For Con-Tech Lighting Symphony Low Voltage Track System Our Symphony Low Voltage Track has solid 10 gauge copper conductors with Noryl® insulators placed in heavy gauge extruded aluminum channels. These 25A rated track sections are supplied with toggle bolts and wood screws for a simple installation. The 2', 4' and 6' sections are pre-drilled with two mounting holes and the 8' section has three mounting holes. Track sections may be cut in the field, but take care to back out the bus bar before cutting. Every section is supplied with a MLA-1 End Feed Connector/Cover and a MLA-11 End Cap. Polarity is not an issue with low voltage lighting. Symphony track can be fed at the MLA-1 End Feed Connector, MLA-8 Conduit End Feed, or MLA-9 Outlet Box/T-Bar Ceiling Canopy with use of a remote transformer. Connections can be made by using the MLA-2 Straight Connector, MLA-3 Flexible Connector, or MLA-12 Right Angle Connector. Compatible transformers are available in various configurations: • MLA-415: 125VA Canopy Transformer, Junction Box Mount, 120/12V, End or Center Feed • MLA-60: 60VA Plug-in Electronic Transformer with 10’ Cord and Plug, 120/12V, End Feed • MLA-830: 240VA, Surface Electronic Transformer Feed with Knockouts and Switch, 120/12V, End Feed Transformers/Voltage Drop Chart for Low Voltage Power Systems When voltage and lamp brightness at the beginning of an illuminated section (close to the transformer) are higher than the voltage and lamp brightness at the end, the difference is known as “Voltage Drop.” For a proper low voltage lighting system, circuit runs must be of sufficient size wire to maintain a proper operating voltage to all lamps. Maximum allowable voltage drop should not exceed 5%. Electronic Transformers Maximum wiring distance (from remote transformer to start of track): 12' (Max.*) with AC Electronic Transformer (use minimum 10 ga. wire) 40' (Max.*) with DC Electronic Transformer (use minimum 10 ga. wire) These distances may be extended with thicker gauge wire. These transformers may be dimmed with dimmers specifically designed for use with Low Voltage Electronic Transformers. All electronic transformers offer auto-reset short circuit protection, overload protection, and thermal cut-off at 257°F. These electronic transformers will not operate without a minimum 30% load. UL Listed (UL 2108 compliant) Magnetic Transformers Maximum distance with Magnetic Transformer should not exceed 40.' These transformers may be dimmed with dimmers specifically designed for use with Low Voltage Magnetic Transformers. High reliability with magnetic circuit breakers. Primary 5% boost tap provided to compensate for voltage drop on long runs of 20' or more. These UL Listed (UL 2108 compliant) transformers will operate with any load. WIRING DISTANCE IN FEET REMOTE TRANSFORMER TO START OF TRACK Ampere Capacity Wire Gauge 25 10 Low Voltage Output Transformer Wattage #10 GA Wire #8 GA Wire #6 GA Wire #4 GA Wire 12 Volt 150 Watt 23' 36' 57' 91' 35 8 12 Volt 250 Watt 14' 21' 34' 55' 50 6 12 Volt 300 Watt 11' 18' 28' 45' 70 4 Transformer/Driver Selection Matrix for MCT-3LED Fixture and MRL-3LED Pendants This matrix is designed to provide multiple options to powering the MCT-3LED Symphony Track fixture and MRL-3LED Symphony Track pendants. All transformers and drivers must be installed according to National Electrical Code and local building codes. Due to minimum wattage requirements of many electronic transformers, Con-Tech offers a low wattage Electronic Transformer option, Magnetic Transformers and Drivers. Mounting Options # of Fixtures (Watts) Electronic Transformer Magnetic Transformer Driver Mono-Point (MLA-8 or MLA-9) 1 (4.7W) RS1260MLED LVT-150 LED10CV12 Symphony Track 2 (9.4W) RS1260MLED LVT-150 LED10CV12 3 (14.1W) RS1260MLED LVT-150 LED25 12V 4 (18.8W) RS1260MLED LVT-150 LED25 12V 5 - 10 (23.5W - 47W) LRT-181, LRT-363, MLA-60 LVT-1200-C-24, LVT-150, LVT-300, LVT-300 277V, LVT-300-24, LVT-500-C, LVT-600-24, LVT-600-277V-24, LVT-600-C LED60WDC12V LRT-181, LRT-363, LVT-151, LVT-151 24V, LVT-175-DC, LVT-303, LVT-303 24V, LVT-303-DC, MLA-60, MLA-415, MLA-830 LVT-1200-C-24, LVT-150, LVT-300, LVT-300 277V, LVT-300-24, LVT-500-C, LVT-600-24, LVT-600-277V-24, LVT-600-C 11 or > (51.7W+) All specifications subject to change without notice. 1-847-559-5500 www.con-techlighting.com This document can be recycled. LED100WDC12V Continued on Page 2 SYM INST 1 For Con-Tech Lighting Symphony Low Voltage Track System MLA-1 End Feed Connector: Figure 1 • Remove the MLA-1 connector cover and loosen the terminal block allen screws. • Attach the terminal block to the Symphony track and tighten the terminal block Philips mounting screw. • Mount the Symphony track to the ceiling (2', 4', & 6' pieces have 2 mounting holes and 8' pieces have 3 mounting holes). Toggle bolts and screws are provided with the track. The copper bus bars must be inserted into the terminal block for 5/16". • Connect the 12V secondary wires from the transformer to the terminal block using the slotted set screws. MAKE SURE ALL CONNECTIONS ARE TIGHT! • Properly secure the cover to the terminal block with (1) 6-32 x 1/4" Philips Head Screws. Symphony Track Busbars/10 Gauge Locking Screw Slotted Screws for Bus Bars Slotted Screws for Transformer Feed 12V or 24V Feed from Transformer MLA-1 Cover Mounting Screw MLA-2 Straight Connector and MLA-12 Right Angle Joiner/“L” Connector: Figure 2 • Remove the (1) dead end and (1) MLA-1 end feed connector from the track assembly. • Remove the covers from the MLA-2 or MLA-12 connectors. • Slide the terminal blocks onto the track bus bars by 5/16", tighten the slotted and locking screws. • Connect the 12V conductors to the terminal block using the slotted set screws. MAKE SURE ALL CONNECTIONS ARE TIGHT! • Properly attach the covers to the terminal block assemblies. • Save the extra components in case of emergency. Continued on page 3 Dead End Busbars End Feed Connector (MLA-1) 10 Gauge Wires End Feed Terminal Block End Feed Terminal Block Slotted Set Screws Locking Screw Right Angle Cover OR Straight Connector Cover All specifications subject to change without notice. 1-847-559-5500 www.con-techlighting.com This document can be recycled. SYM INST 2 For Con-Tech Lighting Symphony Low Voltage Track System MLA-3 Flexible Connector: Figure 3 Dead End • Remove the (1) dead end and (1) MLA-1 end feed connector from the track assembly. • Remove the covers from the MLA-3 assemblies. • Slide the MLA-3 terminal blocks onto the track bus bars by 5/16", tighten the slotted and locking screws. • Connect the 12V conductors to the terminal block using the slotted set screws. MAKE SURE ALL CONNECTIONS ARE TIGHT! • Properly attach the MLA-3 covers to the terminal block assemblies. • Save the extra components in case of emergency. Busbars End Feed Connector (MLA-1) Flexible Wire Sleeve End Feed Terminal Block End Feed Terminal Block Locking Screw MLA-3 Cover MLA-3 Cover 6-32 Screw 6-32 Screw MLA-8 Conduit Feed: Figure 4 • Attach the Conduit or BX (Flexible Conduit) to the MLA-8 backplate either through the end 7/8" hole or through the back 7/8" pryout. (Connectors supplied by others) • Remove and set aside the end feed connector (MLA-1) from the track. • Fasten the Conduit feed backplate portion to the track. Tighten the locking screw. • Insert the busbar into the terminal block by 5/16". Tighten the slotted screws. • Mount the Symphony track to the ceiling (2', 4', & 6' pieces have 2 mounting holes, 8' pieces have 3 mounting holes). Toggle bolts and screws are provided with the track. • Connect the 12V secondary wires from the transformer to the terminal block using the slotted set screws. MAKE SURE ALL CONNECTIONS ARE TIGHT! • Properly secure the cover to the backplate. ML8 Backplate Flexible Conduit Connector 10 Gauge Transformer Secondary 12V Wires End Feed Terminal Block Locking Screw End Cut Out ML8 Cover Continued on page 4 All specifications subject to change without notice. 1-847-559-5500 www.con-techlighting.com This document can be recycled. SYM INST 3 For Con-Tech Lighting Symphony Low Voltage Track System MLA-9 Outlet Box/T-Bar Ceiling Feed Outlet Box Feed: Figure 5 • Attach the back mounting plate onto the octagon (8B) outlet box by (2) 8-32 screws provided on the outlet box • Remove and set aside the cover from the MLA-1 end feed connector. • Mount the terminal block to the mounting plate using a 6-32 x 1/2" screw. • Mount the Symphony track to the ceiling (2', 4', & 6' pieces have 2 mounting holes; 8' pieces have 3 mounting holes). Toggle bolts and screws are provided with the track. The copper bus bars must be inserted into the terminal block for 5/16". • Connect the 12V secondary wires from the transformer to the terminal block using the slotted set screws. MAKE SURE ALL CONNECTIONS ARE TIGHT! • Properly secure the cover to the mounting plate with (2) 6-32 x 1/2" Philips Head Screws. • If feeding two pieces of track at 180º, carefully remove the cutout in the canopy. 10 Gauge Transformer Secondary 12V Wires MLA-9 Mounting Plate End Feed Terminal Block 6-32 x 1/2" Screw T-Bar Ceiling Feed: Figure 6 • Attach the LA-1 T-Bar clip (Ordered separately) to the 15/16" Grid. • Install the back mounting plate onto the 8-32 x 5/8" stud (Trim to size) with the barrel nut. The center hole on the plate is 3/16". • Properly connect the 12V secondary wires to the back mounting plate by using 1/2" conduit and BX ļ¬ttings (Provided by others). The plate has (2) 7/8" knockouts for conduit. • Mont the terminal block to the mounting plate using a 6-32 x 1/2" screw. • Mount the Symphony track to the ceiling (2', 4', & 6' pieces have 2 mounting holes; 8' pieces have 3 mounting holes). The LA-1 T-Bar Clip (Ordered separately) should be used for mounting. The copper bus bars must be inserted into the terminal block for 5/16". • Connect the 12V secondary wires from the transformer to the terminal block using the slotted set screws. MAKE SURE ALL CONNECTIONS ARE TIGHT! • Properly secure the cover to the mounting plate with (2) 6-32 x 1/2" Philips Head Screws. • If feeding two pieces of track at 180º, carefully remove the cutout in the canopy. MLA-9 Cover 4-11/16" Square Single or Dual Feed 180° Flexible Conduit LA-1 15/16" Grid Twist Fastener with #8-32 x 5/8" Stud Size MLA-9 Mounting Plate Brass Nut All specifications subject to change without notice. 1-847-559-5500 www.con-techlighting.com This document can be recycled. SYM INST 4