R280-90-37 Communications Point Data Base and Available Data Points Reclosers

advertisement
Reclosers
Reference Information
SPEAR Single-Phase Recloser Control
R280-90-37
Communications Point Data Base
and Available Data Points
Data 3461
for
Communications Protocol DNP3
For Use With Eaton’s Cooper Power Systems
SPEAR Single-Phase Recloser Control
March 2014 • Supersedes 10/2013
SPEAR DNP3 Device Profile Data Dictionary
SPEAR DNP3 Map Points
March 19, 2014
v1.01
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.01
Date
8/19/2013
3/19/2014
Description
Initial Release
Removal of extra binary output point
Page 1
Cover Page
SPEAR DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
Recloser Closed
Recloser Open
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non Reclosing
CLPU Blocked
Fast Trips Disabled
Profile Selected Normal
Profile Selected Alt
Hot Line Tag
Bus Voltage Present
Battery Test In Progress
No AC Power
Battery Alarm
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
Hex Index
Default
Event
Class
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 2
Default Event Variation
Obj 02 Var 2 Binary input with time
Class 0 - 3, Binarys
SPEAR DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters
Description
Fault Trip Counter
Operations Counter
Default Static Variation
Obj 20 Var 2 16 bit Counter
Index
Hex Index
00
01
00
01
Default Event Variation
Obj 22 Var 2 16 bit Counter w/o time
Default
Event Deadband
Class
1
1
1
1
Page 3
Class 0 - 3, Counters
SPEAR DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Analog Inputs
Description
Primary Current Magnitude
Primary Voltage Magnitude
Power Factor
Primary Apparent Power
Primary Real Power
Primary Reactive Power
Line Frequency
Primary Demand Currents
Battery Test Voltage
Battery Test Current
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
00
01
02
03
04
05
06
07
08
09
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Scale Factor
Class
2
2
2
2
2
2
1
2
2
2
10
1
10000
1
1
1
100
10
1
1
Page 4
Units
Deadband
Amps
Volts
N/A
kVA
kW
kvar
Hz
Amps
Volts
Amps
100
1000
1
1000
1000
1000
10
100
1000
1000
Class 0 - 3, Analog Inputs
SPEAR DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Default Static Variation
Description
Index Hex Index Obj Var
Desc
Operation Type
Operation
(Support)
Mask
Default
Condition
Self-Resetting
Self-Resetting
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
00
01
02
03
04
05
06
07
08
09
10
11
12
13
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
12
12
12
12
12
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
01
01
01
01
01
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
00
01
02
03
04
05
06
07
08
09
10
11
12
13
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
10
10
10
10
10
10
10
10
10
10
10
10
10
10
02
02
02
02
02
02
02
02
02
02
02
02
02
02
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Status
Conditioned by
Supervisory State Description
(Factory Default)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Close Mechanism
Trip Mechanism
Block Reclosing
Block CLPU
Disable Fast Trips
Profile Normal
Profile Alt
Reset Targets
Reset Demand Meters
Test Battery
Hot Line Tag Set
Hot Line Tag Reset
Combined Trip and Close
Reset Energy Meters
Close Mechanism
Trip Mechanism
Block Reclosing
Block CLPU
Disable Fast Trips
Profile Normal
Profile Alt
Reset Targets
Reset Demand Meters
Test Battery
Hot Line Tag Set
Hot Line Tag Reset
Combined Trip and Close
Reset Energy Meters
Page 5
CROB
SPEAR Available Data Points
SPEAR Communications Point Availability
March 19, 2014
v1.01
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
1.01
Date
8/19/2013
3/19/2014
Description
Initial Release
Removal of extra binary input and output points
The data points listed in this document are available for mapping to the SCADA protocol User Maps
as described in service document S280-101-3, SPEAR Recloser Control Communications.
Page 1
Cover Page
SPEAR Available Data Points
Binary Input Points
Description
Recloser Closed
Recloser Open
Control is Locked Out
Any Control or System Alarm
Above Minimum Trip
Supervisory Off
Non Reclosing
CLPU Blocked
Fast Trips Disabled
Profile Selected Normal
Profile Selected Alt
Hot Line Tag
Bus Voltage Present
Battery Test In Progress
No AC Power
Battery Alarm
Phase Fault
Hot Line Tag On from Communications
Hot Line Tag On from Front Panel Switch
Control Circuit Interrupted
Page 2
Binary Input Points
SPEAR Available Data Points
Analog Input Points
Description
Primary Current Magnitude
Primary Voltage Magnitude
Power Factor
Primary Apparent Power
Primary Real Power
Primary Reactive Power
Line Frequency
Primary Demand Currents
Battery Voltage
Battery Current
Demand Voltage
Demand Power Factor
Demand Apparent Power
Demand Real Power
Demand Reactive Power
Depleted
KW Hours
Battery Test Voltage
Battery Test Current
Firmware Revision Number
Last Update Time
Fault Current
Page 3
Analog Input Points
SPEAR Available Data Points
Counter Input Points
Description
Fault Trip Counter
Operations Counter
Page 4
Counter Input Points
SPEAR Available Data Points
Binary Output Points
Description
Close Mechanism
Trip Mechanism
Block Reclosing
Block CLPU
Disable Fast Trips
Profile Normal
Profile Alt
Reset Targets
Reset Demand Meters
Test Battery
Hot Line Tag Set
Hot Line Tag Reset
Combined Trip and Close
Reset Energy Meters
Page 5
Binary Output Points
SPEAR Single-Phase Recloser Control SCADA Communications Protocol DNP3
©2014 Eaton. All Rights Reserved.
Eaton, Cooper Power Systems, and SPEAR are valuable trademarks of
Eaton in the U.S. and other countries. You are not permitted to use
Eaton trademarks without the prior written consent of Eaton.
One Cooper | www.cooperpower.com | Online
2300 Badger Drive
Waukesha, WI 53188
Download