Voltage Regulators Reference Information CL-6 Series Regulator Control Ordinal Points Assignments R225-90-9 Ordinal Points Assignments For Communications Protocol 2179 For Use With Cooper Power Systems CL-6 Series Regulator Controls June 2004 • New Issue Printed in USA CL-6A 2179 Ordinal Points Map CL-6A 2179 Protocol - Ordinal Point Assignments May 3, 2004 v 1.00 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF COOPER INDUSTRIES, INC. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 1.01 Date 5/3/2004 6/1/2004 Description Initial Release Update - FJR Page 1 CL-6A 2179 Ordinal Points Map INPUT SUBSYSTEM Binary Input Status Simple Status Sequence 48 (0x30) 49 (0x31) 50 (0x32) 51 (0x33) BITSTRING Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Description BANDWIDTH LOW BANDWIDTH HIGH VOLTAGE LIMITING LOW VOLTAGE LIMITING HIGH VOLTAGE REDUCTION ACTIVE RESERVED RESERVED RESERVED REGULATION STATE RESERVED POWER DIRECTION RESERVED RESERVED RESERVED RESERVED RESERVED AUTO SWITCH RESERVED RESERVED SUPERVISORY STATE SOURCE VOLTAGE CALCULATION ENABLE RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED HMI TAP RAISE SWITCH HMI TAP LOWER SWITCH HMI SUPERVISORY SWITCH HMI POWER SWITCH INTERNAL HMI POWER SWITCH EXTERNAL HMI AUTO-OFF-MANUAL SWITCH MANUAL HMI AUTO-OFF-MANUAL SWITCH OFF HMI DRAG HAND RESET ON HMI NEUTRAL POSITION INDICATION BLOCKING RELAY ACTIVE RESERVED DISCRETE INPUT 1 DISCRETE INPUT 2 DISCRETE INPUT 3 DISCRETE INPUT 4 RESERVED USER LED DISCRETE OUTPUT 1 DISCRETE OUTPUT 2 DISCRETE OUTPUT 3 DISCRETE OUTPUT 4 PIO TAP RAISE PIO TAP LOWER RESERVED USER EQUATION 17 USER EQUATION 18 USER EQUATION 19 USER EQUATION 20 INTERVAL OPERATIONS COUNTERS ACTIVE TAP TO NEUTRAL PMT MODE A ENABLED PMT MODE B ENABLED Page 2 Index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Basic Scan, Status CL-6A 2179 Ordinal Points Map INPUT SUBSYSTEM Binary Input Status (Continued) Simple Status Sequence 52 (0x34) 53 (0x35) 54 (0x36) 55 (0x37) BITSTRING Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Description USER EQUATION 01 USER EQUATION 02 USER EQUATION 03 USER EQUATION 04 USER EQUATION 05 USER EQUATION 06 USER EQUATION 07 USER EQUATION 08 USER EQUATION 09 USER EQUATION 10 USER EQUATION 11 USER EQUATION 12 USER EQUATION 13 USER EQUATION 14 USER EQUATION 15 USER EQUATION 16 EVENT RECORDER ENABLED HISTOGRAMS ENABLED DATA ALARMS ENABLED STATUS ALARMS ENABLED PROFILER ENABLED EVENT RECORDER PIO ENABLED HISTOGRAMS PIO ENABLED DATA ALARMS PIO ENABLED STATUS ALARMS PIO ENABLED PROFILER PIO ENABLED USER INTERMEDIATE EQUATION 01 USER INTERMEDIATE EQUATION 02 USER INTERMEDIATE EQUATION 03 USER INTERMEDIATE EQUATION 04 USER INPUT 01 USER INPUT 02 USER INPUT 03 USER INPUT 04 USER INPUT 05 USER INPUT 06 USER INPUT 07 USER INPUT 08 USER INPUT 09 USER INPUT 10 USER INPUT 11 USER INPUT 12 USER INPUT 13 USER INPUT 14 USER INPUT 15 USER INPUT 16 USER INPUT 17 USER INPUT 18 USER INPUT 19 USER INPUT 20 USER INPUT 21 USER INPUT 22 USER INPUT 23 USER INPUT 24 USER INPUT 25 USER INPUT 26 USER INPUT 27 USER INPUT 28 USER INPUT 29 USER INPUT 30 USER INPUT 31 USER INPUT 32 ALARM LED WARNING LED Page 3 Index 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 Basic Scan, Status CL-6A 2179 Ordinal Points Map INPUT SUBSYSTEM Binary Input Status (Continued) Simple Status Sequence 56 (0x38) BITSTRING Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Description DIAGNOSTIC ERROR LED VOLTAGE LIMITER HIGH LED OUT OF BAND HIGH LED OUT OF BAND LOW LED VOLTAGE LIMITER LOW LED TAPPING BLOCKED LED REVERSE POWER LED VOLTAGE REDUCTION LED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED Page 4 Index 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 Basic Scan, Status CL-6A 2179 Ordinal Points Map INPUT SUBSYSTEM Counters Sequence 64 (0x40) 65 (0x41) 66 (0x42) 67 (0x43) 68 (0x44) 69 (0x45) 70 (0x46) 71 (0x47) 72 (0x48) 73 (0x49) 74 (0x4A) 75 (0x4B) 76 (0x4C) 77 (0x4D) 78 (0x4E) 79 (0x4F) 80 (0x50) 81 (0x51) 82 (0x52) 83 (0x53) 84 (0x54) 85 (0x55) 86 (0x56) 87 (0X57) Index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Description RESERVED RESERVED OPERATIONS COUNTER 100S OPERATIONS COUNTER 10S AND 1S OPERATIONS DURING PAST 24 HOURS OPERATIONS DURING PAST 30 DAYS OPERATIONS SINCE BEGINNING OF MONTH OPERATIONS DURING LAST CALENDAR MONTH OPERATIONS SINCE BEGINNING OF YEAR OPERATIONS DURING LAST CALENDAR YEAR RESERVED TPI NEUTRAL RESYNCH COUNTER TAPS PAST 16R COUNTER TAPS PAST 16L COUNTER RESERVED RESERVED COM1 MSG RX COUNTER COM2 MSG RX COUNTER COM1 MSG TX COUNTER COM2 MSG TX COUNTER COM1 MSG ERROR STATUS COM2 MSG ERROR STATUS COM1 FRAMING ERRORS COUNTER COM2 FRAMING ERRORS COUNTER Page 5 Basic Scan, Counters CL-6A 2179 Ordinal Points Map INPUT SUBSYSTEM Analog Input Data (All data is signed 16-bit integer format) Sequence 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 Index (0x80) (0x81) (0x82) (0x83) (0x84) (0x85) (0x86) (0x87) (0x88) (0x89) (0x8A) (0x8B) (0x8C) (0x8D) (0x8E) (0x8F) (0x90) (0x91) (0x92) (0x93) (0x94) (0x95) (0x96) (0x97) (0x98) (0x99) (0x9A) (0x9B) (0x9C) (0x9D) (0x9E) (0x9F) (0xA0) (0xA1) (0xA2) (0xA3) (0xA4) (0xA5) (0xA6) (0xA7) (0xA8) (0xA9) (0xAA) (0xAB) (0xAC) (0xAD) (0xAE) (0xAF) (0xB0) (0xB1) (0xB2) (0xB3) (0xB4) (0xB5) (0xB6) (0xB7) (0xB8) (0xB9) (0xBA) (0xBB) (0xBC) (0xBD) (0xBE) (0xBF) (0xC0) (0XC1) 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 Scale Factor 1 1 1 10 10 100 10 100 1 1 1 100 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1 1 1 10 10 10 10 10 10 10 10 10 10 1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 100 100 100 100 Description RESERVED RESERVED RESERVED LOAD CURRENT, PRIMARY LOAD VOLTAGE, SECONDARY LOAD VOLTAGE, PRIMARY SOURCE VOLTAGE, SECONDARY SOURCE VOLTAGE, PRIMARY KVA LOAD KVAR LOAD KW LOAD POWER FACTOR PERCENT REGULATION COMPENSATED VOLTAGE, SECONDARY VOLTAGE HARMONIC 3rd VOLTAGE HARMONIC 5th VOLTAGE HARMONIC 7th VOLTAGE HARMONIC 9th VOLTAGE HARMONIC 11th CURRENT HARMONIC 3rd CURRENT HARMONIC 5th CURRENT HARMONIC 7th CURRENT HARMONIC 9th CURRENT HARMONIC 11th FREQUENCY FORWARD DEMAND LOAD CURRENT, PRIMARY FORWARD DEMAND KVA LOAD FORWARD DEMAND KVAR LOAD FORWARD DEMAND KW LOAD FORWARD DEMAND LOAD VOLTAGE, SECONDARY FWD DEMAND COMPENSATED VOLTAGE, SECONDARY REVERSE DEMAND LOAD CURRENT, PRIMARY REVERSE DEMAND KVA LOAD REVERSE DEMAND KVAR LOAD REVERSE DEMAND KW LOAD REVERSE DEMAND LOAD VOLTAGE, SECONDARY REV DEMAND COMPENSATED VOLTAGE, SECONDARY CALCULATED MOTOR VOLTAGE PERCENT VOLTAGE REDUCTION IN EFFECT TAP POSITION VOLTAGE HARMONIC 13th CURRENT HARMONIC 13th TOTAL VOLTAGE HARMONIC DISTORTION TOTAL CURRENT HARMONIC DISTORTION FORWARD DEMAND SOURCE VOLTAGE, SECONDARY REVERSE DEMAND SOURCE VOLTAGE, SECONDARY VOLTAGE HARMONIC 2nd VOLTAGE HARMONIC 4th VOLTAGE HARMONIC 6th VOLTAGE HARMONIC 8th VOLTAGE HARMONIC 10th VOLTAGE HARMONIC 12th VOLTAGE HARMONIC 14th VOLTAGE HARMONIC 15th CURRENT HARMONIC 2nd CURRENT HARMONIC 4th CURRENT HARMONIC 6th CURRENT HARMONIC 8th CURRENT HARMONIC 10th CURRENT HARMONIC 12th CURRENT HARMONIC 14th CURRENT HARMONIC 15th FORWARD KW HOURS FORWARD KQ HOURS REVERSE KW HOURS REVERSE KQ HOURS Page 6 Basic Scan, Analog Input Data CL-6A 2179 Ordinal Points Map OUTPUT SUBSYSTEM Select-Before-Operate (SBO) Operations Sequence 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 (0x0) (0x1) (0x2) (0x3) (0x4) (0x5) (0x6) (0x7) (0x8) (0x9) (0xA) (0xB) (0xC) (0xD) (0xE) (0xF) (0x10) (0x11) (0x12) (0x13) (0x14) (0x15) (0x16) (0x17) (0x18) (0x19) (0x1A) (0x1B) (0x1C) (0x1D) (0x1E) (0x1F) (0x20) (0x21) (0x22) (0x23) (0x24) (0x25) (0x26) (0x27) (0x28) (0x29) (0x2A) (0x2B) (0x2C) (0x2D) (0x2E) (0x2F) (0x30) (0x31) (0x32) (0x33) (0x34) (0x35) (0x36) (0x37) (0x38) (0x39) (0x3A) (0x3B) (0x3C) (0x3D) (0x3E) (0x3F) Description RAISE TAP LOWER TAP BLOCK REGULATION SOURCE SIDE VOLTAGE CALCULATION TOTAL OPERATIONS COUNTER ENABLE RESET TOTAL OERATIONS COUNTER INTERVAL OPERATIONS COUNTERS ENABLE RESET OPS MONTH OPERATIONS COUNTER RESET OPS YEAR OPERATIONS COUNTER RESET 24HR OPERATIONS COUNTER RESET 30DY OPERATIONS COUNTER RESET LAST MONTH OPERATIONS COUNTER RESET TPI NEUTRAL RESYNCH COUNTER RESET LAST YEAR OPERATIONS COUNTER ENABLE TAPS PAST 16L COUNTER RESET TAPS PAST 16L COUNTER ENABLE TAPS PAST 16R COUNTER RESET TAPS PAST 16R COUNTER RESET TAP POSITION INDICATION RESYNCH COUNTER RESERVED TAP POSITION INDICATOR DRAGHAND RESET RESET TIME ON TAP RESERVED RESERVED RESERVED RESERVED RESET MSG RX COM1 COUNTER RESET MSG RX COM2 COUNTER RESET MSG TX COM1 COUNTER RESET MSG TX COM2 COUNTER RESET MSG ERRORS COM1 STATUS RESET MSG ERRORS COM2 STATUS RESET FRAME ERRORS COM1 COUNTER RESET FRAME ERRORS COM2 COUNTER RESERVED RESERVED METERING RESET KWHR FWD METERING RESET KWHR REV METERING RESET KQHR FWD METERING RESET KQHR REV METERING RESET ENERGY ALL DEMAND RESET ALL EVENT RECORDER ENABLE EVENT RECORDER MASK ALL EVENT RECORDER UNMASK ALL EVENT RECORDER READ FIRST EVENT RECORDER READ NEXT DATA PROFILER ENABLE DATA PROFILER MASK ALL DATA PROFILER UNMASK ALL DATA PROFILER READ FIRST DATA PROFILER READ NEXT RESERVED DATA PROFILER TAKE SNAPSHOT HISTOGRAM ENABLE HISTOGRAM MASTER CLEAR HISTOGRAM ACTIVE CLEAR RESERVED RESERVED RESERVED ERROR RECORDER MASK ALL ERROR RECORDER UNMASK ALL ERROR RECORDER READ FIRST ERROR RECORDER READ NEXT Page 7 Index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Valid Commands Close Close Close and Open Close and Open Close and Open Close Close and Open Close Close Close Close Close Close Close Close and Open Close Close and Open Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close and Open Close and Open Close Close Close Close Close Close Close and Open Close Close Close Close Close and Open Close Close Close Close Close Close Close and Open Close Close and Open Close and Open Close and Open Close Close Close Close Select Before Operate CL-6A 2179 Ordinal Points Map OUTPUT SUBSYSTEM Select-Before-Operate (SBO) Operations Sequence 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 (0x40) (0x41) (0x42) (0x43) (0x44) (0x45) (0x46) (0x47) (0x48) (0x49) (0x4A) (0x4B) (0x4C) (0x4D) (0x4E) (0x4F) (0x50) (0x51) (0x52) (0x53) (0x54) (0x55) (0x56) (0x57) (0x58) (0x59) (0x5A) (0x5B) (0x5C) (0x5D) (0x5E) (0x5F) (0x60) (0x61) (0x62) (0x63) (0x64) (0x65) (0x66) (0x67) (0x68) (0x69) (0x6A) (0x6B) (0x6C) (0x6D) Description USER INPUT 01 USER INPUT 02 USER INPUT 03 USER INPUT 04 USER INPUT 05 USER INPUT 06 USER INPUT 07 USER INPUT 08 USER INPUT 09 USER INPUT 10 USER INPUT 11 USER INPUT 12 USER INPUT 13 USER INPUT 14 USER INPUT 15 USER INPUT 16 USER INPUT 17 USER INPUT 18 USER INPUT 19 USER INPUT 20 USER INPUT 21 USER INPUT 22 USER INPUT 23 USER INPUT 24 USER INPUT 25 USER INPUT 26 USER INPUT 27 USER INPUT 28 USER INPUT 29 USER INPUT 30 USER INPUT 31 USER INPUT 32 PMT MODE A TEST PMT MODE B TEST ALARM RECORDER SUPPRESS ALL ALARM RECORDER UNSUPPRESS ALL ALARM RECORDER ALL OPERATION MODES OFF ALARM RECORDER QUERY USER ALARM RECORDER QUERY ALL REGISTERED ALARM RECORDER QUERY ACTIVE HIGH PRIORITY ALARM RECORDER QUERY ACTIVE LOW AND HIGH PRIORITY ALARM RECORDER QUERY ACTIVE ALARM RECORDER QUERY SUPPRESSED ALARM RECORDER DATA ALARMS ENABLE ALARM RECORDER STATUS ALARMS ENABLE CL DELETE ACTIVE FORM Page 8 Index 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 Valid Commands Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close Close and Open Close Close Close Close Close Close Close and Open Close and Open Close Select Before Operate CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 5 Offset 0000 0002 0004 0006 0008 0010 0012 0014 0016 0018 0020 0022 0024 0026 0030 0036 0038 0040 0042 0044 0556 0558 0560 0562 0564 0566 0568 0570 0572 0574 0576 0578 0580 0584 0586 0590 0594 0596 0600 0602 0606 0612 0618 0624 0630 0636 0642 0648 0654 0660 0666 0672 0678 0684 0690 0696 0702 0708 0714 0720 0726 0732 0738 0744 0750 Scale Factor 100 1 10 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 100 1 1 100 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Description FIRMWARE VERSION RESERVED USER MEASURED V USER MEASURED IOUT DATE OPERATIONS COUNT SET TIME OPERATIONS COUNT SET ERROR SYS MASKED REC COUNT ERROR SYS UNMASKED REC COUNT ERROR EVENT RECORDER MASKED REC COUNT ERROR EVENT RECORDER UNMASKED REC COUNT ERROR PROFILER MASKED REC COUNT ERROR PROFILER UNMASKED REC COUNT ERROR TIME DAYS ERROR TIME MSECS ERROR TIME STS ERROR ID ERROR CAUSE ERROR DATA SIZE ERROR DATA TYPE ERROR DATA HISTOGRAM ACTIVE COUNTUNDER HISTOGRAM ACTIVE COUNT BIN01 HISTOGRAM ACTIVE COUNT BIN02 HISTOGRAM ACTIVE COUNT BIN03 HISTOGRAM ACTIVE COUNT BIN04 HISTOGRAM ACTIVE COUNT BIN05 HISTOGRAM ACTIVE COUNT BIN06 HISTOGRAM ACTIVE COUNT BIN07 HISTOGRAM ACTIVE COUNT BIN08 HISTOGRAM ACTIVE COUNT BIN09 HISTOGRAM ACTIVE COUNT BIN10 HISTOGRAM ACTIVE COUNTOVER HISTOGRAM ACTIVE MAX VALUE HISTOGRAM ACTIVE MAX DAYS HISTOGRAM ACTIVE MAX MSECS HISTOGRAM ACTIVE MIN VALUE HISTOGRAM ACTIVE MIN DAYS HISTOGRAM ACTIVE MIN MSECS HISTOGRAM ACTIVE RESET DAYS HISTOGRAM ACTIVE RESET MSECS OPERATIONS COUNT LAST CHNG STS OPERATIONS 24HR COUNT STS OPERATIONS 30DY COUNT STS OPERATIONS MONTH COUNT STS OPERATIONS YEAR COUNT STS OPERATIONS LAST MONTH COUNT STS OPERATIONS LAST YEAR COUNT STS TIME ON 16L TIME ON 15L TIME ON 14L TIME ON 13L TIME ON 12L TIME ON 11L TIME ON 10L TIME ON 09L TIME ON 08L TIME ON 07L TIME ON 06L TIME ON 05L TIME ON 04L TIME ON 03L TIME ON 02L TIME ON 01L TIME ON NEUTRAL TIME ON 01R Page 9 Data Type UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED LONG 6 BYTE STRING UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD 512 BYTE STRING UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD SIGNED LONG UNSIGNED WORD UNSIGNED LONG SIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING Ordinal Block 5 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 5 Offset 0756 0762 0768 0774 0780 0786 0792 0798 0804 0810 0816 0822 0828 0834 0840 0846 0848 0850 0852 0854 0856 0858 0860 0862 0864 0866 0868 0870 0872 0874 0875 0877 0881 0883 0887 0888 0890 0894 0896 0900 0902 0906 0908 0912 0914 0918 0920 0924 0926 0930 0932 0936 0938 0942 0944 0948 0950 0954 0956 0960 0962 0966 0968 0972 0974 Scale Factor 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 100 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Description TIME ON 02R TIME ON 03R TIME ON 04R TIME ON 05R TIME ON 06R TIME ON 07R TIME ON 08R TIME ON 09R TIME ON 10R TIME ON 11R TIME ON 12R TIME ON 13R TIME ON 14R TIME ON 15R TIME ON 16R ALARM RECORDER IUU COUNT ALARM RECORDER IUC COUNT ALARM RECORDER ISU COUNT ALARM RECORDER ISC COUNT ALARM RECORDER AUU COUNT ALARM RECORDER AUC COUNT ALARM RECORDER ASU COUNT ALARM RECORDER ASC COUNT ALARM RECORDER ACTIVE COUNT ALARM RECORDER SUPPRESSED COUNT ALARM RECORDER CHANGED COUNT ALARM RECORDER REGISTERED COUNT ALARM RECORDER RPT COUNT ALARM RECORDER RPT ACTIVE ID ALARM RECORDER RPT ACTIVE PRIORITY ALARM RECORDER RPT ACTIVE ON DAYS ALARM RECORDER RPT ACTIVE ON MSECS ALARM RECORDER RPT ACTIVE OFF DAYS ALARM RECORDER RPT ACTIVE OFF MSECS UNUSED TAP POSITION MAX DAYS TAP POSITION MAX MSECS TAP POSITION MIN DAYS TAP POSITION MIN MSECS FORWARD DEMAND LOAD VOLTAGE SECONDARY MAX DAYS FORWARD DEMAND LOAD VOLTAGE SECONDARY MAX MSECS FORWARD DEMAND LOAD VOLTAGE SECONDARY MIN DAYS FORWARD DEMAND LOAD VOLTAGE SECONDARY MIN MSECS FORWARD DEMAND SOURCE VOLTAGE SECONDARY MAX DAYS FORWARD DEMAND SOURCE VOLTAGE SECONDARY MAX MSECS FORWARD DEMAND SOURCE VOLTAGE SECONDARY MIN DAYS FORWARD DEMAND SOURCE VOLTAGE SECONDARY MIN MSECS FORWARD DEMAND COMPENSATED VOLTAGE SECONDARYMAX DAYS FORWARD DEMAND COMPENSATED VOLTAGE SECONDARYMAX MSECS FORWARD DEMAND COMPENSATED VOLTAGE SECONDARYMIN DAYS FORWARD DEMAND COMPENSATED VOLTAGE SECONDARYMIN MSECS FORWARD DEMAND LOAD CURRENT PRIMARY MAX DAYS FORWARD DEMAND LOAD CURRENT PRIMARY MAX MSECS FORWARD DEMAND LOAD CURRENT PRIMARY MIN DAYS FORWARD DEMAND LOAD CURRENT PRIMARY MIN MSECS FORWARD DEMAND TOTAL CURRENT HARMONICS MAX DAYS FORWARD DEMAND TOTAL CURRENT HARMONICS MAX MSECS FORWARD DEMAND TOTAL CURRENT HARMONICS MIN DAYS FORWARD DEMAND TOTAL CURRENT HARMONICS MIN MSECS FORWARD DEMAND TOTAL VOLTAGE HARMONICS MAX DAYS FORWARD DEMAND TOTAL VOLTAGE HARMONICS MAX MSECS FORWARD DEMAND TOTAL VOLTAGE HARMONICS MIN DAYS FORWARD DEMAND TOTAL VOLTAGE HARMONICS MIN MSECS FORWARD DEMAND KVA LOAD MAX DAYS FORWARD DEMAND KVA LOAD MAX MSECS Page 10 Data Type 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED BYTE UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED BYTE UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG Ordinal Block 5 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 5 Offset 0978 0980 0984 0986 0990 0992 0996 0998 1002 1004 1008 1010 1014 1016 1020 1022 1026 1028 1032 1034 1038 1040 1044 1046 1050 1052 1056 1058 1062 1064 1068 1070 1074 1076 1080 1082 1086 1088 1092 1094 1098 1100 1104 1106 1110 1112 1116 1118 1122 1124 1128 1130 1134 1136 1140 1142 1146 1148 1152 1156 1176 1182 1188 1194 1198 Scale Factor 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Description FORWARD DEMAND KVA LOAD MIN DAYS FORWARD DEMAND KVA LOAD MIN MSECS FORWARD DEMAND KVAR LOAD MAX DAYS FORWARD DEMAND KVAR LOAD MAX MSECS FORWARD DEMAND KVAR LOAD MIN DAYS FORWARD DEMAND KVAR LOAD MIN MSECS FORWARD DEMAND KW LOAD MAX DAYS FORWARD DEMAND KW LOAD MAX MSECS FORWARD DEMAND KW LOAD MIN DAYS FORWARD DEMAND KW LOAD MIN MSECS REVERSE DEMAND LOAD VOLTAGE SECONDARY MAX DAYS REVERSE DEMAND LOAD VOLTAGE SECONDARY MAX MSECS REVERSE DEMAND LOAD VOLTAGE SECONDARY MIN DAYS REVERSE DEMAND LOAD VOLTAGE SECONDARY MIN MSECS REVERSE DEMAND SOURCE VOLTAGE SECONDARY MAX DAYS REVERSE DEMAND SOURCE VOLTAGE SECONDARY MAX MSECS REVERSE DEMAND SOURCE VOLTAGE SECONDARY MIN DAYS REVERSE DEMAND SOURCE VOLTAGE SECONDARY MIN MSECS REVERSE DEMAND COMPENSATED VOLTAGE SECONDARYMAX DAYS REVERSE DEMAND COMPENSATED VOLTAGE SECONDARYMAX MSECS REVERSE DEMAND COMPENSATED VOLTAGE SECONDARYMIN DAYS REVERSE DEMAND COMPENSATED VOLTAGE SECONDARYMIN MSECS REVERSE DEMAND LOAD CURRENT PRIMARY MAX DAYS REVERSE DEMAND LOAD CURRENT PRIMARY MAX MSECS REVERSE DEMAND LOAD CURRENT PRIMARY MIN DAYS REVERSE DEMAND LOAD CURRENT PRIMARY MIN MSECS REVERSE DEMAND KVA LOAD MAX DAYS REVERSE DEMAND KVA LOAD MAX MSECS REVERSE DEMAND KVA LOAD MIN DAYS REVERSE DEMAND KVA LOAD MIN MSECS REVERSE DEMAND KVAR LOAD MAX DAYS REVERSE DEMAND KVAR LOAD MAX MSECS REVERSE DEMAND KVAR LOAD MIN DAYS REVERSE DEMAND KVAR LOAD MIN MSECS REVERSE DEMAND KW LOAD MAX DAYS REVERSE DEMAND KW LOAD MAX MSECS REVERSE DEMAND KW LOAD MIN DAYS REVERSE DEMAND KW LOAD MIN MSECS POWER FACTOR AT FORWARD DEMAND KVA LOAD MAX DAYS POWER FACTOR AT FORWARD DEMAND KVA LOAD MAX MSECS POWER FACTOR AT FORWARD DEMAND KVA LOAD MIN DAYS POWER FACTOR AT FORWARD DEMAND KVA LOAD MIN MSECS POWER FACTOR AT DMDREV KVA LOAD MAX DAYS POWER FACTOR AT DMDREV KVA LOAD MAX MSECS POWER FACTOR AT DMDREV KVA LOAD MIN DAYS POWER FACTOR AT DMDREV KVA LOAD MIN MSECS PERCENT REGULATION MAX DAYS PERCENT REGULATION MAX MSECS PERCENT REGULATION MIN DAYS PERCENT REGULATION MIN MSECS REVERSE DEMAND TOTAL CURRENT HARMONICS MAX DAYS REVERSE DEMAND TOTAL CURRENT HARMONICS MAX MSECS REVERSE DEMAND TOTAL CURRENT HARMONICS MIN DAYS REVERSE DEMAND TOTAL CURRENT HARMONICS MIN MSECS REVERSE DEMAND TOTAL VOLTAGE HARMONICS MAX DAYS REVERSE DEMAND TOTAL VOLTAGE HARMONICS MAX MSECS REVERSE DEMAND TOTAL VOLTAGE HARMONICS MIN DAYS REVERSE DEMAND TOTAL VOLTAGE HARMONICS MIN MSECS OPERATIONS COUNT LAST CHNG FIRMWARE VERSION STRING TAP POSITION NEUTRAL RESYNCH COUNTERS TAPS PAST 16R COUNT STS TAPS PAST 16L COUNT STS DCM CONTACT M1 DCM CONTACT M2 Page 11 Data Type UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED WORD UNSIGNED LONG UNSIGNED LONG 20 BYTE STRING 6 BYTE STRING 6 BYTE STRING 6 BYTE STRING FLOATING POINT FLOATING POINT Ordinal Block 5 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 5 Offset Scale Factor Description Data Type 1202 1 DCM CONTACT M3 FLOATING POINT 1206 1 DCM CONTACT M4 FLOATING POINT 1210 1 DCM CONTACT SNA FLOATING POINT 1214 1 DCM CONTACT SNB FLOATING POINT 1218 1 DCM CONTACT S1A FLOATING POINT 1222 1 DCM CONTACT S1B FLOATING POINT 1226 1 DCM CONTACT S2A FLOATING POINT 1230 1 DCM CONTACT S2B FLOATING POINT 1234 1 DCM CONTACT S3A FLOATING POINT 1238 1 DCM CONTACT S3B FLOATING POINT 1242 1 DCM CONTACT S4A FLOATING POINT 1246 1 DCM CONTACT S4B FLOATING POINT 1250 1 DCM CONTACT S5A FLOATING POINT 1254 1 DCM CONTACT S5B FLOATING POINT 1258 1 DCM CONTACT S6A FLOATING POINT 1262 1 DCM CONTACT S6B FLOATING POINT 1266 1 DCM CONTACT S7A FLOATING POINT 1270 1 DCM CONTACT S7B FLOATING POINT 1274 1 DCM CONTACT S8A FLOATING POINT 1278 1 DCM CONTACT S8B FLOATING POINT NOTE: DATA TYPE "FLOATING POINT" IS ACTUALY A SINGLE PRECISION FLOATING POINT NUMBER DATA TYPE Page 12 Ordinal Block 5 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 6 Offset 0000 0002 0004 0006 0008 0010 0012 0014 0016 0018 0020 0022 0024 0026 0028 0030 0032 0034 0036 0038 0040 0042 0044 0046 0048 0050 0052 0054 0056 0058 0060 0062 0064 0066 0068 0070 0072 0074 0076 0078 0080 0082 0084 0086 0088 0090 0092 0094 0096 0098 0100 0102 0104 0106 0108 0110 0112 0114 0116 0118 0120 0122 0124 0126 0128 0130 0132 0134 0136 0138 0140 Scale Factor 10 1 10 1 10 10 10 1 10 1 1 1 1 1 1 1 10 10 10 1 10 1 1 10 10 1 10 10 10 10 1 1 1 1 1 1 1 1 1 1 1 1 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 100 1 1 1 1 1 1 1 1 1 1 Description DEMAND TIME INTERVAL CT RATING OVERALL PT RATIO SYSTEM LINE VOLTAGE REVERSE BANDWIDTH REVERSE LINE DROP COMPENSATION REACTANCE REVERSE LINE DROP COMPENSATION RESISTANCE REVERSE SENSE MODE REVERSE SET VOLTAGE REVERSE TIME DELAY REVERSE THRESHOLD ID NUMBER SECURITY CODE1 SECURITY CODE2 SECURITY CODE3 REGULATOR CONFIGURATION FORWARD BANDWIDTH FORWARD LINE DROP COMPENSATION REACTANCE FORWARD LINE DROP COMPENSATION RESISTANCE CONTROLOPERATING MODE FORWARD SET VOLTAGE FORWARD TIME DELAY VOLTAGE LIMITING MODE VOLTAGE LIMITING HIGH VOLTAGE LIMITING LOW VOLTAGE REDUCTION MODE VOLTAGE REDUCTION PERCENT ANALOG VOLTAGE REDUCTION SETTING #1 ANALOG VOLTAGE REDUCTION SETTING #2 ANALOG VOLTAGE REDUCTION SETTING #3 COM PORT 2 BAUD RATE COM PORT 1 & 3 BAUD RATE 2179 COM2 SLAVE ADDRESS HANDSHAKE MODE COM2 UNUSED COM2 TX ENABLE ON DELAY COM2 TX ENABLE OFF DELAY UNUSED UNUSED UNUSED UNUSED ANAL0G VOLTAGE REDUCTION STEP COUNT VOLTAGE REDUCTION PER STEP YEAR SECURITY OVERRIDE REGULATOR TYPE TAP CHANGER TYPE SOFTADDAMP STATE SOFT ADD AMP HIGH LIMIT SOFT ADD AMP LOW LIMIT DATA PROFILER SAMPLE PERIOD UNUSED PROTOCOL COM2 PROTOCOL COM1 ADD AMP HIGH LIMIT ADD AMP LOW LIMIT UNUSED ALARM RECORDER RPT CURRENT LINE ALARM RECORDER CONFIG ACTIVE ID ALARM RECORDER OP MODE ALARM RECORDER DATA LIMIT ALARM RECORDER EVENT OP MODE ALARM RECORDER PROFILE OP MODE ALARM RECORDER PRIORITY ALARM RECORDER CHANGE DELAY SEC ALARM RECORDER SUPPRESS ID ALARM RECORDER UNSUPPRESS ID ALARM RECORDER QUERY ACTIVITY STATE ALARM RECORDER QUERY SUPPRESSION STATE ALARM RECORDER QUERY CHANGE STATE ALARM RECORDER QUERY PRIORITY LOW Page 13 Data Type UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD SIGNED WORD SIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD SIGNED WORD SIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD SIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD SIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD Ordinal Block 6 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 6 Offset 0142 0144 0146 0148 0150 0152 0154 0156 0158 0160 0162 0164 0166 0168 0170 0172 0174 0176 0178 0180 0182 0184 0186 0188 0190 0192 0194 0196 0198 0200 0202 0204 0206 0208 0212 0216 0217 0218 0219 0220 0221 0226 0230 0232 0234 0236 0238 0240 0253 0254 0255 0256 0257 0258 0259 0260 0261 0262 0263 0264 0265 0266 0267 0268 0269 0270 0271 0272 0273 0274 0275 Scale Factor 1 1 1 1 1 1 1 100 1 1 100 1 1 1 1 1 10 1 1 100 1 1 100 1 1 1 1 1 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Description ALARM RECORDER QUERY PRIORITY HIGH 2179 DEFAULT PORT MAP 2179 COM1 SLAVE ADDRESS 2179 COM2 SLAVE ADDRESS 2179 COM1 MAP ID 2179 COM2 MAP ID DNP DEFAULT MAP PORT DNP TRANSMIT DELAY COM2 UNUSED DNP LINK CONFIRM MODE COM2 DNP LINK CONFIRM TIMEOUT COM2 DNP LINK MAX RETRIES COM2 UNUSED UNUSED UNUSED DNP LOGICAL DEVICE 1 UNSOLICITED PERMITTED COM2 DNP LOGICAL DEVICE 1 UNSOLICITED RETRY DELAY COM2 UNUSED DNP LOGICAL DEVICE 1 MAP ID COM2 DNP TRANS DELAY COM1 UNUSED DNP LINK CONFIRM MODE COM1 DNP LINK CONFIRM TIMEOUT COM1 DNP LINK MAX RETRIES COM1 UNUSED UNUSED UNUSED DNP LOGICAL DEVICE 1 UNSOLICITED PERMITTED COM1 DNP LOGICAL DEVICE 1 UNSOLICITED RETRY DELAY COM1 UNUSED DNP LOGICAL DEVICE 1 MAP ID COM1 PMT MODE A TIME DELAY PMT MODE B TIME DELAY PMT MODE B START TIME PMT MODE B STOP TIME PMT MODE B MAX DEV PMT MODE B I LIMIT PMT MODE B MASTER SLAVE PMT MODE A ENABLE PMT MODE B ENABLE UNUSED OPERATIONS COUNTER DATA PROFILER DURATION DATA PROFILER START TIME DATA PROFILER START DATE DATA PROFILER STOP DATE DATA PROFILER SAMPLE PERIOD UNUSED DATA PROFILER FORWARD DEMAND CURRENT PRIMARY LOAD DATA ENABLE DATA PROFILER REVERSE DEMAND CURRENT PRIMARY LOAD DATA ENABLE DATA PROFILER FORWARD DEMAND LOAD VOLTAGE SECONDARY ENABLE DATA PROFILER REVERSE DEMAND LOAD VOLTAGE SECONDARY ENABLE DATA PROFILER FORWARD DEMAND SOURCE VOLTAGE SECONDARY ENABLE DATA PROFILER REVERSE DEMAND SOURCE VOLTAGE SECONDARY ENABLE DATA PROFILER FORWARD DEMAND COMPENSATED VOLTAGE SECONDARY ENABLE DATA PROFILER REVERSE DEMAND COMPENSATED VOLTAGE SECONDARY ENABLE DATA PROFILER FORWARD DEMAND KVA LOAD ENABLE DATA PROFILER REVERSE DEMAND KVA LOAD ENABLE DATA PROFILER FORWARD DEMAND KW LOAD ENABLE DATA PROFILER REVERSE DEMAND KW LOAD ENABLE DATA PROFILER FORWARD DEMAND KVAR LOAD ENABLE DATA PROFILER REVERSE DEMAND KVAR LOAD ENABLE DATA PROFILER CURRENT PRIMARY LOAD DATA ENABLE DATA PROFILER LOAD VOLTAGE SECONDARY ENABLE DATA PROFILER SOURCE VOLTAGE SECONDARY ENABLE DATA PROFILER COMPENSATED VOLTAGE SECONDARY ENABLE DATA PROFILER LOAD VOLTAGE PRIMARY ENABLE DATA PROFILER SOURCE VOLTAGE PRIMARY ENABLE DATA PROFILER PRECENT REGULATION ENABLE DATA PROFILER POWER FACTOR ENABLE DATA PROFILER KVA LOAD ENABLE Page 14 Data Type UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED LONG UNSIGNED LONG UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE 5 BYTE STRING UNSIGNED LONG UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD 13 BYTE STRING UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE Ordinal Block 6 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 6 Offset 0276 0277 0278 0279 0280 0281 0282 0283 0284 0285 0286 0287 0288 0289 0290 0291 0292 0293 0294 0295 0296 0297 0298 0299 0300 0301 0302 0303 0304 0305 0306 0307 0308 0309 0310 0311 0312 0313 0314 0316 0318 0574 0576 0578 0834 1090 1346 1602 1604 1608 1612 1613 1614 1615 1616 1617 1618 1619 1620 1621 1622 1623 1624 1625 1626 1627 1628 1629 1630 1631 1632 Scale Factor 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 100 100 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Description DATA PROFILER KW LOAD ENABLE DATA PROFILER KVAR LOAD ENABLE DATA PROFILER KQH ENABLE DATA PROFILER KQH REVERSE ENABLE DATA PROFILER KWH ENABLE DATA PROFILER KWH REVERSE ENABLE DATA PROFILER FREQ ENABLE DATA PROFILER HARMONICS VOLTAGE TOTAL ENABLE DATA PROFILER HARMONICS VOLTAGE 2ND ENABLE DATA PROFILER HARMONICS VOLTAGE 3RD ENABLE DATA PROFILER HARMONICS VOLTAGE 4TH ENABLE DATA PROFILER HARMONICS VOLTAGE 5TH ENABLE DATA PROFILER HARMONICS VOLTAGE 6TH ENABLE DATA PROFILER HARMONICS VOLTAGE 7TH ENABLE DATA PROFILER HARMONICS VOLTAGE 8TH ENABLE DATA PROFILER HARMONICS VOLTAGE 9TH ENABLE DATA PROFILER HARMONICS VOLTAGE 10TH ENABLE DATA PROFILER HARMONICS VOLTAGE 11TH ENABLE DATA PROFILER HARMONICS VOLTAGE 12TH ENABLE DATA PROFILER HARMONICS VOLTAGE 13TH ENABLE DATA PROFILER HARMONICS VOLTAGE 14TH ENABLE DATA PROFILER HARMONICS VOLTAGE 15TH ENABLE DATA PROFILER HARMONICS CURRENT TOTAL ENABLE DATA PROFILER HARMONICS CURRENT 2ND ENABLE DATA PROFILER HARMONICS CURRENT 3RD ENABLE DATA PROFILER HARMONICS CURRENT 4TH ENABLE DATA PROFILER HARMONICS CURRENT 5TH ENABLE DATA PROFILER HARMONICS CURRENT 6TH ENABLE DATA PROFILER HARMONICS CURRENT 7TH ENABLE DATA PROFILER HARMONICS CURRENT 8TH ENABLE DATA PROFILER HARMONICS CURRENT 9TH ENABLE DATA PROFILER HARMONICS CURRENT 10TH ENABLE DATA PROFILER HARMONICS CURRENT 11TH ENABLE DATA PROFILER HARMONICS CURRENT 12TH ENABLE DATA PROFILER HARMONICS CURRENT 13TH ENABLE DATA PROFILER HARMONICS CURRENT 14TH ENABLE DATA PROFILER HARMONICS CURRENT 15TH ENABLE DATA PROFILER TAP POSITION INDICATION ENABLE 2179 ACTIVE COM ID 2179 ACTIVE BLOCK ID 2179 MAP DNP ACTIVE COM ID DNP ACTIVE BLOCK ID DNP MAP DNP CLASS CODE DNP DEADBAND 1 DNP DEADBAND 2 HISTOGRAM ACTIVE ID HISTOGRAM ACTIVE BIN01 LOW HISTOGRAM ACTIVE BIN10 HIGH USERINPUT CFG 01 USERINPUT CFG 02 USERINPUT CFG 03 USERINPUT CFG 04 USERINPUT CFG 05 USERINPUT CFG 06 USERINPUT CFG 07 USERINPUT CFG 08 USERINPUT CFG 09 USERINPUT CFG 10 USERINPUT CFG 11 USERINPUT CFG 12 USERINPUT CFG 13 USERINPUT CFG 14 USERINPUT CFG 15 USERINPUT CFG 16 USERINPUT CFG 17 USERINPUT CFG 18 USERINPUT CFG 10 USERINPUT CFG 20 USERINPUT CFG 21 Page 15 Data Type UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED WORD UNSIGNED WORD 256 BYTE STRING UNSIGNED WORD UNSIGNED WORD 256 BYTE STRING 256 BYTE STRING 256 BYTE STRING 256 BYTE STRING UNSIGNED WORD SIGNED LONG SIGNED LONG UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE Ordinal Block 6 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 6 Offset 1633 1634 1635 1636 1637 1638 1639 1640 1641 1642 1643 1644 1646 1648 1650 1652 1654 1656 1658 1660 1662 1664 1666 1668 1670 1672 1674 1676 1678 1680 1682 1684 1686 1688 1690 1692 1694 1696 1698 1700 1702 1704 1706 1708 1710 1878 1894 1896 1898 1900 1902 1904 1906 1908 1910 1912 1914 1916 1918 1920 1922 1924 1926 1928 1930 1932 1934 1936 1938 1940 1942 Scale Factor 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 100 1 1 1 1 1 1 1 1 1 1 1 1 100 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Description USERINPUT CFG 22 USERINPUT CFG 23 USERINPUT CFG 24 USERINPUT CFG 25 USERINPUT CFG 26 USERINPUT CFG 27 USERINPUT CFG 28 USERINPUT CFG 29 USERINPUT CFG 30 USERINPUT CFG 31 USERINPUT CFG 32 ALARM RECORDER QUERY EXECUTE ID HANDSHAKE COM1 SYNC TIME COM2 SYNC TIME COM1 TX ENABLE ON COM1 TX ENABLE OFF COM1 DNP LOGICAL DEVICE 1 SLAVE ADDRESS COM2 DNP LOGICAL DEVICE 2 SLAVE ADDRESS COM2 DNP MASTER ADDRESS COM2 DNP APPLICATION CONFIRM MODE COM2 DNP APPLICATION CONFIRM TIMEOUT COM2 DNP RESPONSE FRAGMENT SIZE COM2 DNP COM2 OBJ1 VARIATION DNP COM2 OBJ2 VARIATION DNP COM2 OBJ20 VARIATION DNP COM2 OBJ22 VARIATION DNP COM2 OBJ30 VARIATION DNP COM2 OBJ32 VARIATION DNP COM2 OBJ40 41 VARIATION DNP LOGICAL DEVICE 1 SLAVE ADDRESS COM1 DNP LOGICAL DEVICE 2 SLAVE ADDRESS COM1 DNP MASTER ADDRESS COM1 DNP APPLICATION CONFIRM MODE COM1 DNP APPLICATION CONFIRM TIMEOUT COM1 DNP RESP FRAG SIZE COM1 DNP COM1 OBJ1 VAR DNP COM1 OBJ2 VAR DNP COM1 OBJ20 VAR DNP COM1 OBJ22 VAR DNP COM1 OBJ30 VAR DNP COM1 OBJ32 VAR DNP COM1 OBJ40 41 VAR CL FORM ACTIVE ID CL FORM CL FORM LABEL DNP COM2 ARM SEL TM DNP COM2 UNSOLICITED MIN EVENT C1 DNP COM2 UNSOLICITED MIN EVENT C2 DNP COM2 UNSOLICITED MIN EVENT C3 DNP COM2 UNSOLICITED DELAY C1 DNP COM2 UNSOLICITED DELAY C2 DNP COM2 UNSOLICITED DELAY C3 DNP COM2 UNSOLICITED MAX RETRIES DNP COM2 UNSOLICITED OFFLINE TM DNP COM2 UNSOLICITED FLUSH DNP COM2 UNSOLICITED END BK USR DNP COM2 UNSOLICITED END BK MSG DNP COM2 UNSOLICITED TIMEOUT INC DNP COM2 SELF ADDRESS DNP COM2 EVENT MODE OBJ20 DNP COM2 EVENT MODE OBJ30 DNP COM2 EVENT BUF SZ Obj1 DNP COM2 EVENT BUF SZ Obj20 DNP COM2 EVENT BUF SZ Obj30 DNP COM1 ARM SEL TM DNP COM1 UNSOLICITED MIN EVENT C1 DNP COM1 UNSOLICITED MIN EVENT C2 DNP COM1 UNSOLICITED MIN EVENT C3 DNP COM1 UNSOLICITED DELAY C1 DNP COM1 UNSOLICITED DELAY C2 Page 16 Data Type UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD 168 BYTE STRING 16 BYTE STRING UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD Ordinal Block 6 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 6 Offset 1944 1946 1948 1950 1952 1954 1956 1958 1960 1962 1964 1966 1968 1970 1972 1974 1976 1978 2010 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 2026 2027 2028 2029 2030 2031 2032 2033 2034 2290 2294 2298 2302 2306 2310 2314 2318 2322 2326 2330 2334 2338 2342 2346 2350 2354 2358 2362 2366 2370 2374 2378 2382 2386 2390 2394 2398 2402 Scale Factor 1 1 1 1 1 1 1 1 1 1 1 1 1 10 10 10 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Description DNP COM1 UNSOLICITED DELAY C3 DNP COM1 UNSOLICITED MAX RETRIES DNP COM1 UNSOLICITED OFFLINE TM DNP COM1 UNSOLICITED FLUSH DNP COM1 UNSOLICITED END BK USR DNP COM1 UNSOLICITED END BK MSG DNP COM1 UNSOLICITED TMOUT INC DNP COM1 SELF ADDRESS DNP COM1 EVENT MODE OBJ20 DNP COM1 EVENT MODE OBJ30 DNP COM1 EVENT BUF SZ Obj1 DNP COM1 EVENT BUF SZ Obj20 DNP COM1 EVENT BUF SZ Obj30 DNP COM2 UNSOLICITED FIXED DLY DNP COM2 UNSOLICITED RANDOM DLY DNP COM1 UNSOLICITED FIXED DLY DNP COM1 UNSOLICITED RANDOM DLY UNUSED VIN CONFIG EVENT USER RESET REQUEST ENABLE EVENT SET TIME ENABLE EVENT FACT CALIBRATION REQUIRED ENABLE EVENT DID NOT ACQ DATA ENABLE EVENT TAP RAISE ENABLE EVENT TAP LOWER ENABLE EVENT TAP AT NEUTRAL ENABLE EVENT NEUTRAL SYNC ENABLE EVENT MAX TAP POS SYNC ENABLE EVENT MIN TAP POS SYNC ENABLE EVENT VOLT LIMIT ACTIVATED ENABLE EVENT VOLT LIMIT HIGH HIT ENABLE EVENT VOLT LIMIT LOW HIT ENABLE EVENT VOLT REDUC ACTIVATED ENABLE EVENT SOFT ADD AMP HIGH HIT ENABLE EVENT SOFT ADD AMP LOW HIT ENABLE EVENT PMT MODEA COMPLETE ENABLE EVENT PMT MODEB COMPLETE ENABLE EVENT INPUT VOLTAGE MISSING ENABLE EVENT INPUT VOLTAGE RESTORED ENABLE EVENT OUTPUT VOLTAGE MISSING ENABLE EVENT OUTPUT VOLTAGE RESTORED ENABLE USER TEXT RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED Page 17 Data Type UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD UNSIGNED WORD 32 BYTE STRING UNSIGNED WORD UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE UNSIGNED BYTE 256 BYTE STRING FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT FLOATING POINT Ordinal Block 6 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block 6 Offset Scale Factor Description 2406 1 RESERVED 2410 1 RESERVED 2414 1 RESERVED NOTE: DATA TYPE "FLOATING POINT" IS ACTUALY A SINGLE PRECISION FLOATING POINT NUMBER DATA TYPE Page 18 Data Type FLOATING POINT FLOATING POINT FLOATING POINT Ordinal Block 6 CL-6A 2179 Ordinal Points Map ORDINAL BLOCK SUBSYSTEM Ordinal Block B (All data is signed 16-bit integer format) Offset 0000 0002 0004 0006 0008 0010 0012 0014 0016 0018 0020 0022 0024 0026 0028 0030 0032 0034 0036 0038 0040 0042 0044 0046 0048 0050 0052 0054 0056 0058 0060 0062 0064 0066 0068 0070 0072 0074 0076 0078 0080 0082 0084 0086 Scale Factor 100 100 100 100 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1 1 10 10 10 10 10 10 10 10 10 10 10 10 Description POWER FACTOR AT FORWARD DEMAND KVA LOAD MAXIMUM POWER FACTOR AT FORWARD DEMAND KVA LOAD MINIMUM POWER FACTOR AT REVERSE DEMAND KVA LOAD MAXIMUM POWER FACTOR AT REVERSE DEMAND KVA LOAD MINIMUM FORWARD DEMAND PRIMARY LOAD CURRENT MINIMUM FORWARD DEMAND PRIMARY LOAD CURRENT MAXIMUM FORWARD DEMAND KVA LOAD MINIMUM FORWARD DEMAND KVA LOAD MAXIMUM FORWARD DEMAND KVAR LOAD MINIMUM FORWARD DEMAND KVAR LOAD MAXIMUM FORWARD DEMAND KW LOAD MINIMUM FORWARD DEMAND KW LOAD MAXIMUM FORWARD DEMAND SECONDARY LOAD VOLTAGE MINIMUM FORWARD DEMAND SECONDARY LOAD VOLTAGE MAXIMUM FORWARD DEMAND SECONDARY COMPENSATED VOLTAGE MINIMUM FORWARD DEMAND SECONDARY COMPENSATED VOLTAGE MAXIMUM REVERSE DEMAND PRIMARY LOAD CURRENT MINIMUM REVERSE DEMAND PRIMARY LOAD CURRENT MAXIMUM REVERSE DEMAND KVA LOAD MINIMUM REVERSE DEMAND KVA LOAD MAXIMUM REVERSE DEMAND KVAR LOAD MINIMUM REVERSE DEMAND KVAR LOAD MAXIMUM REVERSE DEMAND KW LOAD MINIMUM REVERSE DEMAND KW LOAD MAXIMUM REVERSE DEMAND SECONDARY LOAD VOLTAGE MINIMUM REVERSE DEMAND SECONDARY LOAD VOLTAGE MAXIMUM REVERSE DEMAND SECONDARY COMPENSATED VOLTAGE MINIMUM REVERSE DEMAND SECONDARY COMPENSATED VOLTAGE MAXIMUM PERCENT REGULATIONMAXIMUM PERCENT REGULATIONMINIMUM TAP POSITION MAXIMUM TAP POSITION MINIMUM FORWARD DEMAND SECONDARY SOURCE VOLTAGE MINIMUM FORWARD DEMAND SECONDARY SOURCE VOLTAGE MAXIMUM REVERSE DEMAND SECONDARY SOURCE VOLTAGE MINIMUM REVERSE DEMAND SECONDARY SOURCE VOLTAGE MAXIMUM FORWARD DEMAND TOTAL CURRENT HARMONIC DISTORTION MINIMUM FORWARD DEMAND TOTAL CURRENT HARMONIC DISTORTION MAXIMUM REVERSE DEMAND TOTAL CURRENT HARMONIC DISTORTION MINIMUM REVERSE DEMAND TOTAL CURRENT HARMONIC DISTORTION MAXIMUM FORWARD DEMAND TOTAL VOLTAGE HARMONIC DISTORTION MINIMUM FORWARD DEMAND TOTAL VOLTAGE HARMONIC DISTORTION MAXIMUM REVERSE DEMAND TOTAL VOLTAGE HARMONIC DISTORTION MINIMUM REVERSE DEMAND TOTAL VOLTAGE HARMONIC DISTORTION MAXIMUM Page 19 Ordinal Block 5 Appendix A: Analog Variable Values Use the values below when reading or writing to a point that is normally selected from a list directly on the CL-6 control or through the interface software. For additional information on how to program the control, see the S225-11-1 instruction manual. Example: SOFT-ADD-AMP State (Ordinal Block 6 Offset 94, Function Code 79) requires the entry of an “Off” or “On” value. Looking in the Off/On portion of the list Off = 0 and On =1. Off /On 0 = Off 1 = On False / True 0 = False 1 = True No / Yes 0 = No 1 = Yes Regulator Configuration 1 = Wye 2 = Delta Regulator Configuration 0 = Wye (or Star) 1 = Delta Lagging 2 = Delta Leading Add Amp Upper Limit 8 = 8 Raise 10 = Raise 12 = Raise 14 = Raise 16 = Raise Add Amp Lower Limit -8 = Lower -10 = Lower -12 = Lower -14 = Lower -16 = Lower PMT Designation 0 = Off 1 = Master 2 = Slave Baud Rate 0 1 2 3 4 5 6 7 Control Operating Mode 0 = Sequential (Std) 1 = Time Integrating 2 = Voltage Averaging Regulator Type 0=A 1=B 2=C 3=D Tap Changer Type 0 = Cooper QD8 1 = Cooper QD5 2 = Cooper QD3 3 = Cooper Spring Drive 4 = Cooper Direct Drive 5 = Siemens 6 = General Electric 7 = Toshiba 8 = ----Reverse Sensing Mode 0 = Locked Forward 1 = Locked Reverse 2 = Reverse Idle 3 = Bidirectional 4 = Neutral Idle 5 = Cogeneration 6 = Reactive Bidirectional Security Override 0 = Standard 1 = Override Level 1 2 = Override Level 2 3 = Override Level 3 Voltage Limiter Mode 0 = Off 1 = High Volt Limit 2 = Low Volt Limit = 300 = 600 = 1200 = 2400 = 4800 = 9600 = 19200 = 38400 Protocols 0 = DNP 3.0 1 = 2179 Handshaking Mode 0 = RTS without CTS 1 = RTS with CTS 2 = RTR without CTS 3 = RTR with CTS PIO Equation Form Type 0 = None 1 = Standard 4 = If-Then 5 = Timer 6 = If-Else 7 = If-Else-If Communications Protocol Map ID 0 = User 32 = CL-5D 33 = CL-5E 34 = CL-6A Default Map Port 0 = User1-COM1 User2COM2 1 = User1 on COM1/2 2 = User2 on COM1/2 Control Function Switch 0 = Manual 1 = Auto DNP Link Confirmation Mode 0 = Never 1 = Multi-Frame Fragments 2 = Always Default DNP Object 01 Variation 1 = State 2 = Status+State Default DNP Object 02 Variation 1 = State 2 = Status+State Default DNP Object 20 Variation 1 = 32Bt Flag and Value 2 = 16Bt Flag and Value 5 = 32Bt Value 6 = 16Bt Value Default DNP Object 22 Variation 1 = 32Bt Flag and Value 2 = 16Bt Flag and Value 5 = 32Bt Flag and Value with Time Stamp 6 = 16Bt Flag and Value with Time Stamp Default DNP Object 30 Variation 1 = 32Bt Flag and Value 2 = 16Bt Flag and Value 3 = 32Bt Value 4 = 16Bt Value 5 = Float Flag and Value Default DNP Object 32 Variation 1 = 32Bt Flag and Value 2 = 16Bt Flag and Value 3 = 32Bt Flag and Value with Time Stamp 4 = 16Bt Flag and Value with Time Stamp 5 = Float Flag and Value Default DNP Object 40 Variation 1 = 32Bt Flag and Value 2 = 16Bt Flag and Value 3 = Float Flag and Value DNP Event Mode 0 = SOE 1 = Current CL-6A 2179 Ordinal Points Map CL-6A 2179 Ordinal Points Map ©2004 Cooper Power Systems, Inc. ADD-AMP™, PMT™, AND SOFT-ADD-AMP™ are trademarks of Cooper Industries, Inc. 1045 Hickory Street Pewaukee, WI 53072 USA www.cooperpower.com KDL 6/04