E S nviro cience

advertisement
EnviroScience
, Inc.
An Environmental Consulting and Industrial Hygiene Company
PATH OF CONSTRCUTION
INSPECTION & SAMPLING REPORT
FOR SUSPECT
ASBESTOS-CONTAINING MATERIALS &
LEAD-CONTAINING PAINTS
AT
CABRILLO COLLEGE — BUILDING 1500
6500 Soquel Drive • Aptos, Ca 95003
1.0
INTRODUCTION
The undersigned representative of EnviroScience, Inc. (ESI), an independent industrial
hygiene (IH) consulting firm representing Cabrillo Community College, hereby presents
the findings of the limited Site inspection and sampling conducted at the location referenced
below (Site).
The purpose of ESI’s limited Site investigation and sampling was to determine the extent of
asbestos-containing materials (ACMs), and lead-containing paints (LCPs) present (if any)
in the path of constrcution of a new HVAC upgrade project at Building 1500 of the
Cmapus.
This survey and sampling does not cover any other buildings on Cmapus, and it’s limited to
path of construction for the upcoming HVAC upgrade project, only.
2.0
GENERAL INFORMATION
SITE LOCATION
Cabrillo College
6500 Soquel Drive • Aptos, CA 95003
BUILDING SURVEYD
Building 1500 — Path of construction
for the new HVAC project
SAMPLING DATE
REPORT DATE
February 24, 2016
March 3, 2016
ON-SITE INSPECTOR
Alfredo Rocha III
PROJECT MANAGER
Hooman Sotoodeh, Ph.D., PE
SIGNATURE
EPA-Certified Building Inspector/Contractor Supervisor
Cal/OSHA-Certified Site Surveillance Technician (#00-2806)
CDPH-Certified Lead Inspector (#20474)
EPA-Certified Building Inspector/Project Designer
Cal/OSHA-Certified Asbestos Consultant (#93-1097)
CDPH-Certified Lead Inspector/Assessor/Project Designer (#1820)
H. Sotoodeh
2220 S. Bascom Avenue • Campbell, California 95008 • (408) 371-4181 • Fax (408) 371-4186
3.0
SITE DESCRIPTION
The Site inspected is Building 1500 building at the Cabrillo College campus in Soquel, CA.
This survey and sampling was limited to the areas of the building, which were going to be
affected by the proposed HVAC upgrade project.
At the time of our Site inspection and sampling, Building 1500 was fully occupied and in
operation. ESI’s inspection & sampling was limited to visible and accessible areas
identified herein, and the findings presented in our report do not apply to unsampled
materials or other parts of the Site, which were inaccessible or not related to the upcoming
HVAC project (i.e., flooring materials, etc.).
The photos below depit the mechanical room and the main level of the building inspected by
ESI.
MECHANICAL ROOM
Photo #1 — Interior view of the mechanical room
(Wallboard joint compound
confirmed to be ACM)
Photo #2 — Interior view of mechanical room
(Wallboard joint compound
confirmed to be ACM)
Photo #3 — Interior view of the mechanical room
Showing bare sheet metal ducts
(Wallboard joint compound
confirmed to be ACM)
Photo #4 — Interior view of the mechanical room
(Wallboard joint compound
confirmed to be ACM)
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 2
EnviroScience, Inc.
2ND LEVEL
Photo #5 — Grills & vents inspected
at the 2n d level of Building 1500
Photo #6 — Grills & vents inspected
at the 2n d level of Building 1500
Photo #7 — Wallboard joint compound
above ceiling tiles at the 2nd level
(Confirmed to be ACM)
Photo #8 — Air duct insulation (Fiberglass)
& open attic cavity
above ceiling tiles
(All Wood)
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 3
EnviroScience, Inc.
GROUND LEVEL
Photo #9 — Exterior view of
ground level windows
(Window glazing putty
confirmed to be ACM)
Photo #10 — Wallboard joint compound
above ceiling tiles
(Confirmed to be ACM)
Photo #11 — Air duct joint tape in
the open attic above ceiling tiles
Photo #12 — Air ducts and open attic cavity
above ceiling tiles
(All Insulations are Fiberglass)
Photo #13 — Black caulking around
Windows & doors on the N. Side
(Confirmed to be ACM)
Photo #14 — Black caulking on the interior &
exterior of all dorrs & windows
(Confirmed to be ACM)
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 4
EnviroScience, Inc.
4.0
METHODS
4.1
ACM Sample Collection Procedures
Samples of suspect asbestos-containing materials (ACMs) were collected by coring
or by carefully scraping a small portion of a surface. In areas where sampled
material posed a high risk of dust release, a half-face type H respirator equipped
with a HEPA filter was worn by the inspector for respiratory protection. The
sampled material was immediately contained in plastic ziplock bags. The sampling
information was recorded in a bound field
notebook. Samples were then properly
labeled with a unique sample identification
umber, and delivered via overnight to a
NVLAP-certified, independent laboratory
(EMSL Testing, Inc., of San Leandro,
California) for 24-hour RUSH analysis along
with the appropriate chain-of-custody
documentation.
4.2
ACM Sample Analysis Procedures
All ACM samples were analyzed using polarized light microscopy (PLM)
techniques at a state-certified independent laboratory. Samples were examined for
homogeneity and percent composition of fibrous versus nonfibrous components
using a 20x stereoscopic microscope. A small portion of the material was placed in
refractive index liquid on a microscope slide and examined for the presence of
asbestos species utilizing a polarized light microscope at a magnification of 100x to
200x. Crystallographic and dispersion-staining techniques were employed for
positive characterization. If the presence of asbestos was confirmed, the percentage
of asbestos versus non-asbestiform materials was visually estimated.
4.3
Paint Chip Sampling for Lead
Samples of suspect lead-based paints (LBPs) were collected by carefully scraping
approximately 1 gram or about 1 teaspoon-full of the paint from the substrate. The
paint was either peeled from the substrate or
scraped to the substrate, avoiding dust. ESI's onsite inspector tried to minimize the amount of
substrate submitted with the paint, as this would
affect the true concentration of lead in the paint.
The sampling information was recorded in a bound
field notebook. The paint samples were then
properly labeled and delivered to the independent
laboratory for analysis along with the appropriate
chain-of-custody documentation.
4.4
LCP Sample Analysis Procedures
Samples of suspect paint were analyzed in accordance with EPA Method 7420,
analysis by flame Atomic Absorption (AA) spectroscopy, direct aspiration, and
results were reported in percent by weight. AA spectroscopy is a laboratory
analytical technique that provides precise determination of specific inorganic
elements. These elements are more commonly referred to as “metals.” There are
approximately 65 metallic elements including lead, aluminum, tin, silver and copper.
AA refers specifically to the reaction of metal atoms to heat. When these atoms are
exposed to very high heat or are atomized in other ways, they absorb light. Each
element absorbs light of a specific wavelength and the absorption of light is directly
proportional to the concentration of atoms in solution.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 5
EnviroScience, Inc.
5.0
ANALYTICAL DATA & RESULTS
5.1
Bulk Samples for Asbestos
Sample
Number
Sampled
Material
Sample
Location
Asbestos
Concentration
Recommendation
MECHANICAL ROOM
1500-L1
Drywall joint
compound
N. Wall of
mechanical room
Drywall
Joint Compound
ND*
2%C***
N/A**
Abate as ACM
Drywall joint
compound
Ceiling of
mechanical room
Drywall
Joint Compound
ND
2%C
N/A
Abate as ACM
Drywall joint
compound
S. Wall of
mechanical room
Drywall
Joint Compound
ND
2%C
N/A
Abate as ACM
Pipe
canvas
Around the pipes
in mechanical room
White Canvas
ND
N/A
Pipe
insulation
Interior of the pipes
in mechanical room
Yellow Insulation
Air duct
joint tape
Around air ducts of
mechanical room
White Tape
Furnace
tape
Around furnace in
mechanical room
White Tape
Vibration
damper
Around pipes above
mechanical room
Drywall joint
compound
W. Wall of
mechanical room
......................................................................................................................................................................................................................
1500-L2
......................................................................................................................................................................................................................
1500-L3
......................................................................................................................................................................................................................
1500-L4
......................................................................................................................................................................................................................
1500-L5
ND
N/A
......................................................................................................................................................................................................................
1500-L6
ND
N/A
......................................................................................................................................................................................................................
1500-L7
ND
N/A
......................................................................................................................................................................................................................
1500-L8
White/Black Damper
ND
N/A
......................................................................................................................................................................................................................
1500-L9
Drywall
Joint Compound
ND
2%C
N/A
Abate as ACM
ND
N/A
2ND LEVEL
(around ceiling registers and grills)
1500-L10
Ceiling tile
material
Room
1522A
White Tile
Drywall joint
compound
Above ceiling tiles
of room 1522A
Wall
texture
Wall of
room 1522A
White Texture
Ceiling
tiles
S. ceiling of
room 1520
White Tile
Ceiling
tiles
Ceiling near board
of room 1520
White Tile
Drywall joint
compound
Above ceiling tiles
of room 1520
Drywall
Joint Compound
......................................................................................................................................................................................................................
1500-L11
Joint Compound
ND
N/A
......................................................................................................................................................................................................................
1500-L12
ND
N/A
......................................................................................................................................................................................................................
1500-L13
ND
N/A
......................................................................................................................................................................................................................
1500-L14
ND
N/A
......................................................................................................................................................................................................................
1500-L15
ND
ND
N/A
N/A
*
None Detected
* * None Applicable
* * * Chrysotile-type Asbestos
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 6
EnviroScience, Inc.
5.1
Bulk Samples for Asbestos
Sample
Number
Sampled
Material
Sample
Location
Asbestos
Concentration
Recommendation
2ND LEVEL
(around ceiling registers and grills)
1500-L16
Air duct
joint tape
In the attic space
of room 1520
White Tape
Wall
texture
Wall of
room 1520
Air duct
joint tape
In the attic space
of room 1520
White Tape
Ceiling
tiles
N. ceiling of
room 1520
White Tile
Ceiling
tiles
Ceiling of
room 1524
White Tile
Drywall joint
compound
Above ceiling tiles
of room 1524
Air duct
joint tape
In the attic space
of room 1524
ND*
N/A**
......................................................................................................................................................................................................................
1500-L17
White Texture
ND
N/A
......................................................................................................................................................................................................................
1500-L18
ND
N/A
......................................................................................................................................................................................................................
1500-L19
ND
N/A
......................................................................................................................................................................................................................
1500-L20
ND
N/A
......................................................................................................................................................................................................................
1500-L21
Drywall
Joint Compound
ND
2%C***
N/A
Abate as ACM
......................................................................................................................................................................................................................
1500-L22
White Tape
ND
N/A
......................................................................................................................................................................................................................
1500-L23
Drywall joint
compound
Wall of the2nd level Drywall
men’s restroom
Joint Compound
ND
2%C
N/A
Abate as ACM
2%C
Abate as ACM
Abate as ACM
......................................................................................................................................................................................................................
1500-L24
Wall
texture
Wall of
men’s restroom
White Texture
GROUND LEVEL
(around ceiling registers and grills)
1500-L25
Door
caulking
Around exterior
Black Caulking
doors on the N. side
6%C
Window
caulking
Around exterior
Black Caulking
windows on the N. side
ND
Window
caulking
Around exterior
Black Caulking
windows on the N. side
6%C
Window
caulking
Around interior
Black Caulking
windows on the N. side
6%C
Door
caulking
Around interior
Black Caulking
doors on the N. side
ND
Window
caulking
Around interior
Black Caulking
windows on the N. side
6%C
......................................................................................................................................................................................................................
1500-L26
N/A
......................................................................................................................................................................................................................
1500-L27
Abate as ACM
......................................................................................................................................................................................................................
1500-L28
Abate as ACM
......................................................................................................................................................................................................................
1500-L29
N/A
......................................................................................................................................................................................................................
1500-L30
Abate as ACM
*
None Detected
* * None Applicable
* * * Chrysotile-type Asbestos
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 7
EnviroScience, Inc.
5.1
Bulk Samples for Asbestos
Sample
Number
Sampled
Material
Sample
Location
Asbestos
Concentration
Recommendation
GROUND LEVEL
(around ceiling registers and grills)
1500-L31
Ceiling
tiles
Ceiling of the
entry way
White Tile
Pipe
canvas
In the attic space
of the entry way
Drywall joint
compound
Above ceiling tiles
of the entry way
Air duct
joint tape
In the attic space
of room 1508
White Tape
Gray air duct
joint tape
In the attic space
of room 1506B
Silver Tape
White air duct
joint tape
In the attic space
of room 1506B
White Tape
Ceiling
tiles
Ceiling of
room 1506B
White Tile
Drywall joint
compound
Above ceiling tiles
of room 1503B
Gray air duct
joint tape
In the attic space
of room 1503B
ND*
N/A**
......................................................................................................................................................................................................................
1500-L32
Tan/Silver Canvas
ND
N/A
......................................................................................................................................................................................................................
1500-L33
Drywall
Joint Compound
ND
2%C***
N/A
Treat as ACM
......................................................................................................................................................................................................................
1500-L34
ND
N/A
......................................................................................................................................................................................................................
1500-L35
ND
N/A
......................................................................................................................................................................................................................
1500-L36
ND
N/A
......................................................................................................................................................................................................................
1500-L37
ND
N/A
......................................................................................................................................................................................................................
1500-L38
Joint Compound
ND
N/A
......................................................................................................................................................................................................................
1500-L39
Silver Tape
ND
N/A
*
None Detected
* * None Applicable
* * * Chrysotile-type Asbestos
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 8
EnviroScience, Inc.
5.2
Paint Chip Samples for Lead
Sample
Number
Painted Surface
(Color)
Paint
Location
Lead
Concentration
Recommendation
1500-P1
Furnace Paint
(Green)
Furnace in the
mechanical room
0.44 %
or
4,400 ppm*
Treat all interior
surfaces painted
this color as
lead containing
...................................................................................................................................................................................................................
1500-P2
Interior wall
paint
(White)
Interior walls
of room 1522A
Interior wall
paint
(Tan)
Interior walls
of room 1520
Interior wall
paint
(Beige)
Interior walls
of the 2nd floor
men’s restroom
<0.029 %
or
<LOD**
None
<0.019 %
or
<LOD
None
<0.010 %
or
<LOD
None
...................................................................................................................................................................................................................
1500-P2
...................................................................................................................................................................................................................
1500-P2
*
**
Parts Per Million
Limit of Detection
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 9
EnviroScience, Inc.
6.0
REGULATIONS
The National Emission Standard for Hazardous Air Pollutants (NESHAP) regulations is
part of the Clean Air Act and is found in 40 CFR 61 part M. NESHAP requires that
building owners inspect a building (regardless of age) for asbestos prior to renovation or
demolition. The EPA must be notified in advance of all demolitions and when more than a
listed amount of Regulated Asbestos-Containing Material (RACM) are going to be
disturbed during a renovation or demolition. Furthermore, construction work disturbing
RACMs by unlicensed and non-registered asbestos abatement contractors are prohibited by
California and Federal laws.
The United States Environmental Protection Agency (US EPA) considers a material to be
asbestos-containing if at least one homogeneous sampling material confirms presence of
asbestos fibers greater that one percent (>1%). Asbestos-containing materials (ACM) are
regulated by federal, state, and local agencies.
EPA classifies ACMs into the following three (3) categories:
•
Friable ACM — Asbestos-containing materials which can be pulverized into
dust by hand pressure (definition of friability);
•
Category I non friable ACM — Asbestos-containing asphalt roofing
products, vinyl floor tiles, gaskets, sealants, and other packing material;
•
Category II non friable ACM — All asbestos-containing materials other than
Category I non-friable, that when dry, cannot be pulverized or reduced to powder
by hand pressure.
The above-referenced ACM categories can become Regulated-Asbestos Containing
Materials (RACM) under certain conditions (i.e., demolition or renovation). These
conditions are:
•
Friable ACM;
•
Category I non friable ACM which has become friable;
•
Category I non friable ACM which has been, or will be subjected to cutting,
grinding, sanding, or other abrasive contact;
•
Category II non friable ACM which has, or will be, pulverized, crumbled, or
reduced to powder under mechanical forces exerted during demolition or
renovation operations.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 10
EnviroScience, Inc.
7.0
FINDINGS
7.1
Asbestos Containing Materials (ACM)
Based on the analytical findings of the 48 sample layers collected from the
mechancal room and 2nd level, and ground level of Building 1500 and analyzed for
asbestos, it is confirmed that the following building materials contain asbestos above
the 0.1% limit regulated by Cal/OSHA, and above the 1.0% limit regulated by EPA.
7.1.1 The wallboard joint compound
throughout the entire Building
1500 contains 2% Chrysotile-type
asbestos; and
7 . 1 . 2The black-colored caulking
material around all interior and
exterior doors and windows on the
N. side of Building 1500 contains
6% Chrysotile-type asbestos. The
same caulking material is more
than likely present on other sides
of the building and they should all
be assumed to be asbestos
containing based on material
homogeneity.
7.2
Lead-Containing Paint (LCPs)
The California Occupational Safety and Health Administration (Cal/OSHA),
considers any paint with any concentration of lead above the limit of detection
(LOD) of the analytical procedure, to be considered as lead-containing paint (LCP).
All construction or renovation work where employees may be occupationally
exposed to LCP shall be conducted in compliance with California Code of
Regulations (CCR), Title 8, Section 1532.1 "Lead in Construction."
Based on the analytical findings of the 4 paint
chip samples collected from various paints
throughout building 1500, and analyzed for
lead, it is confirmed that the following surfaces
contain lead above the LOD of the analytical
procedure, and is thus considered to be LCP
per OSHA’s definition.
7.2.1
The green-colored furnace paint in the
mechanical room of Building 1500
contains 4,400 parts per million (ppm)
lead.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 11
EnviroScience, Inc.
8.0
RECOMMENDATIONS
8.1
ACMs
This survey was conducted in anticipation for installation of a new HVAC system in
Building 1400.
If disturbing or removing more than 100 sq. ft. of asbestos-containing material
(even below 1%), the California State License Board (CSLB) requires that the
contractor be licensed as C-22 (Asbestos Abatement), and be registered by DOSH
as an asbestos abatement contractor.
Under the United States Environmental Protection Agency (US EPA)'s National
Emissions Standards for Hazardous Air Pollutants (NESHAP) regulations, all
asbestos-containing materials shall be properly abated and disposed of, prior to
disturbance or demolition.
According to the OSHA Construction Industry Standard for Asbestos (29CFR
1926.1001), and the general industry asbestos standard (29CFR 1019.1001)
workers performing asbestos abatement must be trained, equipped with respirators
and full body protection, and be medically fit to wear respirators. Furthermore, all
removal shall be performed using wet abatement procedures and waste containing
greater than 1% asbestos shall be packaged in accordance with EPA's NESHAP
regulation (40 CFR Parts 61 and 763) and according to California Department of
Health Services (DHS), California Code of Regulations, Title 22, Division 4,
Chapter 30, Section 66699 and Health and Safety Code 25179.3 et. Seq.
During the site inspection, ESI’s field inspector determined that the following
homogeneous material contains asbestos above EPA and OSHA levels.
8.1.1
Wallboard Joint Compound
The compound and textured skim coat applied to the surface of all
interior walls throughout Building 1500 contains <1-2% Chrysotile-type
asbestos; and
8.1.2
Door and Window Caulkings
The black-colored caulkings around interior and exterior of all N. side
windows and doors contain 6% Chrysotile-type asbestos. The same
caulking material is more than likely present on other sides of the
building and they should all be assumed to be asbestos containing based
on material homogeneity.
If either of the materials listed above are scheduled for disturbance during the
upcoming HVAC renovation project, ESI recommends that a State-licensed and
DOSH-registered asbestos abatement contractor perform the removal and disposal
of these ACMs, under proper regulatory guidelines, and under the supervision of the
Owner’s IH consultant.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 12
EnviroScience, Inc.
8.2
LCPs
Any construction-related demolition or cleanup where employees may be
occupationally exposed to lead shall be conducted in compliance with the California
Code of Regulations (CCR), Title 8, Section 1532.1 and 5216 "Lead in
Construction", and in accordance with Federal Occupational Safety and Health
Administration (OSHA) section 29 CFR 1926.62.
In compliance with Cal/OSHA and California Department of Public Health (CDPH)
regulations, ESI requires that an RRP-certified contractor using CDPH-certified
lead workers and supervisors conduct any demolition or debris cleanup activity that
may involve either of the following two lead containing paints:
8.2.1
The green-colored paint on the furnace of the Mechanical room,
which contains 4,400 ppm lead.
Any demolition or debris cleanup shall be conducted using wet methods for dust
suppression, and work practices by the CDPH-certified lead personnel shall be such
that the 8-hour time weighted average (TWA) permissible exposure limit (PEL)
shall not exceed 50 µg/m3 . If any worker’s 8-hr TWA exposure exceeds the action
level of 30 µg/m3 , work practices causing elevated lead levels shall cease or be
modified under the directive of the IH consultant.
In addition, the contractor must continue to conduct daily personnel air monitoring,
and institute medical surveillance and training programs. If the Cal-OSHA
permissible exposure level (PEL) of 50 µg/m3 for lead is exceeded, more stringent
and additional requirements such as engineering controls, respiratory protection,
regulated work areas, and warning signs in lead work areas, become effective, as
directed by the IH Consultant.
LBP Waste Disposal
Rags and paint chips shall be treated as hazardous waste if laboratory results
indicate a lead (Pb) concentration of 5 milligrams per liter (mg/L), or greater using
the EPA-approved Toxicity Characteristic Leaching Procedure (TCLP) test or
equivalent, or greater than 1,000 mg/Kg using the total lead assay.
Building components with lead-based paint still intact (i.e., not flaking, chipping, or
blistered paint) are categorized as “Architectural Components”, and may be
disposed of as regular construction waste, as long as the paint remains intact.
Extreme care shall be exercised, however, to make sure that the intact paint on these
Architectural Components stay tightly adhered to the substrate. If during packaging,
disposal, or transport, any lead-based paint chips flake off from the Architectural
Component, all such paint chips shall be packaged as stated in the previous
paragraph, the waste properly profiled, and then disposed of.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 13
EnviroScience, Inc.
9.0
LIMITATIONS
This report was prepared solely for the use of our client Cabrillo Community College
and their designated representatives, only. No part of this report shall be copied or used for
any purpose by anyone other than the client, without written consent of ESI. Any reliance
on this report by a third party is at such party's sole risk. The content and conclusion
provided by ESI in this report are based on information collected during its assessment,
which include, but are not limited to visual site inspection and limited sampling and
laboratory testing of suspect ACMs, and our professional judgment based on these
information.
ESI assumes that the samples collected and analytical data presented herein, are reasonably
representative of the entire area of the Site inspected, which may not be the case at
unsampled areas or materials. The results of the sampling and the recommendations made
are applicable to a small window of time on the date, time, and location that sampling was
conducted. Any generalization of these recommendations to others dates, times, or locations
will not be applicable or accurate.
This report is issued with the understanding that it is the responsibility of the owner, or its
representatives, to ensure that the information contained herein is brought to the attention of
the appropriate regulatory agencies, where required by law. Additionally, it is the sole
responsibility of the owner to properly dispose of any hazardous substances on site, in
accordance with existing laws and regulations.
This assessment was performed in accordance with generally accepted principles and
practices of environmental engineering and assessment in northern California at the time of
the work. This report presents our professional opinion based on our findings, technical
knowledge, and experience working on similar projects. No warranty, either expressed or
implied, is made. The limited conclusions presented are based on the current regulatory
climate. We are not responsible for the impact of any changes in environmental standards
or regulations in the future.
To the fullest extent permitted by law, Client agrees to limit the liability of ESI, its officers,
shareholders and employees, for any acts, errors or omissions or breaches of contract to the
greater of $2,500 or the amount of ESI's fees for services rendered under this Agreement.
Client agrees to defend, indemnify and hold ESI harmless from any loss, cost, damage or
expense, including attorney's fees, in excess of the foregoing limits. In no event shall ESI
be liable for, and Client shall indemnify and hold ESI harmless against, any indirect, special
or consequential loss or damage. Failure of Client to give written notice to ESI of any claim
of negligent act, error or omission within one (1) year of performance shall constitute a
waiver of such claim by Client.
ESI will retain the records related to this project including lab data for a period of six (6)
months from the date of this investigation, only. Thereafter all paper and electronic records
will be discarded safely. It will be the responsibility of the client to retain all records related
to this project after the 6-month period. ESI assumes no responsibility for document
reproduction in legal dispute matters after the 6-month expiration period.
There are no third party beneficiaries of this agreement between Client and ESI and no third
party shall be entitled to rely upon any work performed or reports prepared by ESI
hereunder for any purpose. Client shall indemnify and hold ESI harmless against any
liability to any third party for any loss, expense, or damages arising out of or in connection
with reliance by any such third party on any work performed or reports issued by ESI
hereunder.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 14
EnviroScience, Inc.
Appendix A
Independent Laboratory
Analytical Results for
Bulk Material Samples
Analyzed for Asbestos Content
(EPA Method 600/R-93-116, Visual Area Estimation)
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 15
EnviroScience, Inc.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 16
EnviroScience, Inc.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 17
EnviroScience, Inc.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 18
EnviroScience, Inc.
Appendix B
Independent Laboratory
Analytical Results for
Paint Chip Samples
Analyzed for Lead Content
(EPA Method 3050B/7420)
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 19
EnviroScience, Inc.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 20
EnviroScience, Inc.
Appendix C
Site Map with Sample Locations
At Cabrillo CollegeBuilding 1500
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 21
EnviroScience, Inc.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 22
EnviroScience, Inc.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 23
EnviroScience, Inc.
Limited Site Inspection & Sampling Report for Suspect Asbestos-Containing Materials & Lead-Containing Paints at
Cabrillo College • Building 1500 • Soquel, California
Page 24
EnviroScience, Inc.
Download