(Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red CHAPTER 3 GENERAL REGULATIONS 1) (Q) A cooling tower is being erected on the roof of a High Rise building. It is being assembled using parts that are individually listed. Would this installation be allowed under the 2012 code? (A) No. The inspector would not allow the installation to be constructed, however, if the design is sealed by a professional engineer, registered in the State of North Carolina, the inspector must accept the design and construction of the equipment. Ref: 301.4, Exception 2, 2012 MC 2) (Q) Exhaust Ductwork is installed on the back wall of a garage extends out about 4 feet from the wall into the garage area at an elevation of 6 feet above the floor. How should the ductwork be protected from vehicle damage per code? (A) Protection may not be required depending on what types of vehicles are worked on in the garage, however, reflective tape or a bollard would provide adequate protection. Ref: 303.4, 2012 MC 3) Heating Requirements for Sunrooms (Q) Are sunrooms exempt from the requirements of the NC Residential Code? (NCRC), Section R303.8 which requires that all habitable rooms meet certain design temperatures? (A) Yes, rooms meeting the definition of “sunroom” are exempt from the requirements of R303.8. Sunroom is defined by both the NCRC and the NC Energy Conservation Code (NCECC) generally as “a one story structure attached to a dwelling with a glazing area in excess of 40% of the gross area of the structure’s exterior walls and roof”. The North Carolina Mechanical Code, Section 309.1, requires that “interior spaces intended for human occupancy shall be provided with active or passive space-heating systems”. However, there is an exception that excludes spaces where the primary purpose is not associated with human comfort. This is how DOI addresses sunrooms. They are considered “outdoor” rooms that are used seasonally and are not intended to be for human comfort throughout the year. If the structure attached to the dwelling and opening into the dwelling has glazing less than 40% of the gross area of the structure’s exterior walls and roof, then it is not a sunroom and is required to conform to the insulation and heating requirements of the dwelling. R303.8 NCRC 1 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 4) (Q) A barbeque grill has been installed on the covered porch of a residence. The owner has constructed the hood himself per NSF requirements. Should the hood be allowed by the Mechanical Inspector? (A) NO. The grill is an appliance that is listed for outdoor use. To allow the grill to be under a covered porch, indoors, per code, the grill would have to have a hood built by the manufacturer of the grill that is approved and compatible with the grill. 304.1, 2012 MC 5) (Q) A tractor trailer has a trailer 11 feet 6 inches high. It is backing into a loading dock inside a public garage. The ceiling of the garage is 20 feet high. What is the minimum height to the bottom of the unit heater from the top of the trailer if the unit heater is installed directly over the trailer? (A) Unless the manufacturers installation instructions specify a greater height the unit heater shall be at least 1 foot 6 inches from the top of the trailer to the bottom of the unit heater. Ref: 304.6, 2012 MC 6) (Q) Can mastic be used in the joints for bonding stacked masonry instead of mortar or surface bonding cement? (A) Mastic is required to protect duct joints by adhering to metal duct which is generally a non porous dry surface when applied. It is not approved for the installation specified above. 304.1, 304.10.3, 2012 MC 7) (Q) If we are changing out a like for like roof top unit and it is over 16' above the roof does it have to have permanent access? (A) A like for like change out will not require the addition of permanent access unless it is obvious the original approved access has been removed. Ref: 306.5 (2012 NCMC) 8) (Q) I am installing a wood burning stove in my home. When installing the appliance I will always be able to use table 308.6 for unlisted equipment to reduce clearances. Is this a true statement? (A) No. If the solid fuel burning appliance is labeled with clearances those clearances shall be used when installing the solid-fuel burning appliance. Ref: 2 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code 2012 st 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 308.7, 2012 MC 9) (Q) What improvement in sizing mechanical equipment for single family dwellings and duplexes has made it possible in the 2012 code to provide equipment that is properly sized. (So equipment is not under sized nor is it over sized)? (A) The use of Manual S for sizing requirements. Ref: 312.1, 2012 MC CHAPTER 4 VENTILATION 1) (Q) To properly balance air flow and have a constant temperature exchange between all spaces in an occupied building should ventilation be required at a constant value for building occupants? (A) NO. Ventilation shall be provided during the periods that a room or space is occupied. Ref: 401.3, 2012 MC 2) Situation: We are working on a Nail Salon that will be going in a building downtown. From speaking with the owner they will not be doing acrylic nails, and nearly all their products will be organic. In moving forward with the design it has been determined that per 2012 NCMC (table 403.3 footnote b) we are not allowed to recirculate any air, therefore, one would think all the air conditioning in the space must be exhausted. This is not the case per DOI. In conversations with Billy Hinton concerning this section, it is his interpretation that the reference to, “all air supplied to such spaces” means the ventilation air supplied, and does not include the air for conditioning the space, therefore, air for conditioning the space could be returned to the space, but not returned to any other spaces. Due to the occupancy location on a lower floor of a multi-story building the designer would like to utilize one of the existing exhaust shafts near the space. One of the shafts is for toilet exhaust; one shaft is for the pool equipment room. Both exhaust fans are located on the roof; therefore the shafts are negatively pressurized. (Q) From reading through Chapter 5 of the code I cannot find any section that will not allow me to combine the exhaust from the nail salon with either of the existing shafts. Is this allowed? (A) Yes. The ventilation requirement for a nail salon, (as determined by 2012 NC 3 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 4th Quarter Land Use and Environmental Service Agency mechanical code and footnote b in table 404.3), would require mechanical exhaust for the entire amount of ventilation air supplied for the space for the nail stations. The code would not require all the conditioned air to be exhausted from the space. The exhaust from the nail stations may be connected to the exhaust for environmental air since the system is negatively pressurized. Ref: 403.2.1, Table 403.3 foot note b, 2012 MC 3) (Q) We traded emails recently regarding the 2012 code requirement for exhaust in residential kitchens, such as apartments and condos. The requirement stems from the footnotes on the ventilation calculation schedule. I was told by another engineer recently that Mecklenburg County will not require the kitchen exhaust if we are utilizing natural ventilation for the apartments. (A) We have not received an interpretation for the table below from DOI at this time. For Natural verses Mechanical Ventilation we have sent a clarification document to list conflicts between the two codes.(See charts below for comparisons) 401.2, 2012 MC vs. R303.4, 2012 Residential Building Code. (A) We have received the interpretation from Dan Dittman in the 3rd quarter, PE, DOI Chief Mechanical Engineer on our ventilation comparison chart. I am adding the chart with DOI answers. The original chart is shown below the DOI chart with answers. Memo To: DOI-David Conner/Dan Dittman from Jeff Griffin Re: Differences in the 2012 NC Mechanical code vs. the 2012 NC Residential Code. Below is a comparison of the 2 codes (NCRC & NCMC) and the sections related to Natural Ventilation. There is some language in multiple sections that seem to conflict along with the available commentary that shows some differences as well. Side by side comparison is listed below to illustrate, question related to application are listed below. NCRC (Residential) NCMC (Mechanical) R303.1 Habitable rooms. All habitable rooms shall have an 401.2 Ventilation required. Every occupied space shall be aggregate glazing area of not less than 8 percent of the floor ventilated by natural means in accordance with Section 402 or area of such rooms. Natural ventilation shall be through windows, doors, louvers or other approved openings to the by mechanical means in accordance with Section 403. 4 (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. Exceptions: 1. The glazed areas need not be openable where the opening is not required by Section R310 and an approved mechanical ventilation system capable of producing 0.35 air change per hour in the room is installed or a whole-house mechanical ventilation system is installed capable of supplying outdoor ventilation air of 15 cubic feet per minute (cfm) (78 L/s) per occupant computed on the basis of two occupants for the first bedroom and one occupant for each additional bedroom. HABITABLE SPACE. A space in a building for living, sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not considered habitable spaces. OCCUPIABLE SPACE. An enclosed space intended for human activities, excluding those spaces intended primarily for other purposes, such as storage rooms and equipment rooms, that are only intended to be occupied occasionally and for short periods of time. R303.4.1 Intake opening. Mechanical and gravity outdoor 401.4 Intake opening location. Air intake openings shall air intake openings shall be located a minimum of 10 feet (3048 mm) from any hazardous or noxious contaminant, comply with all of the following: 1. Intake openings shall be located a minimum of 10 feet such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks, except as otherwise specified in this code. Where a source of contaminant is located within 10 feet (3048 mm) of an intake opening, such opening shall be located a minimum of 2 feet (610 mm) below the contaminant source. For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious. (3048 mm) from lot lines or buildings on the same lot. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, streets, alleys, parking lots and loading docks, 5 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red except as specified in Item 3 or Section 501.2.1. 3. Intake openings shall be located not less than 3 feet (914 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. R303.5 Outside opening protection. Air exhaust and intake 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion-resistant openings that terminate outdoors shall be protected with screens, louvers or grilles. Openings in louvers, grilles and corrosion-resistant screens, louvers or grilles having a minimum opening size of 1/4 inch (6 mm) and a maximum opening size of 1/2 inch (13 mm), in any dimension. Openings shall be protected against local weather conditions. Outdoor air exhaust and intake openings shall meet the provisions for exterior wall opening protectives in accordance with this code. R303.1 Habitable rooms. All habitable rooms shall have an aggregate glazing area of not less than 8 percent of the floor area of such rooms. Natural ventilation shall be through windows, doors, louvers or other approved openings to the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with the International Building Code. [B] 402.1 Natural ventilation. Natural ventilation of an occupied space shall be through windows, doors, louvers or other openings to the outdoors. The operating mechanism for such openings shall be provided with ready access so that the openings are readily controllable by the building occupants. R303.1 Habitable rooms. All habitable rooms shall have an [B] 402.2 Ventilation area required. The minimum openable aggregate glazing area of not less than 8 percent of the floor area to the outdoors shall be 4 percent of the floor area being area of such rooms. Natural ventilation shall be through windows, doors, louvers or other approved openings to the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. ventilated. 6 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red R303.2 Adjoining rooms. For the purpose of determining [B] 402.3 Adjoining spaces. Where rooms and spaces without light and ventilation requirements, any room shall be considered as a portion of an adjoining room when at least one-half of the area of the common wall is open and unobstructed and provides an opening of not less than onetenth of the floor area of the interior room but not less than 25 square feet (2.3 m2). openings to the outdoors are ventilated through an adjoining 4th Quarter Land Use and Environmental Service Agency room, the opening to the adjoining rooms shall be unobstructed and shall have an area not less than 8 percent of the floor area of the interior room or space, but not less than 25 square feet (2.3 m2). The minimum openable area to the outdoors shall be based on the total floor area being ventilated. Exception: Openings required for light and/or ventilation Exception: Exterior openings required for ventilation shall shall be permitted to open into a thermally isolated sunroom or patio cover of not less than one-tenth of the floor area of be permitted to open into a thermally isolated sunroom addition or patio cover, provided that the openable area between the sunroom addition or patio cover and the interior room has an area of not less than 8 percent of the floor area of the interior room or space, but not less than 20 square feet (1.86m2). The minimum openable area to the outdoors shall be the interior room but not less than 20 square feet (2 m2). The based on the total floor area being ventilated. addition or patio cover, provided that there is an openable area between the adjoining room and the sunroom addition minimum openable area to the outdoors shall be based upon the total floor area being ventilated. R303.3 Bathrooms. Bathrooms, water closet compartments No separate listing for Bathrooms and other similar rooms shall be provided with aggregate glazing area in windows of not less than 3 square feet (0.3 m2), one-half of which must be openable. Exception: The glazed areas shall not be required where artificial light and a mechanical ventilation system are provided. The minimum ventilation rates shall be 50 cubic feet per minute (24 L/s) for intermittent ventilation or 20 cubic feet per minute (10 L/s) for continuous ventilation. Ventilation air from the space shall be exhausted directly to the outside. Questions: 1. The definitions between the 2 codes are different NCRC uses habitable rooms and the NCMC uses occupiable spaces. It appears that the NCMC has more requirements than the NCRC in that bathrooms, toilet rooms, laundry rooms, hallways, and possible closets if using natural ventilation would be required openings to the exterior that match floor area, NCRC has natural ventilation minimum opening for bathroom and toilet rooms but NCMC doesn’t. Does the NCMC require hallways (No, provided the “hallway” is not so large as to become a Habitable Space, as defined in NCRC Section R304.2 and R304.3), laundry 7 (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 4th Quarter Land Use and Environmental Service Agency rooms(Yes, if it meets the minimum habitable room requirements of NCRC Section 304.3, No, if it is less than that, but in any case makeup air must be provided to the dryer in accordance with Section 504.5 of the NCMC, and manufacturer’s instructions), closets(No) and bathroom/toilet rooms(Yes) to have windows to the exterior or adjoining room option if using natural ventilation? 2. In reference to both codes is a door or window considered an intake opening? With respect to Natural Ventilation, yes, if it is an exterior door or window. 3. If a door/window is an intake opening is screening required for opening protection. No, in regards to the NC Building Code, I cannot find any requirement for screens on windows and doors, going back to 1968, 2002, 2006, or 2009. Section R303.5 require a minimum opening size of ¼”, and a maximum of ½”. A screen with ¼” openings would not stop most flies or mosquitoes. However, there may be other State or Federal Agencies that have requirements. I did a little research and found reference to Section 8 Housing administered by HUD that may require screens in certain cases, but I could not find the details. 4. If a door/window is an intake opening, does the lot line or between building requirements apply to NCRC as listed in the mechanical code (Yes. Windows are not prohibited from these walls, if not prohibited by other parts of the code like Section R302, but there must be sufficient ventilation provided by other openings or means), would this be the interpretation related to potential contaminants. (Yes, please note specific allowances for Environmental Air, Definitions, and Section 501.2.1, Item 3.) 5. The IRC and the IMC commentary that support the 2012 codes (2009 version) has conflicting information related to what is a intake opening and when screening is required (Windows) and Lot line issues. The IMC clearly has requirements for lot lines that the IRC doesn’t talk about and the IRC has no reference to “except windows and doors” as listed in the IMC commentary for intake openings. How should this be applied? Please refer to the following link for an interpretation on a related matter. http://www.ncdoi.com/osfm/engineering/interpretations4/2012%20residential/0302%20%20location%20on%20lot%20related%20to%20zoning,%20deed%20restrictions%20and%2 0covenants.pdf By restricting ventilation intake opening from 10’ from a Lot line, it allows development of property nearby without requiring the existing structure to be rebuilt. If local ordinances allow a zero-lot line, and the required ventilation intakes are on this side, and the future residence is built less than 10’ from the lot line, now the existing structure has ventilation intakes that no longer meet the Code. Windows can be provided in this wall, where allowed by other parts of the code, they cannot be considered the sole source of ventilation for the space they serve. 6. Should the requirements match in both codes? It certainly would be nice, but the 8 (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 4th Quarter Land Use and Environmental Service Agency Residential Code is usually tweaked to make it more flexible than the Technical codes. A petition to rule making either be performed in accordance with Section 202.5 of the Administrative Code, or through the ICC code-making process. As a general rule, where there is a difference/discrepancy between the Residential Code and a referenced Technical Code, please refer to Section R102.4. NCRC (Residential) NCMC (Mechanical) R303.1 Habitable rooms. All habitable rooms shall have an 401.2 Ventilation required. Every occupied space shall be aggregate glazing area of not less than 8 percent of the floor ventilated by natural means in accordance with Section 402 or area of such rooms. Natural ventilation shall be through windows, doors, louvers or other approved openings to the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants. The minimum open able area to the outdoors shall be 4 percent of the floor area being ventilated. by mechanical means in accordance with Section 403. Exceptions: 1. The glazed areas need not be open able where the opening is not required by Section R310 and an approved mechanical ventilation system capable of producing 0.35 air change per hour in the room is installed or a whole-house mechanical ventilation system is installed capable of supplying outdoor ventilation air of 15 cubic feet per minute (cfm) (78 L/s) per occupant computed on the basis of two occupants for the first bedroom and one occupant for each additional bedroom. HABITABLE SPACE. A space in a building for living, sleeping, eating or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces and similar areas are not considered habitable spaces. OCCUPIABLE SPACE. An enclosed space intended for human activities, excluding those spaces intended primarily for other purposes, such as storage rooms and equipment rooms, that are only intended to be occupied occasionally and for short periods of time. 9 (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red R303.4.1 Intake opening. Mechanical and gravity outdoor 401.4 Intake opening location. Air intake openings shall air intake openings shall be located a minimum of 10 feet (3048 mm) from any hazardous or noxious contaminant, comply with all of the following: 1. Intake openings shall be located a minimum of 10 feet such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks, except as otherwise specified in this code. Where a source of contaminant is located within 10 feet (3048 mm) of an intake opening, such opening shall be located a minimum of 2 feet (610 mm) below the contaminant source. For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious. (3048 mm) from lot lines or buildings on the same lot. Where openings front on a street or public way, the distance shall be measured to the centerline of the street or public way. 2. Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) horizontally from any hazardous or noxious contaminant source, such as vents, streets, alleys, parking lots and loading docks, except as specified in Item 3 or Section 501.2.1. 3. Intake openings shall be located not less than 3 feet (914 mm) below contaminant sources where such sources are located within 10 feet (3048 mm) of the opening. R303.5 Outside opening protection. Air exhaust and intake 401.5 Intake opening protection. Air intake openings that terminate outdoors shall be protected with corrosion-resistant openings that terminate outdoors shall be protected with screens, louvers or grilles. Openings in louvers, grilles and corrosion-resistant screens, louvers or grilles having a minimum opening size of 1/4 inch (6 mm) and a maximum opening size of 1/2 inch (13 mm), in any dimension. Openings shall be protected against local weather conditions. Outdoor air exhaust and intake openings shall meet the provisions for exterior wall opening protectives in accordance with this code. 10 screens shall be sized in accordance with Table 401.5, and shall be protected against local weather conditions. Outdoor air intake openings located in exterior walls shall meet the provisions for exterior wall opening protectives in accordance with the International Building Code. 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, R303.1 Habitable rooms. All habitable rooms shall have an aggregate glazing area of not less than 8 percent of the floor area of such rooms. Natural ventilation shall be through windows, doors, louvers or other approved openings to the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. th 4 Qtr. 10/1/12-12/31/12 Q&A in red [B] 402.1 Natural ventilation. Natural ventilation of an occupied space shall be through windows, doors, louvers or other openings to the outdoors. The operating mechanism for such openings shall be provided with ready access so that the openings are readily controllable by the building occupants. R303.1 Habitable rooms. All habitable rooms shall have an [B] 402.2 Ventilation area required. The minimum openable aggregate glazing area of not less than 8 percent of the floor area to the outdoors shall be 4 percent of the floor area being area of such rooms. Natural ventilation shall be through windows, doors, louvers or other approved openings to the outdoor air. Such openings shall be provided with ready access or shall otherwise be readily controllable by the building occupants. The minimum openable area to the outdoors shall be 4 percent of the floor area being ventilated. ventilated. R303.2 Adjoining rooms. For the purpose of determining [B] 402.3 Adjoining spaces. Where rooms and spaces without light and ventilation requirements, any room shall be considered as a portion of an adjoining room when at least one-half of the area of the common wall is open and unobstructed and provides an opening of not less than onetenth of the floor area of the interior room but not less than 25 square feet (2.3 m2). openings to the outdoors are ventilated through an adjoining room, the opening to the adjoining rooms shall be unobstructed and shall have an area not less than 8 percent of the floor area of the interior room or space, but not less than 25 square feet (2.3 m2). The minimum openable area to the outdoors shall be based on the total floor area being ventilated. Exception: Openings required for light and/or ventilation Exception: Exterior openings required for ventilation shall shall be permitted to open into a thermally isolated sunroom or patio cover of not less than one-tenth of the floor area of be permitted to open into a thermally isolated sunroom addition or patio cover, provided that the openable area between the sunroom addition or patio cover and the interior room has an area of not less than 8 percent of the floor area of the interior room or space, but not less than 20 square feet (1.86m2). The minimum openable area to the outdoors shall be the interior room but not less than 20 square feet (2 m2). The based on the total floor area being ventilated. addition or patio cover, provided that there is an openable area between the adjoining room and the sunroom addition minimum openable area to the outdoors shall be based upon the total floor area being ventilated. R303.3 Bathrooms. Bathrooms, water closet compartments and other similar rooms shall be provided with aggregate glazing area in windows of not less than 3 square feet (0.3 m2), 11 No separate listing for Bathrooms 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 4th Quarter Land Use and Environmental Service Agency one-half of which must be openable. Exception: The glazed areas shall not be required where artificial light and a mechanical ventilation system are provided. The minimum ventilation rates shall be 50 cubic feet per minute (24 L/s) for intermittent ventilation or 20 cubic feet per minute (10 L/s) for continuous ventilation. Ventilation air from the space shall be exhausted directly to the outside. Questions: 7. The definitions between the 2 codes are different NCRC uses habitable rooms and the NCMC uses occupiable spaces. It appears that the NCMC has more requirements than the NCRC in that bathrooms, toilet rooms, laundry rooms, hallways, and possible closets if using natural ventilation would be required openings to the exterior that match floor area, NCRC has natural ventilation minimum opening for bathroom and toilet rooms but NCMC doesn’t. Does the NCMC require hallways, laundry rooms, closets and bathroom/toilet rooms to have windows to the exterior or adjoining room option if using natural ventilation? 8. In reference to both codes is a door or window considered an intake opening? 9. If a door/window is an intake opening is screening required for opening protection. 10. If a door/window is an intake opening, does the lot line or between building requirements apply to NCRC as listed in the mechanical code, would this be the interpretation related to potential contaminants. 11. The IRC and the IMC commentary that support the 2012 codes (2009 version) has conflicting information related to what is a intake opening and when screening is required (Windows) and Lot line issues. The IMC clearly has requirements for lot lines that the IRC doesn’t talk about and the IRC has no reference to “except windows and doors” as listed in the IMC commentary for intake openings. How should this be applied? 12. Should the requirements match in both codes? 4) (Q) Are screens allowed on outside vents? (A) Yes. 401.5 MC and IBC, sizing Table 401.5, 2012 MC (Exception: Dryer Vents) 5) (Q) We recently discussed the requirement for exhaust/ventilation in a residential (apartment or condo) kitchen. At that time, you indicated the 100 cfm exhaust would be required in the residential kitchen(s) per table 403.3 of the 2012 NCMC. I have heard other engineers say they are getting a different interpretation. I have heard that the exhaust is not required if natural ventilation or mechanical ventilation is applied to the dwelling unit. Which is correct? We have several projects in design and in plan review at this time. We received a code comment on one project that the exhaust is required. However, I want to make sure we follow the correct 12 (Code Enforcement) NC Mechanical Code 2012 st 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red interpretation. (A) The following informal interpretation was received from Dan Dittman, PE, Chief Mechanical Engineer on June 22, 2012 per the email I forwarded to him from the project designer. Mr. Horton, I can find no requirements for a hood over a residential range, either gas or electric. There have been proposals to change it, see the first two pages of the attached .pdf, but no actual requirement. I checked the installation instructions for some residential ranges and ovens, and there are no requirements for a hood. They only show clearance to combustible requirements. If they install a hood, either recirculation or ducted, it has to be done in a manner prescribed by code, but there is not a code requirement in a dwelling. The UL 858 listing is required for this to hold true. Domestic gas ranged need to be listed and labeled for domestic use, See NCFGC 623.3. 6) (Q) This is a follow up answer from Mr. Dittman which is also part of his informal interpretation. Question: If separate ventilation is not required in question 11 above would it make a difference if you have an interior kitchen without a window or opening to the outside? Would ventilation be required in the interior Kitchen since we have class 2 contaminants even when using the 402 natural ventilation calculations for a dwelling? Are we confirming no hood or mechanical ventilation is required if you have the kitchen on an exterior wall with an operable window or permanent opening to the outside? Mr. Horton (A) Our North Carolina Code does not address the level of contamination that is in ASHRAE which I use in trying to understand the basis for our code. In a dwelling kitchen with an exterior wall, it is clear that ventilation via the Natural Ventilation Methods, Section 402, can be used, and nothing more is required. In a dwelling kitchen that does not have an exterior wall, the NC Code does not prohibit the dwelling kitchen from being ventilated via Natural Methods, Section 402. 13 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red The ASHRAE 62.1 – 2007 would seem to limit the transfer of air from a domestic kitchen (class 2 air) into the dwelling, (class 1 air). However, this is in the mechanical ventilation section of ASHRAE 62.1-2007, and not the natural ventilation section. With Natural Ventilation, the code minimums are the size of openings, the responsibility for performance does not go way, but the designer of record is accountable for that. Thanks, Dan Dittman (We currently have a formal interpretation from DOI that verifies the informal Interpretation above) 7) Make-Up Air to Gang Toilet Rooms (Q) Must gang toilet rooms in commercial buildings be provided directly with outdoor air for make-up of required exhaust air? (A) No, Section 401 requires that the supply air be approximately equal to the exhaust air. In effect, the required ventilation air replaces the transfer air to the toilet rooms, even though it is brought in through the HVAC supply air system. 403.1 NCMC 2012 8) Ventilation Rate Requirements (Q) Must the estimated maximum occupant load from Table 403.3 of the NC Mechanical Code be used when determining the minimum required outdoor ventilation air requirements? (A) No. Section 403.3 requires that ventilation systems be designed to have the capacity to supply the minimum outdoor airflow rate determined in accordance with Table 403.3. The occupant density entries in Table 403.3 are based on empirical data and are reasonably accurate for the typical cases in each type of occupancy; however, there are actually three acceptable options. Options: 1) Use the values in Table 403.3. 2) The occupancy shall be determined by an approved engineering analysis. 3) Approved statistical data shall document the accuracy of an alternate anticipated occupant density. An example of this would be a factory setting where statistical data shows that the occupant load in the table is much 14 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red higher than would be required for a particular industrial process. 403.3 NCMC 2012 CHAPTER 5 EXHAUSTS SYSTEMS 1) (Q) What would be an adequate amount of make-up air in a residential occupancy if the dryer is exhausting 50 cfm and the Kitchen hood is exhausting through the roof at the same time at 40 cfm. How much make- up air would be required? (A) It depends. Make up air is not required in residential occupancies if natural ventilation is used per 402, however, if 403 is used then make up air would be required. Ref: 501.3 exception. 2012 MC 2) (Q) Would environmental air exhaust ever be considered hazardous or noxious per the Mechanical code? (A) No. 501.2.1 #3, 2012 MC “Such exhaust shall not be considered hazardous of noxious.” 3) (Q) A garage is installing a ventilation system to avoid consideration by the electrical code to be a class 1 division 2 area. Should the fan motors be interlocked with the electrical receptacles and /or equipment/appliances in the garage to shut down the power to the apparatus above if the ventilation fans lose power? (A) Yes. “Electrical equipment and appliances used in operations that generate explosive or flammable vapors, fumes or dusts shall be interlocked with the ventilation system so that the equipment and appliances cannot be operated unless the ventilation fans are in operation.” 503.1 MC 2012 4) (Q) A contractor sent an attached cut sheet of the fan being used in a pool chemical storage room. They claim to have used this model fan for many projects in the Charlotte area for many years. The exhaust is ducted to the exterior with a makeup air louver in the door or wall. The electrical inspector, not mechanical, is rejecting the fan. (a) Is this fan acceptable for this application? (b) Should the mechanical inspector look at the listing/labeling of the fan? (A) (a) This fan is not acceptable because it is not rated as non corrosive. The atmosphere in 15 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red a pool chemical storage room is required to be exhausted per the fire code because of the corrosive nature of pool chemicals. Provide a fan listed as non corrosive by the manufacturer. (b) The Mechanical Inspector should require the correctly listed fan per code. Ref; 503.4 (2012 NCMC) 5) Dryer Duct Rated Assembly Membrane Penetrations (Q) Since Section 504.2 of the NC Mechanical Code prohibits the placement of fire dampers and smoke dampers in dryer ducts, can a dryer duct penetrate the membrane of a rated floor/ceiling, roof/ceiling, or wall assembly? (A) Yes. Items #1 and #2 below are examples of two possible methods to penetrate the rated assembly. Item #3 shows how one might run the duct without penetrating the rated assembly. 1) The duct can be wrapped with rated duct wrap from the point that the duct enters the rated assembly to the point where it leaves the rated assembly The duct wrap must be listed and labeled for the specific intended use. The duct wrap must be rated the same as the floor/ceiling assembly, roof/ceiling, or wall assembly. The penetration must be sealed to prevent the passage of smoke or flame. 2) If the rated floor/ceiling, roof/ceiling, or wall assembly test report indicates that penetrations of the assembly membrane by ducts is acceptable, then the dryer duct may pass through the assembly membrane as prescribed in the test report unless the report requires dampers. Dampers are never allowed. 3) Relocate the membrane of the rated floor/ceiling, roof/ceiling, or wall assembly such that the duct is not within the assembly. 716.6.2 NCBC, 504.2 & 607.6.2 NCMC 2012. 6) (Q) The contractor has the installation instructions for dryer vents for a specific make of Maytag dryer that will be installed in all the apartments in a 40 unit complex. The Manufacturers’ instructions show lengths of duct runs that exceed the minimum code and no equivalent lengths for the fittings used with the dryer duct. Should the inspector approve the installation? (A) NO. The inspector should require the contractor to supply an equivalent length chart for fittings from the manufacturer or re-calculate the runs using the equivalent length chart in the code (table 504.6.4.1) Ref: 504.6.4.2, 2012 MC 16 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 7) (Q) A mechanical contractor is insulating the makeup air duct to a type 1 hood with standard fiberglass insulation. He has installed the insulation all the way to the hood. (a) Would this be allowed by the 2012 mechanical code? (b) What should be used as an alternate method if this is not allowed? (A) (a) The standard duct insulation should not be allowed within 18 inches of the hood because of the heat generated by the hood. 506.3.6, 2012 MC (b) A rated fire wrap material could be used to wrap the duct within 18 inches of the hood termination. 506.3.6, exception # 3, 2012 MC 8) (Q) A placard has been provided five feet above the dryer exhaust duct connection on the wall with the dryer manufacturer’s information for duct equivalent length. Does this meet the identification requirements of the 2012 code for length identification? (A) Yes. It would be considered permanent identification. Ref: 504.6.5 MC 2012 9) Listed Type I Hood Clearance to Combustibles (Q) Can Table 308.6 be used to reduce the clearance requirement in Section 507.9 for a listed Type I kitchen exhaust hood? (A) Yes. The clearance reduction methods in Table 308.6 are applicable for equipment and appliances that are not listed for clearance to combustibles. UL710 is the test standard for listing factory built Type I hoods and is referenced in Section 507.1. The UL710 standard does not include testing for clearance to combustibles; therefore the listing does not address clearance to combustibles. The 18 inch clearance required by Section 507.9 may be reduced by application of Table 308.6. 308.6, 507.1 and 507.9 NCMC 2012 10) (Q) The 2012 Code would allow, under the exceptions to 507.2.3, two domestic ranges in dwelling units, churches, schools, day care centers, break areas and similar locations. The new 2012 code change has no restriction to 4 burners for domestic ranges, you can have as many burners as the manufacturer provides or even a grill on the domestic range cook top and meet the code. Would a clubhouse for an apartment complex require a hood if they install two 5 burner ranges? (A) We have an interpretation that applies on our web site. The interpretation would allow a type II hood in an apartment clubhouse occupancy over domestic ranges rather than a 17 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red Type I hood if the cooking would be considered sporadic and non intensive. If two ranges are installed the cooking capabilities would be considered intensive and the two ranges would produce large amounts of smoke and grease laden vapors, therefore a type I hood, not a type II hood, would be required. Ref: 507.2.1, 507.2.2, 507.2.3 & exception (2012 NCMC) 11) Situation: A restaurant has installed two barbeque cookers under type I hoods which exhaust high-medium- & low heat cooking appliances. The food services inspector discovered the cookers and reported it to the Code Enforcement Department. Answer a. through e. below. a. (Q) The owner says the cookers are safe as installed and they are code compliant. (1) Is the owner correct? (2) What are the obvious code violations related to this installation? (A) (1) The owner is not qualified to determine the safety of the equipment. The restaurant installed the cookers without plans or permits. Require cookers to meet the code. Ref: 106.1, 106.2.1 Administrative Code. (2) Since the cookers use solid fuel and gas for heat for cooking they are classified as extra-heavy-duty cooking appliances and cannot be located under the same type I hood with high-medium & low heat appliances. Ref: 507.3.4 MC b.(Q)Three Type 1 hoods for the cooking equipment are connected to single grease exhaust duct that exits the building into a covered parking garage. (1) Can the separate hoods required for the two Extra-heavy-duty cooking appliances be combined with the existing grease duct exhaust if properly sized? (2) May the grease duct from the extraheavy-duty appliances exhaust into the covered Parking deck? (A) (1) No. Hoods for the two extra-heavy–duty barbeque cookers shall exit the building through a separate exhaust duct system. The two cookers may, however, be under the same Type 1 hood rather than having separate hoods or under a hood or hoods listed for the application by the manufacturer. The exhaust systems may also be combined since both are extra-heavy-duty cooking appliances. Ref: 507.2.4, 506.3.5 exception # 4 (2) No. It is a violation to have the current hood system grease duct exiting the building into a parking garage, unless, it is an open parking garage. If open parking garage then 18 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red terminating in the parking lot with a water wash hood or installing an approved environmental air unit is used. The new grease duct shall exit the building either vertically or horizontally to the outside. Ref: 506.3.12.2, 506.3.12.3, 506.5.5 c.(Q) Are there more stringent exhaust requirements for hood exhaust CFM and safety devices for a hood over an extra-heavy-duty cooking appliance than over high-mediumlow & heat cooking appliances? (A) Yes, see ventilation tables. Ref: 507.13.1 d.(Q) The manufacturer of the barbeque cookers sends a letter to the Code Administrator with information on the engineering of the cookers. The letter explains how the cookers are engineered/designed to make it virtually impossible for a spark or ember to be exhausted into the duct system. The letter also states the cookers can be located under the same type I hood with high-medium-low heat cooking appliances. Further, the letter states the information will be included in the manufacturer’s literature in the future on the two cookers installed at the restaurant plus 5 other models of cookers with similar exhaust characteristics. Should the Code Administrator accept the manufacturers letter and approve the cookers? (note: The manufacturer does not have a registered PE on their staff.) (A) The code official may accept the letter under the conditions stated above if a professional engineer who works directly for the factory provides a letter under his seal that the changes to the literature will be made. The letter must also provide information as to how the engineering/design of the product is such that a spark or ember can never be exhausted from the cookers that may cause a grease fire in the ductwork and ignite fires in heavy-medium or light duty appliances that may also be under the hood. Ref: 105.2 MC e. (Q) Should the Code Administrator require a third party test that confirms the cookers will not emit sparks or embers into the grease duct system before he approves the cookers? (A)This may be one solution the Code Administrator would allow. Ref: 105.3, 105.3.1, 105.3.2 (MC). 12) (Q) a. What is the new clearance requirement in the 2012 Mechanical Code from operable 19 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red openings for all environmental air ducts? b. Can environmental air ducts ever be considered hazardous or noxious? (A) a. Three feet, Ref: 501.2.1 (MC) b. No. Ref: 501.2.1 (MC) 13) (Q) Is exhausted air ever allowed to discharge into walkways or hallways? (A) No. Ref: 501.2.1.1, 2012 MC 14) (Q) Will the mechanical code allow exhaust outlets to discharge at or below the design flood level (elevation)? (A) No. 501.2.1 # 4 required 2012 MC, interpreted as required by the 2009 code (2009 501.4 ref. Ch 6, [B] 602.4) 15) (Q) (a) Are all occupancies required to provide pressure equalization when the system is exhausting quantities of air? (b) Are there specific occupancy exceptions for appliances and fans and if so what are they? (A) [note: The 2009 code exempted R 3 occupancies only with no mention of specific appliances or exhaust exceptions.] (a) The 2012 code exempts dwelling units in R 2 occupancies. (b) The 2012 code does not require pressure equalization for domestic exhaust systems in residential occupancies and similar uses (domestic clothes dryers, domestic range hoods, domestic bathroom exhaust). 501.3 and 501.3 exception, 2012 MC 16) (Q) I have a customer with an underground basement. He is going to install an ERV fresh air ventilator for the basement area. With the situation we are facing we cannot achieve the 18” ground clearance from grade to the bottom of the ventilator per the manufacturer’s instructions. We are considering the installation of a dry well. The manufacturer’s instructions do not say whether or not we can install the exhaust and intake in a dry well. I have looked through the Residential Code book in sections 401.4, 401.5, 501.2 and 501.2.1. There is no information on this situation. Am I missing it in the code book? Am I ok to have the builder install a dry well as long as I maintain the 18” clearance below the opening as required by the manufacturer’s instructions? (A) We would require a letter from the manufacturer, mailed to the CA, on the 20 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red manufacturers letterhead, signed by the engineer that works for the factory that the installation would meet ventilation clearance requirements. 505.1 Exception, 105.2, 2012 MC 17) (Q) A Mechanical Contractor is installing a 100 cfm bathroom exhaust fan in the kitchen ceiling for a new housing development to meet requirements of table 403.3 footnote b in the 2012 Mechanical Code. He is not installing a kitchen hood over the 4 burner electric range and the manufacturer does not call for a hood. Does this installation meet the code for table 403.3 ft. note b requirements of the 2012 Mechanical Code? (A) Yes. If a mechanical ventilation means is provided per 403.1 MC 2012. [See 401.2. Ventilation shall be required either by using 402 (Natural Ventilation) or 403 (Mechanical Ventilation).] [See 505.1 Exception 1 “where natural or mechanical ventilation is “otherwise provided” listed and labeled ductless range hoods shall not be required to discharge to the outdoors.] Question: If the manufacturer does not require a hood over the cooking equipment would a ductless hood be required? No. 18) TYPE I HOODS – FINISHING OVENS (Q) Do electric counter-top conveyor finishing ovens for pizza and other similar products require a hood, and if so, what type? (A) NCMC 507.2.1 requires a Type I hood over light-duty cooking appliances and medium-duty cooking appliances that produce grease or smoke. Therefore, if smoke or grease from animal or plant oils is produced during cooking with this appliance, a Type I hood is required. However, if a third-party testing agency accredited by NC Building Code Council demonstrated that the emissions are below the levels identified in NFPA 96 2011 4.1.1.1, (reprinted below), and it is used only for food products that were tested by the test agency, either a Type I hood or the requirements of NCMC 2012 507.2.2 can be used. The level of smoke or grease produced is dependent on the food being processed. If the appliance meets or exceeds the ANSI/UL 197 standard for reduced emissions, and is installed without a Type I hood, the finishing oven shall be provided with a permanent placard explaining the food product(s) that the permit was issued for a change in food product may require a change in hood requirements References: NFPA 96 2011 21 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 4.1.1.1* Cooking equipment that has been listed in accordance with ANSI/UL 197 or an equivalent standard for reduced emissions shall not be required to be provided with an exhaust system. 4.1.1.2 The listing evaluation of cooking equipment covered by 4.1.1.1 shall demonstrate that the grease discharge at the exhaust duct of a test hood placed over the appliance shall not exceed 5 mg/m3, when operated with a total airflow of 500 cfm. 507.2.1 NCMC 2012 19) (Q) Is a Type I or a Type II hood required over an electric egg cooker that operates under 3000 Watts? (A) No hood is required. Ref: 507.2.2 Exception #4, 2012 MC 20) Project Information: The mechanical design for the a Plant Upgrade consists of the installation of an air cooled chiller and a chilled water pumping system on the roof adjacent to the existing air cooled chillers. The electrical design for this work included an electrical equipment room located within the garage having a UPS system having closed cell batteries. The electrical equipment room design has a 2 hour fire rating and includes an air conditioning unit for heat removal with an exhaust air system, if required, for the removal of hydrogen gas vapors. The closed cell batteries are limited to the UPS equipment and emit very little hydrogen gas. As a result, these batteries do not require an exhaust air system by the mechanical code. However, to be safe, the owner has designed an exhaust air system to protect the electrical equipment room in the event of an emergency. The exhaust air system will be normally off and will be controlled by a hydrogen gas detector installed within the electrical equipment room. When activated, the hydrogen gas detector will start the exhaust air system and provide a local audio and visual alarm at the electrical equipment room and at the building BAS system. The exhaust airflow rate from the electrical equipment room is 150 CFM and it discharges into the garage which is open to atmosphere for its ventilation air requirements. As a result, it is our opinion that the exhaust air system is discharging to the outside and that it will have no impact on the garage environment. The plans examiner has turned the plans down 22 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red requiring the exhaust to go outside the building. He says garage or loading dock is not considered outside the building per mechanical code. The exhaust duct also has fire dampers in three locations where it penetrates fire rated walls. The plans examiner will not allow fire dampers in a hazardous exhaust system and is requiring the installation to be in shaft from the electrical room to the outside wall penetration. (Q) What can be done to allow the protection as shown on the plans? (A) The plans examiner is correct. If your intent is to protect the electrical room from a possible emergency situation then the installation as described by the plans examiner is in compliance with minimum code. You have two choices. Meet the code minimums described or remove the emergency system. Ref: 510.1, 510.5.7, 510.6.1, 510.6.3 MC 2012 21) (Q) The laboratory exhaust hoods in a hospital room are ducted through a vertical two hour wall and into a chase that extends between the buildings and up through the roof. As the designer, I intend to wrap the duct from the penetration in the lab room in 3M approved 2 hour shaft wrap. The inspector is requiring the exhaust to be wrapped from the hood all the way to the roof. I see no justification in the code for this requirement. Is this required by code? (A) No. The continuous wrapping would be required for a grease duct from a Type I hood. In discussing this situation with Dan Dittman, the State Mechanical Engineer, it is required to wrap the non-hazardous lab exhaust duct 10 feet minimum on each side of a 2 hour rated barrier. A fire damper would not be allowed at the penetration. In your case the wrap would start 10 feet from the rated wall and run continuously through the wall and up to the roof penetration. Rated barriers less than one hour are not defined. (NFPA 4.1.12, 4.1.13) 607.2.2, 510.6.1 MC 22) Performance Test Requirements for Type I Hoods (Q) What are the performance test requirements for a Type I hood? (A) Section 507.16 requires a performance test for Type I and Type II hoods. The testing for a Type I hood shall verify the makeup and exhaust air flow, proper operation, and capture and containment performance of the exhaust system. The field test shall be conducted with all appliances under the hood at operating temperatures, with all sources of outdoor air providing make-up air 23 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red for the hood operating, and with all sources of recirculated air providing conditioning for the space in which the hood is located operating. Capture and containment shall be verified visually by observing smoke or steam produced by actual or simulated cooking, such as with smoke candles, smoke puffers, etc. The test shall be witnessed by the code official or at the code official’s option by a professional engineer who shall provide certification of performance to the code official. 507.16, 507.16.1, 507.16.2 NCMC 2012 CHAPTER 6 DUCT SYSTEMS 1) Plenums versus Habitable Rooms (Q) Would a habitable room be considered a plenum if it is used as part of the return air path from an adjacent habitable room or would a habitable room be considered a plenum if an HVAC unit with a free return is located within the room? (A) No, Section 602.1 and Section 202 define a plenum as an enclosed portion of the building structure that is designed to allow air movement and thereby serve as part of an air distribution system. Plenums are limited to uninhabited crawl spaces, areas above a ceiling or below the floor, attic spaces, and mechanical equipment rooms. The code does not consider a habitable room intended for human occupancy containing air handling equipment with a free return to be a plenum space. 602.1 NCMC 2012 2) (Q) DOI, September 1, 2011, 2012 MC If two or more air-handling systems serve a common space and one or more of these systems serve additional spaces and the aggregate capacity of the combined systems exceeds 2,000 cfm, what are the requirements for smoke detectors per Section 606.2.2? (A) Section 606.2.2 requires that when two or more air systems serve common supply or return ducts or plenums with a combined design capacity greater than 2000 cfm, the return system shall be provided with smoked detectors. Section 606.2 states that smoke detectors are not required where the air distribution system is incapable of spreading smoke beyond the closing walls, floors and ceiling of the room or space in which the smoke is generated. If two or more systems serve a common space, but do not share common ducts or plenums, and each system has a design capacity of 2,000 cfm or less, no smoke detector is required. If their combined design capacity is > 2,000 cfm, and no single unit has a design capacity of 2,000 cfm or more, no smoke 24 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red detector is required because they do not share common ducts or plenums. If multiple systems share common ducts or plenums and the distribution system is incapable of spreading smoke beyond the enclosure of the room or space where the smoke is generated, and then no smoke detector is required. Keywords: smoke detection system control. 602.2, 2012 MC 3) (Q) Is painting exposed galvanized duct allowed by code for weather protection? (A) Weather protection would not be required if the ductwork installation is approved by the manufacturer for outdoor locations. Ref: 303.6, 603.1, MC 2012 4) (Q) Does a filter box have to be manufactured of can it be constructed in the shop of the Mechanical Contractor? (A) The Mechanical Contractor may construct the box to meet the code. 603.1, 2012 MC 5) Flexible Air Duct and Air Connector Ground Clearance (Q) May flexible air ducts or flexible air connectors be run in contact with the polyethylene installed as a ground cover in a crawl space? (A) No, Section 603.14 requires that flexible air ducts and connectors not be located in or within 4 inches of the earth. This would apply to duct installations in crawl spaces where the ground is or is not covered with polyethylene. 603.14 NCMC 2012 6) (Q) If I have a newly construction house that also has a finished garage that will be used for a sales center for X amount of years and we run R4.2 flex in the ceiling of the 1st floor and a section of it passes through the conditioned garage ceiling, does the R4.2 flex have to be R-8? It's technically in conditioned space is it not? (A) If the garage is converted back to a garage then R8 insulation will be required as a minimum. Section 604 (2012 NCMC) , 405.2 (2012 NCECC) 7) (Q) Two HVAC units are located in an equipment room with one hour fire rated walls. One wall of the equipment room is common to the corridor wall. The supply and return ducts both penetrate the membrane of a floor/ceiling assembly in the equipment room then turn horizontally and penetrate the wall of a fire/smoke rated corridor. 25 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red How should the floor/ceiling membrane be protected? How should the corridor wall penetration be protected? (A) The penetration at the membrane should be a rated dynamic fire or radiation damper approved per UL 555 or UL 555C. The penetration at the corridor wall should be protected by a fire/smoke damper. Ref: 607.3.1, 607.3.2.3, 607.5 (2012 NCMC) **Questions 6, 7, and 8 are from questions directed to the Ruskin fire damper manufacturer representative in the May 29th consistency team meeting. 8) (Q) The first question relates to membrane penetration of a floor /ceiling assembly (not a through penetration). We are looking for a radiation damper as specified in UL 555 C with a one hour rating. We cannot find a radiation damper with dynamic closure in one hour. We know they come in 3 hour radiation dampers but they are cost prohibitive to install in a one hour membrane. Does any manufacturer produce the one hour dynamic radiation damper? (A) Currently, there are no damper manufacturers with a dynamic rated UL 555C ceiling tested radiation dampers. However, the test standard has recently added criteria addressing this matter (see below in RED). In regard to the 3-hr radiation damper being cost prohibitive for a 1-hr membrane, are you referring to wood-constructed ceilings or non-wood constructed? Yes. UL 555C 1.3.1 The fire performance measured by ANSI/UL 263 is based upon air movement being stopped at the start of a fire. Ceiling dampers and ceiling air diffusers intended for use in HVAC systems where the airflow is operational at the time of a fire, such as in a smoke control system, or from other situations in which the fan system is operational at the time of a fire are investigated for dynamic closure. Ceiling dampers and ceiling air diffusers intended for use where the air movement is effectively stopped at the start of a fire are not required to be investigated for dynamic closure. 9) (Q) The topic of UL 555 C was brought up as the required listing for radiation type dampers. It was stated the UL 555 C test was not in the new 2012 North Carolina Mechanical Code. Is this testing still required? 26 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red (A) Yes the test is still required. The 2012 NC Mechanical code still specifies UL 555 C as the radiation damper test (607.3.1 2012 code) and dynamic closure is required where air would still be flowing in the opposite direction of the installation of the radiation damper in a fire condition. 10) (Q) In the example given in class there was concern when the round base of the radiation damper was egg shaped after installation. Inspectors typically find this installation problem. Contractors typically used caulk instead of squaring up the roundness of the damper base. How should this be properly corrected? (A) Ruskin would suggest that the damper be “worked” back into shape by the contractor to avoid the use of caulks and to ensure blades close freely and are not obstructed. 11) (Q) There are existing apartment complexes that are currently permitted and many new apartments under construction. Can you clarify how plan reviewers and inspectors should handle these situations? (A) Yes. See interpretation below. Problem: Static radiation dampers installed in the supply duct at the ceiling penetration of floor/ceiling assemblies in apartment buildings. The particular installation was not code compliant because a dynamic fire radiation damper would be required by UL 555C. Per UL 555C air flowing against the static radiation damper from the air handler could cause the damper to fail open and spread smoke to other areas of the apartment through the supply duct system. Initial solution approved by the department: Install a dynamic, shutter type, damper at the ceiling penetration. A dynamic fire radiation damper could not be found for the installation that met the manufacturer’s installation requirements for the floor/ceiling assembly membrane penetration. Part of the approval for the Lloyd and Metal-Fab one hour dampers included an approved mounting detail for the floor/ceiling assembly membrane since no manufacturers installation detail was shown to meet the actual installation. A Mechanical Engineer from the project A/E firm provided the installation detail. We also required a smoke detector as an extra measure of safety to shut down the unit and required it to be tied in to the apartment smoke detector system. 27 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red DOI ruling: The procedure above was used for a period of 3 or 4 months from January to April on two apartment complexes. Prior to April 10th 2012 we contacted Dan Dittman the Mechanical Chief for DOI. He informed us that we had to use a manufactured, approved, UL 555C dynamic radiation damper in the supply duct penetration. Mr. Dittman assisted in a search for the code required damper but one could not be found for any manufacturer. Once this exercise was completed to his satisfaction Mr. Dittman did consent to allow a standard static radiation fire damper with a means to shut the unit down to stop air flow from the supply fan. Mr. Dittman approved the use of a smoke detector to shut the unit down. He also informed us we could no longer use the Lloyd or Metal-Fab dampers in the membrane penetration of the floor /ceiling assembly. Mr. Dittman ALLOWED the individual apartment buildings that were already under construction as of April 10th, 2012 to complete the building using the Lloyd/Metal-Fab dampers with smoke detectors as originally approved. Current approved methods: Currently, individual apartment buildings that started construction after April 10th 2012 are required to use a one hour dynamic radiation fire damper to meet 607.3.1 and 607.6.2.1 of the NC 2012 Mechanical Code. A 3 hour dynamic radiation damper may also be used that will meet the code requirements. If a one hour dynamic radiation damper is not manufactured and available on the open market the approved alternate method is as follows: use a standard static one hour radiation damper that meets 607.3.1 and 607.6.2.1 NCMC 2012. The alternative requirement includes a Smoke Detector either installed in the return at the unit or located just outside the closet of the HVAC unit to shut the unit down. The smoke detector located outside the unit enclosure shall be a 120 volt smoke detector with battery backup. The detectors are not required to be tied into the apartment smoke detector system. Willis W. Horton, MCP, CBO Plumbing /Mechanical Code Administrator Code Enforcement Department 700 N. Tryon St. Charlotte, NC 28202 Phone: (704) 336-4301/E-mail: Willis.Horton@mecklenburgcountync.gov 12) Fire Damper Access Requirements 28 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red (Q) May flexible duct be allowed to be removed as a method to provide access to fire dampers as a substitute for fire damper access doors? (A) No, flexible duct is not allowed to be removed as a method to provide access to fire dampers as a substitute for fire damper access doors. Access means must be provided without requiring disassembly of the duct system. Section 607.4 identifies specific requirements for fire damper access. 607.4 NCMC 2012 13) (Q) What method can be used to protect the openings in a floor/ceiling or roof/ceiling assembly where supply air duct from the HVAC unit penetrates the membrane of the assembly? The type of occupancy is R2 multi-story with type V construction. Note: The Mechanical Code calls for either a shaft, 607.6.2 #1, or a listed ceiling radiation damper installed at the ceiling line, 607.6.2 #2, and a listed ceiling radiation damper installed at the diffuser with no duct attached 607.6.2 #3 (supply plenum). (A) There is an issue that needs to be addressed with 607.6.2 #2. UL 555C and 607.3.1 would require the radiation damper to have dynamic closure because the unit fan will continue to run in a fire or smoke condition. 607.3.1 States; “Only fire dampers listed or labeled for dynamic systems shall be installed in heating, ventilating, an airconditioning systems designed to operate with fans on during a fire.” There is no shut down required by code for the fan of an air handler in an apartment HVAC system for example, therefore, the code and UL 555C require a dynamic type damper for this installation. Per current DOI information a dynamic radiation damper listed for mounting in the membrane ceiling of the penetration shall be used. As an alternate method the air handler must be shut down in case of fire. This can be accomplished by installing a smoke detector in the room adjacent and open to the air handler. You are no longer required to tie it into the smoke detector system of the apartment unit. If you opted for the smoke detector you still are required to protect the penetration with a radiation damper, however, since you have provided a means to shut the air down via the smoke detector you can install a standard radiation damper with static and not dynamic closure. These are the only two methods approved at the present time. Ref: 607.6.2 #2, 607.3.1, UL 555 C, 2012 MC CHAPTER 11 REFRIGERATION 29 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red 1) (Q) What is the proper procedure to use for changing out the outside condenser only in a mixed system where the old evaporator continues to be used? Current system refrigerant is R22 and the new refrigerant will be R 407 C. (Both are Class A1) (A) Recovered refrigerants shall meet 1102.2.2.2 requirements. 1101.8 notification of code Official of change of refrigerant. 105.5 equipment re use. 304.1 manufacturers data req’d. See also 301.1.1, All references in this answer are from the 2012 MC . ENERGY CONSERVATION CODE 1) (Q) What are the plan review requirements for compliance with the new energy code when a plan is submitted for an addition to a single family home to RTAC? The contractor is submitting plans for an addition. The plans show extending the existing duct and using the existing HVAC system. (A) RTAC will not be checking the plans for energy code requirements. 2) (Q) What tools are currently available to help inspectors with Energy Code field compliance? (Ref. Dept. of Energy information below, will discuss DOI information under training information later on the agenda) (A) Per the meeting on energy code on Friday May 18th at the Dept of energy site has both a residential and commercial checklist for the IECC codes. See the link below. http://www.energycodes.gov/arra/compliance_checklists.stm 3) (Q) Can a two-story single family dwelling be considered a single HVAC zone? (A) Yes, subject to a conditional performance requirement. A “Zone” is defined in Chapter 2 as: A space or group of spaces within a building with heating or cooling requirements, or both, sufficiently similar so that comfort conditions can be maintained throughout by a single controlling device. ACCA (Air Conditioning Contractors of America) Manual D “Residential 30 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red Duct Systems” indicates the maximum allowable temperature difference between any two rooms in a single zone is 4 degrees Fahrenheit. 202 Definition “Zone” NCECC 2012 4) (Q) (1) Would the 2012 Energy Code require the inspector to witness a duct leakage test for a single family dwelling? (2) Is a whole house or partial blower door test required to be witnessed by the inspector? (A) (1) No. 402.4.2 EC (2) Yes. 4032.2 EC 5) (Q) Does Section 403.1.2 of the 2012 NCSECC require the use of an outdoor thermostat as a means to prevent supplemental heater operation when the heat pump alone can satisfy the heating load for a single family dwelling? (A) Yes, Section 403.1.2 requires a two-stage thermostat with set points that control supplementary heating on the second stage (lower set point) and compression heating on the first stage (higher set point). Standard heat pump thermostats supplied by heat pump manufacturers meet this requirement. Use of an outside thermostat wired in series with the second stage to lock out the supplemental heating when the heat pump alone can meet the heating load is an additional energy conservation measure and is a new requirement in the 2012 NCECC. 403.1.2 NCECC 2012 6) Partial Replacement of a Split System Heat Pump or Air Conditioner (Q) When the outdoor section of a split system residential heat pump or air conditioner must be replaced, is the replacement equipment required to perform at the current efficiency requirements for a new system? Also, what is the inspector’s responsibility for the replacement equipment? (A) No, it has been common practice for many years for an outdoor section of a split system residential heat pump or air conditioner to be replaced due to failure while retaining the indoor section since it remains suitable for continued use. The outdoor section may be replaced without requiring replacement of the indoor section given the replacement outdoor section is compatible with the indoor section and the pair will function acceptably together as a system. The inspector is responsible to assure that the replacement equipment is installed in accordance with the manufacturers installation instructions. Because the system is not replaced in whole, the 31 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red efficiency requirements for a new system do not apply. This interpretation follows from a special joint meeting with the Mechanical Committee Chairman of the NC Building Code Council, Dept. of Insurance management and staff, inspectors from various jurisdictions, and the State Board of Plumbing, Heating, and Fire Sprinkler Contractors. 503.2.3 NCECC 2012, 301.4 NCMC 2012 7) Unlisted Duct Tape for Sealing Commercial Duct (Q) For commercial buildings, can unlisted duct tape be used to seal metal ductwork? (A) No. For commercial buildings, Section 503.2.7 requires compliance with Section 603.9 of the 2012 NC Mechanical Code. Section 603.9 of the NC Mechanical Code requires duct tape to be listed and labeled. 503.2.7 NCECC 2012 8) Process Refrigerant Piping Insulation for Commercial Buildings (Q) Do the piping insulation requirements of Section 503.2.8 apply to process refrigerant piping such as for refrigerant piping for walk in coolers or open case coolers in grocery stores? (A) No, the refrigerant piping insulation requirements in Section 503.2.8 apply only to piping serving as part of a building HVAC system. Process piping associated with other refrigeration processes are not within the scope of the NC Energy Code. However, the NC Mechanical Code, Section 1107.4 requires that process refrigerant piping that will reach a surface temperature below the dew point of the surrounding air, and is located in spaces or areas where condensation will cause a safety hazard to the building occupants, structure, electrical equipment, or any other equipment or appliances, shall be protected in an approved manner to prevent such damage. This may be accomplished by installing adequate insulation to prevent condensation. 503.2.8 NCECC 2012 GENERAL INFORMATION (Admin. Code/ Mech. Code Admin. Section/ Policy) 1) (Q) Are permits required for B vents when a re-roof permit is pulled for a building with gas flues penetrating the roof? 32 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red (A) Yes. Alteration of the vent will require a permit. Ref: (102.1/GS 87-21/GS 153-327 Admin. Code), (102.9 2012 MC). A letter is on the Meckpermit.com web site under the Mechanical Section click on “news and updates” there is a link on that page for the reroof permit requirements. 2) (Q) Unitary equipment is being installed in a hotel room. E.g. ptac unit in a hotel. Are permits required for this installation? (A) If this is a like for like change out permits are not required. If it is a new installation it should have permits and inspections if it has a hidden drain/ electrical connection. Ref: 106.1 Administrative codes. 3) (Q) What types of installations do not apply to a refrigeration trade or business and are not required to be installed by a refrigeration contractor? (A) House Bill 1105 was recently passed by the General Assembly and signed into law by Governor Perdue. Changes to the law are summarized as follows: Section 1 provides that “refrigeration trade or business” does not apply to the following: (1) The installation of self-contained commercial refrigeration units equipped with an original equipment manufacturer (OEM) molded plug that does not require the opening of service valves; (2) the replacement of lamps, fuses and door gaskets; and (3) the installation and servicing of domestic house-hold self-contained refrigeration appliances equipped with an OEM molded plug connected to suitable receptacles which have been permanently installed and do not require the opening of service valves. 4) Situation per Designer: A couple of weeks ago we discussed an old (approx. 35 years) building (approx. 15,000 sq. ft.) utilizing the original hallway for the return. The ceiling is extremely tight and there is no real room or access or practical method for adding a return duct. It is served now by a couple of self-contained single zone units utilizing boiler hot water and condenser water. We want to replace the ancient units with split systems with the AHU installed in the same mechanical rooms, with condensing units on the roof and utilizing the same single zones – no changes to ductwork. There is really no other practical/efficient/cost effective way to replace the ancient units and get rid of the ancient boilers and cooling towers. We know we need to submit the mechanical, electrical, and structural but really need to know about the hallway return before we spend a lot of effort and money. When we 33 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red talked before you indicated that this hallway return could be grandfathered since it is very close to being like-for-like and there is no work other than replacing the central unit. 4)(Q) Can we still utilize the hallways for returns? (A) Yes. Since you are doing away with an ancient cooling tower and boiler you we will need a split system with a condenser on the roof. There will be no changes outside of the mechanical room and roof. The installation will be allowed per the conditions specified. 105.3, 2012 MC 5) (Q) What are the current requirements for installing Carbon Monoxide detectors in residential single family dwellings, duplexes and townhomes? Is the requirement the same for commercial construction? (A) In general, a change out of fossil fuel equipment in a residence will require the addition of a Carbon Monoxide Detector per GS. CO2 detectors are currently required adjacent to each sleeping area per BCC rules. An all electric residence is exempt unless they currently have an existing attached garage or are adding a new attached garage or have or are adding a fireplace. If these conditions are present Carbon Monoxide Detectors are required even if they do not have fossil fuel equipment. Fossil fuel fired equipment such as a hot water heaters in a hut attached to the house are exempt from the CO2 detector requirements, however, a gas pack or other appliance that is communicating with the inside of the house is not exempt. The “special exemptions” only apply to single family dwellings, duplexes and townhomes. Not required for commercial occupancies. If a “plug in type or table model” Carbon Monoxide detector will be used the inspector shall have ready access to the detector on the premises. It must be in the box and readily accessible for the inspector. Having an empty box for the inspector or taping a box to the inside of a window is not acceptable. 6) (Q) I would like to get some information from you concerning our HVAC unit replacements. We currently manage 3 apartment communities in Charlotte and we are considering trying to have one of our more experienced technicians get a NC license so we can obtain permits and change out the units ourselves. I contacted Mr. John Todaro of the NC licensing board and he indicated that once qualifications and fees were met and the 34 4th Quarter Land Use and Environmental Service Agency (Code Enforcement) st NC Mechanical Code 2012 1 Qtr. 1/1/12-3/31/12 Q&A in Brown, 3rd Qtr. 7/1/12-9/30/12 Q&A in blue 2 nd Qtr. 4/1/12-6/30/12 Q&A in green, th 4 Qtr. 10/1/12-12/31/12 Q&A in red State exam passed that our tech could get a H3 Class 1 license and that would meet the State requirements. My question is if there is additional licensing that Mecklenburg County would require? (A) We would require a qualified individual to be at the site to answer questions from the inspector. A journeyman tested and certified through Mecklenburg County would meet the requirements if the contractor cannot be on the job site. 7) (Q) I have a question about existing equipment. The home owner wants to relocate the existing air handler in the basement. We are moving the air handler from one room to another and adjusting the duct work accordingly. I know the duct work that I install to make the adjustments will have to meet today’s code, but the equipment runs both the main level and basement and is not zoned. Will I be required to zone this existing system? Again, I am only moving it from one room to another which is 8’ away from its current location. (A) You would not be required to zone the new equipment it would be similar to a like for like change out. 102.4 (2012 NCMC) 8) (Q) Would a mechanical permit be required for replacing diffusers only? The project involves making a duct connection to the new diffuser and sealing this connection. (A) Yes. This is considered new work not maintenance. GS 87-21 # 5 35 4th Quarter Land Use and Environmental Service Agency