7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com WESTGATE ELEMENTARY SCHOOL REPLACEMENT 2514 W. 4th Ave. Kennewick, WA 99336 ADDENDUM No. 3 April 6, 2016 GENERAL INFORMATION ITEM DETAIL/DESCRIPTION 1 Window coverings are called out in the specifications. Window coverings on elevation drawings are shown as graphic representation only. Quantities should be taken from the specifications and door schedule. 2 Geotechnical Engineering Evaluation: Footing drains are not required for this project, contrary to the recommendations in the Geotechnical report. IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH DESCRIPTION 3 05 4000 2.01A ADD approved manufacturer Scafco: www.scafco.com. 4 07 4213 2.01A ADD manufacturer/product: AEP Span TW-12: www.aepspan.com. 5 07 4213 2.02C ADD manufacturer/product: AEP Span Prestige Series, 12: No Reveal - Flat Pan: www.aepspan.com. 6 07 4214 2.01B ADD approved manufacturer Metposite Flat Metal Wall Systems, Product STD-DRI-RS with 2" Poly-Iso: www.metposite.com. 7 07 5400 2.04A.1 ADD approved manufacturer/product: USG Securock GlassMat Roof Board: www.usg.com. 8 09 6429 2.01A ADD approved manufacturer/product: Action Floor Systems; Product Action Aero NR: www.actionfloors.com. 9 09 6800 2.01 ADD approved manufacturer: Mannington Commercial, Raffia: www.manningtoncommercial.com. (Contingent on final approval of samples) 10 09 6813 2.01 ADD approved manufacturer: Mannington Commercial, Raffia: www.manningtoncommercial.com. (Contingent on final approval of samples) Addendum #3 Page 1 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH 11 09 9123 2.03D DESCRIPTION REVISE portion to read: Paint CI-TR-2S.....2 Coats. 12 09 9123 3.06 Add paragraph I to read: I. Cementitious wood fiber plank acoustical treatment: WI-OP2DF. 13 09 9123 3.06A ADD paragraphs to read: 2. Interior Concrete Floors: CI-OP-4E. 3. Interior CMU Walls: CI-TR-2S 14 09 9123 3.06B.2 REVISE to read: Interior Walls: GI-OP-3L, eggshell. 15 10 1400 2.07A REVISE paragraph 1 to read: 1. Metal: Aluminum casting or flat cut. 16 10 1400 2.07A ADD paragraph 6 to read: 6. Thickness: 3/8 inch. 17 10 2113.19 2.02A ADD subparagraph to read: 1. Texture: Hammered; Color: To be chosen from manufacturer's full range. 18 10 2226.33 2.02A.1 REVISE a to read: a. Vinyl coated fabric VWC-1, as specified in Section 09 7200. 19 10 2226.33 2.03B.1 REVISE 1 to read: 1. Vinyl coated fabric VWC-1, as specified in Section 09 7200. 20 10 2800 2.04D.2 REVISE subparagraph b to read: b. Classrooms: 2'-0" x 2'-0" mirrors, mounted above sinks. Verify location with Owner. 21 ADD paragraph 3.04 to read: 10 5100 3.04 SCHEDULES: A. Custodial Office 135B: One double tier. B. Staff Lounge 103: Three, double-tier. C. Kitchen 119: Two, double-tier. 22 11 3100 2.01B ADD paragraph 6 to read: 6. Size: 32 inch maximum width; confirm dimensions with casework. Addendum #3 Page 2 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH 23 11 3100 2.01C DESCRIPTION ADD paragraph 6 to read: 6. Size: 34 inch maximum width; confirm dimensions with casework. 24 11 3100 2.01D.2 REVISE to read: 2. Size: To fit under typical 36 inch high countertop; 24 inch maximum width; verify with casework. 25 11 3100 2.02B.1 & C.1 REVISE paragraph 1 to read: 1. Compact, 27 inch width, maximum. 26 11 5100 2.03B DELETE paragraph B. 27 11 5100 2.03C REVISE paragraph C to read: C. Unit Sizes: 1. Shelf Depths: 9 inches nominal for single-faced units, 18 inches nominal for double-faced units. 2. Unit Heights: 43 inches high with 2 adjustable shelves (plus fixed base shelf). 3. Unit Lengths: a. 3 units at 90 inches (includes 2, 9 inch deep x 18 inch wide end units and 2, 36 inch wide units). b. 1 unit at 126 inches (includes 2, 9 inch deep x 18 inch wide end units and 3, 36 inch wide units). c. 1 unit at 66 inches (includes 2, 9 inch deep x 18 inch wide end units and 3, 36 inch wide units). 28 ADD window covering 12 2113 to west, room 101. 12 2000 ADD Note 2 to room 101. REVISE window covering on north wall (entry) of Classroom 241 to be 12 2113. 29 12 2000 30 12 2400 2.01A ADD approved manufacturer: Sun Or Shade: www.sosshades.com. 31 12 2400 2.01B ADD approved manufacturer: Sun Or Shade: www.sosshades.com. 32 12 2400 2.03F.1 REVISE maximum audible noise to Maximum 44 dBA measured 3 feet from the motor unit. 33 12 2400 2.03F.3 REVISE to read: 3. Motor Type: AC motors. Addendum #3 Page 3 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH 34 14 2010 2.03 DESCRIPTION ADD paragraph H to read: H. Provide card reader operation-with security interface strip outside elevator machine room Card reader system to be furnished and installed by others. Card reader can be installed on the elevator car operation panel or be located at each hall station. 35 23 7200 2.3.B.1 REVISE unit base specs to 2-inch thick insulated floor with minimum 20 gauge G-90 galvanized outer and 10 gauge inner surface. 36 23 7200 2.3.C.1 REVISE exterior panel thickness to minimum 22-gauge. 37 23 7200 2.3.E.1 REVISE casing spec to allow 2” thick foam injected panels. 38 23 7200 2.3.J.7 REVISE pressure requirement to 6” w.c. max differential. 39 27 5100 2.01H.2 Change the amplifier model to Crown DCi4/600. 40 27 5100 2.01L.8 Replace with the following: 8. Multipurpose Room Microphone Splitter: a. Three outputs: one Direct and two Transformer Isolated Output per input b. Eight Inputs using Whirlwind Transformers c. Steel frame with rear tie bar, tie downs and standoffs d. Phoenix Block connector e. Whirlwind SPC-83P with Whirlwind DCSP1 Power Supply 41 32 8400 1.5A REVISE paragraph to read: A. New controller to be Hunter ACC-99D series, with additional modules as needed to serve site; and required equipment relays. Programming Remote for Decoders shall be Hunter ICD-HP. Operational Remote control shall be Hunter Industries ROAMXL-KIT, including transmitter, receiver, wiring harness and carrying case. Communication to KSD IMMS central control, located at the KSD maintenance office, will require ACC-COM-GPRS module. Provide additional accessories as required for a complete and operable system. 42 32 8400 ADD paragraph 2.16A to read: 2.16A: Provide master flow sensor, Hunter model HFS with FCT-400, 4” schedule 40 sensor (white). Install downstream of main point of connection per manufacturer’s standard details. Addendum #3 Page 4 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET 43 C0.05 44 C0.10 45 C1.00 46 C1.01 47 C1.13 48 C2.01 REVISE Scale bar to 1” = 20’ (see attached drawing CA-3/4 for reference) 49 C2.02 REVISE scale bar to 1” = 20’ and grading and as shown in attached drawing CA3/4 50 C5.01 REVISE Section F as shown in attached drawing CA-3/5 51 L2.2 52 3/L5.3 REVISE specification section referenced to 12 9300. 53 1/A1.2 DELETE 1" dimension from bottom of steel tube fascia to bottom of metal panel soffit. ADD 2" dimension from bottom of steel tube fascia to bottom of steel stud framing for soffit. 54 3/A1.2 DELETE 1" dimension from bottom of steel tube fascia to bottom of flashing. ADD 1/2" dimension from bottom of steel tube fascia to bottom of flashing. 55 13/A1.2 REVISE dimensions at canopy (see attached drawing AA-3/1). Addendum #3 DETAIL/DESCRIPTION REMOVE construction entrance from north driveway on S Conway Pl and add clouded area and plan note as shown in attached drawing CA-3/1 to read: “EXISTING KEEWAYDIN DISCOVERY CENTER BUS TRAFFIC AREA TO BE KEPT OPEN AND FREE OF CONSTRUCTION ACTIVITY, MATERIAL AND FENCING DURING SCHOOL YEAR, CONTRACTOR MAY USE THIS AREA DURING NON SCHOOL MONTHS AND/OR ONCE BUS LOOP TO NORTH IS COMPLETED” REVISE extents of fence removal in home owner’s property to the east of the W 4th Ave and S Buntin St intersection as shown in attached drawing CA-3/2, and revise plan note to read: “COORDINATE WITH HOME OWNER IN RELATION TO ADDITIONAL WORK IN THIS AREA, CONTACT ENGINEER OF RECORD FOR CONTACT INFORMATION, REMOVE PORTION OF FENCE FOR RELOCATION, REMOVE POSTS AND BACKFILL, REMOVE LAWN AND/OR LANDSCAPING, IRRIGATION LINES, CONTROLS AND VALVES FOR NEW CONSTRUCTION” REVISE extents of new fence and concrete installation at home owner’s property to the east of the W 4th Ave and S Buntin St intersection as shown in attached drawing CA-3/3, and revise plan note to read: “COORDINATE WITH HOME OWNER IN RELATION TO ADDITIONAL WORK IN THIS AREA, CONTACT ENGINEER OF RECORD FOR CONTACT INFORMATION, INSTALL EXISTING FENCE MATERIAL ON NEW POSTS AS SHOWN, IF EXISTING MATERIAL IS NOT REUSABLE THEN INSTALL NEW MATERIAL TO MATCH EXISTING, ADD 4" CONCRETE OVER 6" TOP COURSE PER WSDOT 9-03.9(3) BEHIND SIDEWALK UP TO RELOCATED FENCE, CONTRACTOR TO SUBMIT A PROPOSED LANDSCAPING PLAN TO MATCH EXISTING LANDSCAPE AND TO BE APPROVED BY THE HOME OWNER, IRRIGATION SHALL BE REPAIR TO PROVIDE 100% COVERAGE” REVISE portion of Keynote 25 to read: 5.0' ornamental fence/gate... CHANGE Key Note 3 to read: “SWALE- 20.0'x3.0'x2.0' DEEP BOTTOM WITH 3:1 SIDE SLOPES, BOTTOM ELEVATION 450.85, DO NOT COMPACT SOILS IN SWALE AREAS BEYOND 85% OF MDD PER ASTM D1557, SEE DETAIL F/C5.01 REVISE portion of landscape plan per LA-3/1. Page 5 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION 56 5/A4.11 DELETE 2'-9 1/2" dimension from canopy (refer to detail 13/A1.2). 57 24/A4.16 REVISE note "SEE DETAIL 1/A8.13" to SEE DETAIL 13/A1.2 FOR BEAM COVER. 58 42/A4.22 DELETE 2'-9 1/2", 2'-2", and 1'-0 1/8" dimensions from canopy (refer to detail 13/A1.2). REVISE note "SEE DETAIL 1/A8.13" to SEE DETAIL 13/A1.2 FOR BEAM COVER. 59 4/A5.01 The opening width to GIRLS 132/202 should be 5'-1 1/4" and wash wall should be 12'-1 1/2" per original drawings (overwriting drawing AA-2/1 in Addendum #2). 60 9/A6.00 REVISE locker callout to read: 2-Tier lockers. 61 16/A6.08 REVISE locker callout to read: 2-Tier lockers. 62 5/A6.10 REVISE locker callout to read: 2-Tier lockers. 63 1/A7.11 Add cubicle track and curtains in HEALTH 110 (see attached drawing AA-3/2). 64 1/A7.11 See 1/A5.01 for location of front curtain and valance. 65 A8.01 66 7/A8.13 67 S6.3 68 M2.21 At the north wall of the elevator machine room delete 8x8 exhaust grille and associated fire damper, 6” branch duct and keynote 14. 69 E2.11 Change (2) Type R40 luminaires in Health Room 110 to Type R23. See Drawing EA2.11A. 70 E3.11 Add an RVC in MPR 118 next to the CIFP on the west wall 71 E3.11 Delete the south RVC on the west wall of Gym 127 72 E3.11 Add dryer booster fan EF-9 connection in room 112, south wall 73 E3.11 Add a manual pull station in room 101 located on the east wall, north of the security pushbuttons 74 E3.11 Delete the receptacles for powered receptacles in Music 115 on circuit G-8 and keynote 28 Addendum #3 Add note #4 Integral blinds in upper and lower glazing panels (under COMMENTS) to doors 101, 114, 118A, 118B, and 127D. DELETE 1" dimension from bottom of steel tube fascia to bottom of metal panel soffit. ADD 2" dimension from bottom of steel tube fascia to bottom of steel stud framing for soffit. Detail 9: Change the vertical dimension between the bottom of canopy beam and top of HSS6x6 crossbar from 2’-2” to 2’-2½”. Also change the dimension from top of crossbar to center of beam cover support tube from 1’-0½” to 1’-0¼”. Page 6 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION 75 E3.11 Add a 4-plex receptacle on circuit G-25 and surface EMT conduit for sound system cabling for the MPR sound system rack located on the west wall of room 113. See EA3.11D 76 E3.11 Add (3) 1”C. and wiring from each CIP to the MPR rack. CIP plates shall be custom to meet interface requirements 77 E3.12 Add fire alarm and control relays to immediately release the electronic door hardware on doors 153 & 158. See detail Note: Addendum #2 added the electronic hardware 78 E3.21 Delete the Fire/Smoke damper connection and circuit MB-21 at the wall between rooms 200 & 201 79 E3.21 Add circuit EL-4 to serve the 135 degree, 120VAC fixed temperature heat detectors in the elevator machine room 201 80 E3.30 Add a duct smoke detector and associated relays as required for shutdown to AHU-5 & 6. See detail B/E7.07 81 E3.30 Delete one of the two duct smoke detectors shown for AHU 1-4. Provide associated relays as required for shutdown. See detail B/E7.07 82 E6.02 Replace panel schedules for MDS, DS1, PDP & SDP with the schedules issued in this addendum; drawings E6.02A & E6.02B 83 E6.03 Add dryer booster fan EF-9 to panel A2, circuit 9 84 E6.03 Change circuit MB-21 to ‘SPARE’ 85 E6.04 Add ‘FIXED TEMPERATURE HEAT DETECTORS’ to circuit EL-4 86 E7.06 Add a 3rd TEC-1 CONTROLLER in a wall box, to the MPR DSP. See drawing EA7.06A 87 E7.06 Revise the Multi-Purpose riser to add wiring to second CIP. See drawing EA7.06A 88 E7.07 Change the note at the 120V output in detail A to read; TO DOOR HARDWARE POWER SUPPLY OR OTHER 120V POWER SOURCE REQUIRING FA CONTROL PRIOR APPROVALS ITEM SECTION DETAIL/DESCRIPTION This approval is an approval of quality only. No attempt has been made to check each material as to special features, capacities or physical dimensions especially required by this project. It shall be the responsibility of supplier, manufacturer and Contractor to check all requirements before submitting for final approval. Final approval of exact features, sizes, capacities, etc., all of which must match materials indicated/specified, will be determined when submitted during construction period. Certain approvals are subject to conditions as noted. 89 23 3300 Backdraft Dampers - Greenheck 90 23 3300 Volume Dampers – Greenheck Addendum #3 Page 7 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com PRIOR APPROVALS ITEM SECTION DETAIL/DESCRIPTION 91 23 3300 Pressure Relief Doors - Greenheck 92 23 3600 Air Terminal Units – Price 93 23 8226 Electric Unit Heaters - Raywall 94 23 8233 Panel Heaters - Vulcan 95 23 8233 Finned Tube Radiators - Vulcan TYPE 96 MANUFACTURER SERIES/CATALOG# 97 26 0923 Douglas Ltg Ctls Dialog Rm Cntlr (Networked) 98 26 0923 FifthLight DALI / Central Manager, 99 26 0923 Encelium GreenBusII/SSU, 100 26 5100 A03/E Metalux GRLED 101 26 5100 A04 Metalux GRLED 102 26 5100 A06/E Metalux GRLED 103 26 5100 A24 Forum, Pinnacle SRT, E2A 104 26 5100 A28 Forum, Pinnacle SRT, E2A 105 26 5100 B10/E Portfolio LD6 106 26 5100 B15 Portfolio LD6 107 26 5100 B20/E Portfolio LD6 108 26 5100 D01-4 Ledalite Sync 109 26 5100 D01-8/E Ledalite Sync 110 26 5100 D02-4/8/8E/12 Ledalite Boldplay 111 26 5100 G08 Camman P8 MOD 112 26 5100 R04/E Metalux ALN 113 26 5100 R23/E Metalux ALN 114 26 5100 R30 Metalux ALN 115 26 5100 R40 Metalux ALN 116 26 5100 S03 Invue, Gardco ICM, SFRA 117 26 5100 S11 Lumiere, Lumenton 3002A, IG28 118 26 5100 S13 Invue, Gardco ICM, SFRA 119 26 5100 S20 McGraw Edison, Gardco IST, 101/121 120 26 5100 S20P McGraw Edison IST, 101/121 Addendum #3 Page 8 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com PRIOR APPROVALS ITEM SECTION DETAIL/DESCRIPTION 121 26 5100 S23 Invue, Gardco ICM, SFRA 122 26 5100 T12 Camman, W8 123 26 5100 TR20 Lighting Services Inc, LumeLEX 2060, 124 26 5100 X01 Sure-Lites, Emergi-Lite CX, Preceptor 125 26 5100 X02 Sure-Lites, Emergi-Lite CX, Preceptor 126 26 5100 X03 Sure-Lites, Emergi-Lite UX, SVX END OF ADDENDUM NO. 3 Addendum #3 Page 9 NORTH 0' 25' 50' 100' 150' Date: Drawn by: 04-04-16 ASW 1" = 50' REF. DWG C0.05 Westgate Elementary School Replacement 2514 West 4th Ave, Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #3 Checked by: Scale: Sheet No: PTK 1" = 50' CA-3/1 NORTH 0' 25' 50' 100' 150' Date: Drawn by: 04-04-16 ASW 1" = 50' REF. DWG C0.10 Westgate Elementary School Replacement 2514 West 4th Ave, Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #3 Checked by: Scale: Sheet No: PTK 1" = 50' CA-3/2 NORTH 2-10 0' 25' 50' 100' 150' Date: Drawn by: 04-04-16 ASW 1" = 50' REF. DWG C1.00 Westgate Elementary School Replacement 2514 West 4th Ave, Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #3 Checked by: Scale: Sheet No: PTK 1" = 50' CA-3/3 NORTH 0' 10' 20' 40' 60' 1" = 20' REF. DWG C2.02 Westgate Elementary School Replacement 2514 West 4th Ave, Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #3 Date: Drawn by: Checked by: Scale: Sheet No: 04-04-16 ASW PTK 1" = 20' CA-3/4 REF. DWG C5.01 Westgate Elementary School Replacement Date: Drawn by: 04-04-16 ASW H:\Projects\2014\14.05 KSD Westgate Elementary\Current Drawings\Revit\Custom Families\Custom Titleblocks\2014MMECTitle8-5x11-MMECLogoH_Sptone-Model-9610704.jpg 2514 West 4th Ave, Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #3 Checked by: Scale: Sheet No: PTK AS NOTED CA-3/5 PROVIDE 12"x12" REMOVABLE ACCESS PANEL IN SOFFIT @ EA. FIXTURE 3 2' - 9 3/4" 3 A 1 1/2" 2' - 2" 1' - 0 1/4" STEEL STUD FRAMING SEE STR'L. METAL PANEL SOFFIT W/ TRIM PIECES TYP. 1' - 0 1/4" BEAM - SEE STR'L. 2'-0" DIA. 2 PIECE ALUMINUM BEAM COVER CUSTOM COLOR CENTER TUBE - SEE STR'L. A 1' - 3 1/2" NOTE: 1. PAINT ALL EXPOSED STEEL. 2. PROVIDE SUPPORT ANGLES FROM CENTER TUBE TO 2 PIECE ALUMINUM BEAM COVER 3. NEATLY CUT AND SEAL ALUMINUM BEAM COVER @ PIPE SUPPORTS 3 13 MAIN ENTRY COLUMN SCALE: 3/4" = 1'-0" REF. DWG. 13/A1.2 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #3 Date: Drawn by: Checked by: Scale: Sheet No: 04/06/16 RMS DCM 3/4" = 1'-0" AA-3/1 8 10' - 0" P-6 P-6 P-6 I P-1 RR J 19 A8.16 9'-6" A.F.F. 10' - 0" 111 3 K J HEALTH 3 110 3 10' - 0" 4' - 4" L 7' - 6" 3' - 9" L 10' - 0" M M RECEPTION 10' - 0" 101 8 1 PARTIAL LEVEL 1 REFLECTED CEILNG PLAN (WEST) SCALE: 1/8" = 1'-0" REF. DWG. 1/A7.11 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #3 Date: Drawn by: Checked by: Scale: Sheet No: 04/06/16 RMS DCM 1/8" = 1'-0" AA-3/2