NC Fuel Gas Code 2011 Attention: Denotes a new question from the most current month! Denotes a revised/revisited question. September 2011 Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Chimneys & Vents Chapter 7 Gaseous Hydrogen S. POLICY Chapter 2 Definitions Chapter 4 Gas Piping Install. Chapter 6 Specific Appliances. Chapter 8 Ind./Special Waste OTHER Chapter 1 Administrative: 1) (Q) An engineer provides combustion and ventilation air louver calculations on a Mechanical Plan for an equipment room with both oil and gas fired equipment. Can the plans examiner accept the calculations as an alternate design? (A) Yes. The plan reviewer would need to decide if the calculations and louver Meet the equivalency test per 105.2. 2) (Q) A Mechanical Inspector is inspecting a furnace change out which did not require plan review. He notices the new furnace is significantly heavier that the old unit that has been replaced. Can the inspector pass the inspection as is? (A)The inspector can use his discretionary powers as a sworn official of the state in one of three ways. 1. He can determine that the weight of the unit is sufficiently supported as installed and approve the inspection as is. 2. He can turn the unit down until he receives a letter from a structural engineer that the installation is supported per code. 3. He can require plans to be submitted with structural information about support of the unit to be approved by plan review. Ref: 107.3 NCSBC; Admin. Code. Chapter 3General Regulations: 1) Q) The installation instructions for an 80 percent furnace cautions against providing combustion air from areas such as laundry rooms. The manufacturer states that installation of a furnace adjacent to laundry equipment can lead to premature corrosion from chemicals in laundry detergents. Would it be acceptable to draw combustion air from an open basement or garage, which by definition is not a confined space, even though laundry equipment is also located in that space? A) The unit must be installed according to manufacturer's specifications; however, as long as it is not in a confined space and the area can provide adequate combustion air, the installation described above would not be an issue. The intent of the manufacturers' caution statement is to address a small room specifically designated as a laundry room. 303.1 3rd Quarter Land Use and Environmental Service Agency (Code Enforcement) NC Fuel Gas Code 2011 Attention: Denotes a new question from the most current month! Denotes a revised/revisited question. September 2011 2) Q) At the final inspection the mechanical inspector finds the 3rd party label is missing from a gas regulator. The contractor tells the inspector that the factory “self certifies” the regulator to meet the ASTM requirements and presents a letter from the factory verifying the product has been tested at the factory. Should the inspector approve the regulator “as is” and final the inspection? (A) The field inspector should turn the regulator down until it can be determined if the product meets the ASTM standard specified by the code with the proper label from the testing lab. Per the Department of Insurance a factory is not allowed to “self certify” a product. It must have the listing and labeling information from an approved testing facility. Approved facilities can be found on the DOI web site. Ref: 301.3, 301.5 3) (Q) A gas appliance has been changed out “like for like” in a residential single family dwelling, however, it is located in a closet opening directly into a bathroom. The closet door is not louvered; however, the door has been undercut. Can this change out be approved by the inspector without additional changes? (A) No. Combustion and ventilation air shall come directly from the outside and the door shall be weather stripped with a self-closing device. In addition the closet cannot be used for any other purpose. Ref: 303.3, exception # 5 4) (Q) A boiler requires a barrier separation per the NC Building Code. The boiler is gas fired and exceeds 15 PSI and 10 Boiler Horsepower. What code requirements would the boiler have to meet to be approved for minimum combustion and ventilation air requirements? (A) Combustion and ventilation air shall be calculated per Section 304 of the NC Fuel Gas code. If the boiler is regulated by the NC Department of Labor per GS 95 and different criteria exist for combustion and ventilation air then either code calculation is acceptable as meeting minimum code requirements. Chapter 4 Gas Piping Installation: 1) (Q) When and where are sediment traps required? A) Section 408 requires a sediment trap as close as practical to the inlet side of the equipment. This would include gas regulators. Regulators for individual appliances may utilize a single trap for both the regulator as well as the appliance. Illuminating appliances, ranges, clothes dryers, gas logs, log lighters and outdoor grills are exempt from traps. Ref: 408 2) (Q) May a flexible gas connector run through the appliance housing? A) No! Ref: 411.1.3.3 3rd Quarter Land Use and Environmental Service Agency (Code Enforcement) NC Fuel Gas Code 2011 Attention: Denotes a new question from the most current month! Denotes a revised/revisited question. September 2011 3) 3rd Quarter Land Use and Environmental Service Agency (Code Enforcement) (Q) A home inspector has disapproved the material for a “T” fitting in a gas line stating in his report: “There is a galvanized “T” fitting in the gas line at the first floor furnace. This is not an acceptable material for gas piping. The galvanizing will flake off and cause problems with the gas equipment. I recommend correction by a qualified plumber.” Is this a correct call by the home inspector? (A) NO. Galvanized pipe and fittings are an approved material. See material listing. Re: Section 403. Chapter 5 Chimneys and Vents: 1) (Q) I am terminating a direct vent appliance on the exterior wall of a residential building. The fireplace I am venting is on the same wall as the porch. The porch is open on three sides and the termination cap provides adequate protection for the vent opening. Am I allowed to install this per code? A) Yes. A venting system shall be designed and constructed so as to develop a positive flow adequate to convey flue or vent gases to the outdoor atmosphere. Once a deck is completely covered and/or screened in, it now could be an occupied space and would no longer be considered outdoors. We have to depend on the field Inspector to make an informed judgment. There are special circumstances where this would be allowed. If the manufacturer’s instructions allow the installation on an open porch (3 sides) and the termination vent is protected the installation may be allowed. Ref: 503.3 2) (Q) Screws in venting: Are they necessary? For example, in type B venting. A) No. Some Manufacturer’s instructions actually allow screws at joints as long as 3 they do not penetrate past the outer wall of the B vent. Ref: 503.6 3) (Q)Under what circumstances, if any, may gas appliance connectors pass through the following? (a) An appliance housing. (b) A factory built fireplace. (c) A floor. (d) A wall. (A) (a) If the appliance housing is listed and approved for the vent material passing through the housing. (b) Similar to answer (a) Ref: 501.7.2 3. (c) & (d) Not allowed. Single Wall Connector Ref: 503.10.14, (see exceptions) Medium heat connectors. Ref: 503.10.16 4) (Q) A Mechanical Contractor has insulated the vent for a 90+ furnace within an unconditioned space in a single family home. Should the Mechanical Inspector turn him down? The contractor tells the inspector the requirement is in the manufacturer’s instructions. (A) The inspector would have to approve the installation if the contractor is correct about the manufacturer’s instructions. The inspector can still call the manufacturer for clarification. Ref: 503.4.1, 503.4.2 NC Fuel Gas Code 2011 Attention: Denotes a new question from the most current month! Denotes a revised/revisited question. September 2011 Chapter 6 Specific Appliances: 1) (Q) I want to install code approved unvented gas logs in a commercial restaurant that seats 100 people. Can this appliance be installed in an assembly occupancy? A) No. Unvented room heaters shall not be installed within Groups A, E, and I Occupancies. Ref: 621.4 (FGC) 2) (Q) A new 5 million BTUH instantaneous water heater is being installed in an existing food processing plant. The water heater is located in an existing pump room that also contains electrical panels. The pump room area is 1000 square feet. Combustion and ventilation air openings are installed high and low and meet code sizing requirements. Does the pump room have to comply with the boiler room requirements of [B] 1015.3 for egress? A) Yes. At 15.1 Boiler Horse Power it will require two remote exit doors per the Building Code. 3) (Q) What is the BTUH conversion factor for BTUH to Boiler Horse Power? A) One boiler horse power equal 330,000 BTUH. 4) (Q) Are there other factors or trade requirements that may be effected by the installation of the boiler in the pump room? A) Inspectors should be aware of clearance to combustibles. Ref: 631.3. (FGC) 5) (Q) When the stamping on a pressure-retaining item becomes indistinct or the nameplate is lost, illegible, or loose, but traceability to the original pressureretaining item is still possible, can a new nameplate be made and attached to anexistingboiler? Answer: Yes. All re-stamping must be done in accordance with the original code of construction. Requests for permission to re-stamp or replace nameplates must be made to the jurisdiction in which the pressure-retaining item is located. The jurisdiction may grant such requests if satisfied with the information submitted. Permission from the jurisdiction is not required for the reattachment of nameplates that are loose or not fully attached. When traceability cannot be established, the jurisdiction must be contacted. Ref; 105, 301.4, 631.1, 631.2 6) (Q) I am a homeowner and I have built a new home. I am selling my existing home which is being moved off site to make way for a new highway. The gas water heater is only 2 years old. I am going to re-locate it to my new residence. I am doing all of the work myself. Is this allowed in Mecklenburg County? 3rd Quarter Land Use and Environmental Service Agency (Code Enforcement) NC Fuel Gas Code 2011 Attention: Denotes a new question from the most current month! Denotes a revised/revisited question. September 2011 (A) Yes. You must pass the homeowners test and pull all required permits. The installation must meet current code. Ref: 102.7, 624.1 3rd Quarter Land Use and Environmental Service Agency (Code Enforcement) NC Fuel Gas Code 2011 Attention: Denotes a new question from the most current month! Denotes a revised/revisited question. September 2011 4th 3rd 2nd 1st Note: The questions above are color coded to identify the quarter of the calendar year that questions were completed. Quarters color coded L to R, 1st, 2nd, 3rd, and 4th. 3rd Quarter Land Use and Environmental Service Agency (Code Enforcement)