Voltage Regulators R225-90-4

advertisement
Voltage Regulators
McGraw-Edison® Voltage Regulator
CL-5A Microprocessor-Based Control
Digital Communications
Cooper Power Systems
Reference Data
R225-90-4
DATA 2458
ORDINAL POINT ASSIGNMENTS
FOR CL5A REGULATOR CONTROL
For Use With Data 2179 Protocol
The information contained herein is for specific use by the party of initial issue.
This information remains the property of Cooper Power Systems and is not to be
forwarded beyond the initial issue party without the written consent of
Cooper Power Systems.
When additional information is desired to satisfy a question not covered sufficiently for the users purpose, please contact your Cooper Power Systems representative.
April 1994 • 1994 ©Cooper Power Systems, Inc.
CL-5A Microprocessor-Based Control Digital Communications
p. 2
CL5 REGULATOR CONTROL COMMUNICATIONS INTERFACE
SEQUENCE NUMBER AND ORDINAL MEMORY ADDRESS ASSIGNMENTS
for the Cooper Power Systems subset of the PG&E Protocol
Revision
Revision
Revision
Revision
Revision
01...........
02...........
03...........
04...........
05...........
June 14, 1991 (UNDER CONSTRUCTION)
June 12, 1992 (UNDER CONSTRUCTION)
October 13, 1992 (UNDER CONSTRUCTION)
December 7, 1993
February 2, 1994
Note: The following definitions apply to the tables below:
“Scale Factor” is factor by which a signed integer value read from the CL5 is divided to get the value of
the variable in the indicated units.
“Function code” is the code used to access the parameter through the CL5 frontpanel controls, if
applicable, and is listed for information only.
“Cross Reference” is with reference to the control’s internal data base, and is listed for designers’
information only. Not useful to user.
R225-90-4
p. 3
INPUT SUBSYSTEM: Sequence numbers used in BASIC SCAN and
SCAN-BY-TABLE operations
Simple Status data type...
SEQ #
(HEX)
SCALE
CROSS FUNC
FACTOR UNITS REF
CODE
30
5-1
2-42
ADDITIONAL COMMENTS/NOTES
State of Display Annunciators
69
1-13
(0 = OFF, 1 = ON)
Bit 0 - “LOW” Bandwidth
Bit 1 - “HIGH” Bandwidth
Bit 2 - “LOW” Voltage Limiting
Bit 3 - “HIGH” Voltage Limiting
Bit 4 - “V. RED.” Voltage Reduction
Bit 5 - Spare
Bit 6 - Spare
Bit 7 - Spare
State of Regulation TaskBit 8 0 = Normal Automatic Operation
(Blocked/Unblocked)
1 = Automatic Operation Inhibited
Power Direction Indication
Bit 9 0 = Current flow is Determinate
1 = Current flow Indeterminate
(Bit 10 is undefined)
Bit 10 - 0 = Forward current flow
1 = Reverse current flow
Control Power Direction Status Bit 11 - 0 = Forward current flow
1 = Reverse current flow
Bit 12 - New Min/Max Time-tagged Avail.
Bit 13 - Spare
Bit 14 - Spare
Bit 15 - Spare
1-27
31
DESCRIPTION
4-1
State of Auto/Off/Manual Switch
Bit 0 -
0 = OFF/MANUAL
1 = AUTO
4-0
State of Voltage Reduction Inputs
Bit 1 - Reduction #1
Bit 2 - Reduction #2
State of Supervisory Switch
Bit 3 - Supervisory On
Bit 4 - Spare
Bit 5 - Spare
Bit 6 - Spare
Bit 7 - Spare
Bit 8 - Spare
Bit 9 - Spare
Bit 10 - Spare
Bit 11 - Spare
Bit 12 - Spare
Bit 13 - Spare
Bit 14 - Spare
Bit 15 - Spare
4-7
Pulse Accumulator input (counter) data type.....resettable
All data is 16-bit positive integer format.
SEQ #
(HEX)
40
41
42
43
SCALE
FACTOR
1
1
1
1
UNITS
Repairs
Resets
CROSS FUNC
REF
CODE
0-1
0-2
4-5
4-6
93
94
0
0
DESCRIPTION
ADDITIONAL COMMENTS/NOTES
Number of EPROM Corrections
Number of Resets (Insanity)
Operations Counter (100s)
These two operation counter points
Operations Counter (10s & 1s) must be concatenated to form the
total count. (Reset will NOT be
allowed through remote
communication.)
CL-5A Microprocessor-Based Control Digital Communications
p. 4
Analog Input data type...
All data is signed 16-bit integer format.
SEQ #
(HEX)
SCALE
FACTOR
80
81
82
83
84
85
86
87
88
89
8A
8B
8C
8D
8E
8F
90
91
92
93
94
95
96
97
98
99
9A
9B
9C
9D
9E
9F
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
AA
AB
1
1
1
See Comments
10
1
10
100
1
1
1
100
10
10
10
10
10
10
10
10
10
10
10
10
10
See Comments
1
1
1
10
10
See Comments
1
1
1
10
10
10
10
1
10
10
10
10
UNITS
Amps
Volts
KV
Volts
KV
KVA
KVAR
KW
%
Volts
%
%
%
%
%
%
%
%
%
%
hertz
Amps
KVA
KVAR
KW
Volts
Volts
Amps
KVA
KVAR
KW
Volts
Volts
Volts
%
%
%
%
CROSS FUNC
REF
CODE
0-3
1-1
1-2
1-3
1-4
1-5
1-8
1-9
1-10
1-11
1-12
1-14
1-15
1-16
1-17
1-18
1-19
1-20
1-21
1-22
1-23
1-24
1-26
3-0
3-1
3-2
3-3
3-4
3-5
3-6
3-7
3-8
3-9
3-10
3-11
4-4
5-0
4-08
1-31
1-32
1-33
1-34
DESCRIPTION
ADDITIONAL COMMENTS/NOTES
CALIBRATION REFERENCE
Fixed at 90% of full scale. (29491/7333H)
CALIBRATION REFERENCE
Fixed at zero.
95
Hardware Status
9
Load Current (primary)
IF(CT RATIO <= 50) THEN 10, ELSE 1
6
Load Volts (secondary)
10
Load Volts (primary)
7
Source Volts (secondary)
11
Source Volts (primary)
14
KVA Load
16
KVAR Load
15
KW Load
13
Power Factor
12
Percent Regulation
8
Compensated Volts (secondary)
18-3
3rd Voltage Harmonic
18-5
5th Voltage Harmonic
18-7
7th Voltage Harmonic
18-9
9th Voltage Harmonic
18-11 11th Voltage Harmonic
19-3
3rd Current Harmonic
19-5
5th Current Harmonic
19-7
7th Current Harmonic
19-9
9th Current Harmonic
19-11 11th Current Harmonic
17
Line Frequency
22-P
Current Demand (forward present) IF(CT RATIO <= 50) THEN 10, ELSE 1
24-P
KVA Demand (forward present)
26-P
KVAR Demand (forward present)
25-P
KW Demand (forward present)
20-P
Load Volts Demand (forward present)
21-P
Compensated Volts Demand (forward present)
32-P
Current Demand (reverse present) IF(CT RATIO <= 50) THEN 10, ELSE 1
34-P
KVA Demand (reverse present)
36-P
KVAR Demand (reverse present)
35-P
KW Demand (reverse present)
30-P
Load Volts Demand (reverse present)
31-P
Compensated Volts Demand (reverse present)
Tapchanger Calculated Motor Voltage
71
Voltage Reduction Active Remote
12-P
Present Tap Position
18-13 13th Voltage Harmonic
19-13 13th Current Harmonic
18-THD Total Voltage Harmonic Distortion
19-THD Total Current Harmonic Distortion
R225-90-4
p. 5
TIME-TAGGED INFORMATION SUBSYSTEM:
Types and formats used in retrieving time-tagged information
TYPE 0, Time-tagged information record.........Minimum/maximum Demand Values
CODE/PARAMETER
01...Max Forward Load Voltage
02...Min Forward Load Voltage
10
03...Max Forward Compensated Voltage 10
04...Min Forward Compensated Voltage
10
05...Max Forward Load Current
*
Amps
06...Min Forward Load Current
*
Amps
07...Max Forward kVA
1
kVA
08...Min Forward kVA
1
kVA
09...Max Forward kW
1
kW
10...Min Forward kW
1
kW
11...Max Forward kVAR
1
kVAR
12...Min Forward kVAR
1
kVAR
13...Max Tap Position
1
14...Min Tap Position
1
15...Max Reverse Load Voltage
16...Min Reverse Load Voltage
10
17...Max Reverse Compensated Voltage 10
18...Min Reverse Compensated Voltage
10
19...Max Reverse Load Current
*
Amps
20...Min Reverse Load Current
*
Amps
21...Max Reverse kVA
1
kVA
22...Min Reverse kVA
1
kVA
23...Max Reverse kW
1
kW
24...Min Reverse kW
1
kW
25...Max Reverse kVAR
1
kVAR
26...Min Reverse kVAR
1
kVAR
SCALE FACTOR
10
Volts
Volts
Volts
10
UNITS
Volts
Volts
Volts
Volts
Volts
* IF(CT RATIO <= 50) THEN 10, ELSE 1
TYPE 1, Time-tagged information record.........Regulator Load-profile Record
Event Type codes used:
Data values returned:
00...this is a time event
Parameter
Scale Factor
Units
As defined by user with Function Code 85 or Ordinal 6, offset 4A - 51
CL-5A Microprocessor-Based Control Digital Communications
p. 6
CONTROL OUTPUT SUBSYSTEM:
Sequence numbers used in SELECT/OPERATE operations
SEQ #
(HEX)
SCALE
FACTOR
UNITS
00
01
02
CROSS FUNC
REF
CODE
4-3
4-3
2-42
69
DESCRIPTION
ADDITIONAL COMMENTS/NOTES
Raise Tapchanger one tap
Lower Tapchanger one tap
Control Regulation Enable
“Close” is only valid command.
“Close” is only valid command.
“Close” = Blocked
“Open” = Unblocked
CL5 MEMORY, ORDINAL BLOCK 0: CL5 error information file (R/W)
Table format per specification PGE RTU Protocol REV 11, Appendix 2
Error codes defined for CL5 control :
ERROR
CODE
(HEX)
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
ERROR
RESPONSE
BITS
NOP&ERR
NOP&ERR
NOP&ERR
RST&ERR
RST&ERR
RST&ERR
RST&ERR
ERR ONLY
NOP&ERR
NOP&ERR
NOP&ERR
Note 1
NOP&ERR
ERR ONLY
NOP&ERR
NOP&ERR
ERR ONLY
Note 1
ERR ONLY
DESCRIPTION
SPECIFIC DATA
———————————
| 08 | 09 | 0A | 0B | 0C | 0D | 0E | 0F |
No Error
| 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Illegal Command Code
| CC | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Illegal Sequence Number
| SN | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Illegal Scan-table Number
| TN | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Not Used
|
|
|
|
|
|
|
|
|
Not Used
|
|
|
|
|
|
|
|
|
Not Used
|
|
|
|
|
|
|
|
|
Not Used
|
|
|
|
|
|
|
|
|
Not Used
|
|
|
|
|
|
|
|
|
SBO Operate without Arm
| SN | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
SBO Arm with another Arm Pending
| SN | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Not Used
|
|
|
|
|
|
|
|
|
Another request with SBO Armed
| 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Another request with Write Pending
| 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Not Used
|
|
|
|
|
|
|
|
|
Not Used
|
|
|
|
|
|
|
|
|
Previous SBO Operation not prfrmd. satisfctly.
| SN | LE | 00 | 00 | 00 | 00 | 00 | 00 |
Illegal Function Code
| 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Illegal Ordinal Number
| ON | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Illegal Ordinal Bias or Bias is out of range | ON | OL | OH | CT | CT | 00 | 00 | 00 |
Unsuccessful Data Read or Write
| LE | ON | OL | OH | 00 | 00 | 00 | 00 |
Illegal time-tagged table Number
| TN | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
Default Real Time Clock Data, Clock not Set
Illegal Real Time Clock Julian Day
Illegal Real Time Clock HH:MM:SS
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Calculated Number of Events is out of range
Recloser Main CPU Access Error
Basic Scan Database Access Error
Note 1: Responds with ERR only for “Reads”, and NOP & ERR for “Writes”
| 00 | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
| JH | JL | HR | MN | SC | 00 | 00 | 00 |
| JH | JL | HR | MN | SC | 00 | 00 | 00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| EN | 00 | 00 | 00 | 00 | 00 | 00 | 00 |
| TO | LE | 00 | 00 | 00 | 00 | 00 | 00 |
| TO | LE | 00 | 00 | 00 | 00 | 00 | 00 |
R225-90-4
p. 7
LEGEND
CC Command Code
CT Count
EN Event Number
JH Julian Day High Byte
JL Julian Day Low Byte
HR Hour
LE Local Control Error as follows ...
01 Control is in “Local Mode”
02 Requested Data is Invalid
03 Requested Data is Invalid and Default
04 Reserved
05 Value is too Large
06 Value is too Small
07 Invalid Internal Point Offset
08 Invalid Operation for this Internal Point
09 Invalid Internal Point Number
0A Invalid Number of Internal Points
0B Mechanism Does Not Respond to Command
0C Not Used
0D Not Used
0E Not Used
0F Not Used
MN Minute
OH Ordinal Offset, High Byte
OL Ordinal Offset, Low Byte
ON Ordinal Number
SC Seconds
SN Sequence Number
TO Time-Out Indication (FF if true, other data is irrelevant)
TN Table Number
CL5 MEMORY, ORDINAL BLOCK 3: SCAN-BY-TABLE scan tables (R/W)
initialize
NOTE: Scan table data is stored in non-volatile memory in the CL5 Control. It is not required to rethe data
from the master after a reset.
Table format per specification...maximum length is 256 bytes
*** For more detailed information about this table’s format, refer to (SPEC. DATA-2179, pg. 14-18 of 42, sec. 3.4) ***
CL5 MEMORY, ORDINAL BLOCK 5: CL5 RAM (R)
All data is 2 bytes long, low byte first.
OFF
SET
0000
0002
0004
0006
SCALE
FACTOR
100
UNITS
CROSS
REF
0-0
0-6
1-28
1-30
89
61
47
48
FUNC
CODE
DESCRIPTION
ADDITIONAL COMMENTS/NOTES
Software Version/Device Number
Control Communication Type/revision
Voltage Calibration
Current Calibration
CL-5A Microprocessor-Based Control Digital Communications
p. 8
CL5 MEMORY, ORDINAL BLOCK 6: CL5 Parameter Table (R/W)
NOTE: Parameter Table data is stored in non-volatile memory in the CL5 Control.
It is not required to re-initialize the data from the master after a reset.
All data is 2 bytes long, low byte first.
OFF
SET
SCALE
FACTOR UNITS
CROSS FUNC
REF
CODE
0000
0002
0004
0006
0008
000A
000C
000E
10
1
10
1
10
10
10
seconds 2-1
Amps
2-2
2-3
Volts
2-4
Volts
2-8
Volts
2-9
Volts
2-10
2-11
46
45
44
43
52
55
54
56
Demand Time Interval
C.T. Primary Rating
P.T. Ratio
300.0
System Line Voltage
36000
Bandwidth(reverse)
Line Drop Compensation Reactive(reverse)
Line Drop Compensation Resistive(reverse)
Reverse Sensing Method
0 = Locked Forward
1 = Locked Reverse
2 = Reverse Idle
3 = Bi-Directional
4 = Neutral Idle
5 = Co-Generation
0010
0012
0014
0016
0018
001A
001C
001E
10
1
1
1
1
1
1
1
Volts
2-12
seconds 2-13
%
2-14
2-15
2-16
2-17
2-18
2-19
51
53
57
40
96
97
98
41
Set Voltage(reverse)
Time Delay(reverse)
Reverse Threshold Value %
Regulator Identification
Level 1 Security Code
Level 2 Security Code
Level 3 Security Code
Regulator Configuration
0020
0022
0024
0026
10
10
10
Volts
Volts
Volts
2-20
2-21
2-22
2-23
2
5
4
42
Bandwidth
Line Drop Compensation Reactive
Line Drop Compensation Resistive
Control Operational Mode
0 = Sequential
1 = Time Integrating
2 = Averaging
6.0
24.0
24.0
2
1.0
-24.0
-24.0
0
0028
002A
002C
10
1
1
Volts
2-24
seconds 2-25
2-26
1
3
80
Set Voltage
Time Delay
Voltage Limiting Mode
135.0
180
2
100.0
5
0
002E
0030
0032
10
10
1
Volts
Volts
2-27
2-28
2-29
81
82
70
High Voltage Limit
Low Voltage Limit
Voltage Reduction Mode
135.0
115.0
3
115.0
105.0
0
0034
0036
0038
003A
003C
10
10
10
10
1
%
%
%
%
baud
2-30
2-31
2-32
2-33
2-40
72
73
74
75
60
Local Voltage Reduction
Remote Setting #1
Remote Setting #2
Remote Setting #3
Communication Channel #1
(Data Port) Baud Rate Code
10.0
10.0
10.0
10.0
4
0.0
0.0
0.0
0.0
1
003E
1
baud
2-44
65
Communication Channel #2
(remote) Baud Rate Code
5
1
DESCRIPTION
ADDITIONAL COMMENTS
0 = Wye
1 = Delta Lag
2 = Delta Lead
1 = 300
2 = 1200
3 = 2400
4 = 4800
1 = 300
2 = 1200
3 = 2400
4 = 4800
5 = 9600
60.0
2000
20.0
2400
6.0
24.0
24.0
5
135.0 100.0
180
5
5
32766
9999
19999
32766
2
0 = Off
1 = High Limit Only
2 = High and Low Limit
0 = Off
1 = Local
2 = Remote
3 = Pulsed Mode
LIMITS
HIGH
LOW
3.0
25
1.0
-24.0
-24.0
0
1
1
1
10000
20000
0
R225-90-4
p. 9
CL5 MEMORY, ORDINAL BLOCK 6: CL5 Parameter Table (R/W)
(continued)
NOTE: Parameter Table data is stored in non-volatile memory in the CL5 Control.
It is not required to re-initialize the data from the master after a reset.
All data is 2 bytes long, low byte first.
OFF
SET
SCALE
FACTOR UNITS
CROSS FUNC
REF
CODE
0040
0042
1
1
2-43
2-45
64
66
Communication SCADA Address
Communication Channel #2
0 = No Handshaking
HandshakeMode Code
1 = RTS/CTS Active
2 = Modem Control Handshaking
32766
2
0
0
0044
1
charact.
2-46
67
Communication Channel #2 Number of
dead-line character times for re-synchronization
10
0
0046
1
millisec.
2-47
68-1
Communication Channel #2 Transmit Enable
Delay for Modem Control Handshake Mode
425
0
0048
1
millisec.
2-48
68-2
Communication Channel #2 Transmit Disable
Delay for Modem Control Handshake Mode
100
0
2-50
2-51
2-52
2-53
2-54
2-55
6-05
2-80
85-1
85-2
85-3
85-4
76
77
50-1
92
Function Code of Parameter Stored at Load Profile Entry #1
Function Code of Parameter Stored at Load Profile Entry #2
Function Code of Parameter Stored at Load Profile Entry #3
Function Code of Parameter Stored at Load Profile Entry #4
Pulsed Mode: Number of Steps
Pulsed Mode: Step Size
Time Calendar/Clock - Year
Security System Bypass
004A
004C
004E
0050
0052
0054
0056
0058
DESCRIPTION
LIMITS
HIGH
LOW
ADDITIONAL COMMENTS
10
1
10.0
2089
3
0.1
1990
1
CL5 MEMORY, ORDINAL BLOCK 0B: CL5 Psuedo-registers (R/W)
NOTE: These data are MAX/MIN registers for operating variables.
When they are written by the WRITE RTU MEMORY function, the write “data” is ignored
and the registers are instead set to the current value of the operating variable. All data is signed 16-bit integer format.
OFF
SET
SCALE
FACTOR
0000
0002
0004
0006
0008
000A
000C
000E
0010
0012
0014
0016
0018
001A
001C
001E
0020
0022
0024
0026
0028
100
100
100
100
See Comments
See Comments
1
1
1
1
1
1
10
10
10
10
See Comments
See Comments
1
1
1
UNITS
CROSS FUNC
REF
CODE
DESCRIPTION
Amps
Amps
KVA
KVA
KVAR
KVAR
KW
KW
Volts
Volts
Volts
Volts
Amps
Amps
KVA
KVA
KVAR
3-12
3-13
3-14
3-15
3-16
3-17
3-18
3-19
3-20
3-21
3-22
3-23
3-24
3-25
3-26
3-27
3-28
3-29
3-30
3-31
3-32
Power Factor at Maximum Demand KVA(forward)
Power Factor at Minimum Demand KVA(forward)
Power Factor at Maximum Demand KVA(reverse)
Power Factor at Minimum Demand KVA(reverse)
Current Demand (forward minimum) IF(CT RATIO <= 50) THEN 10, ELSE 1
Current Demand (forward maximum) IF(CT RATIO <= 50) THEN 10, ELSE 1
KVA Demand (forward minimum)
KVA Demand (forward maximum)
KVAR Demand (forward minimum)
KVAR Demand (forward maximum)
KW Demand (forward minimum)
KW Demand (forward maximum)
Load Volts Demand(forward minimum)
Load Volts Demand(forward maximum)
Compensated Volts Demand(forward minimum)
Compensated Volts Demand(forward maximum)
Current Demand (reverse minimum) IF(CT RATIO <= 50) THEN 10, ELSE 1
Current Demand (reverse maximum) IF(CT RATIO <= 50) THEN 10, ELSE 1
KVA Demand (reverse minimum)
KVA Demand (reverse maximum)
KVAR Demand (reverse minimum)
23-H
23-L
33-H
33-L
22-L
22-H
24-L
24-H
26-L
26-H
25-L
25-H
20-L
20-H
21-L
21-H
32-L
32-H
34-L
34-H
36-L
ADDITIONAL COMMENTS
CL-5A Microprocessor-Based Control Digital Communications
p. 10
CL5 MEMORY, ORDINAL BLOCK 0B: CL5 Psuedo-registers (R/W)
(continued)
NOTE: These data are MAX/MIN registers for operating variables.
When they are written by the WRITE RTU MEMORY function, the write “data” is ignored
and the registers are instead set to the current value of the operating variable. All data is signed 16-bit integer format.
OFF
SET
SCALE
FACTOR
UNITS
002A
002C
002E
0030
0032
0034
0036
0038
003A
003C
003E
1
1
1
10
10
10
10
KVAR
KW
KW
Volts
Volts
Volts
Volts
CROSS FUNC
REF
CODE
DESCRIPTION
3-33
3-34
3-35
3-36
3-37
3-38
3-39
3-40
3-41
3-66
3-69
KVAR Demand (reverse maximum)
KW Demand (reverse minimum)
KW Demand (reverse maximum)
Load Volts Demand(reverse minimum)
Load Volts Demand(reverse maximum)
Compensated Volts Demand(reverse minimum)
Compensated Volts Demand(reverse maximum)
Maximum % Boost/ Minimum % Buck
Minimum % Boost/ Maximum % Buck
Maximum Tap Position
Minimum Tap Position
36-H
35-L
35-H
30-L
30-H
31-L
31-H
27
27
27-H
28-L
ADDITIONAL COMMENTS
Data points accessible through front panel controls of the CL5, but not accessible
through remote communications.
THESE DATA ARE NOT PART OF THE COMMUNICATIONS INTERFACE, AND ARE LISTED HERE FOR
REFERENCE ONLY.
All data is 2 bytes long, low byte first.
OFF
SET
SCALE
FACTOR UNITS
CROSS FUNC
REF
CODE
DESCRIPTION
1
1
0-4
0-5
Channel #1 (front panel) Status
Channel #2 (remote) Status
62
63
ADDITIONAL COMMENTS
LIMITS
HIGH
LOW
Cooper Power Systems
Printed in the USA
McGraw-Edison® is a registered trademark of Cooper Industries, Inc.
2300 Badger Drive, Waukesha, WI 53188-5951
Quality from Cooper Industries