International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 Modeling and Analysis of User-DefinedConstant-Switching Frequency DSTATCOM for Three Phase Four Wire Distribution System S. SURESH1, Dr. DEVARAJAN2,N.VIDHYA3,V. RAJASEKARAN4 1 S. SURESH ,Assistant Professor/ EEE , Kalaignar Karunanidhi Institute of Technology, Coimbatore, India Dr. DEVARAJAN2, Professor/EEE, GCT, Coimbatore, India 3 N.VIDHYA , EEE,KalaignarKarunanidhi Institute of Technology, Coimbatore, India V. RAJASEKARAN4, EEE, Kalaignar Karunanidhi Institute of Technology, Coimbatore, India Abstract - This paper deals with modeling and analysis of User Defined Constant Switching (UDCS) frequency current-controlled based four-leg DSTATCOM. The first three-phase legs are operated in hysteresis current tracking mode, and the neutral is operated by fixed switching square pulses of desired frequency. Consequently, the first three legs get tuned to the fourth leg’s user defined frequency. Analytical expressions arederived to specify the range of frequency at which the scheme functions effectively. Design procedure for selection parameter of the four leg inverter such as hysteresis band, DC link voltage, DC link capacitor and inductor are suggested, and simulations are done to value the design procedure for a UDCS-controller based DSTATCOM. Comparison is made between the performance of the UDCS controlled DSTATCOM and conventional hysteresis-controlled DSTATCOM and presented. Index terms- Active power filter, constant switching frequency, current control, design, voltage source inverter (VSI). I.INTRODUCTION Out of many control strategies for voltage source inverters, the one which is mostly used is hysteresis current control method. Due to its simplicity, fast response and robustness, it is been preferred. But its main disadvantage is that it gives variable switching frequency. In case of four-leg topology, this scheme requires high switching frequency to track the reference neutral current. Many methods have been proposed to attain the constant switching frequency for inverter. The easiness in filter design forms the greater advantage. Many attempts are made in reduction of the switching frequency to reduce the electromagnetic interference and switching ISSN: 2231-5381 losses.The variable hysteresis band methods used to achieve constant switching frequency [7]–[12] are quite computation intensive.In the proposed ramp comparison technique in [3], choice of carrier signal frequency is very important. The predicted current control in [15]–[17] is also computation exhaustive. The error drift in the currents helps to achieve reduction in switching frequency [18]. Spacevector modulation with its variants results in complexity inits operation and also in hardware implementation as it requires thedefinition and sequencing of the 3-D space vectors [19]–[21]. The authors had proposed a novel scheme calledas user-defined constant switching (UDCS) frequency currentcontrol method for three phase four wire distribution network that achievethe fixed switching frequency by exploiting the zero vectorstates [22], [23].Provided, this scheme allows theuser to set the switching frequency forall the switches of the inverter.Reduction in switching frequency can also be obtained.These objectives are parallely obtained by a simplecontrol method, which is free from additional computation,circuitry,or modulation.Analytical expressions are derived thatgive guidelines for the user to choose suitable switching frequency(fsw) to get advantage of zero-vector states. The designof other inverter parameters, such as dc-link voltage (Vdc),dc-link capacitor (Cdc), interface inductor (Lf), and hysteresisband (h) are also detailed. It is shown that the effective operationof this controller requires the dc-link voltage to be above aminimum limit specified by the design. http://www.internationaljournalssrg.org Page 213 International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 II. UDCS CONTROLLER FOR FOUR-LEG DSTATCOM A four-leg VSI-based DSTATCOM is shown in Fig. 1. Eachpower switch has an anti-parallel diode (not shown in the figure for sake of clarity). The block diagram of UDCS current control strategy is given in Fig. 2. The current error signals efa, efb,and efcare generated for the legs a, b, and c by comparing thefilter currents if a,if b, and if cwith their respective referencecurrents ifaref, ifbref, and ifcref. The hysteresis controller thengenerates the required switching signals A1,A2, B1, B2, C1,and C2 so as to track the filter currents within a hysteresis band.Unlike the conventional scheme, tracking of leg-n is avoided,and a switching pulse of fixed user-defined frequency with 50%dutycycle and its complement are used as switching pulses D1and D2 .It is confirmed that for every switching cycle two UC states (UC-1 and UC-0) occur, where UC-1 signifies the state when switches A1 ,Bn , C1 , andD1 are ON and UC-0 refers to the state when all are OFF. Similarly, ifthe instant t2 gets delayed such that it overlaps instant t3, it results in maximum possible UC state, giving the minimum switching frequency limit. Fig. 3. Switching signals for top switches of four legs of inverter. Fig 4.Equivalent circuit for switching state (1 0 0 0). III. ANALYSIS OF UDCS CONTROLLER Fig 1.Four leg VSI based DSATCOM Onepossible snapshot of the switching pulses of the top switchesof the four legs is shown in Fig. 3. At the instants t2 and t4, the UC state is alwaysfragmented by the variation in the state of the user-defined switchingpulse of leg-n. It can be detected thatthe other legs follow this change one by one. Thus, all theswitches operate at constant frequency as set by the user forthe fourth leg. From the figure, it can be realized that lowerthe user-defined frequency, more is the duration of UC stateand vice versa. Thus, the selection of the user-defined frequencyshould be within a range,constrained limits.The upper limit of frequency is obtained when instant of statuschange of leg-n, say t2 occurs earlier such that it overlaps t1 .Thus, the duration of UC state reduces to zero. ISSN: 2231-5381 This section deals with study of the voltages developed across the interface inductances during various switching states of the four-leg inverter [24]. Consider the switching state (1 0 0 0), i.e., switches A1 ,B2, C2, and D2 are ON. Fig. 4 shows the corresponding equivalent circuit for this state. Here, va,vb, and vcare the instant supply voltages, and vLa, vLb, vLc, and vLnare the voltage drops across the interface inductors. Writing KVL Vdc− vLa− va+ vb+ vLb= 0 Vdc− vLa− va+ vc+ vLc= 0 Vdc− vLa− va+ vLn= 0. (1) The equation (1) can be rewritten as http://www.internationaljournalssrg.org Page 214 International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 1 −1 0 0 1 0 −1 0 1 0 0 −1 = − − + + cycle can be fragmented into eight small time periods (p1 to p8 ), and is described in Table II along with its switching states, respectively. It is not possible to find out these eight unknowns with the four instantaneous equations that can be formed from the four legs. Thus, the mathematical analysis is done for the controlling (upper and lower) values of the userdefined switching frequency. (2) − TABLE I INDUCTOR VOLTAGES FOR DIFFERENT SWITCHING STATES Phases a 1 0 0 0 0 0 0 1 1 1 1 1 1 0 1 0 b 0 1 0 0 0 1 1 1 0 0 1 1 0 1 1 0 c 0 0 1 0 1 0 1 0 1 0 1 0 1 1 1 0 n 0 0 0 1 1 1 0 0 0 1 0 1 1 1 1 0 vLa vLb vLc vLn 3Vdc/4-va -Vdc/4-va -Vdc/4-va -Vdc/4-va -Vdc/2-va -Vdc/2-va -Vdc/2-va -Vdc/2-va -Vdc/2-va -Vdc/2-va Vdc/4-va Vdc/4-va Vdc/4-va -Vdc/4-va -va -va -Vdc/4-vb 3Vdc/4-vb -Vdc/4-vb -Vdc/4-vb -Vdc/2-vb Vdc/2-vb Vdc/2-vb Vdc/2-vb -Vdc/2-vb -Vdc/2-vb Vdc/4-vb Vdc/4-vb -Vdc/4-vb Vdc/4-vb -vb -vb -Vdc/4-vc -Vdc/4-vc 3Vdc/4-vc -Vdc/4-vc Vdc/2-vc -Vdc/2-vc Vdc/2-vc -Vdc/2-vc Vdc/2-vc -Vdc/2-vc Vdc/2-vc -Vdc/2-vc Vdc/2-vc Vdc/2-vc -vc -vc -Vdc/4 -Vdc/4 -Vdc/4 3Vdc/4 Vdc/2 Vdc/2 -Vdc/2 -Vdc/2 -Vdc/2 Vdc/2 -3Vdc/4 Vdc/4 Vdc/4 Vdc/4 0 0 The inductor voltages can be obtained as vLa= (3/4)Vdc− va vLb= (−1/4)Vdc– vb vLc= (−1/4)Vdc− vc vLn= (−1/4)Vdc. (3) As given in Table I voltagesacross the interfacing inductors can be calculated for all other switching state, in a comparable manner. These voltages are used to find the variations in filter currents during these switching states. As shown in Fig. 5 any one of the switching transition patterns possible is chosen for examination. This switching arrangement occurs during the zero-crossing period of the phase-a voltage and, consequently instantaneous voltages of the entire phases are identified. The points at which the filter currents hit the hysteresis band limits as a result of switching decisions can be identified by “•” mark in the figure. Thus, by connecting these points the path of the current can be found. One switching ISSN: 2231-5381 Fig. 5. Switching signals and filter currents (actual, reference, and hysteresis Ban limits). A. Lower Limit of User-Defined Switching Frequency As explained in the previously, when the UC states p4 and p8 extend to the maximum possible extent and to the end of the intervals p5 and p1, the lower limit of the UDS frequency is obtained. Thus, p5 and p1 in Fig. 5 are made equal to zero, and the figure is redrawn, as shown in Fig. 6. During p8 , the leg-b current travels from the lower limit to upper limits of the hysteresis band, causing a change of 2h (in amperes). Using Tables I and II TABLE II SWITCHING STATES CORRESPONDING TO EACH TIME INTERVAL P1 P2 P3 P4 P5 P6 P7 A1 1 1 0 0 0 0 1 http://www.internationaljournalssrg.org B1 1 0 0 0 0 0 0 C1 1 1 1 0 0 1 1 D1 0 0 0 0 1 1 1 Page 215 International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 P8 1 1 = 1 1 (9) (4) During p2, p3, p4, p6, p7 , and p8 , the net change in leg-n current is zero. Therefore (5) During p4 , the change in the leg-c current is−2h (in amperes). Thus . (6) The change in current in leg-a during p3 ,p4 , and p6 is −2h (in amperes). Thus =-2h. (10) From (5) to (10), the following matrix equation is obtained (7) . (11) Here, the values of va, vb, and vcare known as the phase-a voltage passes through zero crossing for the chosen switching pattern. Thus, from (5), (6), and (11), the lower limit of the switching frequency flow_lim can be calculated as . (12) Fig 6. Switching signals and filter currents (actual, reference, and hysteresis band limits) corresponding to lower limit of user-defined switching frequency. Similarly, during p2, p3, p4, p6 , and p7 , the change in leg-b current is −2h (in amperes). Thus .(8) The change in the current in leg-c during p6, p7, p8, p2 , and p3 is 2h (in amperes). Thus, ISSN: 2231-5381 http://www.internationaljournalssrg.org Page 216 International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 Fig. 7. Switching signals and filter currents (actual, reference, and hysteresis band limits) corresponding to upper limit of user-defined switching frequency. B. Upper Frequency Limit of User-Defined Switching As the duration of the UC states decreases to zero, the upper limit of the user-defined switching frequency is obtained. Thus, p4 and p8 in Fig. 5 are made zero, and the figure is redrawn inFig. 7.During p1 , the leg-b current traverses a change of 2h (in amperes). Thus 1=− . ( / ) (13) In leg-c during p5 , the change in current is−2h (in amperes). Thus 5=− . ( / ) (14) During p3, p5 , and p6 , the change in leg-a current is given by ( / ) ( / ) ( / ) ( / ) 6+ 3+ ( / ) ( / ) 5+ 7 = −2ℎ.(16) Change in leg-c current during p6, p7, p1, p2 , and p3 is ( / ) 6+ ( / ) ( / ) 2+ −2ℎ 7+ ( / ) ( / ) 1+ + ( / ) 5+ −(1/2) ( / ) 2ℎ 6+ 2+ ( / ) −(1/4) 3 7= (18) Using (13)–(18), the following matrix equation can be written ISSN: 2231-5381 1 4 − 1 2 ⎤ ⎥ ⎥ ⎥. ⎥ ⎥ ⎥ ⎦ ( / ) 2ℎ − ( / ) + 3 4 − − 1 4 ⎤ ⎥ ⎥ ⎥ ⎥ ⎥ ⎥ ⎦ (19) Thus, the upper limit of the switching frequency fupplimcan be calculated using (13), (14), and (19) as = _ ( ) .(20) The UDCS scheme can efficientlyperform only if the userdefined frequency fswis chosen between the specified limits, i.e., < < . IV. MODELING OF THE UDCS CONTROLLER The modeling of the UDCS controller involves the selection of the suitable switching frequency and voltage source parameters such as dc-link voltage, the value of dc storage capacitor, the value of interface inductor, and the hysteresis band. A threephase 440-V distribution system is considered for the formulation. But, the end results are independent of the supply voltage, and thus, can be used for modeling VSI parameters for any supply voltage. A.Selection of the DC-Link Voltage In leg-n, during p1, p2, p3, p5, p6 , and p7 , the current change is 1+ − / ) 2ℎ 0 3= (17) −(3/4) − The done for other switching patterns also converge to similar results. In leg-b, change in current during p2, p3, p5, p6 , and p7 is given as 2+ 1 2 1 − 2 1 2 − 5+ 6 = −2ℎ.(15) ( / ) × ⎡ ⎢ 2 ⎢ 3 =⎢ 6 ⎢ 7 ⎢ ⎢2ℎ ⎣ 1 − 4 1 − − 4 3 − 4 1 − 4 2ℎ ( − _ ( / ) 3+ ⎡ 0 ⎢ 1 ⎢− − ⎢ 2 ⎢ 1 − ⎢ 2 1 ⎢ − ⎣ 2 The suitable choice of the dc-link voltage is essential for the appropriate operation of this scheme. A factor m is defined, which is the ratio of Vdcand peak value of phase voltage. The correct functioning of the UDCS method requires the presence of nonnegative (positive or zero) values for the time periods fromp1 to p8 such that state transition would enable theswitching signals of legs a, b, and c to follow the user-defined signal. TABLE III http://www.internationaljournalssrg.org Page 217 International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 VARIATION OF LIMITING FREQUENCIES AND TIME INTERVALS WITH DC-LINK VOLTAGE resulting change in energy stored in given by (1/2) m Vdc (Volts) 3.1 3.3 3.5 3.7 3.9 4.1 1113.7 1185.6 1257.4 1329.3 1401.1 1473 Upper Limit Fupp_lim Time (Hz) Interval p1 5394 5990.5 Negative 6561.7 7111.5 Positive 7643.4 8159.8 Lower Limit Flow_lim Time (Hz) Interval p2 2855.2 3077.5 Negative 3274.4 3450.1 Positive 3607.7 3749.9 Thus, the value ofmis varied and fupplim, p1 (corresponding to upper limit), flow_lim, and p2 (corresponding to lower limit) are calculated using (20), (13), (12), and (11), respectively. Table IIIillustrates these values for h = 0.4 (in amperes) and Lf= 30mH. It can be observed that the time intervals p1 and p2 attain negative values formless than 3.5. Thus, the UDCS scheme can effectively work only for values of m equal to or greater than 3.5. This limiting value of m is verified by simulation studies too. Also by extensive calculations, it has been found that this minimum value of m holds good for any value of h and Lf, for both upper and lower limits of switching frequency. As the dclink voltage should, thus, be kept as low as possible, the authors choose the value of m near to the minimum value, say 3.7. B. Selection of the DC Storage Capacitor The design of the dc storage capacitor is based on its ability to normalize its voltage under transient conditions. Rate of energy of the system in joules per second is, therefore, given by X × 1000 J/s. Let us further assume a worse case when the load changes from a tenth full load to a full load, i.e., from X/10 to X. The compensator has to supply this from the capacitor. The reduction in capacitor voltage would cease in half-a-cycle or at the worst one cycle by the action of the moving average filter in the control algorithm. The PI controller action does not come to picture as it responds very slowly. Thus, the energy to be supported by the dc capacitor is given as = (21) Wheren is the number of cycles, which is considered as one. If the transient results in capacitor voltage change from 3.7Vmto 3.3Vmor vice versa, the ISSN: 2231-5381 [(3.7 ) − (3.3 capacitor is ) ]= . (22) The aforementioned equation implies that =( ( / ) . ) ( . ) . (23) TABLE IV VARIATION OF LIMITING FREQUENCIES WITH h AND Lf H (Amps) Lf (H) 0.02 0.02 0.02 0.03 0.03 0.03 0.04 0.04 0.04 0.2 0.3 0.4 0.2 0.3 0.4 0.2 0.3 0.4 Fupp_lim (Hz) 21334.1 14222.8 10667 14222.8 9481.8 7111.5 10667.2 7111.5 5333.6 Flow_lim (Hz) 10350.1 6900 5175.1 6900 4600 3450.1 5175 3450.1 2587.6 C . Selection of Switching Frequency Eq (12) and (20) gives the lower limits and upper limits of switching frequencies for the UDCS scheme. An effort is made to express these controlling frequencies in the form of simple and handy equations.Ffrequency limits are computed for different values of h and Lf, using(12) and (20)corresponding to m = 3.7, as given in Table IV. From the obtained values offlowlim and fupplim, the following relations are deduced for the lower limits and upper limits of switching frequencies = _ _ = . . . (24) .(25) The earlier equations describing the limiting cases are valid for any value of h and Lf .Thus, the switching frequency, in general, can be expressed as = (26) http://www.internationaljournalssrg.org Page 218 International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 WhereKswvaries between 15.6 and 32.1 for the limiting cases. The practical restriction on switching frequency offered by the semiconductor switch is also to be considered while making the choice. D. Selection of the Hysteresis Band (h) and Interface Inductor (Lf ) The value of Kwis to be suitably selected. Its choice as 15.6 results in theupper limit of switching frequency. But this is not suitable dueto higher switching losses and EMI considerations. TABLE V SIMULATION PARAMETERS System voltage: 440 V (L-L voltage), 50 Hz Loads:Za=60+j13.2Ω.Zb=100+j15.7Ω,Zc=140 +j18.85Ω and 3Φ full bridge diode rectifier feeding a R-L load of100Ω, 0.1 H Interface inductors (Lf) : 30 mH with series resistance of 0.1 Ω Dc link voltage (Vdc): 1330V Dc Capacitor (Cdc): 1000 µF Hysteresis band (h): 0.4 A Leg-n switching frequency (fsw): 5 kHz Thus, a tradeoff value is chosen for Kw between these limits, say 22. Thus ℎ = . (27) computed using (23) as 1000 µF. Theuser-defined switching frequency fswbeing is taken as 5 kHz. The value of h is taken as0.4 A, for a maximum 10 A rated current. The value of interface inductor Lf is calculated using (27)and is found to be 30mH. It is ensured that fswlies within itslimits (3.45 kHz -7.1 kHz ), obtained using(24) and (25). The designed VSIparameters are shown in Table V. The load contains an unbalancedR–L load along with a threephase diode rectifier. Thesevalues are used for simulation studies as shown in Fig. 1. Thetheoryof instantaneous symmetrical componentsis used for the generationof the reference filter currents [25]. B. Performance Indexes The designed UDCS controller’s performance is comparedwith the conventional hysteresis controller using thefollowing indexes. 1)Total Mean Switching Frequency: The mean switchingfrequency of any leg-k is calculated as the number ofswitching cycles in one time period of power cycle. The totalmean switching frequency, fav total is thus defined as follows: =∑ _ (28) , , , WhereNkis the number of switching cycles in leg-k during onecycle period T of the system voltage. 2) Switching Frequency Deviation Index: The switching frequencydeviation index (DI) is prelude in order to account forthe drift in the instantaneous switching frequencies fromthe mean switching frequency. The DI for any leg-k is definedas = ∑ _ _ , fork = a, b, c, and n _ The value of h cannot be raised beyond a limit as it develops poor quality of compensation. Thus, the value of h is chosenbetween 4% to 10% due to the above mentioned reasons. It is also clear that the switching frequency f sw, hysteresis band h, and interface inductance Lfare related to one other. Therefore, just as the choice of switching frequency can be made over a range, the parametric variations like variation in the value of Lf V. SIMULATION STUDIES A. Design Example A three-phase 440-V distribution power network is contemplated.The dc-link voltage is computed as1330 V, considering mas 3.7, Taking a 10-kVA system, i.e., X = 10, n = 1,andT = 0.02 s, Cdcis ISSN: 2231-5381 (29) Wherefk_instand fkavare the instantaneous and meanswitching frequenciesduring one power cycle. This index is a goodindicator of the dependability of the switching frequency. Thus, avery low value of DI is wanted. 3) Percentage Total Harmonic Distortion: The percentagetotal harmonic distortion (% THD) of the compensated sourcecurrents indicates the quality of the load compensation. C. Simulation Results The DSTATCOM based on the nominated design procedureis cable of compensating the unbalance and http://www.internationaljournalssrg.org Page 219 International Journal of Engineering Trends and Technology- Volume3Issue2- 2012 harmonicsin load currents. Fig. 9(a) and (b), showstheinstantaneous and mean switching frequencies for legs a, b,c, and n for the conventional hysteresis and UDCS controlstrategies,respectively. The supply phase voltages, load currents,and the compensated source currents are shown in Fig. 8. Here,fainst, fbinst, fc inst, and fninstrefer to the instantaneousswitching frequencies for legs a, b, c, and n. These are representedas vertical lines, whereas faav, fbav, fc av, and fnavrefer to the corresponding mean values and arerepresented ashorizontal lines. The indexes based on the simulationresults are tabulated in Table VI. The proposed UDCS controllershows the decrease in switching frequency. The reduction in the totalmean switching frequency is 17.2%. All the legs have gottuned to the user-defined frequency of 5 kHz.Fig. 9(a) shows the frequency variation of conventional scheme. Fig. 10(a) and (b) shows the distinguishing harmonic spectrum of the phase-a source currents for theconventional hysteresis and proposed UDCS. In the proposed scheme, the 100th harmoniccomponent (corresponding to the userdefined switching frequency 5 kHz) is seen to be dominant. Thus, the simulationresults value the UDCS design procedure. VII. CONCLUSION This paper has put forth the modeling and design of a UDCS frequency current-control-based three phase four wire distribution network. Analytical expressions were derived that enables the user to select the switching frequency for the proper working of the UDCS method. Guidelines were also proposed for the choice of inverter parameters like hysteresis band, DC link voltage, DC link capacitor and inductor. The proposed modeling procedure was valued by simulation and experimental studies on a three-phase four-wire distribution network. REFERENCES [1] M. P. Kazmierkowski and L. Malesani, “Current control techniques for three-phase voltage-source PWM converters: A survey,” IEEE Trans. Ind. Electron., vol. 45, no. 5, pp. 691–703, Oct. 1998. [2] C. S. Quinn and N. Mohan, “Active filtering of harmonic currents in three-phase, four-wire systems with three-phase and single-phase nonlinear loads,” in Proc. IEEE Appl. Power Electron.Conf., 1992, pp. 829– 836. [3] J.Holtz, “Pulse width modulation—A survey,” IEEE Trans. Ind. Electron., vol. 39, no. 5, pp. 410–420, Dec. 1992. [4] S. Buso, L. Malesani, and P. Mattavelli, “Comparison of current control techniques for active power filter applications,” IEEE Trans. Ind. Electron., vol. 45, no. 5, pp. 722–729, Oct. 1998. [5] S. M. Ali and M. P. Kazmierkowski, “PWM voltage and current control of four-leg VSI,” in Proc. IEEE ISIE 1998, vol. 1, pp. 196–201. [6] D. M. Brod and D. W. Novotny, “Current control of VSI– PWM inverters,” IEEE Trans. Ind. Appl., vol. 1A-21, no. 4, pp. 562–570, May/Jun. 1985. [7] Q.Yao and D.G.Holmes, “A simple, novel method for variablehysteresis band current control of a three phase inverter with ISSN: 2231-5381 constant switching frequency,” in Proc. IEEE IAS Annu. Meet. Conf. Rec., Toronto, ON, Canada, Oct. 1993, pp. 1122–1129. [8] L. Malesani and P. Tenti, “A novel hysteresis control method for current controlled voltage-source PWM inverters with constant modulation frequency,” IEEE Trans. Ind. Appl., vol. 26, no. 1, pp. 88–92, Jan. 1990. [9] L. Malesani, P. Mattavelli, and P. Tomasin, “High-performance hysteresis modulation technique for active filters,” IEEE Trans. Power Electron., vol. 12, no. 5, pp. 876–884, Sep. 1997. [10] B. K. Bose, “An adaptive hysteresis-band current control technique of a voltage-fed PWM inverted for machine drive system,” IEEE Trans. Ind. Electron., vol. 37, no. 5, pp. 402–408, Oct. 1990. [11] T.W. Chun and M.K.Choi, “Development of adaptive hysteresis band current control strategy of PWM inverter with constant switching frequency,” in Proc. IEEE APEC 1996, San Jose, CA, pp. 194–199. [12] F. Liu and A. I. Maswood, “A novel variable hysteresis band current control of three-phase three-level unity PF rectifier with constant switching frequency,” IEEE Trans. Power Electron., vol. 21, no. 6, pp. 1727–1734, Nov. 2006. [13] M. A. Rahman, T. S. Radwan, A. M. Osheiba, and A. E. Lashine, “Analysis of current controller for voltage source inverter,” IEEE Trans. Ind. Electron., vol. 44, no. 4, pp. 477–485, Aug. 1997. [14] J. Zeng, C. Yu, Q. Qi, Z. Yan, Y. Ni, B. L. Zhang, S. Chen, and F. F. Wu, “A novel hysteresis current control for active power filter with constant frequency,” Electr. Power Syst. Res., vol. 68, pp. 75–82, 2004. [15] H. M. Kojabadi, B. Yu, I. A. Gadoura, L. Chang, and M. Ghribi, “A novel DSP-based current-controlled PWM strategy for single phase grid connected inverters,” IEEE Trans. Power Electron., vol. 21, no. 4, pp. 985– 993, Jul. 2006. [16] R. Wu, S. B. Dewan, and G. R. Slemon, “Analysis of a PWM ac to dc voltage source converter under the predicted current control with a fixed switching frequency,” IEEE Trans. Ind. Appl., vol. 27, no. 4, pp. 756–764, Jul./Aug. 1991. [17] K. P. Louganski and J. S. Lai, “Current phase lead compensation in single phase PFC boost converters with a reduced switching frequency to line frequency ratio,” IEEE Trans. Power Electron., vol. 22, no. 1, pp. 113– 119, Jan. 2007. [18] C. T. Pan and T. Y. Chang, “An improved hysteresis current controller for reducing switching frequency,” IEEE Trans. Power Electron., vol. 9, no. 1, pp. 97–104, Jan. 1994. [19] R. Zhang, V. H. Prasad, D. Boroyevich, and F. C. Lee, “Three-dimensional space vector modulation for four leg voltage source converters,” IEEE Trans. Power Electron., vol. 17, no. 3, pp. 314–326, May 2002. [20] B. H. Kwon, T.W. Kim, and J. H. Youm, “A novel SVMbased hysteresis current controller,” IEEE Trans. Power Electron., vol. 13, no. 2, pp. 297– 307, Jan. 1998. [21] M. A. Perales, M. M. Prats, R. Portillo, and L. G. Franquelo, “Three dimensional space vector modulation in abc coordinates for four-leg voltage source converters,” IEEE Power Electron. Lett., vol. 1, no. 4, pp. 104– 109, Dec. 2003. [22] V. George and M. K. Mishra, “User-defined constant switching frequency current control strategy for a four leg DSTATCOM,” IET Power Electronics, [23] V. George, M. K. Mishra, and S. Sridharan, “A novel constant frequency strategy for a three-leg DSTATCOM,” in Proc. 21st Can. Conf. Electr. Comput. Eng., Niagara Falls, ON, Canada, May 2008, pp. 681–684. [24] P. Lohia, M. K. Mishra, K. Karthikeyan, and K. Vasudevan, “A minimally switched control algorithm for three-phase four-leg VSI topology to compensate unbalanced and nonlinear load,” IEEE Trans. Power Electron., vol. 23, no. 4, pp. 1935–1944, Jul. 2008. http://www.internationaljournalssrg.org Page 220