Voltage Regulators Effective August 2014 New Issue Quick connect assembly (QCA) 12-conductor retrofit kit MN225002EN DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Contents SAFETY INFORMATION Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv PRODUCT INFORMATION Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Acceptance and Initial Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Handling and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 GENERAL Parts Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 SIEMENS CORPORATION/HOWARD INDUSTRIES 12-CONDUCTOR QCA INSTALLATION INSTRUCTIONS Component Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 GENERAL ELECTRIC 12-CONDUCTOR QCA INSTALLATION INSTRUCTIONS Component Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 GENERAL ELECTRIC SM2/SM3 12-CONDUCTOR QCA INSTALLATION INSTRUCTIONS Component Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 CL-7 CONTROL AND ENCLOSURE INSTALLATIONS Option 1: Single-phase CL-7 Control and Enclosure for an Individual Voltage Regulator . . . . . . . . . . . . . . . . . . . . . . . .29 Option 2: Multi-phase CL-7 Control and Enclosure for Two to Three Single-Phase Voltage Regulators. . . . . . . . . . . . . .33 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com iii ! Safety for life SAFETY FOR LIFE ! SAFETY FOR LIFE Eaton’s Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton’s Cooper Power Systems employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our “Safety For Life” mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. A competent technician has these qualifications: • Is thoroughly familiar with these instructions. • Is trained in industry-accepted high and low-voltage safe operating practices and procedures. • Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. • Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates a imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. iv DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Product information Introduction The purpose of the Quick Connect Assembly (QCA) 12-conductor retrofit kit provides the parts and installation instruction for installing the QCA retrofit kit in other voltage regulator manufacturer's (General Electric® (GE®), Howard Industries®, Siemens Corporation®) control enclosures, using them as junction boxes for the purpose of interfacing with Eaton's Cooper Power Systems control/cabling assembly. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your representative. Acceptance and initial inspection Each kit is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the kit and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and storage Be careful during handling and storage of the kit to minimize the possibility of damage. If the kit is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 1 General Parts supplied The parts supplied in this kit will depend on the voltage regulator manufacturer's apparatus interface. The QCA 12-conductor retrofit kit can be used for one of the following four interfaces. Manufacturer Part Number Siemens Corporation 575044887B01 Howard Industries 575044887B01 GE 575044887B02 GE SM2/SM3 575044887B03 Description Qty. QCA, 12conductor 1 The QCA retrofit kit is an application allowing for another manufacturer's voltage regulating apparatus connected to Eaton's Cooper Power Systems control assembly by using the other manufacturer's control enclosure as a junction box. The QCA retrofit kit is terminated within the existing control enclosure, using the manufacturer's juncture for their apparatus and control front panel termination point. Existing control front panel is removed. Once the QCA retrofit kit has been installed, Eaton's Cooper Power Systems control assembly with 12-conductor control cable connector can be interfaced with the circular receptacle end of the QCA retrofit kit. The QCA retrofit kit can be used for a single-phase application or a multi-phase application (three single-phase voltage regulators/one control). This document is divided into three sections for installation of the QCA retrofit kit. Tools required Siemens Corporation/Howard Industries Item Number Description Qty. 1 Pliers 1 2 Wire Cutters 1 3 Standard Flat Head Screwdriver 1 4 Phillips #2 Screwdriver 1 5 3/8 inch Drive Drill 1 6 1-1/4 inch Open End Wrench 1 7 1-3/4 inch Open End Wrench 2 8 Nut Driver or Socket 3/8 inch 1 9 Hammer 1 10 Bi-metal Hole Saw 1 11 Chisel 1 12 3/8 inch Drive Ratchet 1 Application GE GE (SM2/SM3 module connector) GE 12-conductor QCA, Part# 575044887B02 Siemens/Howard 12 conductor QCA, Part# 575044887B01 GE SM2/SM3 12-conductor QCA, Part# 575044887B03 2 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Siemens Corporation/Howard Industries 12-conductor QCA installation instructions Component parts Item Part Number Description Qty. 1 5044886B01 Juncture terminal board harness 12-conductor 1 2 5043000B01 QCA circular receptacle assembly –EXT Cap 12 1 3 08A621282001 Washer 4 4 0537980C03 Gasket 2 5 A5481751 ¾ -14 NPSM STL ZP NUT 1 6 0800069825Z Cable tie adhesive back fastener 3 7 0800011079Z-2 Cable tie 5 Item 2 Item 1 Figure 1. Siemens/Howard 12-conductor QCA kit. Feature Item 4 The highlight of the Siemens/Howard 12-conductor QCA retrofit kit is to transform the Siemens or Howard control enclosures into junction boxes replacing their control panel with Eaton's Cooper Power Systems control assembly with interconnecting cord(s). The circular sealed receptacle assembly (Item 2) shall exit preferably from the bottom of the newly formed junction box. Eaton's Cooper Power Systems 12-conductor cord connector inserts into the end of this receptacle assembly. The acceptable application involves a single regulator or group of two or three regulators mounted on a common platform or pole locating the replacement control assembly at a remote location. This application also applies to regulators in a substation located on the same pad next to each other. Item 5 Item 3 Figure 2. Washer, gaskets and nut. Installation Item 6 The following instructions provide guidelines in removing the other manufacturer's control panel from their enclosure, installing the QCA retrofit kit, and connecting Eaton's Cooper Power Systems control assembly with interconnecting cords. 1. Energized regulator(s) shall be placed in the Neutral Position verifying by using three forms of indication: Neutral Light of control panel lit, Position Indicator pointing to the Neutral Position, and by way of monitoring between the Source and Load Bushings indicating zero volts within meter tolerance. 2. Bypass and de-energize the regulators. 3. Swing open up the control panel allowing entry to the back of the enclosure. Item 7 Figure 3. Fasteners and cable ties. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 3 4. Remove the two wing nuts against the male portion of the juncture terminal board of the QCA harness assembly located at the top inside of the enclosure. See Figure 4. Wing nut 8. Remove the cabling provision at the bottom location of the control enclosure as shown in Figure 6. If cabling provision is not available use a bi-metal hole saw to provide a 1-1/8 inch diameter opening at the bottom of the control enclosure. Wing nut Figure 4. Apparatus/Control juncture terminal board. 5. Disconnect the apparatus/control juncture terminal board assembly as shown in Figure 5. Bottom of enclosure Cabling provision Figure 6. Control enclosure bottom access. 9. Apparatus/control juncture terminal board assembly Remove the Siemens/Howard QCA retrofit kit, as seen in Figure 7, from the package and disconnect the circular sealed receptacle assembly from the rest of the QCA retrofit kit assembly. To disconnect the circular sealed receptacle assembly, press down on the release levers, as shown in Figure 8, of the two "Wire to Wire" connectors and pull them apart. Figure 5. Disconnected juncture terminal board assembly. 6. Disconnect and discard control panel ground wires from ground posts on back of the control enclosure. 7. Remove control panel from the hinges of the enclosure. Figure 7. Siemens/Howard QCA retrofit kit. 4 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 11. From the kit, place one of the gaskets (Item 4), over the QCA retrofit kit harness seating the gasket against the QCA circular sealed receptacle assembly as shown in Figure 10. "Wire to Wire" connector release levers Receptacle white wire Gasket Lever clamp terminal block Circular sealed receptacle assembly Figure 8. "Wire to Wire" connector decoupling. 10. Pull up on the lever of the clamp terminal block where the white wire of the receptacle assembly is connected. See Figure 9. Pull this white wire from the clamp terminal block. Figure 10. QCA circular sealed receptacle assembly and gasket. 12. From outside of enclosure insert the QCA circular receptacle assembly with gasket through the opening at the bottom of the control enclosure. See Figure 11. QCA circular sealed receptacle Lever Circular receptacle assembly white wire Figure 11. QCA circular sealed receptacle location. Figure 9. Lever clamp terminal block. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 5 13. Place second gasket (Item 4) over the inserted QCA circular receptacle assembly on inside surface of control enclosure. See Figure 12. 15. Place the nut (Item 5) over the QCA circular receptacle assembly. See Figure 14. Nut Gasket Figure 14. Receptacle assembly nut installation. Figure 12. Receptacle assembly internal gasket installation. 14. Place flat washer (Item 3) over the QCA circular receptacle assembly with washer on top of previous installed gasket. See Figure 13. 16. Secure QCA receptacle assembly by threading and tightening down the provided internal nut with a 1-¼" open face wrench while holding the outside portion of the receptacle in place with a 1-¾" size wrench. 17. Connect the QCA male portion of the juncture terminal board to the Siemens/Howard female portion located at the top of the control enclosure. Make sure that the terminal block halves are fully engaged with the wing nut studs protruding through the male connector. See Figure 15. Washer Wing nut studs QCA harness terminal board Figure 13. Receptacle assembly internal washer installation. Figure 15. Installation of QCA juncture terminal board harness. 6 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Siemens/Howard Terminals QCA wiring harness Color Code U12 Red/Black P2 Black C2 Green E White* E1 Red U2 White/Black J Blue K Green/Black U10 Orange U11 Orange/Back Lever in upright position CT protector *Two white wires, harness white wire and CT Protector white wire. 18. Replace the two wing nuts onto the wing nut threaded studs tightening down until the two terminal board halves remain fully engaged. See Figure 16. Figure 17. Open position of lever clamp terminal block. Closed lever White wire Wing nuts Circular receptacle assembly Figure 16. Wing nut installation. Figure 18. Installation of white wire from receptacle. 19. Lift into the upright position one of the levers of the clamp terminal block which has an available position as shown in Figure 17. Insert fully the white wire from the circular receptacle assembly into this position, afterwards closing the lever as shown in Figure 18. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 7 20. Link together the two "Wire to Wire" connectors between the circular receptacle assembly and the juncture terminal board harness as shown in Figure 19. Juncture terminal board harness Option 1. Motor capacitor not available in the Siemens/Howard control enclosure. The capacitor is mounted inside the regulator tank on the tap-changer. Remove the shorter wires (blue/black and black/white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 20. To remove, lift the associated levers in the upmost position and pull the wires out. Tie these wires to the QCA harness for future use so they do not interfere with other terminations. "Wire to Wire" connectors Blue/Black motor capacitor lead Circular receptacle assembly Black/White motor capacitor lead Black/White short lead Lever clamp terminal blocks Figure 19. "Wire to Wire" connectors linked. 21. There are two additional wires off of the QCA retrofit kit 12-conductor harness assembly, blue/black and black/white wires. These wires are for connections with tap-changer motor start capacitor mounted inside the control enclosure. There are three options available for use of these wires. Blue/Black short lead Figure 20. External motor capacitor connections. Option 2. Motor capacitor available inside the Siemens/Howard control enclosure and the capacitor is to be left connected to the existing Siemens/Howard enclosure circuitry. Remove the shorter wires (blue/black and black/ white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 20. To remove lift the associated levers into the upmost position and pull the wires out. Tie these wires to the QCA harness for future use so they do not interfere with other terminations. 8 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Option 3. The motor capacitor for Siemens/Howard tap-changer relocated to inside of the Eaton's Cooper Power Systems control enclosure. Remove the shorter wires (blue/black and black/white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 20. To remove lift the associated levers into the upmost position and pull the wires out. Remove from the motor capacitor terminals, the leads coming from the electrical conduit between the control enclosure and regulator cover junction box. Use a pair of wire cutters to remove these capacitor terminals from the capacitor leads. Strip back the insulation 3/16" on both capacitor leads. Lift the lever on one of the QCA retrofit kit lever clamp terminal blocks above the associated open position. Insert one of the Siemens/Howard motor capacitor leads fully into the open position and close the orange lever. Repeat the same process for the other motor capacitor lead. See Figure 21. 22. To help secure the QCA retrofit kit to the back of the Siemens/Howard control enclosure, place one to three tie fasteners (Item 6) as needed as shown in Figure 22. Cable tie fasteners Figure 22. Cable tie fasteners. 23. For each fastener insert a cable tie (Item 7) through the slots in the fastener. Bring both ends of the cable tie together and pull snugly, cutting off excess with wire cutters. See Figure 23. Siemens/ Howard motor capacitor lead Siemens/ Howard motor capacitor lead Blue/Black motor capacitor lead Lever clamp terminal blocks Black/White motor capacitor lead Figure 21. Siemens/Howard motor capacitor lead connections. The motor capacitor leads from the QCA retrofit kit are color coded: one wire is blue/black and the other is black/white. There is no concern for polarity with these connections. The connections are now completed for the Siemens/ Howard motor capacitor to be relocated or a new capacitor installed inside the Eaton's Cooper Power Systems control enclosure. For a multi-phase control application two or three motor capacitors will be installed in the same control enclosure in the proper location (VR1, VR2 and VR3) to match up with the tap-changers they are intended for. The location is important for a bank of different voltage regulators. Cable tie fasteners Figure 23. Secured harness assembly. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 9 24. The male connector of Eaton's Cooper Power Systems 12-conductor cord connects to the QCA circular female receptacle at the bottom of the GE control enclosure shown in Figure 24. To connect the cord to the receptacle, line up the keyway on the cord connector with the keyway guide of the receptacle as shown in Figure 25. 25. Insert the male connector of the cord into the QCA female receptacle, pushing the connector into the receptacle as far as possible. Tighten the male connector nut several turns pushing the connector further into the receptacle. Continue pushing and tightening until the connector and receptacle are fully engaged. 26. Refer to the CL-7 control and enclosure installations section of this service manual following instructions making wiring connections inside the Eaton's Cooper Power Systems control enclosure specific for the application selected. Figure 24. Circular sealed receptacle. Figure 25. Receptacle and connector assembly. 10 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com General Electric 12-conductor QCA installation instructions Component parts Item Part Number Description Qty 1 5044886B02 Juncture terminal board harness 12-conductor GE 1 2 5043000B01 QCA circular receptacle assembly –EXT Cap 12 1 3 08A621282001 Washer 1 4 0537980C03 Gasket 2 5 A5481751 ¾ -14 NPSM STL ZP NUT 1 6 0800069825Z Cable tie adhesive back fastener 3 7 0800011079Z-2 Cable tie 5 Item 1 Item 2 Figure 26. GE 12-conductor QCA kit. Feature The highlight of the GE 12-conductor QCA retrofit kit is to transform the GE control enclosures into junction boxes replacing their control panel with Eaton's Cooper Power Systems control assembly with interconnecting cord(s). The circular sealed receptacle assembly (Item 2) will exit preferably from the bottom of the newly formed junction box. Eaton's Cooper Power Systems 12-conductor cord connector inserts into the end of this receptacle assembly. The acceptable application involves a single regulator or group of two or three regulators mounted on a common platform or pole locating the replacement control assembly at a remote location. This application also applies to regulators in a substation located on the same pad next to each other. Item 4 Item 5 Item 3 Figure 27. Washer, gaskets, and nut. Installation The following instructions provide guidelines in removing the other manufacturer's control panel from their enclosure, installing the QCA retrofit kit assembly, and connecting Eaton's Cooper Power Systems control assembly with interconnecting cords. Item 6 Item 7 Figure 28. Fasteners and cable ties. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 11 1. Energized regulator(s) shall be placed in the Neutral Position verifying by using three forms of indication: Neutral Light of the control panel lit, Position Indicator pointing to the Neutral Position, and by way of monitoring between the Source and Load Bushings, indicating zero volts within meter tolerance. 2. Bypass and de-energize the regulators. 3. Swing open up the control panel allowing entry to the back of the enclosure. 4. Disconnect the GE wiring harness from the bottom half of the two apparatus/control juncture terminal boards, shown in Figure 29, located at the right top side at the back of the enclosure. 5. Disconnect and discard control panel ground wires from ground posts on back of the control enclosure. 6. Remove control panel from the hinges of the enclosure. 7. Remove the cabling provision from the bottom location of the control enclosure as shown in Figure 30. If cabling provision is not available use a bi-metal hole saw to provide a 1-1/8 inch diameter opening at the bottom of control enclosure. Bottom of enclosure 1-1/8" cabling provision GE enclosure wiring harness Figure 30. Control enclosure bottom access. 8. Remove the GE QCA retrofit kit, as shown in Figure 31, from the package and disconnect the circular sealed receptacle assembly from the rest of the QCA retrofit kit assembly. To disconnect the circular sealed receptacle assembly, press down on the release levers as shown in Figure 32, of the two "Wire to Wire" connectors and pull them apart. Figure 29. Apparatus/Control Juncture terminal boards. Figure 31. GE QCA retrofit kit. 12 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 10. From the kit place one of the gaskets (Item 4) over the QCA retrofit kit harness seating the gasket against the QCA circular sealed receptacle assembly as shown in Figure 34. "Wire to Wire" connector release levers Gasket Receptacle white wire Lever clamp terminal block Circular sealed receptacle assembly Figure 34. QCA circular sealed receptacle assembly and gasket. Figure 32. "Wire to Wire" connector decoupling. 9. 11. From outside of the enclosure insert the QCA circular receptacle assembly with gasket through the opening at the bottom of the control enclosure. See Figure 35. Pull up on the lever on the clamp terminal block where the white wire of the receptacle assembly is connected. See Figure 33. Pull this white wire from the clamp terminal block. QCA circular sealed receptacle Circular receptacle assembly white wire Lever Figure 35. QCA circular sealed receptacle location. Figure 33. Lever clamp terminal block. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 13 12. Place second gasket (Item 4) over the inserted QCA circular receptacle assembly on inside surface of the control enclosure. See Figure 36. 14. Place the nut (Item 5) over the QCA circular receptacle assembly. See Figure 38. 15. Secure QCA receptacle assembly by threading and tightening down the provided internal nut with a 1-1/4" open face wrench while holding the outside portion of the receptacle in place with a 1-3/4" size wrench. Gasket Figure 36. Receptacle assembly internal gasket installation. 13. Place flat washer (Item 3) over the QCA circular receptacle assembly with washer on top of previously installed gasket. See Figure 39. Nut Figure 38. Receptacle assembly nut installation. Washer Figure 37. Receptacle assembly internal washer installation. 14 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 16. Connect the QCA retrofit kit assembly to the apparatus/ control juncture terminal boards located in the upper right back side of the control enclosure. Connect this end of the QCA assembly using the wire chart below. GE Terminals (NN) QCA Assembly Color Wire Code 26 White 27 Blue 28 Green/Black 29 Orange/Black 30 Orange 31 Red /Black 32 White/Black 24 Red 23 Green 10 White *20 Internal PT tap Black 20, 21, or 22 Connection Load Volts Pot Ratio Control Volts NN9 TO I TO 7960 66.7:1 119.3 22 H5 7620 66.7:1 114.1 22 H5 7620 63.5:1 120.0 21 H5 7200 60:1 120.0 20 H5 5000 40:1 125.0 20 H4 4330 34.8:1 124.4 20 H3 2500 20:1 125 20 H2 18. Lift into the upright position one of the levers of the clamp terminal block which has an available position as shown in Figure 40. Insert fully the white wire from the circular receptacle assembly into this position, afterwards closing the lever as shown in Figure 41. *21 Internal PT tap Lever in upright position *22 Internal PT tap ** Terminal board mounting threaded studs White * See Step 18 for information on connection. ** Two white harness wires fasten under mounting nuts on top terminal board, one wire on each end of terminal board White harness wires White harness wires CT protector Figure 40. Open position of lever clamp terminal block. Figure 39. QCA retrofit kit harness termination on apparatus/control juncture terminal boards. 17. When connecting the black wire from the QCA retrofit kit wiring harness refer to the GE nameplate on the GE control enclosure or apparatus to determine connection for required regulated system voltage. Note: The following is an example of GE Nameplate chart covering required taps for specified system voltage. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 15 Closed lever 19. Link together the two "Wire to Wire" connectors between the circular receptacle assembly and the juncture terminal board harness as shown in Figure 42. Juncture terminal board harness White wire "Wire to Wire" connectors Circular receptacle assembly Circular receptacle assembly Figure 41. Installation of white wire from receptacle. Figure 42. "Wire to Wire" linked. 20. There are two additional wires off of the QCA retrofit kit 12-conductor harness assembly; blue/black and black/white wires. These wires are for connections with tap-changer motor start capacitor mounted inside the control enclosure. There are three options available for use of these wires. 16 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Option 1. Option 2. Motor capacitor not available in the GE control enclosure. The capacitor is mounted inside the regulator tank on the tap-changer. Remove the shorter wires (blue/ black and black/white with the Push on terminals) from the lever clamp terminal blocks shown in Figure 43. To remove, lift the associated levers in the upmost position and pull the wires out. Tie these wires to the QCA harness for future use so they do not interfere with other terminations. Motor capacitor available inside the GE control enclosure and the capacitor is to be left connected to the existing GE enclosure circuitry. Remove the shorter wires (blue/black and black/white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 43. To remove, lift the associated levers into the upmost position and pull the wires out. Tie these wires to the QCA harness for future use so they do not interfere with other terminations. Blue-Black motor capacitor lead Black/White motor capacitor lead Blue/Black short lead Black/White short lead Lever clamp terminal blocks Figure 43. External motor capacitor connections. Option 3. The motor capacitor for GE tap-changer relocated to inside of Eaton's Cooper Power Systems control enclosure. Remove the shorter wires (blue/black and black/ white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 43. To remove, lift the associated levers into the upmost position and pull the wires out. Remove from the motor capacitor terminals, the leads coming from the electrical cord between the control enclosure and regulator position indicator. Use a pair of wire cutters to remove these capacitor terminals from the capacitor leads. Strip back the insulation 3/16" on both capacitor leads. Lift the lever on one of the QCA retrofit kit lever clamp terminal blocks above the associated open position. Insert one of the GE motor capacitor leads fully into the open position and close the orange lever. Repeat the same process for the other motor capacitor lead. See Figure 44. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 17 21. To help secure the QCA retrofit kit to the back of the GE control enclosure, place one to three tie fasteners (Item 6) as needed and shown in Figure 45. GE motor leads Blue/Black motor capacitor lead Black/White motor capacitor lead Lever clamp terminal blocks Figure 44. GE motor capacitor lead connections. The motor capacitor leads from the QCA retrofit kit are color coded: one wire is blue/black and the other is black/white. There is no concern for polarity with these connections. The connections are now completed for the GE motor capacitor to be relocated or a new capacitor installed inside Eaton's Cooper Power Systems control enclosure. For a multiphase control application two or three motor capacitors will be installed in the same control enclosure in the proper location (VR1, VR2, or VR3) to match up with the tapchangers they are intended for. The location is important for a bank of different voltage regulators. Cable tie fasteners Figure 45. Cable tie fasteners. 22. For each fastener insert a cable tie (Item 7) through the slots in the fastener. Bring both ends of the cable tie together and pull snugly, cutting off excess with wire cutters. See Figure 46. Cable ties Figure 46. Secured harness assembly. 18 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 23. The male connector of Eaton's Cooper Power Systems 12-conductor cord connects to the QCA circular female receptacle at the bottom of the GE control enclosure shown in Figure 47. To connect the cord to the receptacle, line up the keyway on the cord connector with the keyway guide of the receptacle as shown in Figure 48. 24. Insert the male connector of the cord into the QCA female receptacle, pushing the connector into the receptacle as far as possible. Tighten the male connector nut several turns pushing the connector further into the receptacle. Continue pushing and tightening until the connector and receptacle are fully engaged. 25. Refer to the CL-7 control and enclosure installations section of this service manual following instructions making wiring connections inside Eaton's Cooper Power Systems control enclosure specific for the application selected. Figure 47. Circular sealed receptacle. Figure 48. Receptacle and connector assembly. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 19 GE SM2/SM3 12-conductor QCA installation instructions Item 1 Component parts Item Part Number Description Qty 1 5044886B03 Junction terminal board harness 12-conductor 1 2 5043000B01 QCA circular receptacle assembly –EXT Cap 12 1 3 08A621282001 Washer 1 4 0537980C03 Gasket 2 5 A5481751 ¾ -14 NPSM STL ZP NUT 1 6 0800069825Z Cable tie adhesive back fasteners 3 7 0800011079Z-2 Cable tie 5 Item 2 Figure 49. GE SM2/SM3 12-conductor QCA kit. Feature The highlight of the GE SM2/SM3 12-conductor QCA retrofit kit is to transform the GE control enclosures into junction boxes replacing the control panel with Eaton's Cooper Power Systems control assembly with interconnecting cord(s). The circular sealed receptacle assembly (Item 2) shall exit preferably from the bottom of the newly formed junction box. Eaton's Cooper Power Systems 12-conductor cord connector inserts into the end of this receptacle assembly. The accepted application involves a single regulator or a group of two or three regulators mounted on a common platform or pole locating the replacement control assembly at a remote location. This application also applies to regulators in a substation located on the same pad next to each other. Item 5 Item 3 Item 4 Figure 50. Washer, gaskets, and nut. Installation The following instructions provide guidelines in removing the other manufacturer's control panel from their enclosure, installing the QCA retrofit kit, and connecting Eaton's Cooper Power Systems control assembly with interconnecting cords. Item 6 Item 7 Figure 51. Fasteners and cable ties. 20 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 1. Energized regulator(s) shall be placed in the Neutral Position verifying by using three forms of indication: Neutral Light of the control panel lit, Position Indicator pointing to the Neutral Position, and by way of monitoring between the Source and Load Bushings, indicating zero volts within meter tolerance. 2. Bypass and de-energize the regulators 3. Swing open up the control panel allowing entry to the back of the enclosure where the power disconnectcircuit board module is located, shown in Figure 52. 4. To remove the power disconnect circuit board from the rack, first press down on the right and left ejection levers as shown in Figure 53. Secondly, slide downward and out the circuit board from the rack as shown in Figure 54. 5. Detach the 24-pin connector, shown in Figure 54, of the harness connected to the control panel. Rack Ejection lever Figure 52. Power disconnect-circuit board module. Figure 53. Releasing power disconnect-circuit board module. 24-pin harness connector Figure 54. Detached power disconnect-circuit board module and harness assembly. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 21 6. Disconnect the two pin control panel ground connector assembly from ground post on back of the control enclosure. 7. Remove control panel from the hinges of the enclosure. 8. Remove the cabling provision from the bottom location of the control enclosure as shown in Figure 55. If cabling provision is not available use a bi-metal hole saw to provide a 1-1/8 inch diameter opening at the bottom of control enclosure. "Wire to Wire" connector release levers Receptacle white wire Lever clamp terminal block 1-1/8" cabling provision Bottom of enclosure Figure 55. Control enclosure bottom access. Figure 57. "Wire to Wire" connector decoupling. 9. Remove the GE SM2/SM3 QCA retrofit kit, as shown in Figure 56, from the package and disconnect the circular sealed receptacle assembly from the rest of the QCA retrofit kit assembly. To disconnect the circular sealed receptacle assembly, press down on the release levers, as shown in Figure 57, of the two "Wire to Wire" connectors and pull them apart. 10. Pull up on the lever on the clamp terminal block where the white wire of the receptacle assembly is connected. See Figure 58. Pull this white wire from the clamp terminal block. 11. From the kit, place one of the gaskets (Item 4) over the QCA retrofit kit harness seating the gasket against the QCA circular sealed receptacle assembly as shown in Figure 58. Circular receptacle assembly white wire Lever Figure 58. Lever clamp terminal block. Figure 56. GE SM2/SM3 QCA kit. 22 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 12. From outside of the enclosure insert the QCA circular receptacle assembly with gasket through the opening at the bottom of the control enclosure. See Figure 60. 13. Place second gasket (Item 4) over the inserted QCA circular receptacle assembly on inside surface of control cabinet. See Figure 61. Circular sealed receptacle assembly Gasket Figure 59. QCA circular sealed receptacle assembly and gasket. Gasket QCA circular sealed receptacle Figure 61. Receptacle assembly internal gasket installation. Figure 60. QCA circular sealed receptacle location. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 23 14. Place flat washer (Item 3) over the QCA circular receptacle assembly with washer on top of previously installed gasket. See Figure 62. Washer Figure 62. Receptacle assembly internal washer installation. 15. Place the nut (Item 5) over the QCA circular receptacle assembly. See Figure 63. Nut Figure 63. Receptacle assembly nut installation. 16. Secure QCA receptacle assembly by threading and tightening down the provided internal nut with a 1-1/4" open face wrench while holding the outside portion of the receptacle in place with a 1-3/4" size wrench. 17. Both the 24-pin male power disconnect-circuit board connector and the matching QCA female connector are keyed for proper alignment. See Figure 64. Connect the QCA wiring harness female pin connector to the power disconnect-circuit board module as shown in Figure 65. QCA female module connector 24-Pin power disconnect-circuit board connector Figure 64. Alignment of QCA and power disconnectcircuit board connectors. 24 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 19. Press the ejection levers upward toward the circuit board module. These will ensure the connection of the module with the apparatus/control juncture. 20. Lift into the upright position one of the levers of the clamp terminal block which has an available position as shown in Figure 67. Insert fully the white wire from the circular receptacle assembly into this position, afterwards closing the lever as shown in Figure 68. Lever in upright position Figure 65. QCA harness and power disconnect-circuit board module. 18. Engage the power disconnect-circuit board module to the apparatus/control juncture by fully sliding assembly upward into the rack located on the back of the enclosure as shown in Figure 66. CT Protector Figure 67. Open position of lever clamp terminal block. Closed lever White wire Apparatus/control juncture Figure 66. Engaged power disconnect-circuit board module assembly. Circular receptacle assembly Figure 68. Installation of white wire from receptacle. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 25 21. Link together the two "Wire to Wire" connectors between the circular receptacle assembly and the juncture terminal board harness as shown in Figure 69. Power-disconnect circuit board module harness 22. There are two additional wires off of the QCA retrofit kit 12-conductor harness assembly; blue/black wire and black/white wires. These wires are for connections with tap-changer motor start capacitor mounted inside the control enclosure. There are three options available for use of these wires. "Wire to Wire" connectors Circular receptacle assembly Figure 69. "Wire to Wire" connectors linked. 26 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Option 1. Motor capacitor not available in the GE control enclosure. The capacitor is mounted inside the regulator tank on the tap-changer. Remove the shorter wires (blue/ black and black/white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 70. To remove, lift the associated levers in the upmost position and pull the wires out. Tie these wires to the QCA harness for future use so they do not interfere with other terminations. Blue/ black motor capacitor lead Black/ white motor capacitor lead Blue/black short lead into the open position and close the orange lever. Repeat the same process for the other motor capacitor lead. See Figure 71. The motor capacitor leads from the QCA retrofit kit are color coded: one wire is blue/black and the other is black/white. GE motor capacitor leads Lever clamp terminal blocks Black/white short lead Blue/black motor capacitor lead Lever clamp terminal blocks Figure 70. External motor capacitor connections. Option 2. Motor capacitor available inside the GE control enclosure and the capacitor is to be left connected to the existing GE enclosure circuitry. Remove the shorter wires (blue/black and black/white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 70. To remove, lift the associated levers into the upmost position and pull the wires out. Tie these wires to the QCA harness for future use so they do not interfere with other terminations. Black/white motor capacitor lead Figure 71. GE motor capacitor lead connections. There is not concern for polarity with these connections. The connections are now completed for the GE motor capacitor to be relocated or a new capacitor installed inside Eaton's Cooper Power Systems control enclosure. For a multi-phase control application two or three motor capacitors will be installed in the same control enclosure in the proper location (VR1, VR2, or VR3) to match up with the tap-changers they are intended for. The location is important for a bank of different voltage regulators. Option 3. The motor capacitor for GE tap-changer relocated to inside of Eaton's Cooper Power Systems control enclosure. Remove the shorter wires (blue/black and black/ white with the Push On terminals) from the lever clamp terminal blocks shown in Figure 70. To remove, lift the associated levers into the upmost position and pull the wires out. Remove from the motor capacitor terminals, the leads coming from the electrical cord between the control enclosure and regulator position indicator. Use a pair of wire cutters to remove these capacitor terminals from the capacitor leads. Strip back the insulation 3/16" on both capacitor leads. Lift the lever on one of the QCA retrofit kit lever clamp terminal blocks above the associated open position. Insert one of the GE motor capacitor leads fully Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 27 23. To help secure the QCA retrofit kit to the back of the GE control enclosure, place one to three tie fasteners (Item 6) as needed and shown in Figure 72. 24. For each fastener insert a cable tie (Item 7) through the slots in the fastener. Bring both ends of the cable tie together and pull snugly, cutting off excess with wire cutters. See Figure 73. 26. Insert the male connector of the cord into the QCA female receptacle, pushing the connector further into the receptacle as far as possible. Tighten the male connector nut several turns pushing the connector further into the receptacle. Continue pushing and tightening until the connector and receptacle are fully engaged. Cable tie fasteners Figure 74. Circular sealed receptacle. Figure 72. Cable tie fasteners. Cable ties Figure 75. Receptacle and connector assembly. Figure 73. Secured harness assembly. 25. The male connector of Eaton's Cooper Power Systems 12-conductor cord connects to the QCA female receptacle at the bottom of the GE control enclosure shown in Figure 74. To connect the cord to the receptacle, line up the keyway on the cord connector with the keyway guide of the receptacle as shown in Figure 75. 28 27. Refer to the CL-7 control and enclosure installations section of this service manual following instructions making wiring connections inside Eaton's Cooper Power Systems control enclosure specific for the application selected. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com CL-7 control and enclosure installations Two options for CL-7 control and enclosure installations are offered due to the availability of both the single-phase and multi-phase version of the CL-7. As suspected there is more involved in the installation of a multi-phase CL-7 control when interfacing with the Siemens, Howard or GE voltage regulating apparatus. All required interface cords, receptacles and connectors are provided for the installation. Option 1: Single-phase CL-7 control and enclosure for an individual voltage regulator Introduction: This section provides instructions for the application of a single-phase CL-7 control and its enclosure with a Siemens, GE or Howard voltage regulator. Additional steps are provided to supplement the instructions given in previous sections covering installations of QCA retrofit assembly kits within the original control enclosures. Installation instructions 1. The following instructions cover the interconnecting quick disconnect cord and associated components installed within the CL-7 enclosure if not previously installed at the factory. 2. Remove the nut, flat washer, and gasket from the cord receptacle end shown in Figure 76. Gasket Flat washer Nut Figure 76. Cord receptacle end and components. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 29 3. With the gasket located around the outside of the entry hole at the top of the control enclosure, insert the threaded portion of the cord receptacle end as shown in Figure 77. 5. Align the keyway of the enclosure male connector, shown in Figure 79, with the keyway of the cord receptacle end. Note: As an option the control cable can be inserted via a bottom entry or side entry of the enclosure, by removing a knockout. A plug would be required for the unused top entry way. Cord receptacle end Gasket Keyway Enclosure entry way Figure 77. Installation of cord receptacle end. Figure 79. Enclosure male connector assembly. 4. Fully insert cord receptacle end, placing the flat washer and nut onto the threads within the enclosure as shown in Figure 78. Using a 1-3/4 inch open face wrench, tighten the nut securing the cord receptacle end to the control enclosure. Flat washer Nut Figure 78. Components installation. 30 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 6. Push the male connector assembly fully as far as possible onto the cord receptacle end while tightening the knurled nut. Repeat this push and tightening process until connection is fully tightened. See Figure 80. 8. Relocate orange lead from "HS" position to position "5" using the insertion tool shown in Figure 83. Terminal #5 Figure 83. Position "5". Figure 80. Installed cord receptacle and connector assembly. 7. Using the wire insertion tool supplied in the control enclosure, shown in Figure 81, remove the orange lead connected to the "HS" position of the terminal board at the bottom of the rear panel shown in Figure 82. Note: Relocation of the orange wire from position "HS" to position "5" allows for the signal from the Operation Counter switch circuit of the GE, Siemen's and Howard's apparatus to properly increment a tap position and operations count on the display of the CL-7 control. 9. For setting up the features and programming of the CL-7 control panel refer to Service Manual MN225003EN (S225-70-1), CL-7 Voltage Regulator Control Installation, Operation, and Maintenance Instructions. 10. If the GE, Siemens or Howard voltage regulator placed their tap-changer motor capacitor within their control enclosure, install the appropriate capacitor at the provision available in the upper left corner of the CL-7 control enclosure as shown in Figure 84. Figure 81. Wire insertion tool. Orange lead "HS" position Figure 82. Removal of "HS" orange lead. Figure 84. Motor capacitor mounting provision. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 31 11. Place the capacitor terminal boot on to the blue/ black and black/white wires from the male connector assembly. 12. Push the blue/black and black/white wire terminals on to the capacitor terminals as shown in Figure 85. Capacitor terminal protector boot Figure 85. Motor capacitor connections. 13. Place the capacitor protective boot over the capacitor terminals and snap in place. 14. On the bottom left side of the CL-7 Control Panel a recessed switch, shown in Figure 86, is placed in the upward position for applications with Siemens, Howard and GE voltage regulators for the purpose of handling their Neutral light source signal. Figure 86. Neutral light source switch. 32 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Option 2: Multi-phase CL-7 control and enclosure for two to three single-phase voltage regulators 2. Remove the nuts, flat washers and gaskets from the cord receptacle ends as shown in Figure 76. 3. With the multi-phase control enclosure, depending on the application, two to three entry ways are selected for the cord receptacle ends. These entry ways are available on the top, side and bottom of the enclosure. These entry ways are identified as VR1, VR2, and VR3 with two of them shown in Figure 87. Introduction: This section provides instructions for the application of a multi-phase CL-7 control and its enclosure with a combination of two to three GE, Siemens or Howard voltage regulators. Additional steps are provided to supplement the instructions given in previous sections covering installations of QCA retrofit assembly kits within the original control enclosures. VR1 and VR2 cord receptacle entry ways Installation instructions: 1. The following instructions cover the interconnecting quick disconnect cords and associated components installed within the CL-7 multi-phase enclosure if not previously installed at the factory. Figure 87. Enclosure entry ways. 4. Locate gaskets around entry ways, outside of enclosure, while inserting the threaded portion of the cord receptacle ends. See Figure 77. 5. Fully insert the cord receptacle ends, placing the flat washers and nuts onto the threads within the enclosure as shown in Figure 78. Using a 1-3/4" open face wrench, tighten the nuts securing the cord receptacle ends to the control enclosure. 6. Select the identified CL-7 multi-phase control male connector assemblies matching the identified cord receptacle entry ways as shown in Figure 88. Cord receptacle end Male connector assembly Figure 88. Coordination of receptacle and connector assemblies. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 33 7. Align keyway of the enclosure male connector, shown in Figure 89, with the keyway of the cord receptacle end. 9. If the GE, Siemens or Howard voltage regulators placed their tap-changer motor capacitors within their control enclosures, install the appropriate capacitors using the provisions available in the upper left corner of the CL-7 control enclosure as shown in Figure 91. Match the capacitor provisions with the same identifier as used for the entry ways and male connector assemblies. Keyway Figure 89. Male connector assembly. Figure 91. Multi-phase motor capacitor provisions. 8. Push the male connector assemblies fully as far as possible onto the cord receptacle ends while tightening the knurled nuts. Repeat this push and tighten process until connections are fully tightened. See Figure 90. 10. Place the capacitor terminal boots on to the blue/ black and black/white wires from the male connector assemblies. 11. Push the blue/black and black/white wire terminals on to the respective capacitor terminals. Figure 90. Installed cord receptacle and connector assembly. 34 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 12. Place the capacitor protective boots over the capacitor terminals and snap them into place as shown in Figure 92. 14. Using the wire insertion tool supplied in the control enclosure, shown in Figure 81, remove the orange lead of the VR1 male connector assembly from the "HS" position on the left side of the terminal board located at the bottom of the rear panel, shown in Figure 94. "HS" Capacitor terminal protective boot Figure 92. Capacitor protective boots. Figure 94. "HS" position. 13. The next steps involve relocating the holding switch wiring for precise reaction with the Operations Counter circuitry of the GE, Siemens and Howard voltage regulators. Rewiring takes place with the large terminal board shown in Figure 93. 15. Relocate this orange lead of the VR1 male connector assembly to "5" position, twelve (12) positions to the left of the "HS" position as shown in Figure 95. Orange HS lead Figure 93. Multi-phase terminal board. Terminal #5 Figure 95. "5" position. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 35 16. Using the wire insertion tool remove the orange lead of the VR2 male connector assembly from the "HSB" position in the middle of the multi-phase terminal board, shown in Figure 96. 18. Using the wire insertion tool remove the orange lead of the VR3 male connector assembly from the "HSC" position in the middle of the multi-phase terminal board, shown in Figure 98. "HSC" position "HSB" position Figure 96. "HSB" position. 17. Relocate this orange lead of the VR2 male connector assembly to "J" position, adjacent to the right of the "5" position as shown in Figure 97. Figure 98. "HSC" position. 19. Relocate this orange lead of the VR3 male connector assembly to "BR" position, three (3) positions to the right of the "J" position as shown in Figure 99. "J" position "BR" position Figure 99. "BR" position. Figure 97. "J" position. 36 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com Multi-phase control panel setup and programming 20. For setting up the features and programming of the CL-7 control panel refer to Service Manual MN225003EN (S225-70-1), CL-7 Voltage Regulator Control Installation, Operation, and Maintenance Instructions. 21. On the bottom left side of the CL-7 multi-phase control panel, three recessed switches shown in Figure 100, are placed in their upward positions for applications with Siemens, Howard and GE voltage regulators for the purpose of handling their Neutral light source signal. The top switch is identified as VR1, the middle one is VR2, and the bottom one is VR3. VR1 VR2 VR3 Figure 100. Multi-phase Neutral light source switches. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 37 This page is intentionally left blank. 38 Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com This page is intentionally left blank. Quick connect assembly (QCA) 12-conductor retrofit kit installation instructions MN225002EN August 2014 www.cooperpower.com 39 ! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Power Systems Business 2300 Badger Drive Waukesha, WI 53188 United States cooperpower.com © 2014 Eaton All Rights Reserved Printed in USA Publication No. MN225002EN / August 2014 Eaton and Cooper Power Systems are valuable trademarks of Eaton, in the U.S. and other countries. You are not permitted to use these trademarks without the prior written consent of Eaton. All other trademarks are property of their respective owners. For Eaton's Cooper Power Systems CL-7 regulator control product information, call 1-877-277-4636 or visit: www.cooperpower.com.