ConTech Lighting REXA Series Adjustable Recessed or Surface Mount LED Edge-Lit Exit Sign with Battery Back-Up Bar Hangers Recessed Mount Recessed Back Box (Metal Housing) Adjusting Slots Recessed Back Box (Metal Housing) Bar Hangers Tighten Screws After Positioning Black Main Backup Circuit White Green Junction Box 277VAC 120VAC Input Input Orange Ground Wire For AC Power Spring Bracket Main Housing End Cap Rotation Housing Chevron EXIT Panel Chevron Template Screw Trim Plate Recessed Ceiling Mount Recessed Wall Mount INSTALLATION INSTRUCTIONS: The unit can be installed on any surface, you may rotate the Exit panel in any angle from 0 - 180°. Secure Exit panel angle using the locking screws. Recessed Mounting: Ceiling/Wall 1. Refer to assembly drawing before starting installation. (Figure 1) 2. Position metal housing and bar hangers between joists. Make sure bar hangers are oriented in the correct position. Position metal housing temporarily by hammering “nail-in” tabs on bar hangers, then secure permanently with nails. Bar hangers should be level with the bottom of the joists. (Figure 2) 3. Adjust height of metal housing vertically using adjusting slots and tightening all screws on adjusting slots and bar hanger bracket to secure adjusting bracket and bar hanger. 4. Connect test switch and LED indicator cables via connectors. (Figure 1) You must connect battery connectors before connecting AC power. 5. Make proper electrical connections at recessed metal box or at junction box in the ceiling: - Make the proper supply wire connections. - If using 120VAC, connect the black and white wires to the supply wires. If using 277VAC, connect the orange and white wires to the supply wires. (Figure 3) - Cap off unused wires. In all cases, use standard approved wire nuts for connection of wires. NOTE: You may use holding wire during wiring. 6. Determine direction for chevron (arrow) placement. Peel adhesive chevron(s) from backing liner and place into the marked position on the template. Firmly press chevron corners and edges, then peel template off and leave chevron in place. NOTE: When Chevron(s) are being taped on the EXIT panel, you can not use it again once it is removed. 7. Secure trim plate by using provided screws. (Figure 4) 8. Allow battery to charge for 24 hours before first use. For recessed wall mounting, you may follow all procedures above, then rotate the EXIT panel 90º after securing the trim plate. All specifications subject to change without notice. 1-847-559-5500 www.contechlighting.com This document can be recycled. REXA INST ConTech Lighting REXA Series Adjustable Recessed or Surface Mount LED Edge-Lit Exit Sign with Battery Back-Up ISurface Mounting 1. Refer to assembly drawing before starting installation. (Figure 5) 2. Attach crossbar to junction box, using screws if needed (not provided). Open end cap (with test switch and indicator assembled) to connect battery connector before connecting AC power. Ceiling/Wall: Figures 6 and 7. Feed AC supply wires through canopy center hole. End: Figure 8. Remove the opposite mounting end cap and knock out the holes on the cap for pulling through wires and assembly screws. Pull out all AC supply wires and feed wires through the center holes of end cap first, then the canopy. Assemble canopy onto aluminum housing with (2) #10-24 screws (supplied) and make proper wire connections. - Make the proper supply wire connections. - If using 120VAC, connect the black and white wires to the supply wires. If using 277VAC, connect the orange and white wires to the supply wires. (Figure 3) - Cap off unused wires. In all cases, use standard approved wire nuts for connection of wires. 2. Remove bushing and then insert plug and rivets into housing top holes to close the holes on the aluminum housing. 3. Determine direction for chevron (arrow) placement. Peel adhesive chevron(s) from backing liner and place into the marked position on the template. Firmly press chevron corners and edges, then peel template off and leave chevron in place. NOTE: When Chevron(s) are being placed on the Exit panel, you can not use it again once it is removed. 4. Using (2) M4-40 screws (supplied), tighten canopy to mounting plate/crossbar. Surface Mount Canopy Mounting End Cap Bracket Power Wires Hole Plug Bushing Ni-Cad Battery End Cap Test Switch LED Indicator Locking Screw Main Housing Rotation Housing LED PCB Chevron Chevron Template EXIT Panel Surface Ceiling Mount Junction Box (Not Provided) Crossbar Canopy IMPORTANT SAFETY INSTRUCTIONS: • Read all the instructions before installation. Save instructions for later use. • Turn off the power at fuse or circuit breaker box before installation or maintenance work. • Wear rubber soled shoes and work on a sturdy wooden or non-conductive ladder. • Product must be installed in compliance with National Electrical Code and local building codes. For indoor use only. • Do not mount near gas or electric heaters. • Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. • Installing contrary to instructions may cause unsafe conditions. • Warning: Risk of fire. Most dwellings built before 1985 have supply wire rated at 60°C. Consult a qualified electrician before installation. • Avoid hazards to children: account for all parts and properly dispose of all packing materials. • Call the Technical Support department at ConTech Lighting with any installation questions. Surface Wall Mount Junction Box (Not Provided) Crossbar Canopy Surface End Mount Junction Box (Not Provided) Crossbar Canopy All specifications subject to change without notice. 1-847-559-5500 www.contechlighting.com This document can be recycled. REXA INST