BEAM FIRE DETECTOR USE AND UCL BUILDING LOCATIONS Fire Safety Technical Guide

advertisement
UCL Fire Technical Note No: 115
Fire Safety
Technical Guide
BEAM FIRE DETECTOR USE AND
UCL BUILDING LOCATIONS
USE OF BEAM DETECTORS
Beam Smoke Detection - Beam Detection is used where
situations that the installation, testing, and maintenance of point
type detectors is difficult. For example, in spaces with high
ceilings, once construction has been completed and the space is
occupied, it is often difficult to reach the ceiling without the use of
heavy, cumbersome lifts operations or where that there are large
open expanses etc.
UCL use the optical reflective beam smoke detector unit and
reflective mirror type as per the picture.
The Optical Reflective Beam Smoke Detectors
Beam Smoke Detector works on the principle of light obscuration. The photosensitive element of
the Optical Beam Smoke Detector sees light produced by the Transmitter (TR) in a normal
condition and uses a reflective mirror to return the light beam back to the transmitter. Any
obscuration of the beam detector including smoke, objects (poles, helium filled balloons poles
brushes or persons will imitate a fire signal and place the premises into full fire evacuation.
Transmitter
Mirror Reflector
Any object other than smoke will set the beam detector off passing through the
beam.
Procedure For Working by Beam Detectors
Design Consultants, Consultants, UCL Project Managers and Contractors please note that a ‘Permit
to Work’ on fire alarm systems is required to prevent the unwanted automatic calling of the fire brigade
when working at height or in the vicinity of beam detectors - your will require a Permit (requiring 72 Hours
Notice) to be issued and instruction to isolate the beam detectors during the day time only by an approved
Project Manager. Consultation with Fisk Fire Group & UCL Maintenance Engineers before commencing
general or construction work will be necessary
UCL Site Manager - Mark Fisk (Mob: 07977 - 064648) / Email: markfisk@fiskfire.co.uk
UCL Site Foreman - Jim Moughton (07974 - 427843) / Email: jimmoughton@fiskfire.co.uk
Location of Beam Detectors Scheduled at table below:
_________________________________________________________________________________________________________
Date Last Amended: Dec 11
1.
Issued by the - Fire Officer, UCL, Estates & Facilities, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of
requirements and is in addition to relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities.
UCL Fire Technical Note No: 115
___________________________________________________________________________________________________________________________________
LOCATION OF BEAM DETECTORS:
Bldg
No:
Bldg Name:
Fire
Alarm
Zone
Covering
Beam
Detectors
005
Wilkins Building
Zone 27
Basement (South) - South
Junction outside Records Office
(B06/7/8) & Gents WC
Qty x 3
005
Wilkins Building
Zone 28
Ground Fl (South) - in
Provost's Office South Cloisters
Qty x 1
Double Knock
005
Wilkins Building
Zone 29
Ground Fl (South) - South
Cloisters & above Jeremy
Bentham Auto Icon Cupboard
Qty x 3
Double Knock
005
Wilkins Building
Zone 31
Ground Fl (South) - Strang
Print Room (G07) off South
Cloister
Qty x 2
005
Wilkins Building
Zone 32
Ground Fl (Central) - Old
Refectory (Room G12 - Off
Octagon)
Qty x 2
005
Wilkins Building
Zone 33
Ground Fl (North) - North
Cloisters & outside Houseman
Room [
Qty x 3
005
Wilkins Building
Zone 35
Ground Fl (North) - Houseman
Senior Common Room (Room
G20)
Qty x 2
005
Wilkins Building
Zone 36
Ground Fl (North) - Haldane
Meeting Room (Room G18)
Qty x 2
005
Wilkins Building
Zone 37
First Floor (Central) - Flaxman
Gallery
Qty x 1
005
Wilkins Building
Zone 38
First Floor (Central) Donaldson Library (Room 114)
Qty x 3
005
Wilkins Building
Zone 39
Third Floor (South) - Upper
Level of Gustave Tuck Lecture
Theatre
Qty x 2
006
Physics Building
Zone 2.
Staircase - North Junction
(Stair A) on 4th Fl lift
landing at high level
Qty x 1
088
Gordon House
Not
unknown
Location
Number
of Beam
Units
Lecture Theatre First Floor
(Room 106)
Remarks
Double Knock
High Level at the
base of the Dome
Qty x 1
_________________________________________________________________________________________________________
Date Last Amended: Dec 11
2.
Issued by the - Fire Officer, UCL, Estates & Facilities, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of
requirements and is in addition to relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities.
UCL Fire Technical Note No: 115
___________________________________________________________________________________________________________________________________
LOCATION OF BEAM DETECTORS (Cont):
Bldg
No:
Bldg Name:
Fire
Alarm
Zone
Covering
Beam
Detectors
200
Paul O’ Gorman
Building
Zone 103
Fifth Floor Write Up Area
(onto Huntley Street)
Qty x 1
Unit
Units Above the
doors opening on to
the write up rooms
200
Paul O’ Gorman
Building
Zone 96
Fourth Floor Write Up Area
(onto Huntley Street)
Qty x 1
Unit
Above the doors
opening on to the
write up rooms
200
Paul O’ Gorman
Building
Zone 88
Third Floor Write Up Area
(onto Huntley Street)
Qty x 1
Unit
Above the doors
opening on to the
write up rooms
200
Paul O’ Gorman
Building
Zone 80
Fifth Floor Write Up Area
(onto Huntley Street)
Qty x 1
Unit
Above the doors
opening on to the
write up rooms
200
Paul O’ Gorman
Building
Zone 72
Fifth Floor Write Up Area
(onto Huntley Street)
Qty x 1
Unit
Above the doors
opening on to the
write up rooms
200
Paul O’ Gorman
Building
Zone 65
Fifth Floor Write Up Area
(onto Huntley Street)
Qty x 1
Unit
Above the doors
opening on to the
write up rooms
200
Paul O’ Gorman
Building
Zone 60
Fifth Floor Write Up Area
(onto Huntley Street)
Qty x 1
Unit
Above the doors
opening on to the
write up rooms
200
Paul O’ Gorman
Building
Zone 109
Ground Floor Café Atrium
Space
Qty x 2
Unit
Fitted to Med School
Bldg Walls across
atrium
Location
Number
of Beam
Units
Remarks
_________________________________________________________________________________________________________
Date Last Amended: Dec 11
3.
Issued by the - Fire Officer, UCL, Estates & Facilities, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of
requirements and is in addition to relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities.
UCL Fire Technical Note No: 115
___________________________________________________________________________________________________________________________________
_________________________________________________________________________________________________________
Date Last Amended: Dec 11
4.
Issued by the - Fire Officer, UCL, Estates & Facilities, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of
requirements and is in addition to relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities.
Download