Reclosers Reference Information SPEAR Single-Phase Recloser Control R280-90-37 Communications Point Data Base and Available Data Points Data 3461 for Communications Protocol DNP3 For Use With Eaton’s Cooper Power Systems SPEAR Single-Phase Recloser Control March 2014 • Supersedes 10/2013 SPEAR DNP3 Device Profile Data Dictionary SPEAR DNP3 Map Points March 19, 2014 v1.01 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 1.01 Date 8/19/2013 3/19/2014 Description Initial Release Removal of extra binary output point Page 1 Cover Page SPEAR DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Binary Inputs Description Recloser Closed Recloser Open Control is Locked Out Any Control or System Alarm Above Minimum Trip Supervisory Off Non Reclosing CLPU Blocked Fast Trips Disabled Profile Selected Normal Profile Selected Alt Hot Line Tag Bus Voltage Present Battery Test In Progress No AC Power Battery Alarm Default Static Variation Obj 01 Var 01 Binary input w/o status Index Hex Index Default Event Class 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Page 2 Default Event Variation Obj 02 Var 2 Binary input with time Class 0 - 3, Binarys SPEAR DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Counters Description Fault Trip Counter Operations Counter Default Static Variation Obj 20 Var 2 16 bit Counter Index Hex Index 00 01 00 01 Default Event Variation Obj 22 Var 2 16 bit Counter w/o time Default Event Deadband Class 1 1 1 1 Page 3 Class 0 - 3, Counters SPEAR DNP3 Device Profile Data Dictionary INPUT SUBSYSTEM Analog Inputs Description Primary Current Magnitude Primary Voltage Magnitude Power Factor Primary Apparent Power Primary Real Power Primary Reactive Power Line Frequency Primary Demand Currents Battery Test Voltage Battery Test Current Default Static Variation Obj 30 Var 2 16 bit Index Hex Index 00 01 02 03 04 05 06 07 08 09 00 01 02 03 04 05 06 07 08 09 Default Event Variation Obj 32 Var 2 16 bit w/o time Default Division Event Scale Factor Class 2 2 2 2 2 2 1 2 2 2 10 1 10000 1 1 1 100 10 1 1 Page 4 Units Deadband Amps Volts N/A kVA kW kvar Hz Amps Volts Amps 100 1000 1 1000 1000 1000 10 100 1000 1000 Class 0 - 3, Analog Inputs SPEAR DNP3 Device Profile Data Dictionary OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status Default Static Variation Description Index Hex Index Obj Var Desc Operation Type Operation (Support) Mask Default Condition Self-Resetting Self-Resetting Latched Latched Latched Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting Self-Resetting 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff 0xff Off Off Off Off Off Off Off Off Off Off Off Off Off Off Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output 00 01 02 03 04 05 06 07 08 09 10 11 12 13 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 12 12 12 12 12 12 12 12 12 12 12 12 12 12 01 01 01 01 01 01 01 01 01 01 01 01 01 01 CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB CROB Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output Binary Output 00 01 02 03 04 05 06 07 08 09 10 11 12 13 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 10 10 10 10 10 10 10 10 10 10 10 10 10 10 02 02 02 02 02 02 02 02 02 02 02 02 02 02 Status Status Status Status Status Status Status Status Status Status Status Status Status Status Conditioned by Supervisory State Description (Factory Default) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Close Mechanism Trip Mechanism Block Reclosing Block CLPU Disable Fast Trips Profile Normal Profile Alt Reset Targets Reset Demand Meters Test Battery Hot Line Tag Set Hot Line Tag Reset Combined Trip and Close Reset Energy Meters Close Mechanism Trip Mechanism Block Reclosing Block CLPU Disable Fast Trips Profile Normal Profile Alt Reset Targets Reset Demand Meters Test Battery Hot Line Tag Set Hot Line Tag Reset Combined Trip and Close Reset Energy Meters Page 5 CROB SPEAR Available Data Points SPEAR Communications Point Availability March 19, 2014 v1.01 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 1.01 Date 8/19/2013 3/19/2014 Description Initial Release Removal of extra binary input and output points The data points listed in this document are available for mapping to the SCADA protocol User Maps as described in service document S280-101-3, SPEAR Recloser Control Communications. Page 1 Cover Page SPEAR Available Data Points Binary Input Points Description Recloser Closed Recloser Open Control is Locked Out Any Control or System Alarm Above Minimum Trip Supervisory Off Non Reclosing CLPU Blocked Fast Trips Disabled Profile Selected Normal Profile Selected Alt Hot Line Tag Bus Voltage Present Battery Test In Progress No AC Power Battery Alarm Phase Fault Hot Line Tag On from Communications Hot Line Tag On from Front Panel Switch Control Circuit Interrupted Page 2 Binary Input Points SPEAR Available Data Points Analog Input Points Description Primary Current Magnitude Primary Voltage Magnitude Power Factor Primary Apparent Power Primary Real Power Primary Reactive Power Line Frequency Primary Demand Currents Battery Voltage Battery Current Demand Voltage Demand Power Factor Demand Apparent Power Demand Real Power Demand Reactive Power Depleted KW Hours Battery Test Voltage Battery Test Current Firmware Revision Number Last Update Time Fault Current Page 3 Analog Input Points SPEAR Available Data Points Counter Input Points Description Fault Trip Counter Operations Counter Page 4 Counter Input Points SPEAR Available Data Points Binary Output Points Description Close Mechanism Trip Mechanism Block Reclosing Block CLPU Disable Fast Trips Profile Normal Profile Alt Reset Targets Reset Demand Meters Test Battery Hot Line Tag Set Hot Line Tag Reset Combined Trip and Close Reset Energy Meters Page 5 Binary Output Points SPEAR Single-Phase Recloser Control SCADA Communications Protocol DNP3 ©2014 Eaton. All Rights Reserved. Eaton, Cooper Power Systems, and SPEAR are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use Eaton trademarks without the prior written consent of Eaton. One Cooper | www.cooperpower.com | Online 2300 Badger Drive Waukesha, WI 53188