ICI KIT A, B & C, ATEX/IECEX OPERATORS IF 1703 APPlicAtion

advertisement
ICI KIT A, B & C, ATEX/IECEx OPERATORS
IF 1703
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPlication
STANDARDS:
ICI KITs A, B & C are used as circuit breaker, starter and contactor
operators. They are used in panels and enclosures in areas made
hazardous due to the presence of flammable vapors, gases or
combustible dusts. ICI KIT A is typically used for 250-400A Frame
breakers were more leverage is required to compensate for a higher
actuation force. ICI KIT B is used for 150A Frame and lower breakers and
ICI KIT C is used for operating a starter/contactor reset button. ICI KITs
A, B & C are suitable for use indoor or outdoor.
•
•
•
ICI KITs A, B & C meet the ATEX/IECEx directive and are certified by
ETL. Operators have the following classification: II 2 G Ex d IIB+H2 Gb
and II 2 D Ex tb IIIC Db. ICI KITs A & B operators have an IP66 rating and
ICI KIT C has a IP64 rating.
When operators are to be installed in equipment, refer to installation
instruction sheet that came with that equipment for proper installation.
To avoid the risk of fire, explosion, or electric shock: Electrical
power must be off before and during installation and maintenance.
IMPORTANT NOTE:
2.
3.
INSTALLATION
4.
IMPORTANT NOTE
When operators are to be installed in equipment, refer to installation
instruction sheet that came with that equipment for proper installation.
EN 60079-0 2012
EN 60079-1: 2007
EN 6007-31:2009
ICI KITs A, B & C should be installed, inspected and maintained by
qualified and competent personnel.
1.
WARNING
IEC 60079-0 edition 6 2011-06
IEC 60079-1 edition 6 2007-04
IEC 60079-31 edition 1 2008-11
5.
Place Stop Plate over 7/8-20 cover hole “B” and align with detent
hole “A” (See Figure 1).
Screw operator bushing Item 2 (See Figure 2) into cover and ensure
a minimum of 8 threads are engaged with the cover. Tighten to 2530 lb-ft [33.9-40.7 N-m].
Screw shaft Item 3 (See Figure 2) into bushing Item 2 until there is
roughly 1.18” of shaft above the cover.
Assemble two 5/8-11 hex nuts and operating fork items 7 and 8 as
shown in figure 2. Tighten both 5/8-11 hex nuts to 45-55 lb-ft [61-75
N-m].
Align operating handle onto shaft paying attention to the position of
the operating fork.
ICI Kit A
200.1
7.88
1
PER APPLICATION
1.25 [31.8]
B
.25" MIN
[6.4]
A
A
68.3
R2.69
A
PER APPLICATION
1 HOLE "A"
.516 DIA x .12 DEEP
.04 x 45° C'SINK
OUTSIDE SURFACE
9
1 HOLE "B"
7/8-20NEF-1B THRU
Figure 1
SECTION A-A
3
6
65.1
2.56 OFFSET FROM
TOGGLE CENTER
5
1.18 [29.9] REF
PER
APPLICATION
2
7
4
.50 [12.7] REF
8
Figure 2
IF 1703 • 08/14
Item
Description
1
Stop Plate
2
Operating Shaft Bushing
3
Operating Shaft Retaining Ring
4
Operating Shaft
5
Operating Handle
6
Handle Screw, 5/16-18
7
Operating Fork Assembly
8
Hex Nut, 5/8-11
9
Stop Screw and Nut
Copyright© 2014, Eaton’s Crouse-Hinds Business
Page 1
IMPORTANT NOTE
A
125.8
4.95
When operators are to be installed in equipment, refer to installation
instruction sheet that came with that equipment for proper installation.
1
ICI Kit B
PER APPLICATION
.25" MIN
[6.4]
.75 [19.1]
41.3
R1.63
6
A
A
B
1 HOLE "A"
3/4-20NEF-2B THRU
PER APPLICATION
1 HOLE "B"
.437 DIA X .20±.05 DP
OUTSIDE SURFACE
41.1
1.62 OFFSET FROM
TOGGLE CENTER
Figure 4
SECTION A-A
Figure 6
Item
5
2
3
4
Description
1
Stop Plate
2
Operating Shaft Bushing
3
Operating Shaft
4
Operating Handle
5
Operating Fork Assembly
6
Stop Screw and Nut
Operator Installation:
1.03 [26.1] REF
.38 [9.5] REF
PER
APPLICATION
1.
2.
Figure 5
3.
4.
5.
IF 1703 • 08/14
Place Stop Plate over 3/4-20 cover hole “A” and align with detent
hole “B” (See Figure 4).
Screw operator bushing Item 4 (See Figure 5) into cover and ensure
a minimum of 8 threads are engaged with the cover. Tighten to 2530 lb-ft [33.9-40.7 N-m].
Screw shaft Item 5 (See Figure 5) into bushing Item 4 until there is
roughly 1.03” of shaft above the cover.
Assemble operating fork as shown in figure 5. Tighten screw to 3545 lb-in [4.0-5.1 N-m].
Align operating handle onto shaft paying attention to the position of
the operating fork.
Copyright© 2014, Eaton’s Crouse-Hinds Business
Page 2
IMPORTANT NOTE
When operators are to be installed in equipment, refer to installation
instruction sheet that came with that equipment for proper installation.
Fork Adjustment:
1.
2.
3.
4.
5.
6.
Measure distance from body flange to bottom of ICI Kit B and
middle of ICI Kit A toggle (Dimension A).
Measure distance from inside of cover to bottom of ICI Kit B and
middle of ICI Kit A fork (Dimension B).
Adjust fork up or down so that [B = A – 0.06”] for ICI KIT A and [B =
A – 0.12”] for ICI KIT B.
Move breaker toggle to “OFF” position and operator handle to
“OFF” position.
Close cover and check breaker operation.
Adjust fork up or down to optimize breaker operation.
Figure 7
Stop Adjustment:
1.
2.
3.
4.
5.
6.
7.
8.
Move operator to “ON” position.
Put light pressure on handle in the “ON” direction and hold in that
position. Fork should be touching toggle.
Turn stop screw until it touches handle.
Tighten stop nut.
Move operator to “OFF” position.
Put normal pressure on handle in the “OFF” direction until the
handle stops. Hold in that position. This represents the reset
position.
Turn stop screw until it touches handle.
Tighten stop nut.
Figure 8
IF 1703 • 08/14
Copyright© 2014, Eaton’s Crouse-Hinds Business
Page 3
IMPORTANT NOTE
Item
Description
When operators are to be installed in equipment, refer to installation
instruction sheet that came with that equipment for proper installation.
1
Pushbutton Guard
2
Sleeve Locking Ring
ICI KIT C
3
Push Button Shaft
4
Push Button Sleeve
1.
5
Hex Nut, 1/4-20
6
Reset Extension Button
2.
3.
4.
Remove guards, indicating plates, outer locknuts, etc., to enable
barrels to be threaded into the enclosure. Leave final locknut on
barrel for mounting.
Thread barrel assemblies into drilled and tapped holes 3 /4-14
NPSM from behind so they protrude to the enclosure front.
Adjust length of barrel protrusion and thread inner locknut tightly
against inside wall for mounting.
Replace guards, indicating plates, outer locknuts, etc.
WARNING
To avoid explosion: clean both ground-joint surfaces of body and cover
before closing. Dirt or foreign material must not accumulate on flat
ground-joint surfaces. Surfaces must seat fully against each other to
provide a proper explosionproof seal.
50.8
2.00
A
maintenance
A
1.
Regular inspections should be made. A schedule for maintenance
check should be determined by the environment and frequency of
use. It is recommended that it should be at least once a year.
2.
Perform visual, electrical, and mechanical checks on all
components on a regular basis.
50.8
2.00
• Electrically check to make sure that all connections are clean
and tight, and that contacts in the components make or break as
required.
• Mechanically check that all parts are properly assembled, and
operating mechanisms move freely.
55.8
2.20
3.
We recommend an Electrical Preventive Maintenance program as
described in the National Fire Protection Association Bulletin NFPA
No. 70B.
REPLACEMENT PARTS
ICI Kits are designed to provide years of reliable service. However,
should the need for replacement parts arise, they are available through
your Crouse-Hinds Distributor. Assistance may also be obtained through
your Crouse-Hinds Sales Representative or the Crouse-Hinds Customer
Service Department.
Figure 9
SECTION A-A
1.54 [39.2] REF
1
compliances
2
• ATEX:
• IECEx:
ITS07ATEX15652U
ETL14.0005U
CONDITIONS OF USE
•
PER
APPLICATION
3
4
5
.13 [3.2] REF
6
•
•
•
•
•
Operators must be installed to provide a minimum 8 threads of
engagement.
These units have not been evaluated for ambient temperatures
outside of -20°C to +60°C.
The operators may be installed in enclosures where the reference
pressure does not exceed 751.5 kPa (109 PSI) without further
evaluation.
ICI Kits must be installed per manufacturer’s instruction sheet
IF1703.
Machining of flamepaths is not allowed.
Earthing of the components must be addressed in the end use.
Figure 10
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or
completeness thereof are not guaranteed. In accordance with Crouse-Hinds “Terms and Conditions of Sale,” and since conditions of use are outside our
control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Eaton’s Crouse-Hinds Business
1201 Wolf Street Syracuse, New York 13208 • U.S.A.
Copyright© 2014
IF 1703
R
evision 1
New 08/14
Download