For Con-Tech Lighting Ceramic Metal Halide and Compact Fluorescent Decorative Stemlight Pendant Series: CGM8, CGF8, CGM12 and CGF12 INSTALLATION PROCEDURES FC MOUNT: Flexible Cable Mono-Point, Damp Location Listed RS MOUNT: Rigid Stem Mono-Point, Damp Location Listed Prior to assembly, ensure 4" Round or Square (with a Round-to-Square Junction Box Cover Plate) Junction Box is properly mounted to the ceiling structure. The center-tocenter mounting holes on the 4" Round Junction Box are 3-1/2"; the Round-to-Square Junction Box Cover are 2-3/4". Both use 8-32 x 1/2" screws. Loosen the (2) Philips screws that hold the mounting bar to the top round wiring compartment. (Figure 1) Attach the mounting bar to the junction box or junction box cover. Continue with fixture assembly instructions. FIXTURE ASSEMBLY INSTRUCTIONS: Shade/hood assembly comes with 132" of socket lead wiring in a silicone sleeve: 8" and 12" Single Lamp CFL Housings: (2) Blue, (2) Red, (1) Green 12" Two-Lamp CFL Housings: (2) Blue, (2) Red, (2) Yellow, (1) Green 8" and 12" CMH Housings: (1) Black, (1) White, (1) Green; Black = Blue and White = Red Bicycle Cable (CGF8 and CGF12): The Bicycle Cable Connector has (1) 2mm recessed hex head screw for locking into the nipple plus (2) 2mm recessed hex head screws for locking into the bicycle cable. (Figure 2) (1) 2mm hex key wrench is supplied with each fixture. Determine length of bicycle cable required. If cutting is required, loosen bicycle cable from connector. Slide bicycle cable off the wiring. Remove wire grommet. Cut bicycle cable with a hacksaw using a fine tooth (32T) blade, BX Armor cable cutter or high speed metal cutting blade. Remove any sharp edges. Re-insert internal wire grommet. Slide bicycle cable over the wiring. NOTE: The bicycle cable will only accept the wires less the silicone sleeve. Re-insert the bicycle cable connector. Tighten all hex head screws as much as possible. Flexible Cord (CGM8 and CGM12): Determine the length of flexible cord required. If cutting is required, loosen the coiled 18-3 cable. There should not be any excess cable in the ballast compartment. Leave only 6-8" for wiring available. Mark the cable where it needs to be cut. Carefully score the outer jacket around the diameter of the cable about 6-8" below the total length. Then, score the outer jacket lengthwise for that 6-8" section. Use proper rotary cable slitters such as Ideal #45-128 or Eclipse #200-009. Remove the outer jacket. Trim off the individual wire insulations by 1/2". For CMH ballast wiring, mark the white wire with red colored tape and the black wire with blue colored tape. Insert the cut wiring through the cable connector on the ballast housing. Attach the black strain relief bracket to cord. (Figure 5) Tighten the (2) plastic straight blade screws in order to hold the cord to the ballast housing safely. (Figure 4) Make your wiring connections to the CMH ballast inside the ballast compartment. Rigid Stem (CGF8 and CGF12): Determine length of the stem with internal coupling required. A swivel stem attachment (35° adjustment) is included for sloped ceiling applications (Figure 2). Assemble stems onto the shade/hood assembly one at a time, carefully feeding wiring through each section. After all the stems are attached completely, remove the (4) brass screws from the top of the ballast compartment and insert the wiring into the bottom of the compartment. (Figure 1) Screw the stem(s) into the nipple. Tighten all hex head screws as much as possible. Rigid Stem (CGM8 and CGM12): Determine the length of the stem with external couplings required. Loosen the (2) 3.0mm steel hex head screws from the cord grip connector. (Figure 3) Remove the inner grommet. Slide the stems over the flexible cord. Screw into the top cable connector. Tighten the (2) 3.0mm steel hex head screws. Add couplings to the stem (if required). Determine the length of flexible cord required. Use the CGM (8, 12) Flexible Cord Instructions for the balance of the installation. Loosen the (2) plastic straight blade screws from the ballast compartment cord grip connector. (Figure 4) Remove the inner grommet. Insert the flexible cord through the connector. Screw the stem to the ballast compartment cable connector. Tighten the (2) plastic straight blade screws. Continued on Page 2 All specifications subject to change without notice. 1-847-559-5500 www.con-techlighting.com Top of Canopy Mounting Bar Brass Screws on Ballast Plate There should not be any excess cable in the ballast compartment. Leave only 6-8" for wiring available. CFL Connectors Bicycle Cable Connector Swivel Stem Attachment 2mm Hex Head Screw Locks Onto Nipple (2) 2mm Hex Head Screws Lock Onto Bicycle Cable Metal Halide Installation 18-3 Cable Cord Grip Connector (2) 3mm Hex Head Screws 12" Metal Halide Decorative Stemlight Mono-Point Canopy: Metal Halide Installation Cord Grip Connector (2) Plastic Straight Blade Screws This document can be recycled. 1 DECOSTMLT INST For Con-Tech Lighting Ceramic Metal Halide and Compact Fluorescent Decorative Stemlight Pendant Series: CGM8, CGF8, CGM12 and CGF12 WIRING INSTRUCTIONS: Mono-Point Mount: Connect the socket leads (Black/Blue) to Blue, (White/Red) to Red and the Green Ground Lead to the ballast leads. (Figure 5) Connect the primary leads (Black-to-Black, White-to-White, and Green-to-Green) on the Ballast/Supply side. Take the ballast plate and attach the (4) Brass screws through the slots into the threaded brackets. Connect the primary leads from the junction box to the primary leads of the fixture (Black-to-Black, White-to-White, and Green-to-Green). Attach the top round wiring compartment to the junction box and tighten the (2) Philips/Straight Blade screws. The white socket lead with the Red identification marker gets connected to the red ballast lead. The black socket lead with the blue identification marker gets connected to the blue ballast lead. The green socket lead wiring gets connected to the green ballast lead and green housing lead. Warning: When cutting the jacketed socket lead wiring, avoid slitting the individual wire conductor’s insulation which could cause arcing. Per UL1598 and NEC 300.14, “at least 150mm (6in.) of free conductors and less than 8 in., measure from the point in the box where it emerges from its raceway or cable sheath shall be left at each outlet, junction and switch point for splices or the connector of luminaires or devices”. Ceiling Junction Box Mounting Bar Black to Black Green to Green (Ground Wire) White to White Black White SHADE ASSEMBLY INSTRUCTIONS: Loosen the (4) 3.0mm Hex Head Screws from the arms of the cast frame. (Figure 6) Insert the correct wattage lamp(s) into the socket(s). Rest the decorative shade into the bottom cast ring, then reattach the (4) Hex Head Screws into the cast arms. Unpack the floating glass and attach to the bottom of the cast frame using the (4) floating ring attachment mechanisms: screw in the double threaded bolt with the center ribbed collar, then attach the glass. To lock the glass in place, screw on the knurled nut. Blue Red Green Red Identification Marker IMPORTANT SAFETY INSTRUCTIONS: • Read all the instructions before installation. Save instructions for later use. • Turn off power at fuse or circuit breaker box before installation of before doing any maintenance work. • Wear rubber soled shoes and work should be done on a sturdy wooden or non-conductive ladder. • Product must be mounted in locations and at heights in a manner consistent with its intended use, and in compliance with National Electrical Code and local building codes. For indoor use only. • Product must be grounded to avoid potential electric shock and any other potential hazards. • Do not exceed the nominal supply voltage or amperage ratings. • Make sure all screws are properly tightened. • Do not install any lamp holder closer than 6” from any curtain or similar combustible material. • Use only fixtures and fittings intended for use with Con-Tech Decorative Stemlight Pendant systems. • Installing contrary to instructions may cause unsafe conditions. • Warning: Risk of fire. Most dwellings built before 1985 have supply wire rated at 60˚C. Consult a qualified electrician before installation. • Warning: Risk of burns. Lamps are extremely hot when lit. Allow lamps to cool down in temperature before handling. • To avoid hazards to children, account for all parts and properly dispose of all packing materials. • Call the Technical Support department at Con-Tech Lighting with any installation questions: 847-559-5500. Green Ballast Blue Identification Marker White Green Green Black 18-3 Cable Strain Relief Bracket Canopy 6 3.0mm Hex Head Screw Floating Glass Knurled Nut 12" Decorative Stemlight 2 All specifications subject to change without notice. 1-847-559-5500 www.con-techlighting.com This document can be recycled. DECOSTMLT INST