FIRE PROTECTION NOTES: 1. THE CONTRACT DRAWINGS ARE THE “PRELIMINARY PLANS” DEFINED IN NFPA 13, A.22.1 TO OBTAIN A BUILDING PERMIT AND ARE ALSO USED TO DEFINE THE INTENT OF THE CONTRACT TO PROVIDE THE DESIGN, COORDINATION, INSTALLATION AND TESTING OF COMPLETE FIRE PROTECTION SYSTEMS IN COMPLIANCE WITH THE REFERENCED STANDARDS AND APPLICABLE CODES. THE DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE SPECIFIED REQUIREMENTS AND REFERENCED CODES AND STANDARDS TO PROVIDE COMPLETE FULLY FUNCTIONAL AND CODE COMPLIANT SYSTEMS. 2. ALL WORK SHALL BE IN ACCORDANCE WITH SPECIFICATIONS, 2015 INTERNATIONAL BUILDING CODE - NJ EDITION, 2015 INTERNATIONAL FIRE CODE, NJ REHABILITATION SUBCODE, NFPA 13, AUTHORITY HAVING JURISDICTION AND THE OWNER'S INSURANCE REQUIREMENTS. 3. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE EVERY FITTING, COMPONENT AND SPRINKLER REQUIRED BY NFPA 13 FOR FINAL INSTALLATION CONDITIONS BUT INDICATE MINIMUM SYSTEM REQUIREMENTS FOR PRELIMINARY APPROVALS AND PERMITS FROM THE AUTHORITIES HAVING JURISDICTION. COMPLETE CONSTRUCTION COORDINATION SHALL BE PERFORMED BY THE CONTRACTOR WITH ALL OTHER TRADES MAY REQUIRE ADDITIONAL SPRINKLERS UNDER THIS CONTRACT. 4. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY CALCULATED AND DESIGNED BY CONTRACTOR, AND SHALL CONTAIN THE STAMP AND SIGNATURE OF A NEW JERSEY STATE LICENSED PROFESSIONAL ENGINEER. ALLOW FOR A MINIMUM OF 10 PSIG SIZING SAFETY FACTOR FOR FUTURE PIPING MODIFICATIONS AND TO ACCOUNT FOR FLUCTUATIONS IN MUNICIPAL WATER SYSTEM PRESSURE. 5. HYDRANT TEST DATA: CONTRACTOR SHALL PERFORM A FIRE FLOW TEST, PER APPLICABLE CODES AND REQUIREMENTS, PRIOR TO HYDRAULICALLY CALCULATING AND SIZING THE FIRE SPRINKLER SYSTEM. 6. MOST RECENT KNOWN FLOW DATA: 120 PSI STATIC PRESSURE, 65 PSI RESIDUAL PRESSURE, 1,350 GPM WATER FLOW, DATE OF TEST 11/06/2014 7. PROVIDE AUXILLIARY DRAINS AT ALL LOW POINTS FOR COMPLETELY DRAINING THE SYSTEM. 8. CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARING AS-BUILT SPRINKLER PIPING DRAWINGS OF NEW FIRE PROTECTION SYSTEM TO SHOW LOCATION AND ELEVATION OF PIPING, SPRINKLER HEADS, POINTS OF SYSTEM DRAINAGE AND INSPECTOR'S TEST. 9. PIPING TO BE INSTALLED AND COORDINATED WITH ALL OTHER TRADES' WORK. 10. DRAWINGS SHALL BE APPROVED BY OWNER'S INSURANCE AUTHORITY AND AUTHORITY HAVING JURISDICTION PRIOR TO ANY FABRICATION OR INSTALLATION TAKING PLACE. 11. PROVIDE TEMPORARY FIRE PROTECTION AND FIRE WATCH, WHEN NECESSARY AND AS REQUIRED BY CODE, DURING CONSTRUCTION. REFER TO SPECIFICATIONS FOR FIRE WATCH REQUIREMENTS. 12. CONTRACTOR TO OBTAIN ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL WALLS AND PARTITIONS AND CEILINGS. 13. LOCATION OF SPRINKLERS IN CEILING TILES: A. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS AND ROOM FINISH SCHEDULES FOR CEILING TILE TYPES. B. IN STANDARD 2 BY 2 CEILING TILES, LOCATE SPRINKLERS IN THE CENTER OF TILES. C. IN STANDARD 2 BY 4 CEILING TILES WHICH SIMULATE 2 BY 2 CEILING TILES, LOCATE SPRINKLERS IN THE CENTER OF THE 2 BY 2 AREA. 14. IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. 15. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. 16. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. SPRINKLER APPLICATION SCHEDULE LOCATION HAZARD CLASSIFICATION DESIGN DENSITY SPRINKLER K-FACTOR AREA OF SPRINKLER OPERATION DINING AREAS LIGHT HAZARD 0.1 gpm/S.F. 5.6 SERVING / COOKING AREAS ORDINARY HAZARD (GROUP 1) 0.15 gpm/S.F. 5.6 SPRINKLER TYPE RESPONSE CLASSIFICATION 1,500 S.F. CONCEALED PENDENT OR EXPOSED UPRIGHT QUICK RESPONSE, ORDINARY TEMP 1,500 S.F. CONCEALED PENDENT OR EXPOSED UPRIGHT QUICK RESPONSE, ORDINARY TEMP OR HIGH TEMP NOTE: SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 19. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. 20. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. 21. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. 22. SPRINKLER CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH THE REQUIREMENTS OF THE LOCAL FIRE MARSHAL CONCERNING FIRE SPRINKLER SYSTEM SHUTDOWN PLANS, PROCEDURES, AND FIRE WATCH PLANS THAT WILL BE IMPLEMENTED FOR SYSTEM INTERRUPTIONS DURING CONSTRUCTION. 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS DRAWN BY: DAS CHECKED BY: PP ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: FP-001 18031.00 DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 18. RCNJ No. 201437-01C ALTERATIONS OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. ENGINEER: RAMAPO COLLEGE OF NEW JERSEY 17. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com FIRE PROTECTION - CODES & GENERAL NOTES 3/23/2016 2:51:22 PM NJDCA ELECTRONIC SUBMITTAL STAMP: 3/23/2016 2:51:32 PM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION KEYED NOTES E G J N QQ.1 D1. REMOVE ALL EXISTING SPRINKLERS AND PIPING IN THIS AREA. Q.2 Q.3 D2. REMOVE ALL SPRINKLER HEADS AND DROPS IN THIS AREA. BRANCH PIPING AND MAINS TO BE REUSED. D3. HIGH CEILING AREA, REMOVE EXISTING SPRINKLERS. 22 SEALED: LEGEND B C D PIPING TO BE REMOVED 21 EXISTING PIPING TO REMAIN PENDANT SPRINKLER TO BE REMOVED 20 EXISTING PENDANT SPRINKLER TO REMAIN CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 19 UPRIGHT SPRINKLER TO BE REMOVED CABIN TE DA NA1 EA B R , KR0 0 NF D 50 AT B T E R 0 0 EXISTING UPRIGHT SPRINKLER TO REMAIN F V 18 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 17 16 15 ENGINEER: 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS F V 14 10.3 F V 10.9 10.8 F A.4 B.7 10.2 10 9 8 D3 7.1 7 6 5 4 D1 3 2.1 1.9 2 1 F 2.9 A F H I K L M O D2 ISSUED: 3.24.2016 DESCRIPTION: 1 PHASE 2 - FIRE PROTECTION DEMOLITION - FIRST FLOOR BID DOCUMENTS 1/8" = 1'-0" SHEET: FPD-100 18031.00 BIN ET, PP RCNJ No. 201437-01C ALTERATIONS CA ND BATTER A NA 01050F BREAD KR CHECKED BY: RAMAPO COLLEGE OF NEW JERSEY 11 00 DAS FIRE PROTECTION DEMOLITION FIRST FLOOR 12 DRAWN BY: 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 13 D H C F V 3/23/2016 2:51:36 PM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION KEYED NOTES D1. REMOVE ALL EXISTING SPRINKLER BRANCH PIPING IN THIS AREA. E G J N QQ.1 Q.2 Q.3 22 4" SEALED: 4" LEGEND 4" 4" PIPING TO BE REMOVED C D EXISTING PIPING TO REMAIN 4" B PENDANT SPRINKLER TO BE REMOVED CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. 21 EXISTING PENDANT SPRINKLER TO REMAIN DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 20 UPRIGHT SPRINKLER TO BE REMOVED 19 EXISTING UPRIGHT SPRINKLER TO REMAIN 0 0 PIPE CAP F V 18 PIPE BOTTOM CONNECTION 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 4" PIPE DROP 17 PIPE RISE PIPE FITTING - ELBOW 16 PIPE FITTING - TEE 15 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS PIPE FITTING - CROSS 4" F V 4" POINT OF CONNECTION / DISCONNECTION 14 10.3 F V F CHECKED BY: PP ND BATTER A NA 01050F BREAD KR 10.9 10.8 F 10.2 10 9 8 7.1 7 6 5 4 3 2.1 1.9 2 1 F 2.9 D1 F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 PHASE 2 INTERIOR - FIRE PROTECTION DEMOLITIONS - FIRST FLOOR SHEET: 0 8 16 24 1/8" = 1'-0" NORTH FPD-110 18031.00 BIN ET, RCNJ No. 201437-01C ALTERATIONS CA RAMAPO COLLEGE OF NEW JERSEY 11 00 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 3" 12 A DAS FIRE PROTECTION DEMOLITION PHASE 2 INTERIOR 3" 13 D 4" V DRAWN BY: 3/23/2016 2:51:37 PM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION E G J N QQ.1 Q.2 Q.3 SEALED: 22 LEGEND PIPING TO BE REMOVED EXISTING PIPING TO REMAIN PENDANT SPRINKLER TO BE REMOVED CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. B C EXISTING PENDANT SPRINKLER TO REMAIN D DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: UPRIGHT SPRINKLER TO BE REMOVED 21 EXISTING UPRIGHT SPRINKLER TO REMAIN 20 PIPE CAP 19 PIPE BOTTOM CONNECTION 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: CABIN PIPE DROP TE 0 NA1D A EA KR0 B R , F 50 D N AT B T E R 0 0 F V PIPE RISE 18 PIPE FITTING - ELBOW 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com PIPE FITTING - TEE REVISIONS 17 PIPE FITTING - CROSS POINT OF CONNECTION / DISCONNECTION 16 15 F V 11 00 CA BIN ET, ND BATTER A NA 01050F BREAD KR 10.9 10.8 F 10.2 10 9 8 7.1 7 6 5 4 3 2.1 1.9 2 1 F 2.9 F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 PHASE 2 ADD/ALT - FIRE PROTECTION DEMOLITION - FIRST FLOOR 0 8 16 24 SHEET: 1/8" = 1'-0" NORTH FPD-111 18031.00 12 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 13 RCNJ No. 201437-01C ALTERATIONS V 3" A PP RAMAPO COLLEGE OF NEW JERSEY 3" D 3" H C 3" CHECKED BY: FIRE PROTECTION DEMOLTION SERVERY ALTERNATE #1 F 3" DAS 14 10.3 F V 3" DRAWN BY: 3/23/2016 2:51:28 PM NJDCA ELECTRONIC SUBMITTAL STAMP: ADDITION/ALTERATION KEYED NOTES 1. PROVIDE SPRINKLERS IN HIGH CEILING AREA. REUSE EXISTING BRANCH PIPING. 2. 1 1/4" PIPE UP TO TOP OF TOWER. KEEP TIGHT TO WALL. E G J N QQ.1 Q.2 Q.3 3. CONCEALED PENDANT SPRINKLER IN OVERHANG. ROUTE PIPING ABOVE OVERHANG. 4. UPRIGHT SPRINKLER CENTERED BELOW ROOF PEAK. PIPING TO FOLLOW ROOF SLOPE UP. 22 4" 4" SEALED: 4" 4" C D 4" B 21 CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. LEGEND 20 DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 19 NEW PIPING EXISTING PIPING 0 0 F V NEW PENDANT SPRINKLER 18 I NEW INTERMEDIATE TEMPERATURE PENDANT SPRINKLER 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 4" EXISTING PENDANT SPRINKLER 17 NEW UPRIGHT SPRINKLER 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 2" 16 15 1 1/2" EXISTING UPRIGHT SPRINKLER REVISIONS PIPE CAP 4" F 4" 1 1/2" V PIPE BOTTOM CONNECTION F V 4" PIPE DROP 13 PIPE RISE POINT OF CONNECTION / DISCONNECTION 3" 3" F 10.2 10 3" 9 3" 8 1 1/2" 1 1/4" 1 7.1 3" 7 1 1/2" 2" 2 1/2" 2 1/2" 4 3" 2" 2 1/2" 1 1/2" 1 1/4" 1 1/4" 2" 1 1/4" 2" 1 1/4" 2" 6 5 3" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 1 1/4" 3" 2 F 3 3" 2.9 3 2.1 1.9 2 1 3 4 A F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 PHASE 2 INTERIOR - FIRE PROTECTION ALTERATIONS - FIRST FLOOR 0 8 16 SHEET: 24 1/8" = 1'-0" NORTH FP-110 18031.00 3" 10.9 10.8 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 PIPE FITTING - CROSS RCNJ No. 201437-01C ALTERATIONS 11 ND BATTER NA 01050F KR A BREAD 1 1/4" 2 1/2" PP RAMAPO COLLEGE OF NEW JERSEY BIN ET, 1 1/4" 2" CHECKED BY: FIRE PROTECTION ALTERATIONS - FIRST FLOOR 3" 12 CA 2" DAS PIPE FITTING - TEE 00 2" DRAWN BY: PIPE FITTING - ELBOW 3" 1 1/4" 3" D F V 14 10.3 3/23/2016 2:51:31 PM NJDCA ELECTRONIC SUBMITTAL STAMP: ADDITION/ALTERATION E G J N QQ.1 Q.2 Q.3 SEALED: 22 CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. LEGEND DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: B C D NEW PIPING 21 EXISTING PIPING NEW PENDANT SPRINKLER 20 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com I 19 NEW INTERMEDIATE TEMPERATURE PENDANT SPRINKLER ENGINEER: EXISTING PENDANT SPRINKLER I I CABIN TE , NA D 1A EA KR0 B R 0 50D N F AT B T E R 1 1/2" 0 0 F 1 1/4" 1 1/2" NEW UPRIGHT SPRINKLER V 18 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com EXISTING UPRIGHT SPRINKLER I 1 1/2" PIPE CAP 17 2" I REVISIONS PIPE BOTTOM CONNECTION I I PIPE DROP 16 15 2" 1 1/2" PIPE RISE DRAWN BY: DAS CHECKED BY: PP PIPE FITTING - ELBOW F V 13 POINT OF CONNECTION / DISCONNECTION 12 11 00 CA ND BATTER A NA 01050F BREAD KR BIN ET, 10.9 10.8 F 10.2 10 9 8 7.1 7 6 5 4 3 2.1 1.9 2 1 F 2.9 A F H I K L M ISSUED: 3.24.2016 O DESCRIPTION: BID DOCUMENTS 1 PHASE 2 ADD/ALT - FIRE PROTECTION ALTERATIONS - FIRST FLOOR SHEET: 0 8 16 24 1/8" = 1'-0" NORTH FP-111 18031.00 V D 3" H C 3" 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 F 3" PIPE FITTING - CROSS RCNJ No. 201437-01C ALTERATIONS V RAMAPO COLLEGE OF NEW JERSEY 2" 2" 14 10.3 F FIRE PROTECTION ALTERATIONS - SERVERY ALTERNATE #1 PIPE FITTING - TEE