Reclosers Service Information Types VW, VWV27 and VWV38 Maintenance Instructions S280-30-7 14.4 Kv • 560 Amp (Type VW) (Serial No. 510 and after or beginning with CP57.) 24.9 Kv • 560 Amp (Type VWV27) (Serial No. 144 and after or beginning with CP57.) 34.5 Kv • 560 Amp (Type VWV38) (Serial No. 101 and after or beginning with CP57.) RADIATION WARNING Before performing electrical tests on types VW and VWV Reclosers, refer to Service Information S280-90-1. CAUTION Do not energize this equipment out of oil. Figure 1. Type VW vacumm-interrupting, hydraulicaly controlled, automatic circuit recloser. CONTENTS Safety for Life ......................................................................2 Introduction .........................................................................2 Description and Operation ..............................................2 General ..............................................................................2 Manual Operating Handle ...............................................2 Non-Reclosing Lever .......................................................2 Contact Position Indicator ................................................2 Vacuum Interrupters ........................................................3 Closing Solenoid ..............................................................3 Closing Solenoid Contactor .............................................3 Hydraulic Pump and Lockout Piston ..............................3 Series Trip Solenoids .......................................................3 Time Delay Unit ................................................................3 Mechanism Operation ......................................................4 Hydraulic Control System Operation ............................4 Maintenance ........................................................................5 Frequency of Maintenance .............................................5 Periodic Maintenance Inspection ....................................5 Manual Operation of the Recloser ..................................6 Mechanism In Oil ...........................................................6 Mechanism Out of Oil ...................................................7 Insulation Level Withstand Tests ....................................7 Oil Condition ......................................................................8 99001KM Shop Maintenance Procedures .................................9 Control Lever Overtravel Adjustments ......................9 Bushings ...................................................................9 Type VW Bushings ................................................9 Type VWV27 and VWV38 Bushings ....................10 Vacuum Interrupters ................................................12 Closing Solenoid Contactor .....................................12 Closing Solenoid ......................................................12 Series Trip Solenoid ..................................................13 Solenoid Disassembly .............................................13 Solenoid Replacement ............................................13 Time Delay Unit ..........................................................13 Maintenance .............................................................13 Replacement ............................................................14 Removing Mechanism from Head ...........................14 Reinstalling Mechanism into Head ..........................14 Testing .........................................................................14 Notes............................................................................15 Service Parts List .......................................................15 Bushing Part (Figure 25) ..........................................17 Head and Tank Assembly (Figure 26) .....................19 Trip Coil and Interrupter Mechanisms (Figure 27) ...21 (Figure 28) ...............................................................23 These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer. December 1986 • New Issue 1 Types VW and VWV Maintenance Instructions ! ! SAFETY FOR LIFE SAFETY FOR LIFE SAFETY FOR LIFE Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission. SAFETY INFORMATION The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: • Is thoroughly familiar with these instructions. • Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. • Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. • Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER: Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high and low voltage lines and equipment. G103.3 ! WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 ! Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. ! WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. ! G102.1 WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ! CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. ! CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. 2 WARNING: Power distribution equipment must be selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install, or maintain this equipment can result in death, severe personal injury, and equipment damage. G122.2 ! S280-30-7 INTRODUCTION Service Information S280-30-7 provides the maintenance instructions for Type VW, VWV27 and VWV38 three-phase, hydraulically controlled, vacuum reclosers. Included is a general description of the recloser and its operation, instructions for periodic inspection and routine maintenance, testing procedures, and instructions for shop repairs. A service parts list, keyed to exploded-view drawings of the recloser is included at the back of the manual. DESCRIPTION AND OPERATION General The Type VW, VWV27 and VWV38 reclosers are self-controlled devices that sense and interrupt distribution system fault currents. They automatically reclose to restore service if the fault is temporary and then reset for another programmed sequence of operations. If the fault is permanent the recloser locks open after one, two, three or four operations, depending upon its operating settings. All three phases open, close, and lock out simultaneously. Opening sequences of these reclosers can be all fast, all delayed, or any combination of fast followed by delayed operations; up to the maximum of four operations. On coordinated systems, fast operations clear temporary faults before branchline fuses can be damaged. Delayed openings allow time for fuses or other downline protective devices to clear so that permanent faults can be confined to smaller sections of line Closing energy, as well as energy to charge the opening springs, is supplied by a high-voltage closing solenoid which is momentariIy connected phase-to-phase through a high-voltage contactor. Figure 2. Untanked Type VW vacuum recloser. A “trip-free” yellow operating handle, located under the sleet hood, will manually lock open the recloser. It cannot manually close the recloser, but must be in the CLOSED position for the closing solenoid contactor to operate. A red contact position indicator, linked to the recloser mechanism but independent of the yellow operating handle, is also located under the sleet hood. The location of the major components of a VW recloser are shown in Figure 2. They are similar for the VWV27 and VWV38 reclosers. Being aware of the location of these components and their operation will provide a quicker and clearer understanding of the recloser maintenance and repair procedures that follow. Manual Operating Handle When the recloser operates to lockout, the (yellow) manual operation handle drops down (“trips-free”) from under the sleet hood, to give a visual indication of recloser lockout. The handle must be reset manually before the recloser can be closed. Lifting the handle up mechanically closes the closing solenoid contactor, and if power is available to the closing coil circuit, the closing solenoid will energize, resetting the recloser. A closed recloser can be manually opened and locked out by pulling down the yellow handle. Non-Reclosing Lever The non-reclosing lever provides the capability for locking out the recloser on the first trip operation regardless of the programmed number of operations to lockout. Contact Position Indicator The red arrow-like contact position indicator flag is coupled to the recloser mechanism to show the position of the main contacts. When the flag is down, the vacuum interrupter contacts are open; when the flag is up, the contacts are closed. 84603KMA 3 Types VW and VWV Maintenance Instructions Vacuum Interrupters Circuit opening and fault interruption is achieved within the three sealed vacuum interrupters. The moving contact rod assemblies are operated by the recloser mechanism to open and close the vacuum interrupter contacts. Berylium copper garter springs are used in the current exchange assemblies to provide a multi-point low resistance current path between the stationary bushing leads and the moving contact rod of the interrupters. When the recloser mechanism is sequenced to the delayed operation phase, the speed of plunger movement is restrained by a time-delay unit. The restrained plunger movement provides a fixed time delay before the recloser mechanism trips. Closing Solenoid The moving contacts of the interrupters are closed by the closing solenoid, which also extends the opening springs in the head mechanism. This solenoid is energized for only a few cycles during each closing operation when it is momentarily connected across phases B and C. SERIES TRIP SOLENOID Closing Solenoid Contactor Mechanically operated by the head mechanism, the snap-action contacts of the closing coil contactor complete the high-voltage circuit to the closing solenoid for each closing operation. Hydraulic Pump and Lockout Piston The hydraulic pump counts the number of times the recloser trips. With each trip the pump piston is pushed into the pump cylinder, oil is forced through the lockout cylinder check valve into the lockout cylinder. This causes the lockout piston to be raised one step. When the recloser resets the pump piston is pulled back to the top of the pump cylinder and oil is drawn in through the intake check valve. If the recloser trips again the pump piston will actuate causing the lockout piston to be pushed up another step. This cycle will repeat until the recloser locks out. Once locked out the quick reset rod is mechanically raised allowing the lockout piston to quickly resettle. If the recloser does not lockout, the lockout piston will resettle gradually (at a rate of approximately 90 seconds per accumulated operation at 25°C). Figure 3. Series Trip coil. 84612KMA Time Delay Unit Series Trip Solenoids The series trip solenoids (Figure 3) are connected in series with the vacuum interrupters, each carries full line current. When line current exceeds the minimum trip rating of a coil, by approximately 200 percent, the plunger is drawn into the solenoid. Near the end of the plunger stroke the recloser mechanism trips. DELAY ARM When the mechanism is sequenced to a delayed operation the latch assemblies of the trip solenoid plunger linkages are engaged with the arms on the sealed time-delay units, Figure 4a and 4b. Trip solenoid plunger movement is then restrained by the time-delay unit, which provides a consistent delay action by forcing hydraulic fluid through a calibrated orifice within the unit. DELAY ARM FILLER PLUG FILLER PLUG MINIMUM TRIP SPRING MINIMUM TRIP SPRING ADJUSTMENT SCREW ADJUSTMENT SCREW Figure 4a. Time delay unit (old). 4 82020KMA Figure 4b. Time delay unit (new). 86780KMA S280-30-7 MECHANISM OPERATION The operating mechanism, mounted in the head, opens and closes the vacuum interrupter contacts. Contact opening is initiated by a series trip solenoid which triggers the trip mechanism to release the loaded opening springs. Contact closing is performed by the closing solenoid which also charges the opening springs and resets the mechanism for the next trip operation. The basic operation of the mechanism is shown in Figure 5. With the interrupter contacts closed (a), the opening springs are fully extended and the mechanism is in the reset state. When excessive current levels are passing through the series trip coil the solenoid plunger is actuated. The trip solenoid plunger operates the toggle latch, releasing the toggle. This action releases the opening springs (b) which starts the contact bar assembly in motion. The spring-biased reset lever rotates to snap the toggle closed. This action of the reset lever also pulls the plunger out of the closing solenoid. At this point the interrupter contacts are fully open (c) and the mechanism is in the open state. When the closing solenoid plunger reaches the top of its stroke it mechanically closes the closing coil contactor which energizes the closing solenoid. As the plunger is drawn down into the coil the reset lever is pulled back and latched in its original position. The interrupter contacts are closed (d) and the opening springs are extended. The mechanism is now ready for another opening operation. QUICK RESET ROD TRIP PISTON ROD HYDRAULIC PUMP ROD PUMP BODY HYDRAULIC CONTROL SYSTEM OPERATION The hydraulic pump, associated cam, and linkages regulate the number of fast and delayed operations, count the operations to lockout, and initiate lockout after a preset number of operations. The hydraulic pump (Figure 6) is linked to the closing-solenoid plunger and is pushed downward with each return operation of Figure 6. Hydraulic pump. 86796KMA Figure 5. Head mechanism lever arrangement 5 Types VW and VWV Maintenance Instructions the plunger. With its downward stroke, the pump forces a measured amount of oil under the lockout piston (Figure 7), causing it to rise one step. When the closing coil is energized, the recloser contacts close and the pump returns to its normal position. The lockout piston is linked to the sequence selector cam and the lockout bar. Upward movement of the lockout piston causes the cam to rotate counterclockwise and the lockout bar to advance one step. The number of fast operations is preset on the cam. After these operations, the cam engages the roller and pushes it to the right. A mechanism arm attached to the roller engages the time-delay mechanism on each phase. Subsequent operations are then delayed. When the lockout bar completes its travel, it trips the lockout latch. Another set of linkages and springs then lock the recloser contacts open. The quick reset rod is raised, allowing the hydraulic pump and lockout piston assembly to reset quickly. The entire pump and sequencing mechanism is now ready for the next full sequence of operations. For temporary faults that are cleared before the recloser mechanism reaches lockout, the hydraulic pump and lockout piston assembly resettles gradually (at a rate of approximately 90 seconds per operation at 25° C) to reset the recloser mechanism. DUTY CYCLE % of Maximum Interrupting Circuit Rating X/R Value 15-20 45-55 90-100 3 7 14 Number of Unit Operations Type VW Type VWV27 Type VWV38 88 112 32 Total 232 88 112 32 Total 232 88 112 32 Total 232 MAINTENANCE Frequency of Maintenance Because reclosers are applied under widely varying operating and climatic conditions, maintenance intervals are best determined by the user, based on actual operating experience. To assure proper operation, reclosers must be maintained when they have operated the equivalent of a complete duty cycle and before the dielectric strength has deteriorated below prescribed levels. In the absence of specific operating experience, the following procedures are recommended. • When Type VW, VWV27 and VWV38 reclosers are operated under usual service conditions as defined in ANSI (American National Standards Institute) C37.60, “Standard Requirements for Automatic Circuit Reclosers for Alternating Current Systems,” it is recommended that the following maintenance procedures be performed at the completion of an equivalent duty cycle. • However, if the recloser has not completed an equivalent duty cycle within three years, it is recommended that a Periodic Maintenance Inspection be performed at that time. • The bellows used on interrupter moving contact rods have a mechanical life expectance of 7000 operations. Interrupters must be replaced when 7000 operations have been accumulated. CAUTION After 7000 operations bellows may develop leaks, due to machanical wear. If a leak developes the interrupter may be unable to clear load or fault current. Periodic Maintenance Inspection 86717KMA Figure 7. Hydraulic pump cross section. Ratings ELECTRICAL RATINGS Type VW TypeVWV27 Nominal system voltage, kv Maximum rated voltage, kv Rated impulse withstand voltage (BIL) kv crest 60-Hertz withstand voltage, kv Dry, one minute Wet, ten seconds Rated maximum continuous current, amps 6 Type VWV38 14.4 15.5 24.9 27 34.5 38 110 125 150 Each periodic maintenance inspection at the completion of an equivalent duty cycle should include at least the following: 1. Bypass and remove the recloser from service. 2. Thoroughly clean exterior of unit. 3. Inspect external components. A. Check for broken or cracked bushings. Replace as necessary. (See page 8 for procedure.) B. Check for paint scratches and other mechanical damage; paint to inhibit corrosion. C. Note counter reading and enter in the record log. 4. Perform a dielectric withstand test to check the insulation level of the recloser and the vacuum integrity of the interrupters. (See page 7 for procedure.) 5. Manually operate mechanism; operation should match configuration noted on the data plate. A. Partially untank unit and support head and mechanism assembly with clean wooden blocks. B. Use manual closing tool to close interrupters. C. Pull down on strip solenoid trip links until mechanism trips. NOTE: The force required to pull down the trip-links will be increased when the time delay units are engaged. 50 45 60 50 70 60 560 560 560 D. Repeat steps B and C until lockout has been reached (yellow handle will drop). 6. Untank the recloser to expose the internal components. S280-30-7 CAUTION Be sure the recloser is open (yellow operating handle under the sleet hood is down) before untanking, so that the mechanism can not be accidently tripped while out of oil. 7. Clean all internal components. A. Remove all traces of carbon by wiping with a clean, lintfree cloth. NOTE Although current interruption takes place in a sealed vacuum chamber, the closing solenoid contactor operates in oil and will produce some carbon deposits. B. Flush the mechanism with clean transformer oil. CAUTION Never use volatile solutions, detergents, or water-soluble cleaners. 8. Remove bushings. A. Non oil filled bushing should be dismantled, cleaned and inspected. B. Oil filled bushing should be cleaned and inspected. DO NOT dismantle oil filled bushings. 9. Replace all external seals and gaskets. 10. Inspect mechanism for cracks, carbon tracking, flashovers or other damage. Repair or replace as required. 11. Check the condition of the closing solenoid contactor contact tips. If the contact tips are eroded replace entire contactor assembly. (See page 11 for replacement procedure.) A. An oil sample taken near the bottom of the tank should have a dielectric strength of not less than 22 kv rms. B. Low dielectric strength indicates the presence of water or carbon deposits. Replace the oil as necessary. 12. Inspect closing coil for cracks or other damage. 13. Inspect series trip solenoid. 14. Check the contact erosion of the vacuum interrupters. A. Locate the scribe mark on the moving contact rod at the top of the interrupter, Figure 8. B. If the scribe mark falls below the top of the phenolic guide when the interrupter is closed, the interrupter has reached the end of its useful life and must be replaced. (See page 10 for replacement procedure.) 15. Reinstall bushings, use new gaskets. (See page 8 for installation procedures.) 16. Drain the tank, and clean out all sludge and carbon deposits. If oil is to be reused it must be filtered and the dielectric strength checked. 17. Fill with new, clean insulating oil up to 2-1/4 inches below the top of the tank flange. See Oil Condition on page 8. 18. Clean the head gasket seat and retank the recloser. A. Move the yellow operating handle under the sleet hood to the up position to avoid any possible binding while raising the tank. B. Replace the head bolts and tighten to 35-55 ft-lbs torque. Apply clamping force gradually and equally, in rotation, to each bolt to achieve an evenly distributed gasket sealing pressure. 19. Check the oil level with the dipstick in the head and adjust the level to the upper line on the dipstick. NOTE: If the recloser is equipped with an oil-sight gage, the oil level should be above the sight gage. if the oil surface line is visible in the window, add oil to raise the level to the upper line on the dipstick. 20. Perform high-potential insulation withstand test (page ) to make sure the dielectric clearances within the tank have not been compromised. Also, use a suitable tester to verify that the recloser is operating per data plate specifications. Manual Operation of the Recloser The recloser may be closed and opened manually while the mechanism is either in or out of oil. MECHANISM IN OIL For a tanked recloser (mechanism immersed in oil) use the following manual operating procedure. 1. To close the recloser. A. Remove the closing tool port cover and gasket from the side of the head casting. (See Figure 2 for location.) B. Insert the KA9OR T-handle closing tool (furnished as an accessory) into the closing tool port (Figure 9) and engage the pin on the closing shaft. C. Lift up the yellow operating handle under the sleet hood to reset the mechanism. NOTE: Procedure for manually operating the recloser when the mechanism is out of oil is described on page 7. SCRIBE MARK Figure 8. Location of scribe on movable contact rod of vacuum interrupter. 84609KMA Figure 9. Manually closing recloser. 86797KMA 7 Types VW and VWV Maintenance Instructions D. Turn the closing tool one-quarter turn clockwise to close the main contacts. CAUTION TRIP LEVER Never use the KA90R closing tool to close an energized recloser. Forcing the tool beyond the mechanism stop may shear the pin on the closing shaft. 2. To open the recloser. A. Pull down the yellow operating handle to trip open the recloser. NOTE: If the mechanism is partially untanked, and properly supported, the recloser can be tripped open by pulling down on the series trip solenoid linkage. MECHANISM OUT OF OIL To operate the mechanism out of oil, proceed as follows: 1. To close the recloser. A. If the mechanism is still mounted in the head use the procedure for a tanked recloser above (Mechanism in Oil). B. If the mechanism is removed from the head turn the trip reset shaft (Figure 10) with a pair of needlenose pliers to reset the mechanism, then turn the closing shaft clockwise with the closing tool to close the main contacts. 86793KMA Figure 11. Trip lever releases mechanism when opening recloser out of oil. Insulation Level Withstand Tests CAUTION The mechanism may be damaged if it is "quick-tripped" with the yellow operating handle while out of oil. TRIP RESET SHAFT Figure 10. Resetting trip reset. RADIATION WARNING At voltages up to 45 kv the radiation emitted by the vacuum interrupter is negligble. However at higher test voltages radiation injurious to personnel may be emitted. See Radiation Warning Service Information Bulletin S280-90-1 for further details. 84616KMA 2. To open the recloser contacts while the mechanism is out of oil, proceed as follows: A. Using the T-handle closing tool turn the closing shaft clockwise and hold against the stop. B. Release the trip lever (Figure 11 ) by moving it to the right. C. Then slowly allow the closing tool to rotate counterclockwise to open the main contacts. NOTE: This procedure requires two people; one to operate the closing tool, the other to operate the trip lever. 8 High-potential withstand tests provide information on the dielectric condition of the recloser and the vacuum integrity of the interrupters. Testing is performed at 75% of the rated low frequency withstand voltage (37.5 kv for the VW, 45 kv for the VWV27 and 52.5 kv for the VWV38). TEST 1: Proceed as follows: 1. Manually close main contacts of recloser (see page 6 for procedure). 2. Ground recloser tank and head. 3. Connect all three source-side bushings (1, 3, 5) together. 4. Apply proper test voltage to source-side bushings. 5. The recloser should withstand the test voltage for 60 seconds. TEST 2: Proceed as follows: 1. Manually close main contacts of the recloser (see page 6 for procedure). 2. Ground recloser tank and head. 3. Ground Phase A (bushing 2) and Phase C (bushing 6). 4. Apply proper test voltage to Phase B (bushing 3). 5. The recloser should withstand the test voltage for 60 seconds. TEST 3: Proceed as follows: 1. Open main contacts of recloser (see page 6 for procedure). 2. Ground recloser tank and head. 3. Connect and ground all three load-side bushings (2, 4, 6). 4. Connect all three source-side bushings (1, 3, 5). 5. Apply proper test voltage to source-side bushings. 6. The recloser should withstand the test voltage for 60 seconds. 7. Reverse the connections: ground source-side bushings (1, 3, 5); apply test voltage to load-side bushings (2, 4, 6) for 60 seconds. 8. The recloser should withstand the test voltage for 60 seconds. S280-30-7 TEST RESULTS: These high potential withstand tests provide information on the dielectric condition of the recloser and the vacuum integrity of the interrupters. A. If the recloser passes the closed-contacts tests (Tests 1 and 2) but fails the open-contacts test (Test 3) a deteriorated vacuum in one or more of the interrupters is most likely the cause. Retest each vacuum interrupter individually to determine the failed phase or phases, and replace the interrupter(s). Retest to confirm the repair. B. If the recloser faiIs the closed-contacts tests (Test 1 and 2) the cause is likely to be a diminished electrical clearance or a failed insulation. After correcting the problem, retest to confirm the repair. Oil Condition Oil provides the internal insulation barrier between phases and from phase to ground, and must be replaced before it deteriorates below a safe dielectric level. Replace the oil if its dielectric strength falls below 22 kv. New oil should always be filtered before use, even though it is obtained from an approved source. Passing the oil through a blotter press will remove free water and solid contaminants such as rust, dirt, and lint. Keep aeration to a minimum during filtering to prevent moisture in the air from condensing in the oil and lowering its dielectric strength. Used oil must be treated before reusing. Filtering may remove absorbed and free water and other contaminants to raise the dielectric strength to acceptable levels. However, filtering does not always remove water-absorbing contaminants and the dielectric strength may fall rapidly after being returned to service. Therefore the recloser should be filled with new oil, or oil that has been restored to like-new condition. Oil used in these reclosers conforms to ASTM Standard D3487, Type 1; its property limits are shown in Reference Data R280-90-1, “Oil Specifications and Tests.” clockwise to reduce the dimension or counterclockwise to increase the dimension. Slide the control lever back onto the shaft and recheck the dimension. When the proper dimension has been obtained replace the C-ring. Bushings Bushing maintenance generally consists of a thorough cleaning and a careful examination for chips, cracks, or other mechanical damage during the periodic maintenance inspection. Bushings must be replaced whenever damage is discovered. TYPE VW BUSHINGS A damaged bushing can be replaced with the recloser either tanked or untanked, depending upon the circumstance of the damage. • If the bushing porcelain is accidentally chipped during installation of the recloser, and it is obvious that no other damage has occurred, the bushing porcelain only can be replaced without untanking the recloser. • If the bushing has been damaged while in service or storage, the recloser must be untanked. Water or other contaminants may have entered the tank (test the oil) the bushing lead may be damaged (either mechanically or electrical flashover), or pieces of porcelain may have fallen into the tank. Replacing the Bushing Porcelain with the Recloser Tanked Refer to Figure 13 and proceed as follows: SHOP MAINTENANCE PROCEDURES The operations described in this section should be performed under the cleanest conditions possible. The repair work, except for bushing replacement, will be simplified if the work bench is arranged so the mechanism/head assembly can be inverted (bushings down). No special tools are required for any of the repair procedures. Control Lever Overtravel Adjustment Check for proper adjustment of the control lever by first removing the sleet hood cover to expose the control lever. From the OPEN position, slowly push the control lever toward the CLOSED position. As the lever is pushed up, latching of the recloser will be felt. At this point the dimension between the top of the control lever and the underside of the sleet hood should be 1/4 inch (Figure 12). If the control lever is not adjusted properly, remove the C-ring and slide the control lever from the shaft. Rotate the control lever Figure 13. Replacing bushing w/tanked Type VW recloser. 1. Unscrew bushing terminal and discard terminal gasket. 2. Remove three hex head capscrews and clamps that secure the bushing to head and lift out porcelain. 3. Remove and discard lower bushing gasket. 4. Twist off split aluminum clamping ring from old porcelain. If it is in good condition install it on new porcelain; replace if damaged. Figure 12. Overtravel adjustment of control lever. NOTE: The clamping ring cushions and distributes the pressure between the porcelain and the clamps. DO NOT OMIT. 9 Types VW and VWV Maintenance Instructions 5. Using a new gasket, install new porcelain over bushing rod and into the head. Make sure roll pin, on end of the rod, is seated into locking groove at the top of porcelain. 6. Position clamping ring with split centered between the two outside clamping bolts. 7. Reassemble bushing to head casting with bushing clamps. Tighten clamping bolts evenly, a little at a time, to 10-15 ft-lbs torque. NOTE: Clamping forces must be applied gradually and equally in rotation to each bolt. This results in an evenly distributed gasket sealing pressure. 8. Install a new terminal gasket and reassemble terminal to bushing rod, tighen to 35 ft-lbs torque. NOTE: Apply a very small amount of petroleum jelly to the knurled surface of the inside face of the terminal before assembling the terminal to the bushing rod. Replacing the Bushing with the Recloser Untanked. Refer to Figure 14 and proceed as follows: 1. Loosen terminal. 2. Disconnect bushing lead from bottom end of bushing rod. 3. Remove three hex head capscrews and clamps that secure bushing to head and lift out complete bushing assembly. 4. Remove and discard lower bushing gasket. 5. The complete bushing assembly can be replaced or new porcelain only can be installed depending upon the extent of damage. If new porcelain only is to be installed, proceed as follows: A. Unscrew bushing terminal and withdraw the rod from bottom of porcelain; discard terminal gasket. B. Insert rod assembly all the way into the new porcelain, making sure roll pin is seated in the locking groove in top of bushing. C. Assemble terminal to bushing rod using a new terminal gasket; loosely tighten. 6. Twist off the split aluminum clamping ring from old bushing and install on new bushing, if it is in good condition; replace if damaged. NOTE: The clamping ring cushions and distributes the pressure between the porcelain and the clamps. DO NOT OMIT. 7. Install bushing assembly (new or reworked) into head using a new lower bushing gasket. 8. Position clamping ring with split centered between the two outside clamping bolts. 9. Reassemble bushing to head casting. Tighten clamping bolts evenly, a little at a time, to 10-15 ft-lbs torque. NOTE: Clamping forces must be applied gradually and equally in rotation to each bolt. This results in an evenly distributed gasket sealing pressure. 10. Tighten terminal to 35 ft-lbs torque. 11. Reconnect the lead to the bushing rod. TYPE VWV27 and VWV38 BUSHINGS The bushings used on Type VWV27 and VWV38 reclosers are oil-filled. The special fixtures and procedures required to assemble these bushings is beyond the scope of normal shop maintenance repair. Therefore if an oil bushing is in any way damaged, the complete bushing assembly must be replaced. Refer to Figure 15 and proceed as follows: NOTE: Apply a very small amount of petroleum jelly to the knurled surface of the inside face of the terminal before assembling the terminal to the bushing rod. Figure 15. Replacing bushing, Type VWV27 and VWV38. 1. Disconnect bushing lead from bottom end of bushing rod. 2. Remove three hex head capscrews and clamps that secure bushing to head. 3. Remove and discard lower bushing gasket. 4. Twist off split aluminum clamping ring from old bushing and install on new bushing, if it is in good condition—replace if damaged. Figure 14. Bushing parts VW recloser. 10 NOTE: The clamping ring cushions and distributes the pressure between the ceramic and the clamps. DO NOT OMIT. S280-30-7 5. Install new bushing through head. 6. Position bushing with stud end of terminal pointing outward. 7. Position clamping ring with split centered between the two outside clamping bolts. 8. Reassemble bushing to head casting. Tighten bolts evenly, a little at a time, to 10-15 ft-lbs torque. NOTE: Clamping forces must be applied gradually and equally in rotation to each bolt. This results in an evenly distributed gasket sealing pressure. 9. Reconnect lead to bushing rod. Vacuum Interrupters Vacuum interrupters must be replaced when: • They lose their vacuum as evidenced by a failure during the low frequency dielectric withstand test across the open contacts; • The interrupter contacts have eroded beyond their useful life as evidenced by the position of the scribe mark on the moving contact rod; or • The interrupters have completed their mechanical life of 7000 operations. To replace an interrupter, refer to Figure 16 and proceed as follows: UPPER PLATE CONTACT UPPER PLATE FIBER UPPER INTERRUPTER CLAMP action can be verified by observing the scribe mark on the contact rod. It will move downward to just above (or below) the fiber disk at the top of the interrupter. NOTE: If the contact rod does not move, the interrupter may have lost vacuum or the contact rod may be sticking in the clamping fingers of the contact operating rod assembly. Use a screwdriver to gently spread the clamping fingers to free the rod. 4. Disconnect bushing lead from lower contact plate assembly. 5. Loosen and remove lower interrupter clamp. 6. Remove hardware attaching lower contact plate to the three vertical stringers and remove contact plate and interrupter. 7. Install the new vacuum interrupter into the clamping fingers of the contact operating rod and the lower contact plate. Attach the plate to the stringers. NOTE: On side with the single stringer, a spacer on the stringer stud provides a 1/16-inch gap between contact plate and the attaching flat washer and locknut when the interruptercontacts are open. This gap is intentional. 8. Manually close recloser. 9. Coat threads of interrupter clamps and attaching screws with a film of transformer oil and loosely install. 10. Rotate interrupter so that one of the hex nuts at the top of the interrupter is centered directly beneath the gap on one side of the upper clamp. (See Figure 17.) 11. Position the upper and lower interrupter clamps just below the shoulder on the finger-type current exchange connectors so clamping force will be applied to the center of each finger, as shown in Figure 17. CAUTION When rotating the interrupter avoid twisting the contact rod to prevent damaging the bellows and destroying the interrupter. 12. Tighten screws of each interrupter clamp evenly to 75 in-lbs torque . SINGLE STRINGERS NOTE: Clamps must be tight to prevent slippage of interrupter contact rods in their current-exchange connectors. 13. Reconnect bushing lead to lower contact plate. 14. Reinstall vertical insulation barrier plate between long bushing lead and the mechanism. Position plate and secure it and the bushing lead with nylon tie straps. LOWER INTERRUPTER CLAMP LOWER FIBER PLATE Figure 16. Vacuum interrupter replacement. DOUBLE STRINGERS 86787KMA 1. Make sure the recloser contacts are open; the yellow manual operation handle, under the sleet hood, is pulled down. 2. Cut nylon tie straps which secure the vertical insulating barrier and remove barrier. 3. Loosen and remove upper interrupter clamp. As the clamp is loosened, atmospheric pressure on the bellows will cause the contact rod to move down into the interrupter. This Figure 17 Orientation or interrupter and clamp. 11 Types VW and VWV Maintenance Instructions 15. Manually trip and close the recloser several times to check interrupter operation. NOTE: Contact movement can be verified by observing the movement of the scribe mark on the upper contact rod of the interrupter. When the recloser is open the scribe mark will be about 5/8-inch above the fibre disk; on closing the mark will travel 1/2-inch downward. Closing Solenoid Contactor If the contacts are badly burned or eroded, the entire contactor must be replaced. See Figure 18 and proceed as follows: TOGGLE SPRINGS Closing Solenoid The closing solenoid coil is connected phase-to-phase and is rated to operate at full system voltage. It is protected with two fuses, one on either side. A data plate attached to the recloser head between source side bushings 3 and 5 provides the coil connection information. If the solenoid coil must be replaced, due to damage or change in operating voltage, refer to Figure 19 and proceed as follows: 1. Disconnect the two coil leads from closing solenoid contactor. NOTE: Reattach the lockwashers and nut to the contactor terminal immediately after disconnecting the coil lead to prevent loss of parts of the moving contact arm assembly which is attached to the support plate with the same hardware. 2. Remove four capscrews and lockwashers which attach base plate to bottom of solenoid frame posts and lower coil and base plate. 3. Remove coil from the base plate and discard coil gasket. 4. Using a new coil gasket, install new closing coil on the base plate. C-RINGS (4) TOGGLE MECHANISM TOGGLE PIN OPERATING LINK NOTE: A new coil gasket is included in the closing coil replacement kit. 5. Reassemble base plate to solenoid frame posts and connect coil leads to the contactor terminals. Make sure the coil leads clear the solenoid frame by at least 1/2-inch. 6. The closing coil replacement kit includes two new coil fuses which should be installed with the new coil. 7. The closing coil replacement kit also includes a new voltage date plate. Replace the plate on the sleet hood of the recloser head if the operating voltage of the recloser is being changed. NOTE: VWV27 reclosers, with 20 kv closing coils, above serial number 975 have a rigid tube insulator on the long coil lead. 20 kv and above replacement coils for units below serial number 975 include additional parts to modify the solenoid assembly to accommodate the rigid insulating tube. Installation instructions are included with the kit. LEADS CLOSING SOLENOID CONTACTOR Figure 18. Replacing closing coil contactor. SOLENOID FRAME 84614KMA 1. Unhook the two toggle springs from the pin that connects the operating shaft of the contactor to the toggle arm. 2. Remove the C-type retaining rings and withdraw the toggle pin. 3. Disconnect the two coil leads from the contactor. SOLENOID COIL NOTE: Reattach the lockwasher and hex nut to the contactor terminal immediately after disconnecting the coil lead to prevent loss of moving contact parts which are attached to the support plate with the same hardware. 4. Disconnect the two fuse leads from the contactor. 5. Remove three hex head capscrews and lockwasher that attach the contactor to the underside of the recloser mechanism frame and remove contactor. 6. Install new contactor by reversing the disassembly procecure. Use new C-rings to secure the toggle-link pin. 7. Connect solenoid coil leads to lower terminals. 8. Connect fuse leads to upper terminals. NOTE: Be sure coil and fuse leads are positioned for maximum clearance to grounded parts. 12 GASKET HEX HEAD CAPSCREWS BRIDGE PLATE Figure 19. Parts involved in solenoid coil replacement. 86784KMA S280-30-7 SERIES TRIP SOLENOID The continuous current rating and the trip current rating of the recloser can be changed by installing new coils in the series trip solenoids. Tripping occurs at about 200% of the continuous current rating of the standard coil and at about 140% when the alternate (400X or 560X) coils are used. The maximum interrupting rating of the recloser is dependent upon the continuous current rating of the series trip coil. Two different coil replacement kits are required. One for Phase A and Phase B solenoids and another for Phase C (the interrupter furthest away from the sleet hood) which has an opposite wind because it mounts differently on the interrupter. The same basic replacement procedure is used for either type coil. UPPER INSULATING WASHER FRAME Solenoid Disassembly 1. Remove cotter pin; slide out the groove pin and spacer that connect the insulated operating links to the solenoid plunger (Figure 20). 2. Remove bolt that fastens both the outer coil terminal and the short bushing lead to the lead mounting bracket. 3. Remove the capscrew that connects the inner coil terminal strap to the interrupter current interchange. 4. Remove elastic stop nut and flat washer that secure solenoid frame to the upper current exchange mounting board. Lift entire solenoid assembly off board. 5. Remove solenoid plunger, guide clips, guide channels and upper coil washer. 6. Lift coil slightly and pull out of the solenoid frame. 7. Replace any damaged parts at this time. COTTER PIN OPERATING LINKS SOLENOID COIL LOWER INSULATING WASHER Figure 21. Assembling solenoid series trip coil. 82023KMA 3. Replace in order the guide channels, guide clips and plunger. 4. Place the solenoid assembly back on the mounting board and secure it with the flat washers and elastic stop nuts. 5. Connect operating links to the solenoid plunger with the groove pin, spacer and cotter pin. 6. A sleeve is provided with each coil to insulate the outer coil lead from the frame. Slide the lead over the outer lead as illlustrated. 7. Connect the coil terminals to the current interchange and the bushing lead to complete the assembly. TIME DELAY UNIT SOLENOID PLUNGER SHORT BUSHING LEAD INNER COIL TERMINAL BOLT The recloser is equipped with hydraulically-operated time delay units on each phase. These provide the different time-current characteristic (TCC) curves, as shown in Reference Data R28091-6. Each unit can provide either of two-time delay characteristic curves, but not all four (KA1 194R1 provides B and C curves and KA1194R2 provides D and E curves). When the mechanism is sequenced to the delayed operation phase, the latch assembly of the trip-coil plunger linkage is engaged with the arm of the time-delay unit, this provides consistent delay action by forcing hydraulic fluid through an orifice in the unit. Special aircraft-type fluid is used to minimize temperature effects. Maintenance Figure 20. Series trip solenoid removal. 84613KMA Solenoid Replacement Check lower coil washer before installing new coils. For coils rated 280 amperes and below the upper and lower coil washers are identical. For 400 and 560 ampere rated coils, the lower washer requires a larger center slot. The same upper washer is used with all coil sizes. 1. Pass upper insulating washer over terminal strap and align its slot with the coil slot (Figure 21). 2. Insert coil into the frame and slide the upper coil washer into position. Maintenance to the time delay units is limited to checking the fluid level in the units. Some loss of fluid is normal, therefore this inspection should be made each time periodic maintenance is performed. To check the fluid level, remove the socket-head filler plug located on the side of the unit. Add enough fluid to bring the level up to the filler plug hole. Avoid introducing dirt, lint or any other foreign material when filling the unit as this can plug the orifice and cause erratic time-delay action. NOTE: A special fluid replacement kit, catalog number KA806R2, is available. The kit consists of approximately 60 cc (2 US fl. oz. ) of the special hydraulic fluid in an eye-dropper bottle. 13 Types VW and VWV Maintenance Instructions Replacement Replacement time-delay kits include a factory calibrated time delay, four flat head screws and a minimum-trip calibration spring. Remove the malfunctioning unit and install the replacement in its place (see Figure 22). The minimum trip setting of the recloser must be recalibrated by adjusting the spring tension whenever a new time-delay unit is installed. DELAY ARM COUPLERS Figure 23. Disconnect couplers. 84605KMA FILLER PLUG MINIMUM TRIP SPRING ADJUSTMENT SCREW Figure 22. Remove and replace time delay. E-RING 86780KMA Removing Mechanism from Head To gain access to components located in or on the main frame, the following procedure may be used to remove the mechanism from the head. NOTE: These procedures will be simplified if the untanked head and mechanism assembly can be inverted (bushings down). The unit can be supported on its bushings. 1. Disconnect all six bushing leads from the ends of the bushings. 2. Disconnect the lockout lever and contact position indicator shafts by disengaging the spring loaded couplers and locking them in the disengaged position, Figure 23. 3. Disconnect any accessories, such as a ground trip solenoid, at their terminals. 4. If the recloser is equipped with the auxiliary switch accessory, remove the C or E-ring and washer, Figure 24, and disconnect the operating lever of the switch from the recloser mechanism. 5. Remove the six socket head bolts and lockwashers that secure the frame to the head casting and carefully lift the mechanism from the head. Six long pipe spacers will be released when the mechanism is lifted. NOTE: By temporarily substituting eye-bolts for two of the hex head bolts in the bottom of the closing solenoid frame, the mechanism can be easily lifted and handled with a hoist. 6. Remove couplers from contact position indicator and lockout lever shafts. 14 OPERATING LEVER 83375KMA Figure 24. Remove E-ring to disconnect auxiliary switch operating lever. Reinstalling Mechanism into Head To reinstall the recloser mechanism assembly into the head, the following procedure may be used. 1. Install the couplers on the lockout lever and contact position indicator shafts. Lock them in the disengaged position. 2. Carefully lower the mechanism assembly onto the six pipe spacers which have been positioned over the mounting holes in the casting. 3. Install the six socket head bolts and tighten evenly to avoid any binding of the mechanism. NOTE: Replace the hex head bolts in the bottom of the closing solenoid frame if eye-bolts were used for handling the recloser mechanism. 4. Re-engage the lockout lever and contact position indicator shaft by releasing the shaft couplers. 5. Reconnect the operating lever of the auxiliary switch (if used) to the mechanism and secure with the washer and E-ring (Figure 24). 6. Reconnect the bushing leads to the end of the bushings. TESTING Procedures for testing the Type VW, VWV27 and VWV38 reclosers are included in the Installation Manual S280-30-1. S280-30-7 NOTES 15 Types VW and VWV Maintenance Instructions SERVICE PARTS LIST The service parts and hardware listed and illustrated include only those parts and assemblies usually furnished for repair or involved in the maintenance procedures described in this manual. Further breakdown of listed assemblies is not recommended. Dimensions of all common hardware parts have been carefully checked so that they may be locally acquired. The suffix letter of the 14 character catalog number for common hardware parts codes the plating of the part: A - No plating; raw material H - Silver M- Black oxide Q - Cadmium + zinc + chromate Y - Zinc + chromate Z - Electro zinc + bronze irridite Figure 25. Bushing Parts. 16 A hardware kit, Catalog No. KA849R1, contains an assortment of roll pins, cotter pins, retaining rings, stop nuts, etc.—common hardware parts used in Cooper Power System's reclosers that may not be readily locally available. To assure correct receipt of any parts order, always include recloser type and serial number. Because of Cooper Power System's continuous improvement policy, there may be instances where the parts furnished may not look exactly the same as the parts ordered. However, they will be completely interchangeable without any rework of the recloser. All parts carry the same warranty as any whole item of switchgear, i.e. against defects in material or workmanship within a period of one year from date of shipment. S280-30-7 Bushing Parts (Figure 25) Item No. 1 2 3 4 5 6 7 8 9 10 11 Description Bushing assembly—Type VW consists of items 10 thru 13) 13” standard creepage 13” standard creepage with BCT accy. 17” extra creepage 17” extra creepage with BCT accy. Bushing assembly—Type VWV27 (Above S/N 974) and Type VWV38 26-1/2” creepage 26-1/2” creepage with BCT accy. Bushing assy. replacement kit— Type VWV (below S/N 975) includes bushing and conductive gasket (9) 26-1/2” creepage 26-1/2” creepage with BCT accy. Hex jam nut, 1/2-20, brass Flat washer Split lockwasher. med. 1/2. bronze Capscrew, hex hd, 3/8-16 x 2-1/4, stl Bushing clamp Clamping ring Lower bushing gasket Type VW Type VWV27 and VWV38 Terminal assembly Upper bushing gasket Catalog Number Ouan. Req’d. Item No. Description Catalog Number Quan. Req’d. 12 KA717R25 6 KA717R26 KA717R27 6 6 KA717R28 6 KA56RV3 KA56RV4 6 6 KA842W1 KA842W2 K880725320050H KP2028A903 6 6 12 12 K900830050000A 6 K730101127225Q KP1109R KP1111 R 18 18 6 KP2090A66 KA1193R KA17W901 KP2090A57 6 6 1 1 Bushing ceramic—Type VW Standard creepage KP1110R 1 Standard creepage with BCT accy. KP171 W 1 17” extra creepage KP1578R 1 17” extra creepage with BCT accy. KP186W 1 13 Bushing rod assembly— Type VW Standard and 17” creepage KA716R20 1 Standard and 17” creepage with BCT accy. KA716R21 1 The following parts are applicable to the bushing current transformer accessory. 14 Capscrew, hex hd,3/8-16 x 1-7/8, stl K730101157187Q 3 15 Transformer clamping flange KP170W1 1 16 Flange gasket KP2090A73 2 17 Replacement current transformer 600:5 multi-ratio KA159W1S 1 1200:5 multi-ratio KA132W 1 18 CT washer KP312W 1 19 Capscrew, hex hd,3/8-16 x 1, stl K730101137100Q 3 20 Transformer clamping sleeve KP169W1 1 21 O-ring gasket, used with trans former clamping sleeve that has machined groove. Old style clamping sleeve without groove, use KP2090A66. KP2000A64 1 22 Hex nut, 3/8-16, stl K880201116037Q 3 23 Stud KP3149A40 1 24 Bushing spacer KP275W1 1 17 Types VW and VWV Maintenance Instructions Figure 26. Head and tank assemblies. 18 S280-30-7 Head and Tank Assemblies (Figure 26) Item No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Description Cover plate Gasket Capscrew hex hd, 1/4-20 x 3/4 stl Split lockwasher, med, 1/4, sti Dipstick O-ring gasket Closing coil instruction plate Self-tapping screw, Type F. #2 x 3/16, sst Capscrew, hex hd, 1/4-20 x spa, stl Manual closing tool access cover plate Cover plate gasket Capscrew, hex hd, 5/8-11 x 1-1/2.stl Split lockwasher, med, 5/8, stl Lifting lug Ground connector Head casting, includes control shaft bushings Head gasket Nameplate Type VW Type VWV27 Type VWV38 Voltage data plate Coil data plate Operating data plate Self-tapping screw, Type Z. #4 x 3/16, sst Sleet hood cover plate Thread cutting screw, Type T. #12 x 1/2. sst Contact indicator plate Handle designation plate Self-tapping screw, Type F. 2-56 x 3/16, sst Manual operating handle assembly Spacer Lever and split shaft assembly Spacer Spacer Catalog Number Quan. Req’d. Item No. KP609R KP611 R 2 2 33 34 K730101125075Q 8 35 36 K900801025000Z KA363R KP2000A9 KP2312R 8 1 1 1 K751515102018A 2 K730101125062Q 2 KP246R1 KP2000A12 1 1 39 40 41 42 43 44 K730101162150Q 2 45 K900801062000Z KP456H2 KA392R 2 2 1 KA840R KP2103A8 1 1 KRW107F1 KRW127F1 KRW173F KP567R KP2119A9 KP1371R 1 1 1 1 1 1 46 47 48 49 50 51 52 53 54 55 56 K801515004018A K283R 8 1 59 K781515112050A KP1067R KP390R 5 1 1 60 61 62 K751515102018A 4 KA477R KP3009A39 KA313R KP3011A5 KP3011A7 1 1 1 1 1 37 38 57 58 63 64 65 Description Lever and split shaft assembly Retaining ring. Type C, 5/16, stl, WA516 Roil pin,1/8 x 3/4 Retaining ring, Type C, 1/4, stl, WA514 One shot link and pin assembly Retaining ring, Type C,3/8. stl, WA518 Spacer Groove pin One shot handle assembly Spacer Spacer Indicator and support assembly Retaining ring, Type C,3/16 stl, WA510 Groove Pin Spacer Link Shaft and lever assembly Pin Spacer Flatwasher, #14S brass Cotter pin,3/32 x 1/2, stl Roll pin,3/32 x 1/2, stl Counter Self-tapping screw, Type F. 6-32 x 3/8, sst Bracket Self-tapping screw, Type Z. #10 x 3/8, sst Capscrew, hex hd, 1/2-13 x 3/4stl Flatwasher Pipe plug, 1”, sq hd Tank 29-1/2” high 25-1/2” high Pipe plug, 1/2”, sq hd Oil sampling and drain valve assy. Vacuum label Catalog Number Quan. Req’d. KA312R 1 K970901312000M K970801125075C 1 1 K970801250000M 2 KA505R 1 K970801375000M KP3013A91 KP3126A4 KA504R KP301 OA5 KP3013A38 2 1 1 1 1 2 KA317R 1 K970915188000A KP3123A12 K3006A9 KP1059R KA319R KP3190A11 KP3007A8 K900525026056A K970801093050A K970801093050C KA28COA2 3 1 1 1 1 1 1 1 1 1 1 K751515106037A KP1598R 2 1 K801515010037A 2 K730101150325Q KP2028A23 KP2007A4 10 10 1 KRW116FA KRW116FC KP2007A3 1 1 1 KA809R KP1041V4H 1 1 19 Types VW and VWV Maintenance Instructions Figure 27. Trip coil and interrupter mechanisms. 20 S280-30-7 Trip Coil and Interrrupter Mechanisms(Figure 27) Item No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 Description Time-delay unit replacement kit complete (includes attaching screws) For B and C curves For D and E curves Trip link assembly, complete Torsion spring Roll pin, 1/8 X 3/4, stl Trip lever stop Retaining ring, Type C, 1/4, stl Groove pin Spacer Cotter pin, 1/16 X 1/2. stl Capscrew, hex hd, 3/8-16 x 1-3/4, brass Flat washer, #24S, brass Spacer Split lockwasher med 3/8, sil brz Hex nut, 3/8-16, brass Capscrew, hex hd, 3/8-16 X 1”, sil brz Short lead (6 per phase) Short lead insulation Coil strap (400X and 560X trip coils only) Capscrew, hex hd,1/2-13 x 1, sil brz Split lockwasher, med, 1/2, sil brz Hex nut,1/2-13 sil brz Trip solenoid assembly (includes items 25 thru 36) Phases A and B Phase C Flat washer, SAE,1/4, stl Elastic stop nut,1/4 Self-tapping screw, rd hd Type F. #2 x 5/16. stl Eyelet Guide Solenoid plunger assembly Plunger guide Capscrew, hex hd, 1/4-20 x 7/8 stl Solenoid frame Series coil replacement kit (includes item 20, Figure 26) (Add coil rating as suffix to catalog number) Phases A and B Phase C Isoglass sleeve (not used with with 400X and 560X coils) Coil washer Coil washer (used with 400, 400X, 560 and 560X coils) Barrier Contact rod assembly Spacer Groove pin Retaining ring, Type C, 1/4”, stl Capscrew, hex hd, 1/4 X 1/2 with captive lockwasher, stl Catalog Number Quan. Req’d. KA1194R1 KA1194R2 KA161R KP576R K970801125075M KP577R 3 3 3 3 3 3 K970901250000M KP3114A1 KP3007A12 K970501062050A 3 3 3 3 K730125137175A K900525039087H KP3013A63 3 12 3 K900830037000A K880225116037H 9 9 K730133137100A KP3250A1 KP2106A80 6 18 3 KP1085VWS 3 K730133150100A 3 K900830050000A K880133113050A 3 3 KA134VWS2 KA134VWS1 K900201025000Z KP2020A3 2 1 6 6 K751501102031 A KP1351 R KP622R KA604R KP312R 6 6 6 3 6 K730101125087A KA603R 6 3 Item No. 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 KA835W2KA835W1- 2 1 KP2104A15 KP318R 3 6 KP1075R KP1684R1 KA111VWS KP3007A49 KP3124A76 3 3 3 3 3 K970901250000M 12 K830101125050A 6 72 73 74 Description Groove pin Insulation barrier Wire tie, Panduit#SST4H Upper stringer assembly Insulating tubing Lead mounting bracket Machine screw, rd hd, 1/4-20 x 1 brass Fuse mounting clip Lead assembly Flat washer, #14S, brass Split lockwasher, med, 1/4, brz Hex nut,1/4-20, brass Spring Upper current exchange assy. Phases A and B Phase C Machine screw, rd hd,1/4-20 X 3/8, brass Closing coil fuse assembly (also included in closing coil replacement kit, Figure 28, item 36). 2.4-3.3 kv (2 red color bands) 4.16-6 kv (black color band) 7.2 to 11 kv (yellow color band) 12 to 24.9 kv (red color band) Closing solenoid contactor Type VW Type VWV27 and VWV38 Contactor toggle spring Groove pin Retaining ring, Type C,1/4” stl Capscrew, hex hd,1/4-20 x 1/2 with preassembled split lockwasher, stl Lower stringer assembly Lower current exchange and support plate assembly Phases A and B Phase C Flat washer, SAE, 3/8, stl Split lockwasher, med, 3/8, stl Hex nut, 3/8-16, stl Spacer Interrupter clamp Capscrew, hex socket hd 1/4-20 x 1, stl Vacuum interrupter Type VW S/N 3104 and before Phase A & B Phase C Type VWV S/N 976 and before Phase A & B Phase C Type VW S/N 3105 and after Type VWV 27 S/N 977 and after Type VWV38 Long bushing lead (6 per phase) Long lead insulation Toggle assembly Catalog Number Quan. Req’d. KP3124A50 KRW125N1 K994904170004A KA62R KP3230A14 KP1061VWS 3 3 12 9 9 3 K721525125100A KP2006A16 KA28W1 K900525026056A K900830025000A K881025120025A KP1066VWS 3 2 2 3 7 7 6 KRW115FB KRW115FA 2 1 K721525125037A 4 KA259R904 KA259R901 KA259R902 KA259R903 2 2 2 2 KA430R1 KA430R3 KP141R KP1306R K970901250000M 1 1 2 1 4 K830101125050A KA222VS 3 9 KRW446VB KRW446VA K900201037000A K900801037000Z K880201116037A KP3009A11 KP1036VS 2 1 9 9 9 3 12 KP2036A10 12 KRW705VA KRW705VB 2 1 KRW705VC KRW705VD KA215VS2 2 1 3 KA227VS2 KA238VSA2 3 KP3250A27 KP2106A77 KA450R1 18 3 1 21 Types VW and VWV Maintenance Instructions Figure 28. Closing solenoid and hydraulic control parts. 22 S280-30-7 Closing Solenoid and Hydraulic Contol Parts(Figure 28) Item No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 * Description Capscrew, hex socket hd, 1/2-13 x 4-1/2, stl Split lockwasher, med, 1/2, stl Spacer Counter shaft coupler Operating lever coupler Pivot pin Retaining ring, Type C, 1/4, stl Lockout piston link Pin Lockout piston Spring clip Pump link Pump piston Pin Pump piston shell Retaining ring, Type E, 1/8”, stl Quick reset valve assembly Pump and lockout piston block Capscrew, hex hd, 1/4-20 x 1-3/4, stl Split lockwasher, med, 1/4, stl O-ring gasket Ball Ball seat Ball retainer pin Ball retainer pin Gasket Retaining ring, Type C, 3/8”, stl Groove pin Flat washer, SAE, 3/8, stl Plunger and link assembly Stringer assembly Split lockwasher, med, 3/8, stl Quan. Req’d. Item No. KP2036A3 6 K900801050000Z KP3182A1 KP2448R KP2447R KP418H 6 6 1 1 1 33 34 35 36 K970901250000M KP122R KP3055A3 KP112R KP2018A1 KA97R KP1733R KP3055A1 KP1732R 1 1 1 1 1 1 1 1 1 K971001125000A KA423R 1 1 KP1300R 1 K730101125175A 2 K970801025000A KP2000A3 KP2025A2 KP155H2 KP3051 A3 KP3051A1 KP116R 2 2 2 2 1 1 1 K970901312000M KP3126A2 K900201037000A KA50R KA62R 2 1 2 1 4 K900801037000Z 12 Catalog Number 37 38 39 Description Catalog Number Hex nut, 3/8-16, stl K880201116037A Solenoid frame KP100R2 Capscrew, 3/8-16 x 1-1/2, stl K730101137125A Closing coil replacement kit (includes closing coil, lower coil gasket 37 (Figure 28), two fuse assemblies 57 (Figure 27), and voltage data plate, 19 Figure 26). Type VW and VWV27 reclosers below 20 kv 2.4 kv KA834R1 3.3 kv KA834R10 4.16-4.8 kv KA834R2 6.0 kv KA834R6 7.2-8.32 kv KA834R3 11.0 kv KA834R9 12.2-13.2 kv KA834R4 14.4 kv KA834R5 17.0 kv KA834R12 20.0 kv KA834R11 Type VWV27 and VWV38 reclosers 20 kv and above 23.0-24.9 kv KA834R13 34.5 kv KA834R14 Reclosers with low voltage closing 48 vdc KA834R16* 125 vdc KA834R7* 250 vdc KA834R8* Solenoid gasket KP389R Solenoid frame post KP1669R Solenoid bridge plate assembly KA644R3 Quan. Req’d. 4 1 8 1 4 1 No fuses required with low-voltage dc coils when converting a recloser for low-voltage operation use low-voltage contactor and coil kit KA887R; specify desired operating voltage (Vdc or Vac). 23 Types VW and VWV Maintenance Instructions © 2005 Cooper Power Systems or its affiliates. Kyle® is a registered trademark of Cooper Power Systems or its affiliates. 1045 Hickory Street Pewaukee, WI 53072 www.cooperpower.com KDL 7/05