recloser mechanism.
DUTY CYCLE
% of
Maximum
Interrupting
Circuit
Rating
X/R Value
15-20
45-55
90-100
3
7
14
Number of Unit Operations
Type VW
Type VWV27
Type VWV38
88
112
32
Total 232
88
112
32
Total 232
88
112
32
Total 232
MAINTENANCE
Frequency of Maintenance
Because reclosers are applied under widely varying operating and climatic conditions, maintenance intervals are best determined by the
user, based on actual operating experience. To assure proper operation, reclosers must be maintained when they have operated the
equivalent of a complete duty cycle and before the dielectric strength
has deteriorated below prescribed levels. In the absence of specific
operating experience, the following procedures are recommended.
• When Type VW, VWV27 and VWV38 reclosers are operated under
usual service conditions as defined in ANSI (American National
Standards Institute) C37.60, “Standard Requirements for Automatic
Circuit Reclosers for Alternating Current Systems,” it is recommended that the following maintenance procedures be performed
at the completion of an equivalent duty cycle.
• However, if the recloser has not completed an equivalent duty cycle
within three years, it is recommended that a Periodic Maintenance
Inspection be performed at that time.
• The bellows used on interrupter moving contact rods have a
mechanical life expectance of 7000 operations. Interrupters must
be replaced when 7000 operations have been accumulated.
CAUTION
After 7000 operations bellows may develop leaks, due to
machanical wear. If a leak developes the interrupter may be
unable to clear load or fault current.
Periodic Maintenance Inspection
86717KMA
Figure 7.
Hydraulic pump cross section.
Ratings
ELECTRICAL RATINGS
Type VW TypeVWV27
Nominal system voltage, kv
Maximum rated voltage, kv
Rated impulse withstand
voltage (BIL) kv crest
60-Hertz withstand voltage,
kv
Dry, one minute
Wet, ten seconds
Rated maximum continuous
current, amps
6
Type VWV38
14.4
15.5
24.9
27
34.5
38
110
125
150
Each periodic maintenance inspection at the completion of an equivalent duty cycle should include at least the following:
1. Bypass and remove the recloser from service.
2. Thoroughly clean exterior of unit.
3. Inspect external components.
A. Check for broken or cracked bushings. Replace as necessary.
(See page 8 for procedure.)
B. Check for paint scratches and other mechanical damage; paint
to inhibit corrosion.
C. Note counter reading and enter in the record log.
4. Perform a dielectric withstand test to check the insulation
level of the recloser and the vacuum integrity of the interrupters.
(See page 7 for procedure.)
5. Manually operate mechanism; operation should match configuration noted on the data plate.
A. Partially untank unit and support head and mechanism assembly with clean wooden blocks.
B. Use manual closing tool to close interrupters.
C. Pull down on strip solenoid trip links until mechanism trips.
NOTE: The force required to pull down the trip-links will be increased
when the time delay units are engaged.
50
45
60
50
70
60
560
560
560
D. Repeat steps B and C until lockout has been reached (yellow
handle will drop).
6. Untank the recloser to expose the internal components.
S280-30-7
CAUTION
Be sure the recloser is open (yellow operating handle under
the sleet hood is down) before untanking, so that the mechanism can not be accidently tripped while out of oil.
7. Clean all internal components.
A. Remove all traces of carbon by wiping with a clean, lintfree cloth.
NOTE Although current interruption takes place in a sealed vacuum chamber, the closing solenoid contactor operates in oil and
will produce some carbon deposits.
B. Flush the mechanism with clean transformer oil.
CAUTION
Never use volatile solutions, detergents, or water-soluble
cleaners.
8. Remove bushings.
A. Non oil filled bushing should be dismantled, cleaned and
inspected.
B. Oil filled bushing should be cleaned and inspected. DO
NOT dismantle oil filled bushings.
9. Replace all external seals and gaskets.
10. Inspect mechanism for cracks, carbon tracking, flashovers
or other damage. Repair or replace as required.
11. Check the condition of the closing solenoid contactor contact tips. If the contact tips are eroded replace entire contactor
assembly. (See page 11 for replacement procedure.)
A. An oil sample taken near the bottom of the tank should
have a dielectric strength of not less than 22 kv rms.
B. Low dielectric strength indicates the presence of water or
carbon deposits. Replace the oil as necessary.
12. Inspect closing coil for cracks or other damage.
13. Inspect series trip solenoid.
14. Check the contact erosion of the vacuum interrupters.
A. Locate the scribe mark on the moving contact rod at the
top of the interrupter, Figure 8.
B. If the scribe mark falls below the top of the phenolic guide
when the interrupter is closed, the interrupter has
reached the end of its useful life and must be replaced.
(See page 10 for replacement procedure.)
15. Reinstall bushings, use new gaskets. (See page 8 for installation procedures.)
16. Drain the tank, and clean out all sludge and carbon deposits.
If oil is to be reused it must be filtered and the dielectric
strength checked.
17. Fill with new, clean insulating oil up to 2-1/4 inches below the
top of the tank flange. See Oil Condition on page 8.
18. Clean the head gasket seat and retank the recloser.
A. Move the yellow operating handle under the sleet hood to
the up position to avoid any possible binding while raising the tank.
B. Replace the head bolts and tighten to 35-55 ft-lbs torque.
Apply clamping force gradually and equally, in rotation,
to each bolt to achieve an evenly distributed gasket sealing pressure.
19. Check the oil level with the dipstick in the head and adjust the
level to the upper line on the dipstick.
NOTE: If the recloser is equipped with an oil-sight gage, the oil level
should be above the sight gage. if the oil surface line is visible in the
window, add oil to raise the level to the upper line on the dipstick.
20. Perform high-potential insulation withstand test (page ) to
make sure the dielectric clearances within the tank have not
been compromised. Also, use a suitable tester to verify that
the recloser is operating per data plate specifications.
Manual Operation of the Recloser
The recloser may be closed and opened manually while the
mechanism is either in or out of oil.
MECHANISM IN OIL
For a tanked recloser (mechanism immersed in oil) use the following manual operating procedure.
1. To close the recloser.
A. Remove the closing tool port cover and gasket from the
side of the head casting. (See Figure 2 for location.)
B. Insert the KA9OR T-handle closing tool (furnished as an
accessory) into the closing tool port (Figure 9) and engage
the pin on the closing shaft.
C. Lift up the yellow operating handle under the sleet hood to
reset the mechanism.
NOTE: Procedure for manually operating the recloser when the
mechanism is out of oil is described on page 7.
SCRIBE
MARK
Figure 8.
Location of scribe on movable contact rod of vacuum
interrupter.
84609KMA
Figure 9.
Manually closing recloser.
86797KMA
7
Types VW and VWV Maintenance Instructions
D. Turn the closing tool one-quarter turn clockwise to close
the main contacts.
CAUTION
TRIP
LEVER
Never use the KA90R closing tool to close an energized
recloser. Forcing the tool beyond the mechanism stop may
shear the pin on the closing shaft.
2. To open the recloser.
A. Pull down the yellow operating handle to trip open the
recloser.
NOTE: If the mechanism is partially untanked, and properly supported, the recloser can be tripped open by pulling down on the
series trip solenoid linkage.
MECHANISM OUT OF OIL
To operate the mechanism out of oil, proceed as follows:
1. To close the recloser.
A. If the mechanism is still mounted in the head use the procedure for a tanked recloser above (Mechanism in Oil).
B. If the mechanism is removed from the head turn the trip
reset shaft (Figure 10) with a pair of needlenose pliers to
reset the mechanism, then turn the closing shaft clockwise with the closing tool to close the main contacts.
86793KMA
Figure 11.
Trip lever releases mechanism when opening recloser out of
oil.
Insulation Level Withstand Tests
CAUTION
The mechanism may be damaged if it is "quick-tripped" with
the yellow operating handle while out of oil.
TRIP
RESET
SHAFT
Figure 10.
Resetting trip reset.
RADIATION
WARNING
At voltages up to 45 kv the radiation emitted by the vacuum
interrupter is negligble. However at higher test voltages radiation injurious to personnel may be emitted. See Radiation
Warning Service Information Bulletin S280-90-1 for further
details.
84616KMA
2. To open the recloser contacts while the mechanism is out of
oil, proceed as follows:
A. Using the T-handle closing tool turn the closing shaft clockwise and hold against the stop.
B. Release the trip lever (Figure 11 ) by moving it to the
right.
C. Then slowly allow the closing tool to rotate counterclockwise to open the main contacts.
NOTE: This procedure requires two people; one to operate the closing tool, the other to operate the trip lever.
8
High-potential withstand tests provide information on the dielectric condition of the recloser and the vacuum integrity of the
interrupters. Testing is performed at 75% of the rated low frequency withstand voltage (37.5 kv for the VW, 45 kv for the
VWV27 and 52.5 kv for the VWV38).
TEST 1: Proceed as follows:
1. Manually close main contacts of recloser (see page 6 for procedure).
2. Ground recloser tank and head.
3. Connect all three source-side bushings (1, 3, 5) together.
4. Apply proper test voltage to source-side bushings.
5. The recloser should withstand the test voltage for 60 seconds.
TEST 2: Proceed as follows:
1. Manually close main contacts of the recloser (see page 6 for
procedure).
2. Ground recloser tank and head.
3. Ground Phase A (bushing 2) and Phase C (bushing 6).
4. Apply proper test voltage to Phase B (bushing 3).
5. The recloser should withstand the test voltage for 60 seconds.
TEST 3: Proceed as follows:
1. Open main contacts of recloser (see page 6 for procedure).
2. Ground recloser tank and head.
3. Connect and ground all three load-side bushings (2, 4, 6).
4. Connect all three source-side bushings (1, 3, 5).
5. Apply proper test voltage to source-side bushings.
6. The recloser should withstand the test voltage for 60 seconds.
7. Reverse the connections: ground source-side bushings (1, 3,
5); apply test voltage to load-side bushings (2, 4, 6) for 60 seconds.
8. The recloser should withstand the test voltage for 60 seconds.
S280-30-7
TEST RESULTS: These high potential withstand tests provide
information on the dielectric condition of the recloser and the vacuum integrity of the interrupters.
A. If the recloser passes the closed-contacts tests (Tests 1 and 2)
but fails the open-contacts test (Test 3) a deteriorated vacuum
in one or more of the interrupters is most likely the cause.
Retest each vacuum interrupter individually to determine the
failed phase or phases, and replace the interrupter(s). Retest
to confirm the repair.
B. If the recloser faiIs the closed-contacts tests (Test 1 and 2) the
cause is likely to be a diminished electrical clearance or a
failed insulation. After correcting the problem, retest to confirm the repair.
Oil Condition
Oil provides the internal insulation barrier between phases and
from phase to ground, and must be replaced before it deteriorates
below a safe dielectric level. Replace the oil if its dielectric
strength falls below 22 kv.
New oil should always be filtered before use, even though it is
obtained from an approved source. Passing the oil through a blotter press will remove free water and solid contaminants such as
rust, dirt, and lint. Keep aeration to a minimum during filtering to
prevent moisture in the air from condensing in the oil and lowering its dielectric strength.
Used oil must be treated before reusing. Filtering may remove
absorbed and free water and other contaminants to raise the
dielectric strength to acceptable levels. However, filtering does
not always remove water-absorbing contaminants and the dielectric strength may fall rapidly after being returned to service.
Therefore the recloser should be filled with new oil, or oil that has
been restored to like-new condition. Oil used in these reclosers
conforms to ASTM Standard D3487, Type 1; its property limits
are shown in Reference Data R280-90-1, “Oil Specifications and
Tests.”
clockwise to reduce the dimension or counterclockwise to
increase the dimension. Slide the control lever back onto the
shaft and recheck the dimension. When the proper dimension
has been obtained replace the C-ring.
Bushings
Bushing maintenance generally consists of a thorough cleaning
and a careful examination for chips, cracks, or other mechanical
damage during the periodic maintenance inspection. Bushings
must be replaced whenever damage is discovered.
TYPE VW BUSHINGS
A damaged bushing can be replaced with the
recloser either tanked or untanked, depending
upon the circumstance of the damage.
• If the bushing porcelain is accidentally chipped during installation of the recloser, and it is obvious that no other damage has
occurred, the bushing porcelain only can be replaced without
untanking the recloser.
• If the bushing has been damaged while in service or storage,
the recloser must be untanked. Water or other contaminants
may have entered the tank (test the oil) the bushing lead may
be damaged (either mechanically or electrical flashover), or
pieces of porcelain may have fallen into the tank.
Replacing the Bushing Porcelain with the Recloser Tanked
Refer to Figure 13 and proceed as follows:
SHOP MAINTENANCE PROCEDURES
The operations described in this section should be performed
under the cleanest conditions possible. The repair work, except
for bushing replacement, will be simplified if the work bench is
arranged so the mechanism/head assembly can be inverted
(bushings down). No special tools are required for any of the
repair procedures.
Control Lever Overtravel Adjustment
Check for proper adjustment of the control lever by first removing
the sleet hood cover to expose the control lever. From the OPEN
position, slowly push the control lever toward the CLOSED position. As the lever is pushed up, latching of the recloser will be felt.
At this point the dimension between the top of the control lever
and the underside of the sleet hood should be 1/4 inch (Figure
12).
If the control lever is not adjusted properly, remove the C-ring
and slide the control lever from the shaft. Rotate the control lever
Figure 13.
Replacing bushing w/tanked Type VW recloser.
1. Unscrew bushing terminal and discard terminal gasket.
2. Remove three hex head capscrews and clamps that secure
the bushing to head and lift out porcelain.
3. Remove and discard lower bushing gasket.
4. Twist off split aluminum clamping ring from old porcelain. If it is
in good condition install it on new porcelain; replace if damaged.
Figure 12.
Overtravel adjustment of control lever.
NOTE: The clamping ring cushions and distributes the pressure
between the porcelain and the clamps. DO NOT OMIT.
9
Types VW and VWV Maintenance Instructions
5. Using a new gasket, install new porcelain over bushing rod
and into the head. Make sure roll pin, on end of the rod, is
seated into locking groove at the top of porcelain.
6. Position clamping ring with split centered between the two outside clamping bolts.
7. Reassemble bushing to head casting with bushing clamps.
Tighten clamping bolts evenly, a little at a time, to 10-15 ft-lbs
torque.
NOTE: Clamping forces must be applied gradually and equally in
rotation to each bolt. This results in an evenly distributed gasket sealing pressure.
8. Install a new terminal gasket and reassemble terminal to bushing rod, tighen to 35 ft-lbs torque.
NOTE: Apply a very small amount of petroleum jelly to the knurled
surface of the inside face of the terminal before assembling the terminal to the bushing rod.
Replacing the Bushing with the
Recloser Untanked.
Refer to Figure 14 and proceed as follows:
1. Loosen terminal.
2. Disconnect bushing lead from bottom end of bushing rod.
3. Remove three hex head capscrews and clamps that
secure bushing to head and lift out complete bushing
assembly.
4. Remove and discard lower bushing gasket.
5. The complete bushing assembly can be replaced or new
porcelain only can be installed depending upon the extent of
damage. If new porcelain only is to be installed, proceed as
follows:
A. Unscrew bushing terminal and withdraw the rod from bottom of porcelain; discard terminal gasket.
B. Insert rod assembly all the way into the new porcelain,
making sure roll pin is seated in the locking groove in top
of bushing.
C. Assemble terminal to bushing rod using a new terminal
gasket; loosely tighten.
6. Twist off the split aluminum clamping ring from old bushing
and install on new bushing, if it is in good condition; replace
if damaged.
NOTE: The clamping ring cushions and distributes the pressure
between the porcelain and the clamps. DO NOT OMIT.
7. Install bushing assembly (new or reworked) into head using
a new lower bushing gasket.
8. Position clamping ring with split centered between the two
outside clamping bolts.
9. Reassemble bushing to head casting. Tighten clamping bolts
evenly, a little at a time, to 10-15 ft-lbs torque.
NOTE: Clamping forces must be applied gradually and equally in
rotation to each bolt. This results in an evenly distributed gasket
sealing pressure.
10. Tighten terminal to 35 ft-lbs torque.
11. Reconnect the lead to the bushing rod.
TYPE VWV27 and VWV38 BUSHINGS
The bushings used on Type VWV27 and VWV38 reclosers are
oil-filled. The special fixtures and procedures required to assemble these bushings is beyond the scope of normal shop maintenance repair. Therefore if an oil bushing is in any way damaged,
the complete bushing assembly must be replaced. Refer to Figure 15 and proceed as follows:
NOTE: Apply a very small amount of petroleum jelly to the
knurled surface of the inside face of the terminal before assembling the terminal to the bushing rod.
Figure 15.
Replacing bushing, Type VWV27 and VWV38.
1. Disconnect bushing lead from bottom end of bushing rod.
2. Remove three hex head capscrews and clamps that secure
bushing to head.
3. Remove and discard lower bushing gasket.
4. Twist off split aluminum clamping ring from old bushing and
install on new bushing, if it is in good condition—replace if
damaged.
Figure 14.
Bushing parts VW recloser.
10
NOTE: The clamping ring cushions and distributes the pressure
between the ceramic and the clamps. DO NOT OMIT.
S280-30-7
5. Install new bushing through head.
6. Position bushing with stud end of terminal pointing outward.
7. Position clamping ring with split centered between the two outside clamping bolts.
8. Reassemble bushing to head casting. Tighten bolts evenly, a
little at a time, to 10-15 ft-lbs torque.
NOTE: Clamping forces must be applied gradually and equally in
rotation to each bolt. This results in an evenly distributed gasket sealing pressure.
9. Reconnect lead to bushing rod.
Vacuum Interrupters
Vacuum interrupters must be replaced when:
• They lose their vacuum as evidenced by a failure during the low
frequency dielectric withstand test across the open contacts;
• The interrupter contacts have eroded beyond their useful life
as evidenced by the position of the scribe mark on the moving
contact rod; or
• The interrupters have completed their mechanical life of 7000
operations.
To replace an interrupter, refer to Figure 16 and proceed as
follows:
UPPER
PLATE
CONTACT
UPPER
PLATE
FIBER
UPPER
INTERRUPTER
CLAMP
action can be verified by observing the scribe mark on the
contact rod. It will move downward to just above (or below)
the fiber disk at the top of the interrupter.
NOTE: If the contact rod does not move, the interrupter may have
lost vacuum or the contact rod may be sticking in the clamping fingers of the contact operating rod assembly. Use a screwdriver to
gently spread the clamping fingers to free the rod.
4. Disconnect bushing lead from lower contact plate assembly.
5. Loosen and remove lower interrupter clamp.
6. Remove hardware attaching lower contact plate to the three
vertical stringers and remove contact plate and interrupter.
7. Install the new vacuum interrupter into the clamping fingers of
the contact operating rod and the lower contact plate. Attach
the plate to the stringers.
NOTE: On side with the single stringer, a spacer on the stringer stud
provides a 1/16-inch gap between contact plate and the attaching flat
washer and locknut when the interruptercontacts are open. This gap
is intentional.
8. Manually close recloser.
9. Coat threads of interrupter clamps and attaching screws with
a film of transformer oil and loosely install.
10. Rotate interrupter so that one of the hex nuts at the top of the
interrupter is centered directly beneath the gap on one side
of the upper clamp. (See Figure 17.)
11. Position the upper and lower interrupter clamps just below the
shoulder on the finger-type current exchange connectors so
clamping force will be applied to the center of each finger, as
shown in Figure 17.
CAUTION
When rotating the interrupter avoid twisting the contact rod
to prevent damaging the bellows and destroying the interrupter.
12. Tighten screws of each interrupter clamp evenly to 75 in-lbs
torque
.
SINGLE
STRINGERS
NOTE: Clamps must be tight to prevent slippage of interrupter contact rods in their current-exchange connectors.
13. Reconnect bushing lead to lower contact plate.
14. Reinstall vertical insulation barrier plate between long bushing lead and the mechanism. Position plate and secure it
and the bushing lead with nylon tie straps.
LOWER
INTERRUPTER
CLAMP
LOWER FIBER
PLATE
Figure 16.
Vacuum interrupter replacement.
DOUBLE
STRINGERS
86787KMA
1. Make sure the recloser contacts are open; the yellow manual
operation handle, under the sleet hood, is pulled down.
2. Cut nylon tie straps which secure the vertical insulating barrier
and remove barrier.
3. Loosen and remove upper interrupter clamp. As the clamp is
loosened, atmospheric pressure on the bellows will cause the
contact rod to move down into the interrupter. This
Figure 17
Orientation or interrupter and clamp.
11
Types VW and VWV Maintenance Instructions
15. Manually trip and close the recloser several times to check
interrupter operation.
NOTE: Contact movement can be verified by observing the movement of the scribe mark on the upper contact rod of the interrupter.
When the recloser is open the scribe mark will be about 5/8-inch
above the fibre disk; on closing the mark will travel 1/2-inch downward.
Closing Solenoid Contactor
If the contacts are badly burned or eroded, the entire contactor
must be replaced. See Figure 18 and proceed as follows:
TOGGLE
SPRINGS
Closing Solenoid
The closing solenoid coil is connected phase-to-phase and is
rated to operate at full system voltage. It is protected with two
fuses, one on either side. A data plate attached to the recloser
head between source side bushings 3 and 5 provides the coil
connection information. If the solenoid coil must be replaced, due
to damage or
change in operating voltage, refer to Figure 19 and proceed as
follows:
1. Disconnect the two coil leads from closing solenoid contactor.
NOTE: Reattach the lockwashers and nut to the contactor terminal
immediately after disconnecting the coil lead to prevent loss of parts
of the moving contact arm assembly which is attached to the support
plate with the same hardware.
2. Remove four capscrews and lockwashers which attach base
plate to bottom of solenoid frame posts and lower coil and
base plate.
3. Remove coil from the base plate and discard coil gasket.
4. Using a new coil gasket, install new closing coil on the base
plate.
C-RINGS (4)
TOGGLE
MECHANISM
TOGGLE
PIN
OPERATING
LINK
NOTE: A new coil gasket is included in the closing coil replacement
kit.
5. Reassemble base plate to solenoid frame posts and connect
coil leads to the contactor terminals. Make sure the coil leads
clear the solenoid frame by at least 1/2-inch.
6. The closing coil replacement kit includes two new coil fuses
which should be installed with the new coil.
7. The closing coil replacement kit also includes a new voltage
date plate. Replace the plate on the sleet hood of the recloser
head if the operating voltage of the recloser is being changed.
NOTE: VWV27 reclosers, with 20 kv closing coils, above serial number 975 have a rigid tube insulator on the long coil lead. 20 kv and
above replacement coils for units below serial number 975 include
additional parts to modify the solenoid assembly to accommodate the
rigid insulating tube. Installation instructions are included with the kit.
LEADS
CLOSING
SOLENOID
CONTACTOR
Figure 18.
Replacing closing coil contactor.
SOLENOID
FRAME
84614KMA
1. Unhook the two toggle springs from the pin that connects the
operating shaft of the contactor to the toggle arm.
2. Remove the C-type retaining rings and withdraw the toggle
pin.
3. Disconnect the two coil leads from the contactor.
SOLENOID
COIL
NOTE: Reattach the lockwasher and hex nut to the contactor terminal immediately after disconnecting the coil lead to prevent loss of
moving contact parts which are attached to the support plate with the
same hardware.
4. Disconnect the two fuse leads from the contactor.
5. Remove three hex head capscrews and lockwasher that
attach the contactor to the underside of the recloser mechanism frame and remove contactor.
6. Install new contactor by reversing the disassembly procecure.
Use new C-rings to secure the toggle-link pin.
7. Connect solenoid coil leads to lower terminals.
8. Connect fuse leads to upper terminals.
NOTE: Be sure coil and fuse leads are positioned for maximum clearance to grounded parts.
12
GASKET
HEX HEAD
CAPSCREWS
BRIDGE
PLATE
Figure 19.
Parts involved in solenoid coil replacement.
86784KMA
S280-30-7
SERIES TRIP SOLENOID
The continuous current rating and the trip current rating of the
recloser can be changed by installing new coils in the series trip
solenoids. Tripping occurs at about 200% of the continuous current rating of the standard coil and at about 140% when the alternate (400X or 560X) coils are used. The maximum interrupting
rating of the recloser is dependent upon the continuous current
rating of the series trip coil.
Two different coil replacement kits are required. One for Phase A
and Phase B solenoids and another for Phase C (the interrupter
furthest away from the sleet hood) which has an opposite wind
because it mounts differently on the interrupter. The same basic
replacement procedure is used for either type coil.
UPPER
INSULATING
WASHER
FRAME
Solenoid Disassembly
1. Remove cotter pin; slide out the groove pin and spacer that
connect the insulated operating links to the solenoid plunger
(Figure 20).
2. Remove bolt that fastens both the outer coil terminal and the
short bushing lead to the lead mounting bracket.
3. Remove the capscrew that connects the inner coil terminal
strap to the interrupter current interchange.
4. Remove elastic stop nut and flat washer that secure solenoid
frame to the upper current exchange mounting board. Lift
entire solenoid assembly off board.
5. Remove solenoid plunger, guide clips, guide channels and
upper coil washer.
6. Lift coil slightly and pull out of the solenoid frame.
7. Replace any damaged parts at this time.
COTTER
PIN
OPERATING
LINKS
SOLENOID
COIL
LOWER
INSULATING
WASHER
Figure 21.
Assembling solenoid series trip coil.
82023KMA
3. Replace in order the guide channels, guide clips and plunger.
4. Place the solenoid assembly back on the mounting board
and secure it with the flat washers and elastic stop nuts.
5. Connect operating links to the solenoid plunger with the
groove pin, spacer and cotter pin.
6. A sleeve is provided with each coil to insulate the outer coil
lead from the frame. Slide the lead over the outer lead as illlustrated.
7. Connect the coil terminals to the current interchange and the
bushing lead to complete the assembly.
TIME DELAY UNIT
SOLENOID
PLUNGER
SHORT
BUSHING
LEAD
INNER COIL
TERMINAL
BOLT
The recloser is equipped with hydraulically-operated time delay
units on each phase. These provide the different time-current
characteristic (TCC) curves, as shown in Reference Data
R28091-6. Each unit can provide either of two-time delay characteristic curves, but not all four (KA1 194R1 provides B and C
curves and KA1194R2 provides D and E curves).
When the mechanism is sequenced to the delayed operation
phase, the latch assembly of the trip-coil plunger linkage is
engaged with the arm of the time-delay unit, this provides consistent delay action by forcing hydraulic fluid through an orifice in
the unit. Special aircraft-type fluid is used to minimize temperature effects.
Maintenance
Figure 20.
Series trip solenoid removal.
84613KMA
Solenoid Replacement
Check lower coil washer before installing new coils. For coils
rated 280 amperes and below the upper and lower coil washers
are identical. For 400 and 560 ampere rated coils, the lower
washer requires a larger center slot. The same upper washer is
used with all coil sizes.
1. Pass upper insulating washer over terminal strap and align its
slot with the coil slot (Figure 21).
2. Insert coil into the frame and slide the upper coil washer into
position.
Maintenance to the time delay units is limited to checking the fluid
level in the units. Some loss of fluid is normal, therefore this
inspection should be made each time periodic maintenance is
performed.
To check the fluid level, remove the socket-head filler plug
located on the side of the unit. Add enough fluid to bring the level
up to the filler plug hole. Avoid introducing dirt, lint or any other
foreign material when filling the unit as this can plug the orifice
and cause erratic time-delay action.
NOTE: A special fluid replacement kit, catalog number KA806R2, is
available. The kit consists of approximately 60 cc (2 US fl. oz. ) of the special hydraulic fluid in an eye-dropper bottle.
13
Types VW and VWV Maintenance Instructions
Replacement
Replacement time-delay kits include a factory calibrated time
delay, four flat head screws and a minimum-trip calibration
spring. Remove the malfunctioning unit and install the replacement in its place (see Figure 22).
The minimum trip setting of the recloser must be recalibrated
by adjusting the spring tension whenever a new time-delay unit
is installed.
DELAY
ARM
COUPLERS
Figure 23.
Disconnect couplers.
84605KMA
FILLER
PLUG
MINIMUM
TRIP
SPRING
ADJUSTMENT
SCREW
Figure 22.
Remove and replace time delay.
E-RING
86780KMA
Removing Mechanism from Head
To gain access to components located in or on the main frame,
the following procedure may be used to remove the mechanism
from the head.
NOTE: These procedures will be simplified if the untanked head and
mechanism assembly can be inverted (bushings down). The unit can be
supported on its bushings.
1. Disconnect all six bushing leads from the ends of the bushings.
2. Disconnect the lockout lever and contact position indicator
shafts by disengaging the spring loaded couplers and locking
them in the disengaged position, Figure 23.
3. Disconnect any accessories, such as a ground trip solenoid,
at their terminals.
4. If the recloser is equipped with the auxiliary switch accessory,
remove the C or E-ring and washer, Figure 24, and disconnect the operating lever of the switch from the recloser mechanism.
5. Remove the six socket head bolts and lockwashers that
secure the frame to the head casting and carefully lift the
mechanism from the head. Six long pipe spacers will be
released when the mechanism is lifted.
NOTE: By temporarily substituting eye-bolts for two of the hex head
bolts in the bottom of the closing solenoid frame, the mechanism can
be easily lifted and handled with a hoist.
6. Remove couplers from contact position indicator and lockout
lever shafts.
14
OPERATING
LEVER
83375KMA
Figure 24.
Remove E-ring to disconnect auxiliary switch operating lever.
Reinstalling Mechanism into Head
To reinstall the recloser mechanism assembly into the head, the
following procedure may be used.
1. Install the couplers on the lockout lever and contact position
indicator shafts. Lock them in the disengaged position.
2. Carefully lower the mechanism assembly onto the six pipe
spacers which have been positioned over the mounting holes
in the casting.
3. Install the six socket head bolts and tighten evenly to avoid any
binding of the mechanism.
NOTE: Replace the hex head bolts in the bottom of the closing
solenoid frame if eye-bolts were used for handling the recloser
mechanism.
4. Re-engage the lockout lever and contact position indicator
shaft by releasing the shaft couplers.
5. Reconnect the operating lever of the auxiliary switch (if used)
to the mechanism and secure with the washer and E-ring
(Figure 24).
6. Reconnect the bushing leads to the end of the bushings.
TESTING
Procedures for testing the Type VW, VWV27 and VWV38
reclosers are included in the Installation Manual S280-30-1.
S280-30-7
NOTES
15
Types VW and VWV Maintenance Instructions
SERVICE PARTS LIST
The service parts and hardware listed and illustrated include
only those parts and assemblies usually furnished for repair or
involved in the maintenance procedures described in this manual. Further breakdown of listed assemblies is not recommended.
Dimensions of all common hardware parts have been carefully checked so that they may be locally acquired. The suffix letter of the 14 character catalog number for common hardware
parts codes the plating of the part:
A - No plating; raw material
H - Silver
M- Black oxide
Q - Cadmium + zinc + chromate
Y - Zinc + chromate
Z - Electro zinc + bronze irridite
Figure 25.
Bushing Parts.
16
A hardware kit, Catalog No. KA849R1, contains an assortment
of roll pins, cotter pins, retaining rings, stop nuts, etc.—common
hardware parts used in Cooper Power System's reclosers that
may not be readily locally available.
To assure correct receipt of any parts order, always include
recloser type and serial number. Because of Cooper Power System's continuous improvement policy, there may be instances
where the parts furnished may not look exactly the same as the
parts ordered. However, they will be completely interchangeable
without any rework of the recloser.
All parts carry the same warranty as any whole item of
switchgear, i.e. against defects in material or workmanship within
a period of one year from date of shipment.
S280-30-7
Bushing Parts (Figure 25)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
Description
Bushing assembly—Type VW
consists of items 10 thru 13)
13” standard creepage
13” standard creepage with
BCT accy.
17” extra creepage
17” extra creepage with BCT
accy.
Bushing assembly—Type
VWV27 (Above S/N 974) and
Type VWV38
26-1/2” creepage
26-1/2” creepage with BCT accy.
Bushing assy. replacement kit—
Type VWV (below S/N 975)
includes bushing and
conductive gasket (9)
26-1/2” creepage
26-1/2” creepage with BCT accy.
Hex jam nut, 1/2-20, brass
Flat washer
Split lockwasher. med. 1/2.
bronze
Capscrew, hex hd, 3/8-16 x
2-1/4, stl
Bushing clamp
Clamping ring
Lower bushing gasket
Type VW
Type VWV27 and VWV38
Terminal assembly
Upper bushing gasket
Catalog
Number
Ouan.
Req’d.
Item
No.
Description
Catalog
Number
Quan.
Req’d.
12
KA717R25
6
KA717R26
KA717R27
6
6
KA717R28
6
KA56RV3
KA56RV4
6
6
KA842W1
KA842W2
K880725320050H
KP2028A903
6
6
12
12
K900830050000A
6
K730101127225Q
KP1109R
KP1111 R
18
18
6
KP2090A66
KA1193R
KA17W901
KP2090A57
6
6
1
1
Bushing ceramic—Type VW
Standard creepage
KP1110R
1
Standard creepage with BCT
accy.
KP171 W
1
17” extra creepage
KP1578R
1
17” extra creepage with BCT
accy.
KP186W
1
13 Bushing rod assembly—
Type VW
Standard and 17” creepage
KA716R20
1
Standard and 17” creepage
with BCT accy.
KA716R21
1
The following parts are applicable to the bushing current transformer
accessory.
14 Capscrew, hex hd,3/8-16 x 1-7/8,
stl
K730101157187Q
3
15 Transformer clamping flange
KP170W1
1
16 Flange gasket
KP2090A73
2
17 Replacement current transformer
600:5 multi-ratio
KA159W1S
1
1200:5 multi-ratio
KA132W
1
18 CT washer
KP312W
1
19 Capscrew, hex hd,3/8-16 x 1, stl K730101137100Q
3
20 Transformer clamping sleeve
KP169W1
1
21 O-ring gasket, used with trans
former clamping sleeve that has
machined groove. Old style
clamping sleeve without
groove, use KP2090A66.
KP2000A64
1
22 Hex nut, 3/8-16, stl
K880201116037Q
3
23 Stud
KP3149A40
1
24 Bushing spacer
KP275W1
1
17
Types VW and VWV Maintenance Instructions
Figure 26.
Head and tank assemblies.
18
S280-30-7
Head and Tank Assemblies (Figure 26)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Description
Cover plate
Gasket
Capscrew hex hd,
1/4-20 x 3/4 stl
Split lockwasher, med,
1/4, sti
Dipstick
O-ring gasket
Closing coil instruction plate
Self-tapping screw, Type F.
#2 x 3/16, sst
Capscrew, hex hd,
1/4-20 x spa, stl
Manual closing tool access
cover plate
Cover plate gasket
Capscrew, hex hd,
5/8-11 x 1-1/2.stl
Split lockwasher, med,
5/8, stl
Lifting lug
Ground connector
Head casting, includes control
shaft bushings
Head gasket
Nameplate
Type VW
Type VWV27
Type VWV38
Voltage data plate
Coil data plate
Operating data plate
Self-tapping screw, Type Z.
#4 x 3/16, sst
Sleet hood cover plate
Thread cutting screw, Type T.
#12 x 1/2. sst
Contact indicator plate
Handle designation plate
Self-tapping screw, Type F.
2-56 x 3/16, sst
Manual operating handle
assembly
Spacer
Lever and split shaft assembly
Spacer
Spacer
Catalog
Number
Quan.
Req’d.
Item
No.
KP609R
KP611 R
2
2
33
34
K730101125075Q
8
35
36
K900801025000Z
KA363R
KP2000A9
KP2312R
8
1
1
1
K751515102018A
2
K730101125062Q
2
KP246R1
KP2000A12
1
1
39
40
41
42
43
44
K730101162150Q
2
45
K900801062000Z
KP456H2
KA392R
2
2
1
KA840R
KP2103A8
1
1
KRW107F1
KRW127F1
KRW173F
KP567R
KP2119A9
KP1371R
1
1
1
1
1
1
46
47
48
49
50
51
52
53
54
55
56
K801515004018A
K283R
8
1
59
K781515112050A
KP1067R
KP390R
5
1
1
60
61
62
K751515102018A
4
KA477R
KP3009A39
KA313R
KP3011A5
KP3011A7
1
1
1
1
1
37
38
57
58
63
64
65
Description
Lever and split shaft assembly
Retaining ring. Type C, 5/16,
stl, WA516
Roil pin,1/8 x 3/4
Retaining ring, Type C, 1/4,
stl, WA514
One shot link and pin
assembly
Retaining ring, Type C,3/8.
stl, WA518
Spacer
Groove pin
One shot handle assembly
Spacer
Spacer
Indicator and support
assembly
Retaining ring, Type C,3/16
stl, WA510
Groove Pin
Spacer
Link
Shaft and lever assembly
Pin
Spacer
Flatwasher, #14S brass
Cotter pin,3/32 x 1/2, stl
Roll pin,3/32 x 1/2, stl
Counter
Self-tapping screw, Type F.
6-32 x 3/8, sst
Bracket
Self-tapping screw, Type Z.
#10 x 3/8, sst
Capscrew, hex hd,
1/2-13 x 3/4stl
Flatwasher
Pipe plug, 1”, sq hd
Tank
29-1/2” high
25-1/2” high
Pipe plug, 1/2”, sq hd
Oil sampling and drain valve
assy.
Vacuum label
Catalog
Number
Quan.
Req’d.
KA312R
1
K970901312000M
K970801125075C
1
1
K970801250000M
2
KA505R
1
K970801375000M
KP3013A91
KP3126A4
KA504R
KP301 OA5
KP3013A38
2
1
1
1
1
2
KA317R
1
K970915188000A
KP3123A12
K3006A9
KP1059R
KA319R
KP3190A11
KP3007A8
K900525026056A
K970801093050A
K970801093050C
KA28COA2
3
1
1
1
1
1
1
1
1
1
1
K751515106037A
KP1598R
2
1
K801515010037A
2
K730101150325Q
KP2028A23
KP2007A4
10
10
1
KRW116FA
KRW116FC
KP2007A3
1
1
1
KA809R
KP1041V4H
1
1
19
Types VW and VWV Maintenance Instructions
Figure 27.
Trip coil and interrupter mechanisms.
20
S280-30-7
Trip Coil and Interrrupter Mechanisms(Figure 27)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
Description
Time-delay unit replacement
kit complete (includes
attaching screws)
For B and C curves
For D and E curves
Trip link assembly, complete
Torsion spring
Roll pin, 1/8 X 3/4, stl
Trip lever stop
Retaining ring, Type C,
1/4, stl
Groove pin
Spacer
Cotter pin, 1/16 X 1/2. stl
Capscrew, hex hd,
3/8-16 x 1-3/4, brass
Flat washer, #24S, brass
Spacer
Split lockwasher med 3/8,
sil brz
Hex nut, 3/8-16, brass
Capscrew, hex hd, 3/8-16 X 1”,
sil brz
Short lead (6 per phase)
Short lead insulation
Coil strap (400X and 560X trip
coils only)
Capscrew, hex hd,1/2-13 x 1,
sil brz
Split lockwasher, med,
1/2, sil brz
Hex nut,1/2-13 sil brz
Trip solenoid assembly
(includes items 25 thru 36)
Phases A and B
Phase C
Flat washer, SAE,1/4, stl
Elastic stop nut,1/4
Self-tapping screw, rd hd
Type F. #2 x 5/16. stl
Eyelet
Guide
Solenoid plunger assembly
Plunger guide
Capscrew, hex hd,
1/4-20 x 7/8 stl
Solenoid frame
Series coil replacement kit
(includes item 20, Figure 26)
(Add coil rating as suffix
to catalog number)
Phases A and B
Phase C
Isoglass sleeve (not used with
with 400X and 560X coils)
Coil washer
Coil washer (used with 400,
400X, 560 and 560X coils)
Barrier
Contact rod assembly
Spacer
Groove pin
Retaining ring, Type C,
1/4”, stl
Capscrew, hex hd, 1/4 X 1/2
with captive lockwasher, stl
Catalog
Number
Quan.
Req’d.
KA1194R1
KA1194R2
KA161R
KP576R
K970801125075M
KP577R
3
3
3
3
3
3
K970901250000M
KP3114A1
KP3007A12
K970501062050A
3
3
3
3
K730125137175A
K900525039087H
KP3013A63
3
12
3
K900830037000A
K880225116037H
9
9
K730133137100A
KP3250A1
KP2106A80
6
18
3
KP1085VWS
3
K730133150100A
3
K900830050000A
K880133113050A
3
3
KA134VWS2
KA134VWS1
K900201025000Z
KP2020A3
2
1
6
6
K751501102031 A
KP1351 R
KP622R
KA604R
KP312R
6
6
6
3
6
K730101125087A
KA603R
6
3
Item
No.
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
KA835W2KA835W1-
2
1
KP2104A15
KP318R
3
6
KP1075R
KP1684R1
KA111VWS
KP3007A49
KP3124A76
3
3
3
3
3
K970901250000M
12
K830101125050A
6
72
73
74
Description
Groove pin
Insulation barrier
Wire tie, Panduit#SST4H
Upper stringer assembly
Insulating tubing
Lead mounting bracket
Machine screw, rd hd,
1/4-20 x 1 brass
Fuse mounting clip
Lead assembly
Flat washer, #14S, brass
Split lockwasher, med, 1/4, brz
Hex nut,1/4-20, brass
Spring
Upper current exchange assy.
Phases A and B
Phase C
Machine screw, rd hd,1/4-20
X 3/8, brass
Closing coil fuse assembly
(also included in closing coil
replacement kit, Figure 28,
item 36).
2.4-3.3 kv (2 red color bands)
4.16-6 kv (black color band)
7.2 to 11 kv (yellow color band)
12 to 24.9 kv (red color band)
Closing solenoid contactor
Type VW
Type VWV27 and VWV38
Contactor toggle spring
Groove pin
Retaining ring, Type C,1/4” stl
Capscrew, hex hd,1/4-20 x 1/2
with preassembled split
lockwasher, stl
Lower stringer assembly
Lower current exchange and
support plate assembly
Phases A and B
Phase C
Flat washer, SAE, 3/8, stl
Split lockwasher, med, 3/8, stl
Hex nut, 3/8-16, stl
Spacer
Interrupter clamp
Capscrew, hex socket hd
1/4-20 x 1, stl
Vacuum interrupter
Type VW S/N 3104 and before
Phase A & B
Phase C
Type VWV S/N 976 and before
Phase A & B
Phase C
Type VW S/N 3105 and after
Type VWV 27 S/N 977 and
after
Type VWV38
Long bushing lead
(6 per phase)
Long lead insulation
Toggle assembly
Catalog
Number
Quan.
Req’d.
KP3124A50
KRW125N1
K994904170004A
KA62R
KP3230A14
KP1061VWS
3
3
12
9
9
3
K721525125100A
KP2006A16
KA28W1
K900525026056A
K900830025000A
K881025120025A
KP1066VWS
3
2
2
3
7
7
6
KRW115FB
KRW115FA
2
1
K721525125037A
4
KA259R904
KA259R901
KA259R902
KA259R903
2
2
2
2
KA430R1
KA430R3
KP141R
KP1306R
K970901250000M
1
1
2
1
4
K830101125050A
KA222VS
3
9
KRW446VB
KRW446VA
K900201037000A
K900801037000Z
K880201116037A
KP3009A11
KP1036VS
2
1
9
9
9
3
12
KP2036A10
12
KRW705VA
KRW705VB
2
1
KRW705VC
KRW705VD
KA215VS2
2
1
3
KA227VS2
KA238VSA2
3
KP3250A27
KP2106A77
KA450R1
18
3
1
21
Types VW and VWV Maintenance Instructions
Figure 28.
Closing solenoid and hydraulic control parts.
22
S280-30-7
Closing Solenoid and Hydraulic Contol Parts(Figure 28)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
*
Description
Capscrew, hex socket hd,
1/2-13 x 4-1/2, stl
Split lockwasher, med, 1/2,
stl
Spacer
Counter shaft coupler
Operating lever coupler
Pivot pin
Retaining ring, Type C, 1/4,
stl
Lockout piston link
Pin
Lockout piston
Spring clip
Pump link
Pump piston
Pin
Pump piston shell
Retaining ring, Type E, 1/8”,
stl
Quick reset valve assembly
Pump and lockout piston
block
Capscrew, hex hd,
1/4-20 x 1-3/4, stl
Split lockwasher, med, 1/4,
stl
O-ring gasket
Ball
Ball seat
Ball retainer pin
Ball retainer pin
Gasket
Retaining ring, Type C,
3/8”, stl
Groove pin
Flat washer, SAE, 3/8, stl
Plunger and link assembly
Stringer assembly
Split lockwasher, med,
3/8, stl
Quan.
Req’d.
Item
No.
KP2036A3
6
K900801050000Z
KP3182A1
KP2448R
KP2447R
KP418H
6
6
1
1
1
33
34
35
36
K970901250000M
KP122R
KP3055A3
KP112R
KP2018A1
KA97R
KP1733R
KP3055A1
KP1732R
1
1
1
1
1
1
1
1
1
K971001125000A
KA423R
1
1
KP1300R
1
K730101125175A
2
K970801025000A
KP2000A3
KP2025A2
KP155H2
KP3051 A3
KP3051A1
KP116R
2
2
2
2
1
1
1
K970901312000M
KP3126A2
K900201037000A
KA50R
KA62R
2
1
2
1
4
K900801037000Z
12
Catalog
Number
37
38
39
Description
Catalog
Number
Hex nut, 3/8-16, stl
K880201116037A
Solenoid frame
KP100R2
Capscrew, 3/8-16 x 1-1/2, stl
K730101137125A
Closing coil replacement kit
(includes closing coil, lower coil
gasket 37 (Figure 28), two fuse
assemblies 57 (Figure 27), and
voltage data plate, 19
Figure 26).
Type VW and VWV27 reclosers
below 20 kv
2.4 kv
KA834R1
3.3 kv
KA834R10
4.16-4.8 kv
KA834R2
6.0 kv
KA834R6
7.2-8.32 kv
KA834R3
11.0 kv
KA834R9
12.2-13.2 kv
KA834R4
14.4 kv
KA834R5
17.0 kv
KA834R12
20.0 kv
KA834R11
Type VWV27 and VWV38
reclosers 20 kv and above
23.0-24.9 kv
KA834R13
34.5 kv
KA834R14
Reclosers with low voltage
closing
48 vdc
KA834R16*
125 vdc
KA834R7*
250 vdc
KA834R8*
Solenoid gasket
KP389R
Solenoid frame post
KP1669R
Solenoid bridge plate
assembly
KA644R3
Quan.
Req’d.
4
1
8
1
4
1
No fuses required with low-voltage dc coils when converting a
recloser for low-voltage operation use low-voltage contactor and coil
kit KA887R; specify desired operating voltage (Vdc or Vac).
23
Types VW and VWV Maintenance Instructions
© 2005 Cooper Power Systems or its affiliates.
Kyle® is a registered trademark of Cooper Power Systems or its affiliates.
1045 Hickory Street
Pewaukee, WI 53072
www.cooperpower.com
KDL
7/05
Download