MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement 2015 August Consistency Questions/Topics a. Customer Service Discussion b. CMS units, modular labels needed c. Q & A 1. I have a project in plan review showing a 480v generator w/disc. on the outside of the building, it feeds a step down transformer 480delta/208y then to a disc. on the secondary side of the transformer, then a 3 pole transfer switch before it enters the building where the service equipment main is located. All grounding takes place at the transfer switch. Does this require a service disconnect ahead of the transfer on the utility side? How should the transformer ground be treated? -BARNES 1 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement We will need service ocp adjacent to the transfer switch (NEC 230.91) and GEC will be established at the point of service as allowed (NEC 250.24 (A) (1)). The transformer ground can be tied into the GEC at service or can be bonded at transfer switch (NEC 250.30). 2. Can I support MC cable off of EMT? - DELLINGER NO. Not if both carry nominal voltages (NEC 300.11 (B)). There are limited exceptions. 3. I ran my GEC from the transformer to the building steel in EMT - the inspector made me bond both ends of the EMT - was she correct? HARTMAN Yes, the inspector is correct! NEC 250.64 (E) has the answer and requires both ends to be addressed. 2 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement 4. Do all residential sewer lift stations need separate permits pulled or can it be listed on the house permit? -KING A permit can cover whatever the scope of the work is as shown on the plans or documentation if issued correctly. 5. Where does it say I have to have 2 circuits for these pumps? - MULLIS The plumbing code in 712.3.4.1 requires the alarm and pump to be on different circuits. 6. On a mini-split system, do you need a disconnecting means within sight of the inside unit? – WEST Yes. Look at NEC 422.30 and 31(C) for requirements when over 1/8th hp. If the units 3 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement have a compressor and individual multiple fan units see 430.102(B) (2) Excp. 2. 7. When using the service mast as a support, 230.28 states "it shall be of adequate strength." Does this mean IMC or rigid and what would be the minimum size required? - MULLIS Per power company regs, rigid 2” is required. The county agrees with this standard. 8. I'm changing out a residential sub panel to a larger one for the new loads on an addition. The only place I can put this panel is in a closet or in the stairway. Is either of these places acceptable? - BARNES NEC 240.24 controls the location. Clothing closets and bathrooms are not permissible. 4 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Stairways could be used on a landing that meets the working clearances of 110.26. 9. I was turned down the other day for not using a torque wrench on my 1200 amp OCP in my main switchboard. I tightened the lugs with a 2 ft. cheater bar on my 3/4 drive wrench! So what was the problem? - DELLINGER The contractor has this responsibility. A tug test is all we as inspectors have ever employed. We will not assume liability for correct torque. 10. While trenching a ditch I cut a #8 USE cable. The inspector turned me down and stated that I needed a splice box to repair this wire. I used a split bolt and taped the joint, then split a plastic drink bottle. I put this joint inside the bottle and filled the bottle with black tar. Why wasn't this acceptable as per 300.50 D? - HARTMAN 5 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement You must use the listed products intended for this application (NEC 110.3). 11. A. When an Isolated Ground Receptacle as described in NEC 406.3(D) are used in a commercial kitchen as described in NEC Art.100 under “kitchen” are they required to meet the requirements of NEC 210.8(B)(2)? - KING Yes. Some coolers are being found w/o compliance in the grocery stores. The key here is the definition of a kitchen. B. What if they supply power to monitors and are mounted at ceiling level? Yes! C. What if they supply power to POS equipment and are mounted underneath the counters or 6 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement inside cabinets that are not accessible to utilize for other equipment? Yes! 12. A service equipment panelboard has a 400amp main which feeds a bus that has double barrel lugs at the bottom, and then feeds two 200 amp disconnects. Is it permissible to tap directly from the double barrel lugs of a service equipment panelboard? - KING Yes as long as we meet NEC 240.21 and 250.122 (G) and 110.3. 13. I am reviewing plans for an apartment building. Disconnects for the A/C units are located behind condenser with about 2’ of clearance. (A) Are these disconnects required to the meet 7 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement requirements of 110.26? (B) Does it make a difference if they are fused or non-fused? - WEST No, they do not require servicing while energized. They must however be readily accessible if unfused (NEC 404.8) and readily accessible (NEC 240.24) if they contain OCP. These switches additionally have to meet 404.14 (A) (3). 14. Are GFCI receptacles at the rear of commercial cooking equipment, mounted strictly for the ignition of the gas appliance, considered readily accessible? The appliances are on casters and supplied with lanyards to allow movement for cleaning and accessing the back of the units? MULLIS In this case it seems the GFCI unit is accessible. See NEC 422.16 (A) (2). As long as we can 8 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement easily access the unit for test we are fine. We need to always look for the way to pass a job. The skill here is trusting our own good judgment. 15. Explain the vocabulary difference in grounding and bonding (Had one inspector approach me with this because of turn down and notes were confusing because wrong vocabulary was used). BARNES Bonded (Bonding). Connected to establish electrical continuity and conductivity. Basically bonding is done to assure a continual fault current path on all metallic components. Grounding Conductor, Equipment (EGC). The conductive path(s) installed to connect normally non–current-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both. 9 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Grounding is a backup system to operate ocp in the event the grounded conductor is interrupted or nonexistent. Grounded Conductor. A system or circuit conductor that is intentionally grounded. From Soares a) Ground; The earth b) Grounded (Grounding); Connected to Ground or a conductive body that extends to ground c) Grounded Conductor; A system or circuit conductor that is intentionally grounded 16. Is romex allowed to be used between the floor of a 2 story screen porch that has a roof on 2nd story and the floor is covered in rubber lining. The roof of the first level is covered with wood. So basically the romex is concealed. - DELLINGER 10 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement With it totally concealed from the weather we don’t see an issue per NEC 334.10. 17. Can Metallic cable be run in a carport, with open walls? – HARTMAN Perhaps. 330.10 and 330.12 qualify how it is to be used. This would depend on the specific location. Is it a wet location? Is it a position where it needs to be sunlight resistant? Is it going to be exposed to corrosion? Is it exposed to physical damage? Judgment would need to be used in determining the specific applicable conditions. 18. On a final electrical inspection, does the smoke alarm control wire, need to be terminated in the A/H unit, when a dynamic damper is not used? KING 11 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Perhaps. If required for separation requirements for building and mechanical purposes it needs to be connected. This would need to be established with the mechanical inspector if not established on the plans details. 19. When considering clearance issues for large equipment, what does unobstructed egress mean? - HARTMAN NEC 110.26 (C) (2) gives us the requirements for large equipment. The two considerations for qualifying are 1200 amps and over six feet wide. The extra requirements are for worker safety in case of an incident causing uncontained arcing. The concern is always allowing the worker clear access to escape the fault explosion and get to a safe area. Basically there may be no physical or arc fault zone interrupting the egress path. 12 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement 20. Is a baptism pool or cleansing pool covered by NEC 680? - WEST 680.1 Scope. The provisions of this article apply to the construction and installation of electrical wiring for, and equipment in or adjacent to, all swimming, wading, thera- peutic, and decorative pools; fountains; hot tubs; spas; and hydromassage bathtubs, whether permanently installed or storable, and to metallic auxiliary equipment, such as pumps, filters, and similar equipment. The term body of water used throughout Part I applies to all bodies of water covered in this scope unless otherwise amended. While we have in the past required installations to meet Art. 680 as much as possible the answer is NO per NCDOI Mr. Ron Chilton and strictly code. 21. Can I have a service at the house and a circuit from the garage service to control lighting? MULLIS 13 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Yes. See 225.30 (D). Also this would have to be identified per NEC 225.37. 22. Do all sub panels require main ocp? - BARNES The code generally requires ocp per NEC 408.36. Exceptions are allowed. When feeding different buildings or structures be sure to use other applicable references. 23. What parameters determine whether a recess light in a shower would have to be rated for a damp location or a wet location? - DELLINGER Per 410.10 D; Luminaires located within the actual outside dimension of the bathtub or shower to a height of 2.5 m (8 ft.) vertically from the top of the bathtub rim or shower threshold shall be marked for damp locations, or marked for wet locations where subject to shower spray. 14 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Each installation would have to be individually looked at with regard to shower spray. Generally it would seem that if the shower was a normal down flow head a 9’ ceiling would be out of the spray range. 24. Would a smoke detector be counted as a device when calculating box fill? - HARTMAN Not normally. NEC 314.16 shows no specific requirement for the smoke detector. B 4 does mention yoke or strap containing one or more devices or equipment. Typically the smoke detector does not mount inside the box and should not be included for fill count. 25. I was recently turned down on a ceiling inspection because I had installed smoke detectors and strobes and the inspector stated 15 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement he could not see the grommets. Is this correct? KING The inspector needs to see the rough in of the system w/o the devices installed. It is at that point he can judge the condition of the box and cables/conductors. 26. Is aircraft cable acceptable for supporting 2x4 fixtures? - DELLINGER If it meets or exceeds the strength of the #9 ceiling wire we would be fine. d. Service questions review; 16 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement A. HOW TO QUALIFY ADDITIONAL SERVICES ON BUILDING? 230.2 Number of Services. A building or other structure served shall be supplied by only one service unless permitted in 230.2(A) through (D). For the purpose of 230.40, Exception No. 2 only, underground sets of conductors, 1/0 AWG and larger, running to the same location and connected together at their supply end but not connected together at their load end shall be considered to be supplying one service. (A) Special Conditions. Additional services shall be permitted to supply the following: (1) Fire pumps (2) Emergency systems (3) Legally required standby systems (4) Optional standby systems 17 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement (5) Parallel power production systems (6) Systems designed for connection to multiple sources of supply for the purpose of enhanced reliability Section 230.2(A) is fairly straightforward and generally needs no further interpretation. Other code sections may apply specifically to them. (B) Special Occupancies. By special permission, additional services shall be permitted for either of the following: (1) Multiple-occupancy buildings where there is no available space for service equipment accessible to all occupants Section 230.2(B)(1) for decades has been permitted in Mecklenburg County as a matter of policy without written special permission for every project, provided all the 18 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement requirements for the installation of a single service were met for each additional service, and that all the mains were inside each given tenant space inside the building or structure. Where mains are grouped in the same location, either inside or outside the building or structure, we fall back to the other rules of section 230.2 to qualify for additional services and at the same time adhere to the policy that all mains are either inside or outside for a given building or structure. Section 230.2(B) (1) really doesn’t apply here because when they are grouped in one location all tenants must have access to their overcurrent protection, and this installation suggests just that. Where a second service is allowed under 230.2(B) (1) the second service must be located 19 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement a minimum of 50’ away from the first and other services. All proper service identification labeling must be done. An additional service for a house panel must go through the same qualifications per section 230.2 as any other service. A house panel is an exception to the “all mains in or out” policy in that if all mains were inside, we have allowed the house panel to be outside per the requirements of section 230.40 exception 4 and section 210.25. Please note that this is not permission for another service just because there is a need for a house panel nor is it permission to add a seventh main disconnect where you already have six. (2) A single building or other structure sufficiently large to make two or more services necessary. 20 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement To allow an additional service per section 230.2(B) (2) a contractor or designer must show how, per the size of the building or structure served, more than one service is permitted. The typical rule of thumb for this allowance is to show a 5% or greater voltage drop feeder calculation based on the location of the first service to another given point of the building or structure. (C) Capacity Requirements. Additional services shall be permitted under any of the following: (1) Where the capacity requirements are in excess of 2000 amperes at a supply voltage of 600 volts or less According to section 230.2(C)(1) when you have a load calculated in accordance with 21 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Article 220 and that load exceeds 2000 amps you may have a second service and for multiples of 2000 thereafter an additional service. All proper service identification labeling must be done. (2) Where the load requirements of a single-phase installation are greater than the serving agency normally supplies through one service. When a section 230.2(C) (2) allowance is requested the contractor or designer must provide evidence from the serving utility that they indeed can’t meet the serving requirements for a SINGLE PHASE SERVICE. Please note that this section does not address three phase services. (3) By special permission 22 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Case by case judgment. Must for some unforeseen reason not be able to be satisfied by other rules. Aligns with Admin. Code, Alternate Methods and Means (D) Different Characteristics. Additional services shall be permitted for different voltages, frequencies, or phases, or for different uses, such as for different rate schedules. This section is also fairly straightforward. Voltages used in the code are further defined in section 220.5 as follows: “nominal system voltages of 120, 120/240, 208Y/120, 240, 347, 480Y/277, 480, 600Y/347, and 600 volts shall be used.” B. HOW TO APPLY 230.40 EXCEPTION NO 2 23 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement IV. Service-Entrance Conductors 230.40 Number of Service-Entrance Conductor Sets. Each service drop, set of overhead service conductors, set of underground service conductors, or service lateral shall supply only one set of service-entrance conductors. Exception No. 2: Where two to six service disconnecting means in separate enclosures are grouped at one location and supply separate loads from one service drop, set of overhead service conductors, set of underground service conductors, or service lateral, one set of service-entrance conductors shall be permitted to supply each or several such service equipment enclosures. 24 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement One service drop supplying maximum of six service equipment enclosures grouped at one location. For the purpose of 230.40, Exception No. 2 only, underground sets of conductors, 1/0 AWG and larger, running to the same location and connected together at their supply end but not connected 25 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement together at their load end shall be considered to be supplying one service. One service lateral consisting of six sets of conductors 1/0 AWG or larger, terminating in a single service equipment enclosure with maximum of six service disconnecting means. C. Definitions 26 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Service. The conductors and equipment for delivering electric energy from the serving utility to the wiring system of the premises served. Service Cable. Service conductors made up in the form of a cable. Service Conductors. The conductors from the service point to the service disconnecting means. Service Conductors, Overhead. The overhead conductors between the service point and the first point of connection to the service-entrance conductors at the building or other structure. Service Conductors, Underground. The underground conductors between the service point and the first point of connection to the service27 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement entrance conductors in a terminal box, meter, or other enclosure, inside or outside the building wall. Informational Note: Where there is no terminal box, meter, or other enclosure, the point of connection is considered to be the point of entrance of the service conductors into the building. Service Drop. The overhead conductors between the utility electric supply system and the service point. Service-Entrance Conductors, Overhead System. The service conductors between the terminals of the service equipment and a point usually outside the building, clear of building walls, where joined by tap or splice to the service drop or overhead service conductors. 28 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Service-Entrance Conductors, Underground System. The service conductors between the terminals of the service equipment and the point of connection to the service lateral or underground service conductors. Informational Note: Where service equipment is located outside the building walls, there may be no service entrance conductors or they may be entirely outside the building. Service Equipment. The necessary equipment, usually consisting of a circuit breaker(s) or switch(es) and fuse(s) and their accessories, connected to the load end of service conductors to a building or other structure, or an otherwise designated area, and intended to constitute the main control and cutoff of the supply. 29 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Service Lateral. The underground conductors between the utility electric supply system and the service point. Service Point. The point of connection between the facilities of the serving utility and the premises wiring. Informational Note: The service point can be described as the point of demarcation between where the serving utility ends and the premises wiring begins. The serving utility generally specifies the location of the service point based on the conditions of service. Q-1. WE HAVE A 277/480 AND 120/208 SERVICE LOCATED AT THE SAME LOCATION BOTH HAVE ONLY SIX DISCONNECTS CAN WE ALLOW THIS? 30 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement VI. Service Equipment — Disconnecting Means 230.70 General. Means shall be provided to disconnect all conductors in a building or other structure from the service entrance conductors. 230.71 Maximum Number of Disconnects. (A) General. The service disconnecting means for each service permitted by 230.2, or for each set of service-entrance conductors permitted by 230.40, Exception No. 1, 3, 4, or 5, shall consist of not more than six switches or sets of circuit breakers, or a combination of not more than six switches and sets of circuit breakers, mounted in a single enclosure, in group of separate enclosures, or in or on a switchboard. There shall be not more than six sets of disconnects per service grouped in any one location. 31 MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement For the purpose of this section, disconnecting means installed as part of listed equipment and used solely for the following shall not be considered a service disconnecting means: (1) Power monitoring equipment (2) Surge-protective device(s) (3) Control circuit of the ground-fault protection system (4) Power-operable service disconnecting means A-1. Yes and no? If you qualify for a second service of differing characteristics or for over 2k amps or over normal delivery for a single phase size, the location is not restricted to 50’ separation. If you are using the multiple occupancy method the 50’ separation comes in from our “Special Permission”. All proper service identification labeling must be done. 32