Voltage Regulators Technical Data TD225005EN Effective XXX 2015 Supersedes 240-40 August 2012 COOPER POWER SERIES Communications Point Data Base for Communications Protocol IEC60870-5 For use with Eaton’s Cooper Power series CL-7 Voltage Regulator Control CL-7 IEC 60870-5 Device Profile Data Dictionary CL-7 IEC 60870-5 Map Points June 3, 2015 v2.00 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 2.00 Date 4/29/2013 6/3/2015 Description Initial Release Updates for Summer 2015 release This document references the "CL7 Default" point map available in the ProView NXG software. Point Numbering Convention IEC 60870-5 data points consist of 7 main types: single input, double input, measured values, single command, double command, floating point, and integrated totals. The numbering convention refers to the individual data points by prefixing their addresses so that when looking at a number for a given point the user would know which type of data point was being referenced. Data type Single input Double input Measured Value Single command Floating Point Base Address 1 4096 8192 12288 16384 Note: The CL-7 does not have any Double Input or Floating Point points defined. Page 1 Cover Page CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Single Inputs Base Address: 1 Description VR1 Bandwidth Low VR1 Bandwidth High VR1 Voltage Limiter Low VR1 Voltage Limiter High Voltage Reduction Active VR1 Auto Operation Blocking Status Blocked (Follows FC069) VR1 HMI LED Auto Tap Blocked ON VR1 System Power Direction Indeterminate VR1 System Power Direction Reverse VR1 Control Power Direction Reverse VR1 Blocking Relay Active VR1 HMI LED Neutral Position On VR1 HMI Switch Auto/Manual Auto HMI Switch Supervisory Off HMI LED Alarm On HMI LED Warning On HMI LED Diagnostic Error On VR1 Motor Trouble Tap To Neutral Active Soft Add-Amp Active AltConfigActive Configurable Logic Output from SCADA Tap to Neutral Activate Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate Configurable Logic User Defined LED 1 On Configurable Logic User Defined LED 2 On Configurable Logic User Defined LED 3 On Configurable Logic Point 01 to SCADA Configurable Logic Point 02 to SCADA Configurable Logic Point 03 to SCADA Configurable Logic Point 04 to SCADA Offset Hex Offset 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E Page 2 Single Inputs, Single Phase CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Measured Values Base Address: 8192 Description VR1 Load Voltage Secondary VR1 Load Voltage Primary VR1 Compensated Voltage Secondary VR1 Load Current Primary VR1 Source Voltage Secondary VR1 Source Voltage Primary VR1 Tap Position VR1 Percent Reg VR1 Power Factor VR1 KVA Load VR1 kW Load VR1 KVAR Load Frequency VR1 Harm Total Voltage Harmonics VR1 Harm Total Current Harmonics VR1 kWh Forward VR1 KWH Reverse VR1 KQH Forward VR1 KQH Reverse VR1 Operation Counter VR1 Load Current Real VR1 Load Current Reactive VR1 Phase Angle Voltage Reduction In Effect Active Configuration Active Adaptive Add Amp Level VR1 Operations Counter VR1 Operations 24HR Counter VR1 Operations 30DY Counter VR1 Operations Month Counter VR1 Operations Last Month Counter VR1 Operations Year Counter VR1 Operations Last Year Counter VR1 TPI Neutral Resynch Counter VR1 Lower to Neutral Sync Retry Counter VR1 Raise to Neutral Sync Retry Counter VR1 Taps Past 16R Counter VR1 Taps Past 16L Counter Measured/Incremental TPI Mismatch Count Offset Hex Offset Division Scale Factor Default Deadband Units 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 10 100 10 10 10 100 1 10 1000 10 10 10 100 10 10 100 100 100 100 1 10 10 1 10 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1000 1000 1000 1000 1000 1000 1000 10000 10000 10000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 1000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 Volts kVolts Volts Amps Volts kVolts -% -kVA kW kvar Hz % % kWHr kWHr kvarHr kvarHr -Amps Amps Degrees % % --------------- Page 3 Low Limit High Limit 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 Measured Values, Single Phase CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Measured Values Base Address: 8192 Description COM1 Rx Message Counter COM2 Rx Message Counter COM1 Tx Message Counter COM2 Tx Message Counter COM1 Message Error Counter COM2 Message Error Counter Offset Hex Offset Division Scale Factor Default Deadband Units 39 40 41 42 43 44 27 28 29 2A 2B 2C 1 1 1 1 1 1 10000 10000 10000 10000 10000 10000 ------- Page 4 Low Limit High Limit 10 10 10 10 10 10 10000 10000 10000 10000 10000 10000 Measured Values, Single Phase CL-7 IEC 60870-5 Device Profile Data Dictionary OUTPUT SUBSYSTEM Single Commands Base Address: 12288 Description VR1 Raise Tap * VR1 Lower Tap * Auto Block Enable VR1 Source Side Voltage Calculation Interval Operations Counters Enable VR1 Operations Counter Month Reset * VR1 Operations Counter Year Reset * VR1 Operations Counter 24HR Reset * VR1 Operations Counter 30DY Reset * VR1 Operations Counter Last Month Reset * VR1 Operations Counter Last Year Reset * VR1 TPI Neutral Mismatch Reset * VR1 Lower To Neutral sync Retry Count Reset * VR1 Raise To Neutral Sync Retry Count Reset * VR1 Taps Past 16L Counter Reset * VR1 Taps Past 16R Counter Reset * Rx COM1 Counter Reset * Rx COM2 Counter Reset * Tx COM1 Counter Reset * Tx COM2 Counter Reset * Message Error COM1 Counter Reset * Message Error COM2 Counter Reset * Reset Energy All * Reset All Demand Values * Sequence of Events Enable Data Profiler Enable Data Profiler Snapshot * Tap To Neutral Feature Enable PMT Mode A Enable PMT Mode B Enable PMT Mode A Test * PMT Mode B Test * Data Alarms Enable Status Alarms Enable VR1 Time On Tap Reset * Top Side Port LoopShare Enabled Bottom Side Port LoopShare Enabled Leader/Follower Enable Offset Hex Offset Supervisory Enable 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Page 5 Single Commands, Single Phase CL-7 IEC 60870-5 Device Profile Data Dictionary OUTPUT SUBSYSTEM Single Commands Base Address: 12288 Description Configurable Logic Output from SCADA Tap to Neutral Activate Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate Configurable Logic Output from SCADA 1 Configurable Logic Output from SCADA 2 Configurable Logic Output from SCADA 3 Configurable Logic Output from SCADA 4 HMI Remote Security Override Mode Offset Hex Offset Supervisory Enable 38 39 40 41 42 43 44 45 26 27 28 29 2A 2B 2C 2D 1 1 1 1 1 1 1 1 * Momentary/Self Resetting Page 6 Single Commands, Single Phase CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Single Inputs Base Address: 1 Description VR1 Bandwidth Low VR2 Bandwidth Low VR3 Bandwidth Low VR1 Bandwidth High VR2 Bandwidth High VR3 Bandwidth High VR1 Voltage Limiter Low VR2 Voltage Limiter Low VR3 Voltage Limiter Low VR1 Voltage Limiter High VR2 Voltage Limiter High VR3 Voltage Limiter High Voltage Reduction Active VR1 Auto Operation Blocking Status Blocked (Follows FC069) VR2 Auto Operation Blocking Status Blocked VR3 Auto Operation Blocking Status Blocked VR1 HMI LED Auto Tap Blocked ON VR2 HMI LED Auto Tap Blocked ON VR3 HMI LED Auto Tap Blocked ON VR1 System Power Direction Indeterminate VR2 System Power Direction Indeterminate VR3 System Power Direction Indeterminate VR1 System Power Direction Reverse VR2 System Power Direction Reverse VR3 System Power Direction Reverse VR1 Control Power Direction Reverse VR2 Control Power Direction VR3 Control Power Direction VR1 Blocking Relay Active VR1 HMI LED Neutral Position On VR2 HMI LED Neutral Position On VR3 HMI LED Neutral Position On VR1 HMI Switch Auto/Manual Auto VR2 HMI Switch Auto/Manual Auto VR3 HMI Switch Auto/Manual Auto HMI Switch Supervisory Off HMI LED Alarm On HMI LED Warning On HMI LED Diagnostic Error On VR1 Motor Trouble VR2 Motor Trouble VR3 Motor Trouble Tap To Neutral Active Soft Add-Amp Active AltConfigActive Offset Hex Offset 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C Page 7 Single Inputs, Multi Phase CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Single Inputs Base Address: 1 Description Configurable Logic Output from SCADA Tap to Neutral Activate Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate Configurable Logic User Defined LED 1 On Configurable Logic User Defined LED 2 On Configurable Logic User Defined LED 3 On Configurable Logic Point 01 to SCADA Configurable Logic Point 02 to SCADA Configurable Logic Point 03 to SCADA Configurable Logic Point 04 to SCADA Offset Hex Offset 45 46 47 48 49 50 51 52 53 54 2D 2E 2F 30 31 32 33 34 35 36 Page 8 Single Inputs, Multi Phase CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Measured Values Base Address: 8192 Description VR1 Load Voltage Secondary VR2 Load Voltage Secondary VR3 Load Voltage Secondary Average Load Voltage Secondary VR1 Load Voltage Primary VR2 Load Voltage Primary VR3 Load Voltage Primary Average Load Voltage Primary VR1 Compensated Voltage Secondary VR2 Compensated Voltage Secondary VR3 Compensated Voltage Secondary Average Compensated Voltage Secondary VR1 Load Current Primary VR2 Load Current Primary VR3 Load Current Primary Average Load Current Primary VR1 Source Voltage Secondary VR2 Source Voltage Secondary VR3 Source Voltage Secondary Average Source Voltage Secondary VR1 Source Voltage Primary VR2 Source Voltage Primary VR3 Source Voltage Primary Average Source Voltage Primary VR1 Tap Position VR2 Tap Position VR3 Tap Position Average Tap Position VR1 Percent Reg VR2 Percent Reg VR3 Percent Reg Average Percent Reg VR1 Power Factor VR2 Power Factor VR3 Power Factor Average Power Factor Regulator Tap Position Sync Count VR2 KVA Load VR3 KVA Load Total KVA Load VR1 kW Load VR2 kW Load VR3 kW Load Total kW Load VR1 KVAR Load Offset Hex Offset Division Scale Factor Default Deadband Units 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 10 10 10 10 100 100 100 100 10 10 10 10 10 10 10 10 10 10 10 10 100 100 100 100 1 1 1 1 10 10 10 10 1000 1000 1000 1000 1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1 10 10 10 10 10 10 10 1 1 1 10 10000 10 10 10 10 10 10 10 10 Volts Volts Volts Volts kVolts kVolts kVolts kVolts Volts Volts Volts Volts Amps Amps Amps Amps Volts Volts Volts Volts kVolts kVolts kVolts kVolts ----% % % % -----kVA kVA kVA kW kW kW kW kvar Page 9 Low Limit High Limit 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 Measured Values, Multi Phase CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Measured Values Base Address: 8192 Description VR2 KVAR Load VR3 KVAR Load Total KVAR Load Frequency VR1 Harm Total Voltage Harmonics VR2 Harm Total Voltage Harmonics VR3 Harm Total Voltage Harmonics VR1 Harm Total Current Harmonics VR2 Harm Total Current Harmonics VR3 Harm Total Current Harmonics VR1 kWh Forward VR2 kWh Forward VR3 kWh Forward Total kWh Forward VR1 KWH Reverse VR2 KWH Reverse VR3 KWH Reverse Total KWH Reverse VR1 KQH Forward VR2 KQH Forward VR3 KQH Forward Total KQH Forward VR1 KQH Reverse VR2 KQH Reverse VR3 KQH Reverse Total KQH Reverse VR1 Operation Counter VR2 Operation Counter VR3 Operation Counter HMI Last Self-Test Results VR1 Load Current Real VR2 Load Current Real VR3 Load Current Real Average Load Current Real VR1 Load Current Reactive VR2 Load Current Reactive VR3 Load Current Reactive Average Load Current Reactive VR1 Phase Angle VR2 Phase Angle VR3 Phase Angle Voltage Reduction In Effect Active Configuration Active Adaptive Add Amp Level VR1 Operations Counter VR2 Operations Counter Offset Hex Offset Division Scale Factor Default Deadband Units 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 2D 2E 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 53 54 55 56 57 58 59 5A 10 10 10 100 10 10 10 10 10 1 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 1 1 1 1 10 10 10 10 10 10 10 10 1 1 1 10 1 1 1 1 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 kvar kvar kvar Hz % % % % % % kWHr kWHr kWHr kW kWHr kWHr kWHr kW kvarHr kvarHr kvarHr kvar kvarHr kvarHr kvarHr kvar ----Amps Amps Amps Amps Amps Amps Amps Amps Degrees Degrees Degrees % % ---- Page 10 Low Limit High Limit 10 0 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 Measured Values, Multi Phase CL-7 IEC 60870-5 Device Profile Data Dictionary INPUT SUBSYSTEM Measured Values Base Address: 8192 Description VR3 Operations Counter VR1 Operations 24HR Counter VR2 Operations 24HR Counter VR3 Operations 24HR Counter VR1 Operations 30DY Counter VR2 Operations 30DY Counter VR3 Operations 30DY Counter VR1 Operations Month Counter VR2 Operations Month Counter VR3 Operations Month Counter VR1 Operations Last Month Counter VR2 Operations Last Month Counter VR3 Operations Last Month Counter VR1 Operations Year Counter VR2 Operations Year Counter VR3 Operations Year Counter VR1 Operations Last Year Counter VR2 Operations Last Year Counter VR3 Operations Last Year Counter VR1 TPI Neutral Resynch Counter VR2 TPI Neutral Resynch Counter VR3 TPI Neutral Resynch Counter VR1 Lower to Neutral Sync Retry Counter VR2 Lower to Neutral Sync Retry Counter VR3 Lower to Neutral Sync Retry Counter VR1 Raise to Neutral Sync Retry Counter VR2 Raise to Neutral Sync Retry Counter VR3 Raise to Neutral Sync Retry Counter VR1 Taps Past 16R Counter VR2 Taps Past 16R Counter VR3 Taps Past 16R Counter VR1 Taps Past 16L Counter VR2 Taps Past 16L Counter VR3 Taps Past 16L Counter Regulator Tap Position Sync Count COM1 Rx Message Counter COM2 Rx Message Counter COM1 Tx Message Counter COM2 Tx Message Counter COM1 Message Error Counter COM2 Message Error Counter Offset Hex Offset Division Scale Factor Default Deadband Units 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 5B 5C 5D 5E 5F 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F 80 81 82 83 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 10 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 ------------------------------------------ Page 11 Low Limit High Limit 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 Measured Values, Multi Phase CL-7 IEC 60870-5 Device Profile Data Dictionary OUTPUT SUBSYSTEM Single Commands Base Address: 12288 Description VR1 Raise Tap * VR2 Raise Tap * VR3 Raise Tap * VR1 Lower Tap * VR2 Lower Tap * VR3 Lower Tap * Auto Block Enable VR1 Source Side Voltage Calculation VR2 Source Side Voltage Calculation VR3 Source Side Voltage Calculation Interval Operations Counters Enable VR1 Operations Counter Month Reset * VR2 Operations Counter Month Reset * VR3 Operations Counter Month Reset * VR1 Operations Counter Year Reset * VR2 Operations Counter Year Reset * VR3 Operations Counter Year Reset * VR1 Operations Counter 24HR Reset * VR2 Operations Counter 24HR Reset * VR3 Operations Counter 24HR Reset * VR1 Operations Counter 30DY Reset * VR2 Operations Counter 30DY Reset * VR3 Operations Counter 30DY Reset * VR1 Operations Counter Last Month Reset * VR2 Operations Counter Last Month Reset * VR3 Operations Counter Last Month Reset * VR1 Operations Counter Last Year Reset * VR2 Operations Counter Last Year Reset * VR3 Operations Counter Last Year Reset * VR1 TPI Neutral Mismatch Reset * VR2 TPI Neutral Mismatch Reset * VR3 TPI Neutral Mismatch Reset * VR1 Lower To Neutral Sync Retry Count Reset * VR2 Lower To Neutral Sync retry Count Reset * VR3 Lower To Neutral Sync retry Count Reset * VR1 Raise To Neutral Sync Retry Count Reset * VR2 Raise To Neutral Sync Retry Count Reset * VR3 Raise To Neutral Sync Retry Count Reset * VR1 Taps Past 16L Counter Reset * VR2 Taps Past 16L Counter Reset * VR3 Taps Past 16L Counter Reset * VR1 Taps Past 16R Counter Reset * VR2 Taps Past 16R Counter Reset * VR3 Taps Past 16R Counter Reset * Rx COM1 Counter Reset * Offset Hex Offset Supervisory Enable 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Page 12 Single Commands, Multi Phase CL-7 IEC 60870-5 Device Profile Data Dictionary OUTPUT SUBSYSTEM Single Commands Base Address: 12288 Description Rx COM2 Counter Reset * Tx COM1 Counter Reset * Tx COM2 Counter Reset * Message Error COM1 Counter Reset * Message Error COM2 Counter Reset * Reset Energy All * Reset All Demand Values * Sequence of Events Enable Data Profiler Enable Data Profiler Snapshot * Tap To Neutral Feature Enable PMT Mode A Enable PMT Mode B Enable PMT Mode A Test * PMT Mode B Test * Data Alarms Enable Status Alarms Enable VR1 Time On Tap Reset * VR2 Time On Tap Reset * VR3 Time On Tap Reset * Top Side Port LoopShare Enabled Bottom Side Port LoopShare Enabled Leader/Follower Enable Configurable Logic Output from SCADA Tap to Neutral Activate Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate Configurable Logic Output from SCADA 1 Configurable Logic Output from SCADA 2 Configurable Logic Output from SCADA 3 Configurable Logic Output from SCADA 4 Configurable Logic Output from SCADA 5 Configurable Logic Output from SCADA 6 Configurable Logic Output from SCADA 7 Configurable Logic Output from SCADA 8 Offset Hex Offset Supervisory Enable 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 2D 2E 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Page 13 Single Commands, Multi Phase CL-7 IEC 60870-5 Device Profile Data Dictionary OUTPUT SUBSYSTEM Single Commands Base Address: 12288 Description AltConfig1 Auto Block Enable AltConfig1 Tap To Neutral Feature Enable AltConfig2 Auto Block Enable AltConfig2 Tap To Neutral Feature Enable AltConfig3 Auto Block Enable AltConfig3 Tap To Neutral Feature Enable ARL AltConfigTerminate ARLC Ready ARLC Activate Max Deviation Cancel Alt Mode * Test Battery * HMI Remote Security Override Mode Offset Hex Offset Supervisory Enable 79 80 81 82 83 84 85 86 87 88 89 90 4F 50 51 52 53 54 55 56 57 58 59 5A 1 1 1 1 1 1 1 1 1 1 1 1 * Momentary/Self Resetting Page 14 Single Commands, Multi Phase Technical Data TD225005EN Communications Point Data Base Effective June 2015 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries © 2015 Eaton All Rights Reserved Printed in USA Publication No. TD225005EN June 2015 Supersedes R225-70-32 (5/2013) Eaton is a registered trademark. All other trademarks are property of their respective owners. For Eaton's Cooper Power series CL-7 voltage regulator control information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.