W225-10022 June, 2010 Regulator Efficiency: Considerations for Design and Loss Evaluations Craig A. Colopy Global Technology Manager, Step-Voltage Regulator Products Cooper Power Systems 2300 Badger Drive Waukesha, WI 53188 www.cooperpower.com P: 877.CPS.INFO Cooper Power Systems is a valuable trademark of Cooper Industries in the U.S. and other countries. You are not permitted to use the Cooper Trademarks without the prior written consent of Cooper Industries. ©2010 Cooper Industries. All Rights Reserved. Table of Contents Introduction ...................................................................................................................2 Step-Voltage Regulator Types......................................................................................3 No-Load and Load Loss Profiles..................................................................................6 How Regulator Construction Affects Losses and Short Circuit Strength ............... 12 How to Evaluate Losses of Step-Voltage Regulators ............................................... 15 Obtaining and Applying A & B factors....................................................................... 17 June 25 2010 1 Introduction No-load and load losses are a real cost – Evaluation of losses in step-voltage regulators is increasingly a major consideration when evaluating competitive alternatives. A significant amount of focus is directed to the efficiencies of transformer related products. These efficiencies have a direct impact on the energy required to supply quality power to end users. The initial cost of a voltage regulator should not be the only evaluation point when comparing one voltage regulator manufacturer with another, as the initial price of a voltage regulator is not a true reflection of the total cost that will be realized over the life of the unit. Maintenance, installation and operation, technical support, dielectric strength, short circuit strength, and losses are just some of the areas that should be evaluated in addition to the first cost for a true measurement when comparing voltage regulator manufacturers’ offerings. This paper addresses one of those areas: loss evaluation. Loss evaluation formulas have existed for years for distribution transformers and for a limited amount of voltage regulators. These formulas have cost factors (A and B) for the no-load and load losses with the factor applied to the no-load value. Below is a simple example of a total ownership cost (TOC) evaluation. The ownership cost of a Cooper Power Systems (CPS) offering was significantly lower even though the first cost was higher. Exhibit A CPS Alternate Manufacturer First Cost $10,500 $10,000 (-5%) ILLUSTRATIVE EXAMPLE Cost of Losses Total Ownership Cost $9,000 $19,500 $11,250 (+25%) $21,250 (+9%) Losses are related to the quality of the design – Simply stated, poor designs typically lead to higher losses. Design efficiencies are directly related to values of no-load and load losses. Indirectly, loss levels can be used for comparing thermal capabilities and short circuit withstand strengths between competitive alternatives. Losses, thermal characteristics, and short circuit withstand strengths are all dependent on the active material content, internal impedance, and the types of bridging reactor and main core and coil constructions. Therefore, it is very important that commonly used design techniques and their implications on losses be fully understood if realistic and comparable evaluations are to be made. Of even greater importance is an appreciation of the design techniques that are used and to incorporate these designs techniques as part of the evaluation between competitive alternatives. June 25 2010 2 Step-Voltage Regulator Types Single-phase step-voltage regulators use reactive switching to regulate load voltage providing nominal ±10% regulation. This is accomplished with the use of 32 approximate 5/8% voltage steps. Basically, the step-voltage regulator is a tapped autotransformer. The secondary (series) winding is in series with the line, while the primary (shunt) winding is connected phase-to-neutral for 4-wire grounded systems and phase-to-phase for 3-wire ungrounded systems. The series winding connection to the shunt winding is by way of the reversing switch of the tap changer. A raise or lower mode is dependent on the polarity of that connection. The eight approximate 1¼% taps of the series winding and center tapped bridging reactor provide for the individual 5/8% incremental voltage adjustment. In all, there are 33 positions that include Neutral, sixteen lower positions (1L, 2L, 3L, 4L, etc.), and sixteen raise positions (1R, 2R, 3R, 4R, etc.). Voltage regulators are designed and manufactured using three basic types of construction dependent on the voltage and current ratings as well as the manufacturers’ and users’ preference. These are defined by the voltage regulator IEEE Standard C57.15 – 2009 as Type A, Type B, and Series Transformer. Type A step voltage regulators are used for a majority of substation applications. The tapped series winding is located on the load side of the shunt winding, and by adjusting those taps the output load voltage changes. The load current flows in the section(s) of series winding that is in the circuit. The current that flows in the shunt winding is dependent on the tap position that relates to this amount of series winding. The maximum amount of current that can flow in the shunt winding is approximately 10% of the series winding current that occurs at the 16 raise and 16 lower tap positions. With Type A construction (Figure 1), the core excitation varies between 90 to 110% of rated voltage due to the unregulated source supply voltage connected directly across the shunt (excitation) winding of the voltage regulator. A separate voltage transformer is used on the load side of the regulator to provide a voltage supply for the control and tap changer motor. The voltage supply for the control is used for establishing a reference voltage in which the actual load voltage is compared to for possible system voltage correction based on programmed control settings. The use of the tapped series winding in conjunction with the tap-changer reversing switch provides the Type A voltage regulator a ±10% voltage regulation range about the nominal rated voltage by operating in either a “raise” or “lower” mode. June 25 2010 3 Figure 1―Type A Step-Voltage Regulator Type B step-voltage regulators are predominately used for distribution lines outside of the substation and lateral circuits. The tapped series winding is located on the source side of the shunt (excitation) winding, and by adjusting those taps the output load voltage changes. The source side current that flows in the series winding is a sum of the rated load current plus the excitation current that flows in the shunt winding. The value of series winding current is dependent on the tap position with the maximum amount of current occurring at the 16 raise tap position. This value is approximately 110% of the rated load current. At the 16 lower tap position the value is approximately 90% of the rated current. The current that flows in the shunt winding is also dependent on tap position. The maximum amount of current that flows in the shunt winding is also at the 16 raise tap position in which the value is approximately 10.5% of rated load current. A lower amount of current, approximately 8.5% of rated load current, flows in the shunt winding at the 16 lower tap position. With Type B construction (Figure 2), the core excitation is established by the voltage and bandwidth settings due to the shunt winding connected directly across the regulated load voltage circuit. A utility winding in the main coil coupled with the shunt winding is used to provide a voltage supply for the control and tap changer motor. Type B construction due to the nature of the design cannot provide the same amount of maximum voltage regulation for the extreme raise and lower positions. Minimally, 10% voltage regulation is provided at the maximum raise position while the maximum lower position is approximately -8.5% voltage regulation. June 25 2010 4 Figure 2―Type B Step-Voltage Regulator A typical Series Transformer construction (Figure 3) is used for large substation applications in which the nominal load current value exceeds the high end tap changer’s maximum continuous (thermal) current rating. A series transformer is placed in series with the line in lieu of a tapped series winding. A tapped secondary winding of a shunt (excitation) transformer is connected to the tap changer. A division in load current occurs at the series transformer with a portion of it seen by the tap changer contacts. The voltage tapped off of the secondary is reflected back into series transformer for line voltage correction. The resulting voltage and current seen by the tap changer are within its design limitations. The unique designs of the series and shunt transformers and their location with respect to each other have a significant effect on the no-load and load loss values. The CPS Series Transformer design is similar in nature to a Type A design due to the fact the unregulated source voltage is applied across the primary of the shunt (excitation) transformer. A separate voltage transformer is used on the load side of the regulator to provide the voltage supply to the control and tap changer motor. Voltage regulation provided by Series Transformer-Type A construction is ±10%. Figure 3―Series Transformer Step-Voltage Regulator June 25 2010 5 No-Load and Load Loss Profiles Typical load loss profiles for the Type A, Type B, and Series Transformer designs are shown in Figures 4, 5, and 6 respectively. In each case the highest loss position is established as the 100% level with other position’s having losses at a percentage of this maximum loss value. Losses for all tap positions are based on rated current. Regulators are rated and cooled for the highest loss position at rated load. 100% % Load Loss of Max Loss 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 16R 14R 12R 10R 8R 6R 4R 2R N 2L 4L 6L 8L 10L 12L 14L 16L 8L 10L 12L 14L 16L Tap Position Figure 4―Type A Load Loss Profile 100% % Load Loss of Max Loss 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 16R 14R 12R 10R 8R 6R 4R 2R N 2L 4L 6L Tap Position Figure 5―Type B Load Loss Profile June 25 2010 6 100% % Load Loss of Max Loss 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 16R 14R 12R 10R 8R 6R 4R 2R N 2L 4L 6L 8L 10L 12L 14L 16L Tap Position Figure 6―Series Transformer Load Loss Profile The process of moving from one tap to an adjacent tap consists of closing on a circuit on the adjacent tap before opening the circuit on the previous tap. The tap changer movable contacts move through stationary taps alternating in eight bridging and eight non-bridging (symmetrical) positions. Figure 7 shows the two movable tap changer contacts on a symmetrical (even) position; the center tap of the reactor is at the same potential. Figure 7―Reactor Circuitry – Symmetrical (Even) Tap Position An asymmetrical position, as shown in Figure 8, is realized when one tap connection is open before transferring the load to the adjacent tap. Thus all load current flows through June 25 2010 7 one-half of the reactor, magnetizing the reactor, and introducing a reactance voltage drop in the circuit. This transfer takes around 25-30 milliseconds for completion. At a minimum, three current zero opportunities are required for arc extinction. Figure 8―Reactor Circuitry – Asymmetrical Position Figure 9 shows the movable contacts in a bridging (odd) position. Voltage change is one-half the 1¼% tap voltage of the series winding because of its center tap and movable contacts located on adjacent stationary contacts. Figure 9―Reactor Circuitry – Bridging (Odd) Tap Position A circulating current caused by the two contacts at different positions (reactor energized with 1¼% tap voltage) is limited by the reactive impedance of this circuit. Two opposing requirements must be considered in the design of the amount of reactance to which the value of the circulating current is set. First, the circulating current must not be excessive. June 25 2010 8 Second, the variation of reactance during the switching cycle should not be so large as to introduce undesirable fluctuations in the line voltage. The reactor has an iron core with gaps in the magnetic circuit to set this magnetizing circulating current value based on the applied tapped voltage. The value of this circulating current also has a very decided effect on tap changer’s arc interruption ability and contact life. During a tap change operation, voltage and magnetic flux within the reactor (preventive autotransformer) may shift rapidly as the moving contact leaves one stationary contact and closes on another stationary contact at a different voltage. In some cases the core will temporarily saturate when the contacts close, resulting in an inrush current through the reactor circuit. The magnitude and duration of this inrush is dependent upon the geometric structure of the reactor, the number of reactor turns used, the operating flux density of the reactor core, the X/R ratio of the system at the point of regulator application, the system source impedance at the point of regulator application and the timing of contact closure. Abnormal contact wear may result during contact closure depending on the frequency and amount of asymmetrical inrush current. The no-load loss is a result of the excitation of the main core and the reactor and is dependant on the tap position and the applied voltage. IEEE Standard C57.15 states the no-load loss values for the specified tap positions are to be based on rated voltage applied across the shunt winding. Factors that cause differences in the no-load losses of voltage regulators of the same design include variability in characteristics of the core steel, mechanical stresses induced by the manufacturing process, variation in gap structure and core joints, and variability of reactor core gaps. A graph of no-load losses per tap position is shown in Figure 10. In this case, the odd steps have the highest losses due to the reactor excited by the section of the series winding that it is bridged across as shown in Figure 9. The even steps only reflect the excitation of the main core; the reactor is not energized. The highest loss positions are established as the 100% level with other positions having losses as a percentage of this maximum loss value. % No Load Loss of Max Loss 100 90 80 16 L 14 L 12 L 10 L 8L 6L 4L 2L N 2R 4R 6R 8R 10 R 12 R 14 R 16 R 70 Tap Position Figure 10―No-Load Loss Profile without Equalizer Winding June 25 2010 9 An alternative for the voltage regulator design is the use of an equalizer winding. The equalizer winding is physically located in the outside section of the main coil and is inserted by way of the tap changer into a closed circuit with the reactor on symmetrical (even) steps, and with the reactor and a section of the series winding on bridging (odd) steps. The voltage of the equalizer winding is approximately half of the voltage of a section of the series winding or 5/8% of the nominal voltage. The connection of the equalizer winding into the reactor circuitry for bridging (odd) steps is set up so that the reactor sees only the difference in voltage between the series winding section and the equalizer winding. On symmetrical (even) steps, the voltage of the equalizer winding energizes the reactor. Figures 11 and 12 shows circuitry involving the equalizer winding and the reactor for symmetrical (even) and bridging (odd) steps. Figure 11―Equalizer Winding and Reactor Circuitry – Symmetrical (Even) Tap Position Figure 12―Equalizer Winding and Reactor Circuitry – Bridging (Odd) Tap Position June 25 2010 10 This equalizer winding reduces the maximum amount of voltage exciting the reactor to almost half, permitting the use of a smaller reactor and decreasing the amount of difference in no-load loss values between the bridging (odd) and symmetrical (even) tap positions. Equalizer windings are used in the majority of Cooper Power System’s available ratings. It has the additional benefit of reducing the interrupting load during a tap change resulting in minimized and balanced erosion for all contacts. The amount of reactor energization for all of the tap positions is dependent on the number of turns used in the equalizer winding and the series winding sections. % No Load Loss of Max Loss Any tap position, even or odd, can have the maximum value of no-load losses at the applied rated voltage. A graph of no-load losses per tap position of a typical design using equalizer windings is shown in Figure 13. Notice that for this example the even tap positions have the maximum value for the no-load losses and that a majority of the odd tap positions have the same value as the even tap positions. The difference between the minimum and maximum values is minimized resulting in a more even distribution of noload losses for the 33 tap positions. Each rating with an equalizer winding has a unique no-load loss pattern. 100 90 16 L 14 L 12 L 8L 10 L 6L 4L 2L N 2R 4R 6R 8R 10 R 12 R 14 R 16 R 80 Tap Position Figure 13―No-Load Loss Profile with Equalizer Winding June 25 2010 11 How Regulator Construction Affects Losses and Short Circuit Strength Cooper Power Systems uses its 55 years of experience in the design and application of voltage regulators to develop unique techniques in the construction and manufacturing process to address all of the life cycle related costs such as losses, dielectric withstand, short circuit withstand and tap changer contact life. A bridging reactor is required to maintain continuity during a tap change and to provide impedance for limiting the amount of current to be interrupted by the tap changer. The no-load losses and contact life are significantly affected by the amount of impedance used as well as by the type of reactor construction used. The reactor construction also affects the dielectric and short circuit strength of the voltage regulator. Figures 14 and 15 show the two types of reactor constructions available: shell type and core type. Figure 14―Shell Type Reactor Figure 15―Core Type Reactor June 25 2010 12 Cooper Power Systems uses a core type reactor construction to minimize the no-load loss value for all tap positions. A benefit of the core type reactor design is that the two coils are interlaced resulting in minimal impedance-to-load current flow and therefore minimal voltage drop. The use of these interlaced coils with aluminum strip winding also ensures superior short circuit withstand strength. Figure 16 shows a dismantled view of the CPS core type reactor. The 4-gap structure of the core keeps the no-load losses to a minimum due to the reduced thickness of the individual gaps which keeps fringing magnetic flux to a minimum. Shell type constructions (two cores, one coil) typically have one or two larger gaps maintaining the same amount reactive circulating current resulting in a greater fringing magnetic flux causing higher no-load losses and higher hot spots in the reactor windings. Figure 16―CPS Core Type Reactor In addition, CPS isolates their reactors from ground, as shown in Figure 17, resulting in superior dielectric strength and a smaller compact design for even lower no-load losses. Figure17―Ground Isolated Core Type Reactor Minimization of losses related to the main core and coil assembly is accomplished by pressing the sides of the main coil, as shown in Figure 18, during the bake out process. June 25 2010 13 Superior short circuit withstand strength is also a byproduct of this type of manufacturing process. All wasted space is removed which translates to a lean design that uses active material efficiently and keeps losses to a minimum. Figure 18―Hot Pressed Main Coil For Type A substation regulators, CPS uses a unique series-shunt-series coil construction, shown in Figure 18, placing the halves of the tapped aluminum strip series winding on the inside and outside of the centered shunt (excitation) winding. The results are lower stray losses minimizing the load loss values and greater short circuit strength due to improved coupling between windings and the use of an axial force deterrent winding (aluminum strip series winding) on the outside of the coil. The result of the unique CPS design techniques described above is a voltage regulator that has the lowest losses within the smallest package having superior short circuit withstand and dielectric strength. June 25 2010 14 How to Evaluate Losses of Step-Voltage Regulators When losses are evaluated, the tap positions shall be specified per IEEE Standard C57.15-2009, paragraph 5.8.3. Total losses of voltage regulators designed as Type A or Type B are the sum of no-load and load losses defined as follows: NLL = (NLLN + NLL1R)/2 where: NLL = Average No-Load Loss (W) NLLN = No-Load Loss in the “Neutral” position (W) NLL1R = No-Load Loss in the “1 raise” position (W) and: LL = (LL16R + LL15R + LL15L + LL16L)/4 LL = Average Load Loss (W) LL16R = Load Loss in the “16 raise” position (W) LL15R = Load Loss in the “15 raise” position (W) LL15L = Load Loss in the “15 lower” position (W) LL16L = Load Loss in the “16 lower” position (W) Total losses of voltage regulators designed with series transformer are the sum of noload and load losses defined as follows: NLL = (NLLN + NLL15R + NLL16R)/3 where: NLL = Average No-Load Loss (W) NLLN= No-Load Loss in the “Neutral” position (W) NLL15R= No-Load Loss in the “15 raise” position (W) NLL16R= No-Load Loss in the “16 raise” position (W) and: LL = (LL16R + LL15R + LL15L + LL16L)/4 LL = Average Load Loss (W) LL16R = Load Loss in the “16 raise” position (W) LL15R = Load Loss in the “15 raise” position (W) LL15L = Load Loss in the “15 lower” position (W) LL16L = Load Loss in the “16 lower” position (W) The load losses of a voltage regulator are losses resulting from rated load current carried by the voltage regulator at the specified tap positions. Load losses include I²R loss in the windings due to this rated current and stray loss due to eddy currents induced June 25 2010 15 by leakage flux in the windings, core clamps, tank walls, and other conducting parts. Load loss is also called winding or copper loss. No-load losses are those losses resulting from the excitation of the voltage regulator by applying rated voltage directly across the shunt winding at the specified tap positions. The no-load loss of a voltage regulator consists primarily of the iron loss in the voltage regulator main and reactor cores, and the I²R and stray loss due to reactive circulating current within the reactor and equalizer winding circuit. No-Load loss is a function of the magnitude, frequency, and waveform of the impressed voltage. No-load loss is sometimes referred to as core or excitation loss. CPS applies rated voltage up to 35 kV at rated frequency, 50 or 60 Hz, across the shunt (excitation) winding to ensure the noload values measured are accurate and that the least amount of calculation is involved for correction purposes. Total ownership cost (TOC) for a step-voltage regulator then is calculated in the same manner as for a transformer, using the no load and load loss, as follows: TOC = (KFC • FC) + (KNLL • NLL) + (KLL • LL) where: FC = first cost (price) KFC = factor applied against first cost KNLL = factor applied against the average no load loss, expressed in dollars per watt KLL = factor applied against the average load loss, expressed in dollars per watt IEEE C57.15 standard stipulates that the test of a voltage regulator shall be subject to the following tolerances: “the no-load losses of a voltage regulator shall not exceed the specified no-load losses by more than 10%, and the total losses of a voltage regulator shall not exceed the specified total losses by more than 6%. Failure to meet the loss tolerances shall not warrant immediate rejection but lead to consultation between purchaser and manufacturer about further investigation of possible causes and the consequences of the higher losses.” June 25 2010 16 Obtaining and Applying A & B factors Below is an example of a spreadsheet using typical economic values for obtaining and applying A and B factors to typical values of price and losses quoted in a contract. The initial cost of a voltage regulator is one of many parts of a true evaluation when comparing one voltage regulator manufacturer to another. One of those parts, loss evaluation, is a piece of the total cost realized over the life of a voltage regulator. It is a true reflection of design efficiency and of the techniques involved in the manufacturing process. June 25 2010 17