ADDENDUM Page 1 of 2 To: Prospective Bidders From: Wold Architects and Engineers Date: April 27, 2016 Comm. No: 163025 Subject: Addendum No. 1 for Bidding Documents for the Masonry and Flashing Repairs at: Huntley High School, Heineman Middle School, and Marlowe Middle School Huntley Community School District #158 BIDS DUE MAY 2, 2016 AT 3:00 PM This addendum forms a part of the Contract Documents dated April 14, 2016. Acknowledge receipt of this Addendum on the space provided on the Bid Form. Failure to do so may result in disqualification of Bid. This Addendum consists of two (2) typed sheets and attachments: Sheets: A1.53, A2.01, A2.03 and A3.01 PROJECT MANUAL 1. SPECIFICATION SECTION 01 11 00 SUMMARY OF THE WORK A. ADD Paragraph 1.07(D) as follows: “D. Immediately prior to starting work, the Owner will document the existing conditions of the building exterior and site photographically, paying particular attention to existing areas of damage. These photographs will be used to determine damages to the building and site caused by construction operations. The Contractor shall repair any and all damages to the building or site attributable to their construction operations. 2. SPECIFICATION SECTION 04 01 20 MASONRY REPAIRS A. At Paragraph 2.02 (A)(1)(b): 1) DELETE manufacturer information at Brick No. 1 and Brick No. 2. 2) ADD the following note: “The Owner will provide all Facing Brick as required for this Project for installation by the Contractor. The Owner will have the Facing Brick delivered to a single location at ground level of each building site agreeable to both the Owner and Contractor.” B. At Paragraph 2.02 (A)(2)(b): 1) DELETE manufacturer information at Split-Face Concrete Block. ADDENDUM Page 2 of 2 2) ADD the following note: “The Owner will provide all Split-Face Concrete Block for this Project for installation by the Contractor. The Owner will have the Split-Face Concrete Block delivered to a single location at ground level on the building site agreeable to both the Owner and Contractor.” C. ADD Paragraph 2.02 (A)(3) as follows: “3. Smooth-Face Concrete Block a. Quality: 1. Hollow loadbearing units: ASTM C90, Grade N-1, normal weight. Type I. 2. Concrete building brick: ASTM C55, Grade N, normal weight. Type I. b. Prism strength: f'm = 1,500 psi. c. Shapes: Provide plain shapes in dimensions as required.” D. ADD Paragraph 3.06 (Q) as follows: “Q. At locations where new veneer units will be concealed behind new or existing roof membranes, provide smooth-face concrete block in lieu of brick or split-face block. Field-coordinate locations.” SHEETS 1. SHEET A1.53 MARLOWE MIDDLE SCHOOL ROOF PLAN A. Sheet reissued by this Addendum. Extent of Base Bid through wall flashing repair work clarified. (Dashed lines that could be interpreted to be through wall flashing repair work have been removed.) 2. SHEET A2.01 HEINEMAN MIDDLE SCHOOL EXTERIOR ELEVATIONS A. Sheet reissued by this Addendum. A detail reference E4/A3.01 and note has been added to Drawing B7 on this sheet. 3. SHEET A2.03 MARLOWE MIDDLE SCHOOL EXTERIOR ELEVATIONS A. Sheet reissued by this Addendum. A detail reference E4/A3.01 and note has been added to Drawing F2 on this sheet. 4. SHEET A3.01 TYPICAL DETAILS A. Sheet reissued by this Addendum. 1) At Drawing F1 a note describing brick and architectural precast salvage requirements has been revised. 2) Drawing E4 has been added to the sheet. END OF ADDENDUM #1 1 2 3 4 5 6 7 8 MASONRY AND FLASHING REPAIRS AT: HUNTLEY 123 Elm St. Anytown, USA 12345 HIGH SCHOOL, HEINEMAN MIDDLE SCHOOL, AND MARLOWE MIDDLE SCHOOL A HUNTLEY COMMUNITY SCHOOL DISTRICT #158 650 Academic Drive Algonquin, IL 60102 IL B C 1 1 1 31204 TYPICAL OF (2) LOCATIONS 31203 31202 D TYPICAL OF (3) LOUVERS ON THIS WALL ELEVATION SIM (AT LINTEL ABOVE DOOR) 31203 31201 31209 C1 ______ A3.01 C1 ______ A3.01 Central: L:\SD_Huntley\163025_Masonry and Flashing Repairs\163025_masonry and flashing drawings (central).rvt 4/27/2016 2:45:35 PM C:\Users\pjegan\Documents\163025_masonry and flashing drawings (central)_jlafrenz11.rvt GENERAL NOTES: 1. E 120V POWER AVAILABLE AT MULTIPLE POINTS ON ROOF. CONTRACTOR TO PROVIDE POWER CORDS AS REQUIRED. 2. POTABLE WATER IS AVAILABLE AT MULTIPLE POINTS. CONTRACTOR TO PROVIDE HOSES AS REQUIRED. 3. MASONRY VENEER UNITS TO BE REMOVED/REPLACED ARE TYPICALLY UTILITY SIZE BRICK. 4. SEE ALSO EXTERIOR ELEVATION DRAWINGS FOR WORK AT EXTERIOR WALL OF THE BUILDING. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed ARCHITECT IL under the laws of the State of Registration Number TEDD STROMSWOLD 001-020603 Date 4/8/2016 Revisions MIDDLE SCHOOL ROOF LEGEND Description Addendum 1 XXXXX F2 MARLOWE MIDDLE SCHOOL ROOF PLAN 1" = 20'-0" X XXXX 0 15' Date April 27, 2016 Num 1 DENOTES IMAGE INCLUDED WITHIN PROJECT MANUAL (AND WORK DESCRIBED THEREIN). DENOTES DETAIL OF CONSTRUCTION INCLUDED ON DRAWING SHEET. Comm: 163025 Date: 4/14/2016 DENOTES THROUGH WALL FLASHING REPAIR WORK TO BE INCLUDED IN BASE BID. SEE TYPICAL DETAILS C1/A3.01 & D4/A3.01 Drawn: JRK Check: TS 30' North MARLOWE MIDDLE SCHOOL ROOF PLAN A F Scale: As indicated A1.53 1 2 3 4 5 6 7 8 MASONRY AND FLASHING REPAIRS AT: HUNTLEY 123 Elm St. Anytown, USA 12345 HIGH SCHOOL, HEINEMAN MIDDLE SCHOOL, AND MARLOWE MIDDLE SCHOOL A NOTE: DIMENSION INDICATES LENGTH OF P.C. CONCRETE SECTION TO BE REMOVED AND REINSTALLED, TYP. HUNTLEY COMMUNITY SCHOOL DISTRICT #158 F1 ______ A3.01 F1 ______ A3.01 1 (14'-8") F1 ______ A3.01 (9'-8") 650 Academic Drive Algonquin, IL 60102 (10'-4") E4 ______ A3.01 TYP. IL NOTE: THIS DETAIL CONDITION (E4/A3.01) IS TYPICAL AT ALL ENDS OF PRECAST CONCRETE CAP. B B1 EAST ELEVATION 1/16" = 1'-0" B7 12' 0 24' ENLARGED ELEVATION, TYP. 1/8" = 1'-0" 0 6' 12' B7 ______ A2.01 F1 ______ A3.01 F1 ______ A3.01 F1 ______ A3.01 (40') C D1 F1 ______ A3.01 F1 ______ A3.01 (11'-8") (11'-8") (9'-8") F1 ______ A3.01 F1 ______ A3.01 (9'-8") F1 ______ A3.01 F1 ______ A3.01 (9'-8") (9'-10") (9'-8") F1 ______ A3.01 (9'-8") F1 ______ A3.01 (9'-8") F1 ______ A3.01 (13'-6") F1 ______ A3.01 (10'-4") (9'-8") WEST ELEVATION 1/16" = 1'-0" 12' 0 24' F1 A2.01 B4 A2.02 D F1 ______ A3.01 D1 A2.02 (14'-8") PENTHOUSE BEYOND F1 ______ A3.01 F1 ______ A3.01 B3 A2.02 (10'-4") (9'-8") B1 A2.02 E1 A2.02 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed ARCHITECT E1 1/16" = 1'-0" 0 12' 24' A4 A2.02 Registration Number A2 A2.02 TEDD STROMSWOLD 001-020603 Date 4/8/2016 Revisions Description Addendum 1 F1 ______ A3.01 (14'-8") F1 ______ A3.01 (14'-8") F1 ______ A3.01 F1 ______ A3.01 (11'-8") A1 A2.02 A1 A2.02 (25') D1 A2.02 A3.01 NORTH ELEVATION 1/16" = 1'-0" 0 12' Comm: 163025 Date: 4/14/2016 Drawn: JRK Check: TS Num North HEINEMAN MIDDLE SCHOOL- EXTERIOR ELEVATIONS D1 A2.02 F F1 Date April 27, 2016 (11'-10") REV F1 ______ A IL under the laws of the State of SOUTH ELEVATION B1 A2.01 E D1 A2.01 Central: L:\SD_Huntley\163025_Masonry and Flashing Repairs\163025_masonry and flashing drawings (central).rvt 4/27/2016 2:45:20 PM C:\Users\pjegan\Documents\163025_masonry and flashing drawings (central)_jlafrenz11.rvt A6 A2.02 24' Scale: E1 A2.01 ELEVATION KEYPLAN As indicated A2.01 1 1 2 3 F1 ______ A3.01 4 5 F1 ______ A3.01 7 F1 ______ A3.01 F1 ______ (14'-10") (14'-8") 6 F1 ______ A3.01 (14'-9") A3.01 (14'-10") 8 F1 ______ A3.01 MASONRY AND FLASHING REPAIRS AT: HUNTLEY 123 Elm St. Anytown, USA 12345 HIGH SCHOOL, HEINEMAN MIDDLE SCHOOL, AND MARLOWE MIDDLE SCHOOL NOTE: DIMENSION INDICATES LENGTH OF P.C. CONCRETE SECTION TO BE REMOVED AND REINSTALLED, TYP. (11'-10") (11'-10") A HUNTLEY COMMUNITY SCHOOL DISTRICT #158 650 Academic Drive Algonquin, IL 60102 A1 IL NORTH ELEVATION 1/16" = 1'-0" 12' 0 F1 ______ A3.01 F2 ______ A2.03 24' F1 ______ A3.01 (11'-10") F1 ______ A3.01 F1 ______ A3.01 (11'-10") (11'-10") F1 ______ A3.01 F1 ______ A3.01 (9'-8") F1 ______ A3.01 F1 ______ A3.01 (9'-8") (9'-4") F1 ______ A3.01 (9'-10") F1 ______ A3.01 (9'-8") F1 ______ A3.01 F1 ______ (8'-6") A3.01 F1 ______ (9'-8") A3.01 (9'-8") (5'-2") F1 ______ A3.01 (10'-4") F1 ______ A3.01 F1 ______ A3.01 (13'-6") (9'-8") (29''-6") B B1 SOUTH ELEVATION 1/16" = 1'-0" 12' 0 24' F1 ______ A3.01 F1 ______ A3.01 (11'-9") F1 ______ A3.01 (4'-8") F1 ______ F1 ______ A3.01 A3.01 (9'-8") F1 ______ A3.01 (5'-6") (14'-8") F1 ______ A3.01 (8'-7") F1 ______ A3.01 F1 ______ A3.01 (14'-4") (14'-8") F1 ______ A3.01 (10'-4") (9'-8") C C1 EAST ELEVATION 1/16" = 1'-0" 12' 0 24' F1 ______ A3.01 F1 ______ A3.01 (14'-9") F1 ______ A3.01 (14'-8") (14'-8") F1 ______ A3.01 F1 ______ A3.01 (11'-8") F1 ______ A3.01 (11'-10") F1 ______ A3.01 (11'-10") (12'-6") F1 ______ A3.01 F1 ______ A3.01 (9'-10") (25') A1 A2.03 D D1 WEST ELEVATION 1/16" = 1'-0" 12' 0 24' KEYPLAN (9'-8") F1 ______ A3.01 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed (9'-8") ARCHITECT 1 Registration Number C1 A2.03 B5 A2.04 E4 ______ A3.01 TYP. C1 A2.04 NOTE: THIS DETAIL CONDITION (E4/A3.01) IS TYPICAL AT ALL ENDS OF PRECAST CONCRETE CAP. A1 A2.04 REV 0 6' 12' Description Addendum 1 Comm: 163025 Date: 4/14/2016 Drawn: JRK Check: TS B1 A2.04 ELEVATION KEYPLAN Date Num April 27, 2016 North MARLOWE MIDDLE SCHOOL- EXTERIOR ELEVATIONS Scale: B1 A2.03 TEDD STROMSWOLD 001-020603 Date 4/8/2016 Revisions B3 A2.04 F A3 A2.04 1/8" = 1'-0" A1 A2.04 ENLARGED ELEVATION, TYP. A4 A2.04 F2 A IL under the laws of the State of E D1 A2.03 Central: L:\SD_Huntley\163025_Masonry and Flashing Repairs\163025_masonry and flashing drawings (central).rvt 4/27/2016 2:44:56 PM C:\Users\pjegan\Documents\163025_masonry and flashing drawings (central)_jlafrenz11.rvt F1 ______ A3.01 As indicated A2.03 1 1 2 3 4 5 6 7 8 MASONRY AND FLASHING REPAIRS AT: HUNTLEY 123 Elm St. Anytown, USA 12345 HIGH SCHOOL, HEINEMAN MIDDLE SCHOOL, AND MARLOWE MIDDLE SCHOOL NEW CAVITY WALL INSULATION OVER NEW FLEXIBLE FLASHING FIELD VERIFY ACTUAL CAVITY DEPTH (AT EACH OCCURANCE- DEPTH MAY VARY) CONTINUOUS STAINLESS STEEL TERMINATION BAR MECHANICALLY FASTENED @ 12" O.C., WITH MASTIC AT TOP, TYP. EXISTING CONC BLK BACK-UP WALL EXISTING CAVITY WALL INSULATION FLEXIBLE FLASHING- STOPS HORIZONTALLY UNDER TERMINATION BAR AND EXTENDS DOWN VERTICALLY AND HORIZ TO DAYLIGHT MORTAR NET A SPLIT FACE BLOCK EXISTING C. BLK BACK-UP WALL 26 GA GALVANIZED SHEET METAL CLOSURE W/ SLOPED 45 DEGREE SURFACE THRU CAVITY TO SUPPORT FLEXIBLE FLASHING. ANCHOR @ 18" O.C. TO EXISTING MASONRY BACK-UP WALL. UNDERBEND FOLDS TO ENSURE PROPER CONTACT WITH MASONRY BELOW. CELL VENT @ 16" O.C., TYP. EXISTING MASONRY VENEER EXISTING MASONRY VENEER TO REMAIN HUNTLEY COMMUNITY SCHOOL DISTRICT #158 650 Academic Drive Algonquin, IL 60102 PREFABRICATED END DAM MORTAR NET MASONRY VENEER TO BE REMOVED AND REPLACED NEW TERMINATION BAR MECHANICALLY FASTENED AT 12" O.C. IL CUT AND REPLACE EXISTING2" RIGID INSULATION WITH NEW 1.5" RIGID INSULATION TO INSTALL NEW FLASHING PROVIDE FLEXIBLE FLASHING UP AND OVER JOINT EXISTING MASONRY VENEER TO REMAIN 8" (TYP.) REINSTALL NEW MASONRY VENEER WHERE REMOVED FOR NEW WORK B 1" GAP +/- NEW GALVANIZED SHEET METAL CLOSURE BRIDGING WALL CAVITY TO PROVIDE SUPPORT FOR NEW FLEXIBLE FLASHING. ANCHOR TO C. BLK BACK-UP WALL AT 18" O.C.. UNDERBEND FOLDS TO ENSURE PROPER CONTACT WITH MASONRY BELOW. NOTE: WHERE END DAMS ARE CONCEALED BEHIND CONSTRUCTION TO REMAIN SEE F7/A3.01 PRE-FINISHED METAL RECEIVER SET RECEIVER AND SHEET METAL CLOSURE IN CONTINUOUS MASTIC BED. NEW FLEXIBLE FLASHING NEW PRE-FINISHED METAL RECEIVER SET IN MASTIC. PROVIDE MASTIC AT END LAP CONDITIONS. EXISTING ROOF MEMBRANE TERMINATION BAR 3" 7" 26 GA GALVANIZED SHEET METAL CLOSURE- LAID OVER LOWER END DAM 3" 1 1/2" CELL VENT AT 16" O.C., TYP. PREFABRICATED END-DAM NEW PRE-FINISHED METAL COUNTERFLASHING. PREFINISHED METAL COUNTERFLASHINGOVERLAP JOINTS MIN 4", ANCHOR W/ S ST SCREWS W/ NEOPRENE WASHERS @ 2'0" O.C., TYP. ROOFING SYSTEM AS OCCURS NOTE: AT SIMILAR LOCATION THE VENEER TO BE REMOVED AND REPLACED IS BRICK IN UTILITY SIZE PREFABRICATED END DAM ROOF MEMBRANE TERMINATION BAR (BY OTHERS- COORDINATE LOCATIONS WITH ROOFING CONTRACTOR) ROOFING MEMBRANE C C1 TYPICAL THRU-WALL FLASHING REPAIR DETAIL 3" = 1'-0" 3" 0 6" C4 TYPICAL THRU-WALL FLASHING AXON NOTE: INSIDE CORNERS ARE SIMILAR NOT TO SCALE PRE-FABRICATED OUTSIDE CORNER, TYP. MITERED CORNER AT COUNTER-FLASHING F1 ______ A3.01 1 NEW FACE BRICK- MATCH EXISTING JOINT PATTERN D PREFABRICATED END DAM AT END OF GALVANIZED SHEET METAL CLOSURE INSTALL BACKER ROD AND SEALANT AT CONTROL JOINT EXISTING C. BLK BACK-UP WALL CELL VENTS AT 24" O.C., TYP. PREFINISHED METAL DRIP EDGE EXISTING 4" FACE BRICK INSTALL BACKER ROD AND SEALANT BETWEEN SECTIONS OF PRECAST CONCRETE CAP TO BE REMOVED AND REINSTALLED MORTAR NET NEW TERMINATION BAR MECHANICALLY FASTENED AT 12" O.C. NEW GALVANIZED SHEET METAL CLOSURE BRIDGING WALL CAVITY TO PROVIDE SUPPORT FOR NEW FLEXIBLE FLASHING. ANCHOR TO C. BLK BACK-UP WALL AT 18" O.C.. UNDERBEND FOLDS TO ENSURE PROPER CONTACT WITH MASONRY BELOW. CELL VENT @ 24" O.C. E E4 TYPICAL CONDITION AT END OF PRECAST CONCRETE CAP 1 1/2" = 1'-0" 6" 0 1' TERMINATION BAR ARCHITECT PRE FABRICATED END DAM (FOLD) PREFINISHED METAL DRIP EDGE W/ HEMMED EDGE VENEER ANCHOR FOR EXISTING MASONRY (HB-200 OR EQUAL) AT 16" O.C., TYP. (FOLD) 4 5° NOTE: AFTER FABRICATION END DAM IS TO BE HOT-DIP GALVANIZED NOTE: SECTIONS OF PRECAST CONCRETE CAP TYPICALLY 3' LONG (FO Revisions Description Addendum 1 Comm: 163025 Date: 4/14/2016 Drawn: JRK Check: TS Date April 27, 2016 North TYPICAL DETAILS ) LD CAVITY DEPTH (x) 6" TEDD STROMSWOLD 001-020603 Date 4/8/2016 F4 ) LD O (F 45 F 3" Registration Number SOLDERED AT CUT CAVITY DEPTH (x) 0 END DAM RECESSED BEHIND OTHER MATERIAL 2" EXISTING FACE BRICK & C. BLK 3" = 1'-0" LAP UNDER SHEET METAL CLOSURE. 2" MIN. ROPE WEEP- ADHERE TO INSIDE CORNER OF FLEXIBLE FLASHING ) LD O (F TYPICAL THRU- WALL FLASHING REPAIR DETAIL AT MIDDLE SCHOOLS NOTE: FOR CLARITY NOT ALL MATERIALS ARE SHOWN. SOLDERED AT CUT EXISTING METAL AND FLEXIBLE FLASHING TO BE DEMOLISHED F1 ADDITIONAL LAYER FLEXIBLE FLASHINGFOLD TO FIT NOTE: INSIDE CORNERS ARE SIMILAR AND ARE ALSO TO BE PRE-FABRICATED WITH SOLDERED CONNECTION (FOLD) CAVITY DEPTH x2 IL under the laws of the State of 4 5° FLEXIBLE FLASHING A I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed 1 1 2" EXISTING BRICK AND ARCH PRECAST CONCRETE CAP TO BE REMOVED. SALVAGE CAP FOR REINSTALLATION AND INSTALL NEW FACE BRICK. REINSTALLED ARCH PRECAST CONCRETE CAP 2" Central: L:\SD_Huntley\163025_Masonry and Flashing Repairs\163025_masonry and flashing drawings (central).rvt 4/27/2016 2:43:37 PM C:\Users\pjegan\Documents\163025_masonry and flashing drawings (central)_jlafrenz11.rvt CUT AND REPLACE EXISTING 2" RIGID INSULATION WITH NEW 1.5" RIGID INSULATION TO INSTALL NEW FLASHING SOLDERED AT BEND 45 8" 2" TYPICAL PREFABRICATED END DAM DETAIL NOT TO SCALE F5 TYPICAL PRE-FABRICATED OUTSIDE CORNER NOT TO SCALE F7 TYPICAL CONCEALED END DAM CONDITION Scale: As indicated NOT TO SCALE A3.01 Num 1