Research Journal of Applied Sciences, Engineering and Technology 3(11): 1239-1245, 2011 ISSN: 2040-7467 © Maxwell Scientific Organization, 2011 Submitted: July 26, 2011 Accepted: September 18, 2011 Published: November 25, 2011 A New Approach to Dynamic Control of Synchronous Generator in a Bulk Electric Power System by Direct Feedback Linearization S. Sajedi, F. Khalifeh, T. Karimi and Z. Khalifeh Department of Electrical Engineering, Fasa Branch, Islamic Azad University, Fasa, Fars, Iran Abstract: Feedback linearization is a common approach used in controlling nonlinear systems. The approach involves coming up with a transformation of the nonlinear system into an equivalent linear system through a change of variables and a suitable control input. In this paper a new control structure based on the application of the method of exact linearization by Direct Feedback Linearization for a synchronous generator is presented. The power system model consists of a single axis flat rotor machine, connected to an infinite power bus. This way the sub-transient phenomena are ignored. The global system consisting of a turbine and a generator that produces the electrical output power is coupled and it presents multiplicative and harmonic non-linearities. The application of a DFL on the output voltage equation expressed as a function of the electrical system parameters referred to the generator practically turns the non linear system into two uncoupled subsystems with the possibility of independently controlling the output voltage and the frequency. Key words: Control non-linearity, fault-tolerant systems, linearization, linear optimal regulators, power systems control INTRODUCTION The design of most field excitation controllers in energy generators is based on methods that use differential geometry to solve the problems related to the non linear characteristic of the power systems (Isidori, 1989). Recently a different approach to this problem (Gao et al., 1990, 1992; Wang et al., 1993; Junco et al., 1996) which uses the method called “Direct Feedback Linearization” (DFL), has allowed the design of power systems regulators using techniques well-known in the study of linear systems. That is, starting with a high-order differential-equation model, arriving at a linear control through state variables feedback. Contrary to what is proposed in previous works (Gao et al., 1990, 1992; Wang et al., 1993; Junco et al., 1996; Matas et al., 2008), where a state feedback that exactly linearizes the relationship field voltage-electrical output power is carried out, in this paper a DFL-based design strategy applied on the output voltage equation from the generator connected to an infinite power bus, allows the implementation of a voltage linear control practically independent of the frequency modifications caused by mechanical power variations. The results obtained by means of simulation of this control type show a good response in relation to the degree of prospective uncoupling, to the dynamic evolution of the variables and the global stability of the system, when there are modifications in the work points in a wide generator operating range. On the other hand tests carried out taking into account ground faults in the transmission lines, denote a good behavior of the system post-fault in relation to its transient stability. Two types of DFL were kept in mind, one fixed, and the other adaptive which takes into account the variations of its parameters due to line reactance modifications during and after having produced the fault. The power system model consists of a single axis flat rotor machine, connected to an infinite power bus. This way the sub-transient phenomena are ignored. The global system consisting of a turbine and a generator that produces the electrical output power is coupled and it presents multiplicative and harmonic non-linearities. The application of a DFL on the output voltage equation expressed as a function of the electrical system parameters referred to the generator practically turns the non linear system into two uncoupled subsystems with the possibility of independently controlling the output voltage and the frequency. MATHEMATICAL MODEL The power system is modeled as a single turbinegenerator machine connected to an infinite power bus through two parallel transmission line groups (Fig. 1). The mathematical equations that represent the generator dynamics of a flat rotor machine, single axis model, are written following the standard notation. The dynamics of the turbine and the steam control valve are described by: Corresponding Author: S. Sajedi, Department of Electrical Engineering, Fasa Branch, Islamic Azad University, Fasa, Fars, Iran 1239 Res. J. Appl. Sci. Eng. Technol., 3(11): 1239-1245, 2011 where, xds = xT + xL +xd x’ds= xT + xL +x’d xs = xT + xL Fig. 1: Power system consisting of a turbo generator group connected to an infinite power bus P&m (t ) = − 1 TT Pm (t ) + KT TT X E (t ) (1) X& E (t ) = − 1 TG X E (t ) + [ Pc (t ) − KG TG 1 Rω 0 ω ( t )] ( 2 ) The mechanical equations of the generator are: δ&(t ) = ω (t ) ω& (t ) = D 2H Exact linearization of the output voltage Vt: The design requirements for a good robust non- linear voltage stabiliser, lead to maintaining the value of nominal voltage Vt within a band of specified tolerance and in a wide generator operation range. Therefore the voltage Vt must be included as a feedback signal. According to the approach of the linearized plant (Gao et al., 1990; Wang et al., 1993; Junco et al., 1996) as a function of the variables w, d and Pe, the output voltage Vt is a strongly non linear function of these variables, and it is not possible to apply design procedures for linear systems. To solve this problem, in this paper the application of the exact feedback linearization technique on the Eq. (11) is proposed. Differentiating this expression, yields: (3) ω (t ) − ω0 2 H [ Pm ( t ) − Pe ( t )] V&t2 = 2 (4) x s2 2 xds Eq E& q + 2 xsxd xds (12) Vs( Eq cosδ − ωEq senδ ) The generator electrical dynamics is represented by: E& q′ (t ) = ( E f (t ) − Eq (t )) Td1′ 0 where for the sake of simplicity the time variable has been suppressed from the notation, and where: (5) V&t 2 = The complete electrical system equations referred to the generator are represented by: Eq ( t ) = Eq, (t ) − xds , xds ( xd − xd, ) , xds Vs cosδ (t ) = xad I f (t ) senδ (t ) = I q (t ) = Vs xds pe (t ) = Vs Eq ( t ) xds Pe ( t ) xad I f ( t ) senδ (t ) (6) d (Vt2 ) dt (13) Starting from the generator electrical and dynamic equations (Eq. 5, 6) with T'd = T’d0 x'ds /xd , the shortcircuit transient-time constant in the direct axis, the following equation can be written: (7) & = Eq 1 Td, ( k c u f − Eq ) + ( xd − xd, ) , xds Vsωsenδ (14) (8) Replacing (14) in (12) and grouping terms, results in: Q( t ) = Vs xds Eq (t ) cosδ (t ) − E f ( t ) = kc u f ( t ) Vt 2 (t ) = + xs2 2 xds 2 xs xd 2 xds Eq2 (t ) + Vs2 xds (9) (10) xd2 2 xds Vs2 Vs Eq (t ) cosδ (t ) (11) V&t 2 = − 1 Td, Vt 2 + 1 Td, vf (15) which represents a first order system in Vt2 and where vf is expressed in Eq. (16). In accordance with the DFL theory, the exact cancellation of non linearities takes place if the excitation voltage uf is obtained starting from vf according to Eq. (17), written as a function of measurable variables of the plant: 1240 Res. J. Appl. Sci. Eng. Technol., 3(11): 1239-1245, 2011 vf = x s2 2 xds + 2Td, [ {2 kcu f ( Eq + , ( x d − xd ) , xds x − d xs ωVs2 senδ cosδ + uf = 2 xds xs2 xd2 x s2 Vs cosδ ) − Eq2 ]ωVs Eq senδ + 2Td, Vs2 x x 2Td′0 dsxs d ( xd − 2 kc xad I f [1 + (16) , xd xds xs )ωPe Fig. 2: Block diagram of the linearized plant V2 ( Q+ s ) xds xd xds xs . ( x I ) 2 ad f V2 ( Q+ s xds , xd ) ( xad I f ) 2 x ds x d xs , xd ( xd − x d ) , x s xds } v f + ( xad I f ) 2 − 2Td′0 ( xd − xd,& 0 − 2 kc xad I f [1 + − xd xs equations. Pe is a non linear function in Vt, and in the system under study it is considered as an auxiliary input with characteristics of “perturbation”. The control scheme this way defined presents a high uncoupling degree among the voltage and frequency controls, which can be used independently to modify the excitation field and the mechanical power respectively, as it is shown in the simulations carried out in the following sections. (17) xd2 2 V xs2 s ωPe − V2 ( Q+ s ) xds . ( xad I f ) 2 ] Since this procedure leads to a linear equation in Vt2 it is possible to take it to a linear equation in Vt if one keeps in mind that: V&t 2 = − Vt 2 + 1 , Td 2VtV&t 2 = − V&t = − 1 , 2 Td 1 , Td 1 , Td 2 vg = K p (Vt 0 − Vt ) + Ki ∫0t (Vt 0 − Vt )dt vf Vt + Vt + 1 , Td vf vf (18) Pc = Pm0 + Km[ Pco − ( Pm − Pmo )] − K XE ( X E − X E 0 ) − Kωω − Kδ (δ − δ0 ) (22) with Pc0 , Pm0 , XE0 and *0 representing steady state values, and: vf (19) vt J = ∫0∞ ( X T QX + U T RU )dt 0 0 ⎤ ⎡123 0 ⎢ 0 150 0 0 ⎥⎥ Q= ⎢ R=1 ⎢ 0 0 160 0 ⎥ ⎥ ⎢ 0 0 120⎦ ⎣ 0 deriving vf and applying the DFL technique again, the system of equations corresponding to the linearized plant is obtained. where, δ&(t ) = ω (t ) ω& (t ) = − V&t = − (21) with Kp = 2 and Ki = 1/ T’d0 and a LQC - type feedback for the turbine frequency regulator subsystem: 1 , v 2 Td t making: vg = Control law: The following PI-type control for the voltage regulator subsystem is proposed: D 2H 1 2 Td, ω (t ) + Vt + ω0 2 H [ pm ( t ) − 1 2 Td, X T = [δ (t ) ω (t ) Pm (t ) X E (t )] (20) ⎣ ⎦ K = k s Kω km K X E = [1109 . 1317 . 148.731127 . ] Pe (t )] vg The plant block diagram is shown in Fig. 2. The independence of the Vt voltage control regarding the other variables is observed in the linearized system of and considering that the measurements of the angle * are available. (for example by means of the use of an observer). To find the elements of Q (with R = 1) the system was tested for different operating conditions, measuring the overshoot and the response time for each state 1241 Res. J. Appl. Sci. Eng. Technol., 3(11): 1239-1245, 2011 Output voltage [ppu] variable. Then the results were plotted as a function of Q and it was observed that the most satisfactory behaviour of the system takes place for a range of values between 100 and 1000. A later adjustment taking into account the maximum values of the constants in the feedback loops, allows defining the main Q finally adopted. SIMULATION RESULTS For all the tests carried out, typical values of a plant were kept in mind (Wang et al., 1993) and furthermore saturation phenomena were not considered, they were replaced by constraints in the field control voltage, as it will be seen in the section 5.2. The values correspond to: 40 =50 r/s, D = 5.0 ppu, H = 4.0 s, T’d0 = 6. 9 s , Tg = 0. 2 s, TT = 2.0 s ,Kg = KT = kc = 1, R = 0.05 ppu , xd = 1.863 S x’d = 0.257 S, xT = 0. 127 S and max ½kc uf½ = 4. Three types of tests were carried out. The first of them consisting of a step in the voltage Vt set point, the second considering a step in the given mechanical power set point, and the third simulating a symmetrical threephase fault to earth in one of the two transmission line groups. It was also kept in mind a parameter that measures the point on the line where the fault takes place expressed in ppu (0#8<1 ), 200ms after the fault has taken place, the disconnection of the affected line occurs. The reactances that compose the pattern of the system are modified during and after the fault, in accordance with its location along the transmission lines. 1.1 1.05 1 0 5 10 15 20 Time [sec] Deviation from synchronous value [Hz] (a) 2 0 -2 -4 -6 -8 -10 -12 -14 -16 -18 x10 0 -3 5 10 Time [sec] 15 20 (b) Unconstrained field control voltage: The first test shows the voltage and the frequency evolution (Fig. 3a, b) for a voltage step of 10%. It is proven that the response of Vt is exponential and independent of the evolution of w. The frequency graph shows a transient owing to the “perturbation” Pe. The second test allows to check the uncoupling of the system, (Fig. 4a, b) where a modification in the frequency for effect of a mechanical power action, does not affect the output voltage that maintains a constant value. The third test consists of simulating a fault in one of the two transmission lines groups of 200 ms duration previous to the breaking off of the affected line. In this case, two types of DFL were used, one fixed taken from the nominal parameters of the plant, and the other adaptive that contemplates the variations of the line equivalent reactances during and after the fault. The Fig. 5 shows the behaviour of Vt for the two cases. It can be observed that for the adaptive DFL the response Vt recaptures the original value linearly, while for the fixed DFL it presents an offset in the final value with non linear evolution. It should be remarked that the adaptive DFL shows the exact linearization achieved on Vt, but it is not of direct practical implementation. In Fig. 6 the evolution Fig. 3: Output voltage set point step test (10%). (a) evolution of the generator output voltage Vt. (b) deviation from synchronous frequency value 40 of the frequency is shown, where after the transient the synchronous frequency is reached, while in Fig. 7 the electrical output power Pe under identical test conditions for the case of fixed DFL is plotted. There have been carried out tests using three values for the parameter (namely 0.001, 0.1 and 0.5). In Fig. 8 the temporary evolution of the load angle * is shown for different values of the parameter 8. From that figure it is possible to observe during and after to the fault that its evolution remains within the more stable band of operation of the generator, reaching a new value as a function of the line conditions after the fault. In the Fig. 9 and 10 the output voltage of the generator Vt and the excitation control voltage uf, are shown, respectively. As it has been mentioned before, the behaviour of Vt is not too linear but asymptotically stable, while the excitation control voltage remains, during and after the fault, within the typical margins (±2.5 to ±3.5) before the cutting that the limiting circuits produce. 1242 Electrical output power [ppu] 0.7 0.035 0.03 0.025 0.02 0.015 0.01 0.005 0 (a) -0.005 -0.01 -0.015 10 Time [sec] 0.001 0.5 0.1 0.5 0.4 0.3 0.2 0.1 2 20 15 3 4 5 7 6 Time [sec] Fig. 7: Fault to earth test. Plot of the electrical output power Pe for different values of 8 2 (b) 1.8 1.4 1.2 1 0.8 0.6 G enerator load angle [deg] 80 0.4 0.2 0 0 4 10 Time[sec] 15 20 Fig. 4: Mechanical power set point step test (10%) (a) evolution of the frequency referred to the synchronous value w0. (b) evolution of the generator output voltage Vt 0.15 0.001 75 70 0.1 65 0.5 60 55 50 45 40 2 3 4 5 Time [sec] 7 6 Fig. 8: Fault to earth test. Behavior of the load angle d for different values of 8 Fixed DFL 1.00 Output voltage (ppu) 0.6 0 5 0 Output voltage [ppu] Deviation from synchronous value [Hz] Res. J. Appl. Sci. Eng. Technol., 3(11): 1239-1245, 2011 Adaptive DFL 0.95 0.90 0.85 Output voltage [ppu] 0.80 0.75 0.70 0.65 5 0 10 Time (sec) 15 20 Deviation from synchronous value [Hz] Fig. 5: Fault to earth test (200 ms duration). Evolution of the generator output voltage Vt 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 2 0.4 3 4 5 Time [sec] 6 7 0.001 0.3 Fig. 9: Fault to earth test. The evolution of the generator output voltage Vt is less l dependant 0.2 0.1 0.5 0 0.1 -0.1 -0.2 -0.3 2 3 5 4 Time [sec] 6 7 Fig. 6: Fault to earth test (200 ms duration) with later desconection of the affected line. Evolution of the synchronous frequency w in function of 8 Constrained field control voltage: As it can be seen in Fig. 10, the system so designed does not present saturation phenomena (the signal uf lies between the linear excursion band). In the following tests, the excitation control parameters were modified so as to reduce the rise time in the output voltage set point step test (Fig. 3a) by a factor of 10 (Kp = 20, Ki = 10/T’do). The graphics obtained (Fig. 11a, b) show the evolution of the output voltage and the practically negligible variation of 1243 Res. J. Appl. Sci. Eng. Technol., 3(11): 1239-1245, 2011 Excitation control voltage [ppu] 3.5 3 2.5 2 1.5 1 0.5 0 -0.5 -1 -1.5 3.5 3 2.5 2 1.5 1 0.5 0 -0.5 -1 -1.5 0.5 2 3 Excitation control voltage [ppu] 0.001 0.1 4 5 Time [sec] 6 7 Output voltage [ppu] Output voltage [ppu] 1.05 1.0 Deviation from synchronous value [Hz] 10 Time [sec] 15 0.1 20 4 5 Time [sec] 6 7 1.2 1.1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 2 0.04 0.02 3 Fig. 12: Fault to earth test, Field control voltage, showing saturation phenomena for 8 = 0.5, 0.1 and 0.001 1.10 5 0.5 2 Fig. 10: Fault to earth test. Behaviour of the excitation control voltage uf for three value of 8 0 0.001 3 4 5 Time [sec] 6 7 Fig. 13: Fault to earth test, Output voltage Vt for the values of 8 = 0.5, 0.1 and 0.001 0 -0.02 CONCLUSION -0.04 -0.06 -0.08 0 5 10 15 20 Time [sec] Fig. 11: Output voltage step test-10%. Rise time improvement by a factor of 10, (a) output voltage Vt. (b) output frequency T the frequency, as a result of the “perturbation” produced by the modification in the electrical output power. Then, the fault tests were repeated for duration of 200 ms. Due to the new and higher control demand, the field control voltage exceeds the limits values set at ±3.5, thus producing the cuttings shown in Fig. 12. It can be observed that in this case the system remains stable as shown in the output voltage evolution (Fig. 13). It should be remarked that the system does not present noticeable deviations in the evolution of the others variables, i.e., frequency, load angle, electrical output power, with respect to those plotted in Fig. 6, 7 and 8. The results obtained by means of the simulation justify the hypothesis outlined in the definition of the mathematical model, where the implementation of a DFL on the output voltage equation, allows to linearize and uncouple the voltage regulator loop and to act on the frequency loop, considering the electrical output power variations as an “auxiliary input”. It is observed that in the face of a change in the given power, the frequency changes in a controlled form and it does not affect the voltage regulation, while modifications of the output voltage alter the frequency during a bounded transient. As a consequence of the decoupling among the voltage and frequency variables, it is possible to adjust the control maintaining system stability, in a wide range of operating conditions. In tests carried out considering faults in the transmission lines, the obtained results allow to conclude that the response post-fault in the case of using the ideal adaptive DFL is linear and asymptotically stable, while in the practical case of the fixed DFL is non-linear and presents an voltage offset product of the variation of the 1244 Res. J. Appl. Sci. Eng. Technol., 3(11): 1239-1245, 2011 plant parameters with respect to those used in the original DFL calculation. Also, it can be verified that a more severe control action that turns the system into non linear operation, does not produce a loss in the overall plant stability. xd x'd xL xad reactance in the direct axis of the generator transient reactance on the direct axis of the generator reactance of the transmission line mutual reactance between the excitation winding and the winding of the stator NOMENCLATURE REFERENCES Pm XE Pc TT KT TG KG * 4 Pe D H T’d0 E'q Eq Ef If Iq Q Vs Vt uf kc xT mechanical power opening of the steam valve reference of power turbine time constant gain of the turbine valve time constant gain of the speed regulator generator load angle relative speed to the synchronous 40 active power surrendered by the generator damping constant moment of inertia transient time constant in open circuit transient emf in the quadrature axis emf in the quadrature axis equivalent emf in the excitation coil current of excitation field current in the quadrature axis reactive power voltage on the infinite bus output voltage of the generator control input of the excitation amplifier gain of the excitation amplifier reactance of the transformer Gao, L., L. Chen, Y. Fan and H. Ma, 1990. The DFL Nonlinear Control with Applications in Power Systems, Technical Report EE9001, Department of Automation, Tsinghua Univresty., Beijing, China. Gao, L., L. Chen, Y. Fan and H. Ma, 1992. A Nonlinear Control Design for Power Systems. Auto., 28: 975979. Isidori, A., 1989. Nonlinear Control Systems: An Introduction. 2nd Edn., Springer Verlag, NY, USA. Junco, S., S.A. Czajkowski and J.C. Nachez, 1996. Control No lineal de Excitación del Generador Sincrónico Mediante Inversión Causal, AADECA ’96,7º Congreso latino-americano de Control Automático, Argentina, pp: 140-145. Matas, J.C.,M.Guerrero, J.M. Garcia de Vicuna, L. Miret and J. Feedback, 2008. Linearization of direct-drive synchronous wind-turbines VIA a sliding mode approach.IEEE Trans. Power Elec.,23(3):1093-1103. Wang, Y., D.J. Hill, R.H. Middleton and L. Gao, 1993. Transient stability enhancement and voltage regulation of power systems. IEEE Trans. Power Syst., 8: 627. 1245