Quik-Spec Coordination Panelboard - Data Sheet ™ Contents

advertisement
Quik-Spec™ Coordination Panelboard - Data Sheet
600A - 1200A Fusible Panelboards
Contents
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Enclosure Types and Voltages/Systems . . . . . . . . . . . . . . . . . .3
Main, Sub-Feed & Feed Through Lug Specifications . . . . . . . .4
Neutral and Ground Assemblies . . . . . . . . . . . . . . . . . . . . . . .5
Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
Fuse & Disconnect Performance Data . . . . . . . . . . . . . . . . . .11
Low-Peak CUBEFuse Fuse Specifications . . . . . . . . . . . . . . .11
0212
BU-SB11645
Page 1 of 11
Data Sheet: 1171
Catalog Symbol: QSCP12
Description:
Panelboard Short-Circuit Current Ratings:
Fuseible panelboards for commercial/industrial branch or service entrance
applications on systems up through 600Vac.
The QSCP is specifically designed to address the NEC® Selective Coordination
Requirements for Emergency, Legally Required Standby, Healthcare Essential
Electrical and Critical Operation Power Systems (COPS) per NEC® 700.27,
701.18, 517.26 and 708.54. Not for applications requiring AFCI protected
circuits. The QSCP is configured to order for the application. To confirm
availability of options and constructions, contact your Cooper Bussmann
distributor.
Ratings:
Volts: 600Vac (or less), 125Vdc
Amps: 600, 800, 1200A
SCCR: 20kA or 100kA @125Vdc - See Panelboard
Short-Circuit Current Ratings table for AC ratings
Agency Information:
• UL 67 – Standard for panelboards
• UL 50/UL 50E – Enclosures for electrical equipment
• CSA 22.2, No. 29-M1989 – Panelboards and enclosed panelboards
• UL Listed, Class CTL panelboard (meets 2002 NEC® 408.15 limit of
42 overcurrent devices per panel)
• U.B.C. and C.B.C. Seismic Qualified, and I.B.C. Approved
Main Options:
• Main Lug Only (MLO)
Branch Disconnect Options:
• 1-, 2- and 3-Pole 15, 20, 30, 40, 50, 60, 70, 90, 100, 200, 400
and 600A rejecting branch disconnects (see table for details).
Branch ampacity on 125Vdc panels limited to CCPB 80A or less.
Neutral Options:
• Unbonded & Bonded 600, 800, 1200, 1600 and 2400A
Ground Options:
• Isolated & Non-isolated
Enclosures:
• NEMA 1
Spare Fuse Compartment:
• Standard on all models
CCPB Horsepower Ratings:
CCPB Disconnect
CCPB-(Poles)-15CF
CCPB-(Poles)-20CF
CCPB-(Poles)-30CF
CCPB-(Poles)-40CF
CCPB-(Poles)-50CF
CCPB-(Poles)-60CF
CCPB-(Poles)-70CF
CCPB-(Poles)-90CF
CCPB-(Poles)-100CF
CFD200J03
CFD400J03
CFD600J03
0212
BU-SB11645
Amp
Rating
15
20
30
40
50
60
70
80
100
200
400
600
120
0.5
0.75
1.5
2
3
3
3
5
5
–
–
–
Hp Rating @ Vac
240
480
3
5
3
7.5
5
15
7.5
20
7.5
20
7.5
20
15
30
20
40
20
50
60
125
125
250
200
400
600
7.5
10
10
10
10
10
40
50
50
150
350
500
Panelboard Short-Circuit Current Ratings
AC Main Options
DC
Main
Main
Lug Only
Lug Only
SCCR
(MLO)*
(MLO)*
High
200kA
100kA
Std.
50kA
20kA
* For panelboards with subfeed main lugs, or panelboards with
optional feed-through lugs, Class J, T or R fuses are required
upstream – max amps = panel amps.
Branch Disconnects:
Fuse
Max
Time-Delay
Branch* Part
Amp
CCPB
Non-Indicating
Number
Poles Range Ampacity
Fuses
CCPB-1-15CF
1
TCF1RN, TCF3RN,
CCPB-2-15CF
2
1-15
15
TCF6RN, TCF10RN,
CCPB-3-15CF
3
TCF15RN
CCPB-1-20CF
1
1
⁄2RN,
TCF17CCPB-2-20CF
2
171⁄2-20
20
TCF20RN
CCPB-3-20CF
3
CCPB-1-30CF
1
TCF25RN,
CCPB-2-30CF
2
25-30
30
TCF30RN
CCPB-3-30CF
3
CCPB-1-40CF
1
TCF35RN,
CCPB-2-40CF
2
35-40
40
TCF40RN
CCPB-3-40CF
3
CCPB-1-50CF
1
TCF45RN,
CCPB-2-50CF
2
45-50
50
TCF50RN
CCPB-3-50CF
3
CCPB-1-60CF
1
CCPB-2-60CF
2
60
60
TCF60RN
CCPB-3-60CF
3
CCPB-1-70CF
1
CCPB-2-70CF
2
70
70
TCF70RN
CCPB-3-70CF
3
CCPB-1-90CF
1
TCF80RN
CCPB-2-90CF
2
80-90
90
TCF90RN
CCPB-3-90CF
3
CCPB-1-100CF 1
CCPB-2-100CF 2
100
100
TCF100RN
CCPB-3-100CF 3
LPJ-110SP, LPJ-125SP,
CFD200J03
3*** 110-200
200
LPJ-150SP, LPJ-175SP,
LPJ-200SP
LPJ-225SP, LPJ-250SP,
CFD400J03
3*** 225-400
400
LPJ-300SP, LPJ-350SP,
LPJ-400SP
LPJ-450SP, LPJ-500SP,
CFD600J03
3*** 450-600
600
LPJ-600SP
Time-Delay
Indicating
Fuses**
TCF6
TCF10,
TCF15
Fast-Acting
Non-Indicating
Fuses
FCF1RN, FCF3RN,
FCF6RN, FCF10RN,
FCF15RN
TCF17-1⁄2,
TCF20
FCF20
TCF25,
TCF30
FCF25RN,
FCF30RN
TCF35,
TCF40
FCF35RN,
FCF40RN
TCF45,
TCF50
FCF45RN,
FCF50RN
TCF60
FCF60RN
TCF70
FCF70RN
TCF80
TCF90
FCF80RN
FCF90RN
TCF100
FCF100RN
LPJ-110SPI, LPJ-125SPI,
LPJ-150SPI, LPJ-175SPI,
LPJ-200SPI
LPJ-225SPI, LPJ-250SPI,
LPJ-300SPI, LPJ-350SPI,
LPJ-200SPI
LPJ-450SPI, LPJ-500SPI,
LPJ-600SPI
JKS-110, JKS-125,
JKS-150, JKS-175,
JKS-200
JKS-225, JKS-250,
JKS-300, JKS-350,
JKS-400
JKS-450, JKS-500,
JKS-600
*CCPB disconnect can accept CUBEFuses with amp ratings less than or equal to the amp rating of the CCPB disconnect.
**Correct fit with CCPB disconnect requires time-delay CUBEFuses with date code R38 or later.
*** 3-Pole switch used for 1 and 2-pole applications
Page 2 of 11
Data Sheet: 1171
Enclosure Types
AC & DC Voltages & System Types
NEMA 1
AC Voltages
DC Voltage
1-Phase, 2 Wire
• 120V 1-Phase, 2 Wire
• 240V 1-Phase, 2 Wire
1-Phase, 2 Wire
•
•
•
•
Floor mount
Galvanized steel with blank end walls
Box sizes: 27” W x 15” D x 65”/ 38˝ W x 15˝ D x 65˝ or 89˝ H
Enclosure and chassis mounting instructions are found in literature
supplied with unit
• Chassis mounts directly onto studs in the enclosure
• Trim finished with gray powder coat paint over phosphatized steel
(ANSI 61)
• Circuit directory card is located on the inside of the door
• 125Vdc, 2 Wire
(Up to 125Vdc, MLO option
only, CCPB 80A or less)
1-Phase, 3 Wire
• 120/240V 1-Phase, 3 Wire
N
1-Phase, 2 Wire, Wye
• 277V 1-Phase, 2 Wire
A
+125Vdc
B
N
C
1-Phase, 2 Wire, Delta
• 480V 1-Phase, 2 Wire
A
B
C
1-Phase, 3 Wire, Delta
• 240/480V 1-Phase, 3 Wire
A
N
C
3-Phase, 4 Wire, Wye
• 208Y/120V 3-Phase, 4 Wire
• 480Y/277V 3-Phase, 4 Wire
• 600Y/347V 3-Phase, 4 Wire
B
A
B
N
C
3-Phase, 4 Wire, Delta
• 240/120V 3-Phase, 4 Wire
• 480/240V 3-Phase, 4 Wire
A
B
N
C
3-Phase, 3 Wire, Delta
• 240V 3-Phase, 3 Wire
• 480V 3-Phase, 3 Wire
• 600V 3-Phase, 3 Wire
• 240V 3-Phase, 3 Wire, Grounded B
• 480V 3-Phase, 3 Wire, Grounded B
• 600V 3-Phase, 3 Wire, Grounded B
1-Phase, 3 Wire, Wye
• 208Y/120V 1-Phase, 3 Wire
• 480Y/277V 1-Phase, 3 Wire
A
B
C
A
B
N
Busing
C
Tin-plated copper with sufficient cross section to meet UL 67 temperature rise
requirements.
Distributed 1- & 3-Phase Busing
All CCPB branch disconnects can be mounted in any branch circuit position.
Single-Phase
0212
BU-SB11645
Page 3 of 11
Three-Phase
Data Sheet: 1171
600 Amp Main Lugs
800-1200 Amp Main Lugs
Main Mechanical Lugs
Main Barrier Cover Open
Main Mechanical Lugs
Wire Range / Torque Lb-In (N•m)
• 300kcmil-1AWG / 375 (42)
• 2-6AWG / 275 (31)
Wire Rating: 60/75°C, Cu-Al
Wire Range / Torque Lb-In (N•m)
• 600kcmil-4AWG / 500 (56)
Wire Rating: 60/75°C, Cu-Al
Main Sub-Feed Mechanical Lugs
Main Barrier Cover Open
Wire Range / Torque Lb-In (N•m)
• 600kcmil-2AWG/375(42)
Wire Rating: 60/75°C, Cu-Al
Main Sub-Feed Mechanical Lugs
Wire Range / Torque Lb-In (N•m)
• 300kcmil - 6AWG / 275 (31)
Wire Rating: 60/75°C, Cu-Al
Main Compression (Crimp) Lugs*
Main Barrier Cover Open
Wire Range
• 600-250kcmil
Wire Rating: 60/75°C, Cu-Al
Main Compression (Crimp) Lugs*
Wire Range
• 300kcmil-4AWG
Wire Rating: 60/75°C, Cu-Al
Feed-Through Lugs
Compression, mechanical and double (sub-feed) lugs are all
available as feed-through lugs. Lug ampacity ratings will be
based upon panelboard ampacity rating.
Main Mechanical Lugs
Main Sub-Feed Mechanical Lugs
Main Compression (Crimp) Lugs*
* Versa-Crimp® VC-6 crimp tool recommended for wire crimping.
0212
BU-SB11645
Page 4 of 11
Data Sheet: 1171
Neutral Assemblies
600A Unbonded
Wire Range / Torque Lb-In (N•m)
• Main Terminal 600kcmil-2 AWG / 275 (31)
• Branch Connections - See table below
Wire Rating: 60/75°C, Cu-Al
Bar Material: Copper, Tin-plated
Lug Material: Aluminum, Tin-plated
600A Bonded
Wire Range / Torque Lb-In (N•m)
• Main Terminal 600kcmil-2 AWG / 275 (31)
• Branch Connections - See table below
Wire Rating: 60/75°C, Cu-Al
Bar Material: Copper, Tin-plated
Lug Material: Aluminum, Tin-plated
Ground Assemblies
Isolated / Non-isolated
Wire Range / Torque Lb-In (N•m)
• Main Terminal 600kcmil-2 AWG / 275 (31)
• Branch Connections - See table below
Wire Rating: 60/75°C, Cu-Al
Bar Material: Copper, Tin-plated
Lug Material: Aluminum, Tin-plated
Ground and Neutral Bars Connection Wire Torques
Wire*
AWG
14 AWG - 4 AWG
3 AWG - 2/0 AWG
6 AWG - 1/0 AWG
2/0 AWG - 350 kcmil
4 AWG - 3/0 AWG
4/0 AWG
250 kcmil - 600 kcmil
2 AWG - 3/0 AWG
4/0 AWG
250 kcmil - 600 kcmil
Torque
Max. No. Wires Per Opening
Lb-In (N•m)
Neut.
GND
≤100A Branch
20-35 (2.3-3.9)
2
2
35-80 (4.5-9.0)
1
1
110 - 200A Branch
35-200 (3.9-22.6)
2
2
200-375 (22.6-42.0)
1
1
225 - 400A Branch
35-200 (3.9-22.6)
2
2
200 (22.6)
1
1
275-500 (31.0-56.5)
1
1
450 - 600A Branch
35-200 (3.9-22.6)
2
2
200 (22.6)
1
1
275-500 (31.0-56.5)
1
1
*60/75ºC, Cu-Al.
0212
BU-SB11645
Page 5 of 11
Data Sheet: 1171
GROUND
Three-Phase, 3 Wire
Main Lug Only
GROUND
GROUND
NEUTRAL
Single-Phase, 22Wire
Single-Phase,
Wire
Main
Lug
Only
Main Lug Only
Three-Phase, 4 Wire
Main Lug Only
Single-Phase, 3 Wire
Main Lug Only
0212
BU-SB11645
NEUTRAL
NEUTRAL
GROUND
Typical Wiring
Page 6 of 11
Data Sheet: 1171
NEMA 1 Enclosures & Interior
0212
BU-SB11645
Page 7 of 11
Data Sheet: 1171
NEMA 1 Enclosure Dimensions
Panel Ampacity
Base Unit
600A
800A
1200A
0212
BU-SB11645
Branch Configuration
(18) 1-100A
(18) 1-100A + 200A single
(18) 1-100A + 200A twin
200A single + 200A single
200A single + 200A twin
200A twin + 200A twin
(2) 300A single
(18) 1-100A + 200A single
(18) 1-100A + 200A twin
(2) 200A twin
(18) 1-100A + 400A single
200A twin + 400A single
(2) 400A single
(18) 1-100A + 600A single
(3) 200A twin
200A twin + 600A single
(2) 200A twin + 400A single
(3) 400A single
600A single + 400A single + 200A single
600A single + 400A single + 200A twin
(2) 600A single
H
65
Dimensions
W
D
27
15
65
38
15
89
38
15
65
38
15
89
38
15
89
38
15
102
38
15
Page 8 of 11
Data Sheet: 1171
Quik-Spec Coordination Panelboard Replacement Parts
See list on following page for part numbers.
C
G
F
A
I
B
D
E
0212
BU-SB11645
Page 9 of 11
Data Sheet: 1171
Replacement Parts
A & B - Main Devices and Feed-Through Lugs
2A2575-1
2A2575-2
2A2575-3
2A2575-4
2A2575-5
2A2575-6
2A2575-7
2A2575-8
2A2575-9
2A2575-10
2A2575-11
2A2575-12
2A2575-13
2A2575-14
2A2575-15
2A2575-16
2A2575-17
2A2575-18
Kit, compression lug 3 phase 600A
Kit, mechanical lug 3 phase 600A
Kit, double/sub-feed lug 3 phase 600A
Kit, compression lug 1 phase, 3 wire 600A
Kit, mechanical lug 1 phase, 3 wire 600A
Kit, double/sub-feed lug 1 phase, 3 wire 600A
Kit, compression lug 1 phase, 2 wire 600A
Kit, mechanical lug 1 phase, 2 wire 600A
Kit, double/sub-feed lug 1 phase, 2 wire 600A
Kit, compression lug 3 phase 800A & 1200A
Kit, mechanical lug 3 phase 800A & 1200A
Kit, double/sub-feed lug 3 phase 800A & 1200A
Kit, compression lug 1 phase, 3 wire 800A & 1200A
Kit, mechanical lug 1 phase, 3 wire 800A & 1200A
Kit, double/sub-feed lug 1 phase, 3 wire 800A & 1200A
Kit, compression lug 1 phase, 2 wire 800A & 1200A
Kit, mechanical lug 1 phase, 2 wire 800A & 1200A
Kit, double/sub-feed lug 1 phase, 2 wire 800A & 1200A
C - Ground Assemblies
2A2576-1
2A2576-2
2A2576-3
2A2576-4
2A2576-5
2A2576-6
2A2576-7
2A2576-8
2A2576-9
2A2576-10
2A2576-11
2A2576-12
Kit, ground non-isolated 600A
Kit, ground isolated 600A
Kit, ground non-isolated 800A
Kit, ground isolated 800A
Kit, ground non-isolated 800A
Kit, ground isolated 800A
Kit, ground non-isolated 800A
Kit, ground isolated 800A
Kit, ground non-isolated 1200A
Kit, ground isolated 1200A
Kit, ground non-isolated 1200A
Kit, ground isolated 1200A
D - Neutral Assemblies
2A2577-1
2A2577-2
2A2577-3
2A2577-4
2A2577-5
2A2577-6
2A2577-7
2A2577-8
2A2577-9
2A2577-10
2A2577-11
2A2577-12
2A2577-13
2A2577-14
2A2577-15
2A2577-16
2A2577-17
2A2577-18
2A2577-19
2A2577-20
0212
Kit, neutral unbonded 600A for 600A panel
Kit, neutral bonded 600A for 600A panel
Kit, neutral unbonded 1200A for 600A panel
Kit, neutral bonded 1200A for 600A panel
Kit, neutral unbonded 800A for 800A panel
Kit, neutral bonded 800A for 800A panel
Kit, neutral unbonded 1600A for 800A panel
Kit, neutral bonded 1600A for 800A panel
Kit, neutral unbonded 800A for 800A panel
Kit, neutral bonded 800A for 800A panel
Kit, neutral unbonded 1600A for 800A panel
Kit, neutral bonded 1600A for 800A panel
Kit, neutral unbonded 800A for 800A panel
Kit, neutral bonded 800A for 800A panel
Kit, neutral unbonded 1600A for 800A panel
Kit, neutral bonded 1600A for 800A panel
Kit, neutral unbonded 1200A for 1200A panel
Kit, neutral bonded 1200A for 1200A panel
Kit, neutral unbonded 2400A for 1200A panel
Kit, neutral bonded 2400A for 1200A panel
BU-SB11645
D - Neutral Assemblies - (continued)
2A2577-21
2A2577-22
2A2577-23
2A2577-24
2A2577-25
2A2577-26
2A2577-27
2A2577-28
Kit, neutral unbonded 1200A for 1200A panel
Kit, neutral bonded 1200A for 1200A panel
Kit, neutral unbonded 2400A for 1200A panel
Kit, neutral bonded 2400A for 1200A panel
Kit, neutral unbonded 600A for 600A panel
Kit, neutral bonded 600A for 600A panel
Kit, neutral unbonded 1200A for 600A panel
Kit, neutral bonded 1200A for 600A panel
E - Enclosures (Box only, does not include doors)
2A2400-1
2A2400-2
2A2400-3
2A2400-4
NEMA 1, 38x65x15
NEMA 1, 38x89x15
NEMA 1, 27x65x15
NEMA 1, 38x102x15
F - Dead Fronts - Branch Enclosure (1-100A Branches)
2A2578-1
2A2578-2
Kit, branch enclosure 38" wide panels
Kit, branch enclosure 27" wide panels
G - Latch for Spare Fuse Compartment
2A1910-5
Kit, Spare Fuse Compartment Latch
Lockout/Tagout Devices
2A1912-1
2A1912-3
Kit, lockout 200A - 400A branch
Kit, lockout 1-100A branch
Miscellaneous
2A1914
2A1915
2A1917-2
2A1917-3
2A1918-1
2A1918-2
2A1919
2A1961-1
Page 10 of 11
Kit, circuit directory card and sleeve
Kit, circuit number and fuse rating labels (1-100A
branches)
Kit, CCPB hardware (10 screws)
Kit, panelboard hardware
Kit, branch filler plates 1-60A
Kit, branch filler plates 70-100A
Kit, touch up paint
Kit, Spare Fuse Compartment TCF1-100A
Data Sheet: 1171
Branch Disconnects and Fuse Replacement Parts
Fuse & Disconnect Performance Data
I - CCPB Branch Disconnects
For details and specifications, access the following data sheets online at
www.cooperbussmann.com/DatasheetsEle.
Poles
1-Pole
2-Pole
3-Pole
3-Pole
3-Pole
3-Pole
Applicable Fuse Ampacities
15A, 20A, 30A, 40A,
50A, 60A, 70A, 90A, 100A
110A, 125A, 150A, 175A,
200A
225A, 250A, 300A, 250A,
400A
450A, 500A, 600A
Part Number
CCPB-1-(amp)CF
CCPB-2-(amp)CF
CCPB-3-(amp)CF
CFD200J03*
CFD400J03*
CFD600J03*
*3-pole switch for 1- and 2-pole applications
Product
Low-Peak Time-Delay CUBEFuse
Fast-Acting CUBEFuse
Low-Peak LPJ-_SPI Class J fuses
Limitron JKS Class J Fuses
CCPB Branch Disconnect
Data Sheet
Number
9000
2147
1063
1026 & 1027
1161
Additional Reference
Additional information is available online at:
• Selective Coordination (www.cooperbussmann.com/SelectiveCoordination)
J - Branch Fuses for CCPB Disconnects
For CCPB** Part Number
CCPB-(# of Poles)-15CF
CCPB-(# of Poles)-20CF
CCPB-(# of Poles)-30CF
CCPB-(# of Poles)-40CF
CCPB-(# of Poles)-50CF
CCPB-(# of Poles)-60CF
CCPB-(# of Poles)-70CF
CCPB-(# of Poles)-90CF
CCPB-(# of Poles)-100CF
Non-Indicating
Indicating*
Fast-Acting
Time-Delay
Time-Delay
Non-Indicating
TCF(amps)RN
TCF(amps)
FCF(amps)RN
TCF1RN, TCF3RN,
TCF6
FCF1RN, FCF3RN,
TCF6RN, TCF10RN
TCF10
FCF6RN, FCF10RN
TCF15RN
TCF15
FCF15RN
TCF17-1/2RN
TCF17-1/2
FCF20RN
TCF20RN
TCF20
TCF25RN
TCF25
FCF25RN
TCF30RN
TCF30
FCF30RN
TCF35RN
TCF35
FCF35RN
TCF40RN
TCF40
FCF40RN
TCF45RN
TCF45
FCF45RN
TCF50RN
TCF50
FCF50RN
TCF60RN
TCF60
FCF60RN
TCF70RN
TCF70
FCF70RN
TCF80RN
TCF80
FCF80RN
TCF90RN
TCF90
FCF90RN
TCF100RN
TCF100
FCF100RN
J - Branch Fuses for Class J Disconnects
Class J Disconnect
Part Number
CFD200J03*
CFD400J03*
CFD600J03*
Non-Indicating
Time-Delay
LPJ-110SP,
LPJ-125SP,
LPJ-150SP.
LPJ-175SP,
LPJ-200SP
LPJ-225SP,
LPJ-250SP,
LPJ-300SP.
LPJ-350SP,
LPJ-400SP
LPJ-450SP,
LPJ-500SP,
LPJ-600SP.
Indicating
Time-Delay
LPJ-110SPI,
LPJ-125SPI,
LPJ-150SPI,
LPJ-175SPI,
LPJ-200SPI
LPJ-225SPI,
LPJ-250SPI,
LPJ-300SPI,
LPJ-350SPI,
LPJ-400SPI
LPJ-450SPI,
LPJ-500SPI,
LPJ-600SPI,
Non-Indicating
Fast-Acting
JKS-110,
JKS-125,
JKS-150,
JKS-175,
JKS-200
JKS-225,
JKS-250,
JKS-300,
JKS-350,
JKS-400
JKS-450,
JKS-500,
JKS-600,
*3-Pole switch used for 1- and 2-pole applications.
* Correct fit with CCPB disconnect requires indicating CUBEFuse with date code R38 or later.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document
are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user
with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit
distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin.
Once a product has been selected, it should be tested by the user in all possible applications.
0212
BU-SB11645
Page 11 of 11
Data Sheet: 1171
Download