115S Quick Setup Guide - Connections inst_115S_1.13.vsd © ELPRO Technologies. THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2 GROUPS A,B,C AND D, OR NONHAZARDOUS LOCATIONS ONLY. Connection to Modbus Master Set a unique Modbus slave address for each 115S connected to the Modbus Master Example shows address “01” Consult user manual for Modbus addresses ADDRESSING x1 x10 POWER B A Power Supply Modbus Master + 115S 115S 115S Power Connections: ‘+’ : Pos Supply (10.8 to 30 VDC**) ‘-’ : Neg Supply Power Modbus Earth - + Earth Power Modbus Modbus **Check rear label for operating voltages Earth Earth EARTH wiring minimum 2mm² - 14 AWG Up = terminated Down = un-terminated B A ON RS485 termination switch Modbus Master RS485 Termination switch up (terminated) or 120Ω Fitted across RS485 A B - + POWER B A Power Supply + E-Series Radio 115S B 115S A B 115S A, B: Connect RS485 (Modbus) A B Power Connections: Supply RS485 _ + Earth - + ‘+’ : Pos Supply (10.8 to 30 VDC**) ‘-’ : Neg Supply Power RS485 RS485 Power Power 115S-11: 300mA max 115S-12: 900mA max 115S-13: 900mA max Earth Battery Earth Earth Earth EARTH wiring minimum 2mm² - 14 AWG RS485 B A Up = terminated **Check rear label for operating voltages Down = un-terminated RS485 Termination switch up (terminated) RS485 Termination switch up (terminated) E-Series Module A B - + A, B: Connect RS485 (Elpro) ON RS485 Termination switch 115S 115S - Power and Modbus connector 115S A Address switches must be 00 for E-Series protocol Example shows address “00” Setup using ELPRO E-Series configuration utility. Ensure all earth connections are at the same potential. Ensure all earth connections are at the same potential. RS485 x1 x10 115S-11: 300mA max 115S-12: 900mA max 115S-13: 900mA max Power Earth ADDRESSING Connection to E-Series Radio 115S A B Power and RS485 connector 115S A B 115S A B RS485 Termination switch up (terminated) WARNING ‐ EXPLOSION HAZARD ‐ DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF IGNITABLE CONCENTRATIONS. WARNING ‐ EXPLOSION HAZARD ‐ SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2. © ELPRO Technologies inst_115S_1.13.vsd THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS 1 DIVISION 2 GROUPS A,B,C AND D, OR NONHAZARDOUS LOCATIONS ONLY. 115S-11 DIGITAL INPUTS 115S-12 Ensure correct DIP switch positions AND software configuration has been completed for each analogue input BEFORE connecting external signals to the 115S-12 module. 115S Module V+ V+ DIFFERENTIAL CURRENT INPUTS DIO1 Voltage free contact DIO2 115S-12 VGND Supply 115S-12 AOT2 AIN2 AIN2 V- + - AIN4 V- + Externally powered sensor DIFFERENTIAL VOLTAGE INPUTS + GND + Sensors with voltage signals AIN1 AIN2 AIN3 AOT1 V- - + AI- PLC GND VOLTAGE OUTPUT (Select using config software) PLC VOLTAGE INPUT 115S-13 ALS +24V AIN1 ALS +24V AIN2 AOT1 AIN4 AI AOT2 + GND AI+ ALS +24V 115S-12 Sensor with voltage signal - GND 115S-13 V- ALS +24V + - COM (Select using config software) (Select using DIP switches AND config software) 115S-12 _ + CURRENT SINK OUTPUT SINGLE ENDED VOLTAGE INPUTS (Select using DIP switches AND config software) PLC AI AOT1 AOT2 Max 30VDC 200mA GND -+ AIN1 GND DIO1 V- ALS +24V AIN3 DIGITAL OUTPUTS DC Load Loop powered sensor ALS +24V AIN1 Externally powered sensor DIO2 (Default configuration) (Default configuration) ALS +24V Loop powered sensor Power -+ CURRENT SOURCE OUTPUT SINGLE ENDED CURRENT INPUTS (Select using DIP switches AND config software) Transistor switch device 115S Module 115S-13 WARNING ! + COM GND V- V- V- GND - WARNING ‐ EXPLOSION HAZARD ‐ DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF IGNITABLE CONCENTRATIONS. WARNING ‐ EXPLOSION HAZARD ‐ SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.