DESIGNER'S NOTES FOR DETAILS AND SCHEDULES

advertisement
DESIGNER'S NOTES FOR DETAILS AND SCHEDULES
1.
REFER TO DESIGNER'S NOTES ON THE DETAILS.
REMOVE DESIGNER'S NOTES PRIOR TO
ISSUING DETAILS.
2.
3.
GROUP COMMON DETAILS, SUCH AS PIPING, AS MUCH AS POSSIBLE.
MANUAL AIR VENTS ARE REQUIRED ON CHILLED AND HEATING HOT WATER SYSTEMS AND
AT LOCAL HIGH POINTS.
LOCAL HIGH POINT IS A SECTION OF PIPE AT A HIGHER
ELEVATION THAN THE SECTION OF PIPE IMMEDIATELY DOWNSTREAM AND IMMEDIATELY
UPSTREAM.
4.
FOR EQUIPMENT SCHEDULES:
A.
PROVIDE SCHEDULES FOR EXISTING FANS OR OTHER EQUIPMENT THAT MUST BE
MODIFIED OR REBALANCED.
SHOW EXISTING AND FUTURE CAPACITIES AND MOTOR
SIZES.
B.
DO NOT USE TRADE NAMES OR A MANUFACTURER'S NAME OR MODEL ON THE
CONSTRUCTION DOCUMENTS.
C.
DO NOT USE DITTO MARKS FOR REPETITIVE ENTRIES.
A VERTICAL LINE MAY BE
USED TO SHOW REPETITION.
E.
USE A SHORT DASH IN SCHEDULES WHERE THE COLUMN HEADING IS NOT
APPLICABLE TO INDICATE THAT THE LACK OF AN ENTRY WAS NOT AN OMISSION.
F
GROUP SCHEDULES AS MUCH AS POSSIBLE.
SEE HVAC DESIGN MANUAL FOR
SEQUENCE OF SCHEDULES.
6.
SCHEDULE THE COIL CAPACITY DATA WITH AND WITHOUT THE BENEFIT OF THE HEAT
RECOVERY SYSTEM.
7.
ALL DUCTWORK, WITHOUT EXCEPTION, AND ALL PIPING 6" [150mm] AND LARGER SHALL
BE SHOWN IN DOUBLE LINE.
ABBREVIATION AND SYMBOL NOTES
1.
THE COMPOSITE LIST OF ABBREVIATIONS IS COORDINATED WITH THE UNITED STATES
NATIONAL CAD STANDARD VERSION 4.0, LEGACY VA LIST OF ABBREVIATIONS, AND ASHRAE.
THIS LIST SHALL BE USED FOR ALL VA PROJECTS AND EDITED, AS REQUIRED, TO BE
PROJECT SPECIFIC. THE DESIGNER MAY SELECT AND USE ADDITIONAL ABBREVIATIONS, IF
REQUIRED, FROM ANY KNOWN SOURCES.
2.
THE LIST OF SYMBOLS IS MOSTLY BASED ON THE VA MASTER LIST OF STANDARD
SYMBOLS AND HAS BEEN UPDATED IN CONSULTATION WITH OTHER SOURCES, SUCH AS,
NATIONAL CAD STANDARD VERSION 4, AND ISA (THE INSTRUMENTATION, SYSTEMS, AND
AUTOMATION SOCIETY). THIS LIST SHALL BE USED FOR ALL VA PROJECTS AND EDITED,
AS REQUIRED, TO BE PROJECT SPECIFIC.
THE DESIGNER CAN SELECT AND USE
ADDITIONAL SYMBOLS, IF REQUIRED, FROM ANY KNOWN SOURCE
DETAIL TITLE / DESIGNER
NOTES FOR DETAILS AND SCHEDULES
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-01.DWG
GENERAL NOTES
1.
ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A
FURRED CHASE OR ABOVE THE HARD SUSPENDED CEILING.
2.
THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR INDICATED.
DUCT SIZES ARE NET INSIDE DIMENSIONS.
3.
ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL VALVES, TRAPS,
DAMPERS, CLEANOUTS, CONTROLS, ETC.
ACCESS PANELS SHALL BE FURNISHED AND
INSTALLED UNDER THE ARCHITECTURAL SPECIFICATIONS.
4.
TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM, TERMINAL
UNITS, FILTERS, COILS, ETC.
5.
FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE STANDARD
EQUIPMENT DETAILS.
6.
7.
DIFFUSER, REGISTER AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK SIZES.
WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE MADE TO
PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
8.
WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE INSTALLED
WITH BOTTOM ELEVATION OF REGISTER AT 7" [175mm] ABOVE FINISHED FLOOR.
9.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF CEILING
DIFFUSERS, REGISTERS, AND GRILLES.
10. STEAM HEADER SET PRESSURE:
___ PSIG [kPa] NORMAL
___ PSIG [kPa] LOW DEMAND PERIODS
11. ALTITUDE-BOILER ROOM FLOOR:
___
12.
FT. [M] ABOVE SEA LEVEL
SEISMIC PROVISIONS // REQUIRED - SEE SPECS // NOT REQUIRED //
ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS OTHERWISE NOTED
DETAIL TITLE / GENERAL
NOTES
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-02.DWG
DRAWING SYMBOLS
2
H4
A
H7
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
SECTION LETTER
DRAWING NUMBER WHERE SHOWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
EQUIPMENT ABBREVIATION (SUPPLY FAN)
26-SF 3
SUPPLY FAN NO. 3 IN BUILDING NO. 26
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED
ITEM (TERMINAL UNIT SHOWN)
26-TU-I-I
ITEM NUMBER (TERMINAL UNIT NO. 1)
SERVED BY AIR HANDLER UNIT NO. 1
DETAIL TITLE / DRAWING
SYMBOLS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-08.DWG
DUCTWORK SYMBOLS
UP
DN
SUPPLY DUCT (UP & DOWN)
UP
DN
EXHAUST DUCT (UP & DOWN)
UP
DN
RETURN DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
SQUARE 1-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING REGISTER OR GRILLE
EXHAUST OR RETURN BOTTOM REGISTER OR GRILLE
(WALL TYPE)
EXHAUST OR RETURN REGISTER OR TOP GRILLE
(WALL TYPE)
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
CONNECT NEW DUCT TO EXISTING DUCT
R
INCLINED RISE, IN DIRECTION OF AIR FLOW
D
INCLINED DROP, IN DIRECTION OF AIR FLOW
LIMIT OF DEMOLITION
DETAIL TITLE / DUCTWORK
SYMBOLS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-09.DWG
DUCTWORK SYMBOLS
FLEXIBLE CONNECTION, EQUIPMENT,
VIBRATION, OR SEISMIC
FC
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
10x8
NEW DUCT (INSIDE DIMENSIONS:
WIDTH x DEPTH)
EXISTING DUCT TO REMAIN
EXISTING DUCT TO BE REMOVED
LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL
SECTION.)
FLEXIBLE DUCTWORK (INSULATED)
DUCT WITH SOUND LINING
MANUAL VOLUME DAMPER
VD
FD
FIRE DAMPER
BACK DRAFT DAMPER
BDD
DETAIL TITLE / DUCTWORK
SYMBOLS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-10.DWG
DUCTWORK SYMBOLS
F/S DPR
COMBINATION FIRE/SMOKE DAMPER
N
2 1
POINT OF CHANGE IN DUCT CONSTRUCTION BY
STATIC PRESSURE CLASS. THE NUMBER ASSIGNS
PRESSURE CLASS (IN. OF WATER) WHICH WILL
ACCOMMODATE MAXIMUM OPERATING PRESSURE
4
1/2
IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES
THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
AUTOMATIC CONTROL DAMPER MODULATING
AUTOMATIC CONTROL DAMPER TWO POSITION
STAINLESS STEEL DUCT
MANUAL SPLITTER DAMPER
45°
45°
SUPPLY
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
RETURN
DUCT MOUNTED COIL (HOT WATER OR STEAM COIL)
DUCT MOUNTED COIL
(ELECTRIC)
DETAIL TITLE / DUCTWORK
SYMBOLS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-11.DWG
TERMINAL UNIT SYMBOLS
CONVECTOR OR RADIATOR (RECESSED)
CONVECTOR OR RADIATOR (WALL HUNG)
A
FCU
FLOOR MOUNTED VERTICAL RECESSED FAN COIL UNIT.
LETTER INDICATES UNIT SIZE.
A
FCU
FLOOR MOUNTED VERTICAL CABINET FAN COIL UNIT.
LETTER INDICATES UNIT SIZE.
A
TWU
THRU WALL AIR CONDITIONING UNIT.
LETTER INDICATES UNIT SIZE.
A
PTAC
WINDOW TYPE AIR CONDITIONING
UNIT.
A
LETTER INDICATES UNIT SIZE.
PTAC
FLOOR MOUNTED HEAT PUMP. LETTER
INDICATES UNIT SIZE.
AIR CURTAIN
UNIT HEATER (HORIZONTAL)
UNIT HEATER (VERTICAL)
2'x2' RADIANT CEILING PANEL
2'x4' RADIANT CEILING PANEL
DETAIL TITLE / TERMINAL
UNIT SYMBOLS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-12.DWG
AIR TERMINAL SYMBOLS
TERMINAL UNIT WITH REHEAT COIL
DOUBLE DUCT MIXING BOX.
MB
FAN POWERED VARIABLE VOLUME
TERMINAL UNIT WITH HEATING COIL.
DETAIL TITLE / AIR
TERMINAL SYMBOLS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-13.DWG
CADD DETAIL NO. :SD230511-21.DWG
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
WELD
INSULATION SHIELD
AT HANGER
SADDLE
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
HANGER RODS WITH
(8" [200mm] MIN.)
36" [900mm] MAX.
SPACING ON EACH
DETAIL TITLE / PIPE
CHANNEL
BAND
1" MAX.
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
1-5/8" [43mm] 12 GAUGE
CHANNEL OR 2"x2"x1/4"
[50x50x6.4mm] ANGLE
[25mm]
NOTES:
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. [453KG] UNIFORM LOAD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOM. SIZE
IN.
[mm]
PIPE
TUBING
THRU 3/4
THRU [20]
FT.
7
[mm]
[2100]
FT.
5 FT
[mm]
[1500]
1
[25]
7
2
1 1/4 1 1/2
[32] [40] [50]
7
9
10
2 1/2 3
[65] [75]
11
12
4
5
6
8
10
12
14
16
18
20
24
[100] [125] [150] [200] [250] [300] [350] [400] [450] [500] [600]
14
16
17
19
22
23
25
27
28
30
32
[2100] [2100] [2700] [3000] [3400] [3700] [4100] [4900] [5200] [5800] [6700] [7000] [7600] [8200] [8500] [9100] [9600]
7
6
8
8
9
10
12
13
14
16
[1800] [2100] [2400] [2400] [2700] [3000] [3700] [4000] [4100] [4900]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
#
PIPE HANGERS
NTS
DESIGNER'S NOTE:
SHOW ON THE DRAWINGS OTHER SPECIFIED AND SPECIAL PIPE SUPPORTS WHERE
REQUIRED.
SCALE : NONE
& INSERT FOR ALL PIPING
HANGERS
1/2" [15mm] DIA.
PROVIDE INSULATION SHIELD
DATE ISSUED :DECEMBER 2008
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
PROVIDE ALUMINUM
PIPE AND
JACKET
INSULATION
INSULATION
HIGH COMPRESSIVE
PROTECTION
STRENGTH INSULATION
SHIELD
INSERT UNDER SHIELD
2" [50mm]
STEEL PIPE
WELD PIPE SADDLE
2-1/2" [65mm]
SUPPORT TO PIPE.
STEEL PIPE
PROVIDE WATER
TIGHT CONNECTION
SEALANT
FLEXIBLE PIPE
COUNTER FLASHING
ROOF SYSTEM
INSULATION AND
MEMBRANE
ROOF SURFACE
CONCRETE ROOF SLAB
[300mm]
[100mm]
[200mm]
PRE-MOULDED
12" MIN.
4"
8"
CLAMPING RING
8"x8"x3/8"
[203x203x8.0mm]
OR STEEL ROOF DECK
SECURE TO ROOF SLAB
STEEL PLATE
WITH (4) 3/8" [8.0mm]∅
WELD PLATE
EXPANSION BOLTS OR
TO PIPE
WELD TO STEEL DECK
NOTES:
PROVIDE RESTRAINING CLAMPS 8'-0" [2438] O.C.
#
DETAIL FOR SUPPORTING PIPE ON ROOF
NTS
DETAIL TITLE / DETAIL
FOR SUPPORTING PIPE ON ROOF
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-22.DWG
PIPE ANCHOR
SCHEDULE
D
P
MM
IN
IN
C
MM
IN
MM
4"
102
5
8
16
3
4
3"
76
1
2
13
"
"
N
IN
S
MM
IN
BOLT PATTERN
MM
19
4"
102
3
4
1
2
13
4"
102
5
8
16
"
"
"
19
"
22"
64
3
8
10
3
8
10
4"
102
5
8
16
2"
51
3
8
10
3
8
10
4"
102
5
8
16
3
8
10
1
4
6
4"
102
1
2
1
1
12"
38
"
"
"
"
"
"
"
"
"
13
INSULATE AS INDICATED FOR ALL
D+1"
CHILLED WATER. INSULATE PIPE
D+[25]
ONLY FOR STEAM & CONDENSATE
STL PIPE OR
COPPER TUBE
D=PIPE O.D.
D+
ANCHOR BOLTS
N=NUMBER
S=SIZE
5/16"
[8]
DRILL Ø = S+1/16"
DRILL Ø = S+[2]
NOTE a
C
P
D+1 1/2"
D+[38]
D+2 1/2"
D+[64]
D+4 3/4"
D+[121]
D+3 3/4"
D+[95]
NOTE:
a.WHERE USED FOR COPPER TUBE OR PIPE,
BRAZE TO FABRICATED STEEL ANCHOR
#
1
SMALL PIPE ANCHOR 12"- 4"
NTS
DETAIL TITLE / SMALL PIPE ANCHOR 1-1/2"-4"
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-23.DWG
PIPE ANCHOR SCHEDULE
D
IN
P
L
IN
MM
MM
1
MM
IN
19
3
8
"
19
6" 152
82" 216
3
4
8"
203
10" 254
3
4
10" 254
12" 305
3
4
"
12" 305
14" 356
3
4
14" 356
16" 406
16" 406
18" 457
N
E
T
IN
MM
IN
IN
MM
IN
10
1
4
6
4"
102
7
8
1
2
13
1
4
6
4"
102
7
8
19
1
2
13
1
4
6
4"
102
7
8
"
19
1
2
13
1
4
6
4"
102
7
8
3
4
"
19
1
2
13
1
2
13
4"
102
7
8
18" 457
3
4
"
19
1
2
"
13
1
2
13
4"
102
7
8
20" 508
1"
25
5
8
"
16
1
2
13
6"
152
"
"
"
"
"
"
"
"
"
"
"
"
"
BOLT PATTERN
S
MM
MM
"
22
"
22
"
22
"
22
"
22
"
22
1"
25
INSULATE AS INDICATED FOR ALL
CHILLED WATER. INSULATE PIPE
ONLY FOR STEAM & CONDENSATE
D=PIPE O.D.
L+3"[76]
L
T
E
T
P
D+4"[101]
L+4" [101]
D+8"[230]
L+8" [203]
NOTE a
ANCHOR BOLTS
NOTES:
a.INSTALL WALL PLATE FIRST THEN
WELD ON REMAINING ASSEMBLY.
N=NUMBER
S=SIZE
DRILL Ø S+1/8"[3.175]
ONE WALL PLATE FOR BOTH
CHILLED WATER S.&R. IS OPTIONAL.
#
LARGE PIPE ANCHOR 6" -18"
NTS
DETAIL TITLE / LARGE
PIPE ANCHOR 6"-18"
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-24.DWG
PIPE SLEEVE
PIPE
WHERE SPECIFIED
NOTES:
1.
RISER
PROVIDE ANCHORS ONLY
WHERE
CLAMP
SHOWN
ON
DRAWINGS.
BOLT
2.
EXTEND SLEEVE ABOVE
FLOOR WHERE SPECIFIED.
FIRE-STOPPING
MATERIAL
PLAN
RISER
INSULATION
BOLT
(TYPICAL)
RISER
FLOOR
CLAMP
SLAB
PIPE SLEEVE
WHERE
SPECIFIED
RISER CLAMP.
BOTTOM CLAMP
REQUIRED AT
ANCHOR POINTS
ELEVATION
#
ONLY.
SUPPORT/ANCHOR FOR PIPE RISERS
NTS
DESIGNER'S NOTE:
SHOW REQUIRED ANCHORS ON PLAN, SECTIONS OR DIAGRAMS.
DETAIL TITLE / SUPPORT/ANCHOR FOR PIPE RISERS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-25.DWG
1/4"x1 1/4"
[6.4x31.4mm]
WATER STOP
IRON PIPE STRAP
EXTERIOR WALL
FLANGED
PIPE SLEEVE
CONNECTION
HIGH DENSITY
POLYETHYLENE (HDPE)
1/4"x1 1/4"
[6.4x31.4mm]
SLEEVE WITH INTEGRAL
HOLLOW MOLDED WATER
IRON PIPE
STOP RING 4" [100mm]
CLAMP
LARGER THAN OUTSIDE
#
[100mm]
4"
DIAMETER OF PIPE
5/8" [16mm]∅
ROD
SUPPORT ANCHOR (CONDENSER WATER
OR CHILLED WATER)
NTS
DETAIL TITLE / SUPPORT ANCHOR (CONDENSER WATER
OR CHILLED WATER)
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-26.DWG
DETAIL TITLE / PIPE
TRENCH IN BUILDING
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230511-27.DWG
VARIES
#
WITH ARCHITECTURAL &
SEALING & CAULKING.
REFER TO SPECIFICATION,
STRUCTURAL.
COORDINATE TRENCH DETAIL WITH ARCHITECTURAL & STRUCTURAL.
DESIGNER'S NOTE:
NTS
2.
GREATER THAN 24"[600mm]
COORDINATE TRENCH DETAIL
NOTES:
1.
CENTER BOLT FOR SPAN
4"[100mm] 5.4#
AND SEAL
CAULK
2 - SUPPORTS UP TO 24" [600mm] SPAN
SLOPE
7/8"[22mm]∅
SADDLE
TYPE 39
HOT PIPE
TYPICAL
PIPE TRENCH IN BUILDING
PIPE
BANDED TO
TYPE 40 SHIELD
TYPICAL COLD PIPE
HIGH DENSITY INSERT
REMOVABLE COVER
VARIES
3/4"
[19mm]
CONDENSATE
STEAM LINE
RETURN LINE
PROVIDE ONE "U" BOLT
WITH NUT & LOCK NUT
ON RETURN LINE. SPOT
WELD "U" BOLT TO PIPE
PROVIDE TWO "U" BOLTS
& BOLT TO CHANNEL
WITH NUT & LOCK NUT
ON STEAM LINE. SPOT
CHANNEL TO BE SET IN
WELD "U" BOLT TO PIPE
SIDE WALL OF TRENCH.
& BOLT TO CHANNEL.
CONCRETE TRENCH
SIZE OF STEAM LINE
GOVERNS SIZE OF
CHANNEL.
PLAN VIEW
SCHEDULE
SIZE OF PIPE
SIZE OF "U" BOLT
SIZE OF CHANNEL
INCH [mm]
INCH [mm]
INCH [mm]
1 - 2 [25 - 50]
3/8 [10] DIA.
6 x 10.5 [150x265]
2-1/2 - 5 [65 - 125]
1/2 [15] DIA.
8 x 13.75 [200x345]
6 - 8 [150 - 200]
3/4 [20] DIA.
10 x 20 [250x500]
SCHEDULE FOR 8 FT. [2.4m] SPAN OR LESS.
ANCHOR INSTALLATION
#
STEAM/CONDENSATE PIPING IN TRENCH
NTS
DETAIL TITLE / ANCHOR INSTALLATION STEAM/CONDENSATE PIPING IN TRENCH
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230511-28.DWG
b
b
a
FLEXIBLE
MECHANICAL
COUPLING
HANGER (TYPICAL)
(TYPICAL)
c
ANCHOR (TYPICAL)
SEISMIC
d
d
JOINT
DETAIL "A"
(STEEL PIPE FOR WATER/GLYCOL)
NOTE:
1.
SEISMIC SEPARATION ASSEMBLY DETAIL SHOWN IN NFPA 13 (SPRINKLER PIPING),
UTILIZING FLEXIBLE MECHANICAL COUPLINGS, MAY BE USED IN LIEU OF PIPING DETAIL
SHOW ABOVE.
SCHEDULE FOR PIPING CROSSING
A SEISMIC JOINT
DIMENSIONS INCHES [mm]
LOCATION
PIPE
DETAIL
a
b
c
d
e
f
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PIPING CROSSING A SEISMIC
#
JOINT DETAIL "A"
NTS
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION.
THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
DETAIL TITLE / PIPING
CROSSING A SEISMIC JOINT
DETAIL "A"
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230511-29.DWG
b
b
a
c
RISE UP
12" [300mm]
MINIMUM
e
d
HANGER (CLOSE
TO ELBOW)
ANCHOR
ANCHOR
SEISMIC
JOINT
f
f
DETAIL "B"
(PLASTIC PIPE FOR PRESSURIZED SYSTEMS)
SCHEDULE FOR PIPING CROSSING
A SEISMIC JOINT
DIMENSIONS INCHES [mm]
LOCATION
PIPE
DETAIL
b
a
c
d
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PIPING CROSSING A SEISMIC JOINT
#
DETAIL "B"
NTS
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION.
THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
DETAIL TITLE / PIPING
CROSSING A SEISMIC JOINT
DETAIL "B"
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230511-30.DWG
b
b
a
A
6" [150mm]
A
HANGER
d
FLEXIBLE: BRONZE HOSE
HANGER
& BRAID WITH SOLDIERED OR
BRAZED ENDS
c
ANCHOR
ANCHOR
SEISMIC
JOINT
e
e
DETAIL "C"
(COPPER PIPE)
6" [150mm]
COPPER PIPE
4" [100mm]
MINIMUM RISE
FLEXIBLE HOSE
SECTION "A-A"
SCHEDULE FOR PIPING CROSSING
A SEISMIC JOINT
LOCATION
#
PIPE
DIMENSIONS INCHES [mm]
DETAIL
a
b
c
d
e
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PIPING CROSSING A SEISMIC JOINT DETAIL "C"
NTS
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION.
THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
DETAIL TITLE / PIPING
CROSSING A SEISMIC JOINT
DETAIL "C"
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230511-31.DWG
b
b
a
HANGER
c
FLEXIBLE BALL
HANGER
JOINT
HANGER
SEISMIC
JOINT
d
ANCHOR
d
ANCHOR
DETAIL "D"
(STEEL PIPE FOR STEAM OR WATER)
SCHEDULE FOR PIPING CROSSING
A SEISMIC JOINT
LOCATION
PIPE
DIMENSIONS INCHES [mm]
DETAIL
a
b
c
d
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PIPING CROSSING A SEISMIC
#
JOINT DETAIL "D"
NTS
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION.
THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
DETAIL TITLE / PIPING
CROSSING A SEISMIC JOINT
DETAIL "D"
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230511-32.DWG
a
HANGER
d
FLEXIBLE
CONNECTOR
b
c
HANGER
HANGER
SEISMIC
JOINT
e
e
ANCHOR
ANCHOR
DETAIL "E"
(STEEL PIPE FOR WATER)
SCHEDULE FOR PIPING CROSSING
A SEISMIC JOINT
LOCATION
PIPE
DIMENSIONS INCHES [mm]
DETAIL
a
b
c
d
e
f
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
PIPING CROSSING A SEISMIC
#
JOINT DETAIL "E"
NTS
DESIGNER'S NOTE:
1. THIS CONFIGURATION SHOWN IN THIS DETAIL IS A SUGGESTED ARRANGEMENT, NOT
MANDATED FOR USE IN AS IS CONDITION.
THE REGISTERED PROFESSIONAL STRUCTURAL
ENGINEER IN CHARGE OF THE PROJECT SHALL PROVIDE SEISMIC CALCULATIONS AND
MODIFY THE CONFIGURATION AS NEEDED TO MAKE THE ARRANGEMENT PROJECT-SPECIFIC.
THE MECHANICAL DESIGNER SHALL COMPLETE THE BLANK SCHEDULES BY INSERTING THE
DISTANCES, TO BE CALCULATED AND FURNISHED BY PROVIDED BY THE REGISTERED
PROFESSIONAL STRUCTURAL ENGINEER.
DETAIL TITLE / PIPING
CROSSING A SEISMIC JOINT
DETAIL "E"
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230511-33.DWG
+Fy
+My
STEAM NOZZLE
+Mz
+Mx
+Fx
+Fz
LONG AXIS OF BOILER
FRONT OF BOILER
ISOMETRIC VIEW
TABLE OF FORCES AND MOMENTS DUE TO THERMAL EXPANSION AND
WEIGHT OF STEAM LEAD AND VALVES
Fx
BOILER NO.
------
Fy
Fz
Mx
My
Mz
LB [Kg] LB [Kg] LB [Kg] FT LB [J] FT LB [J] FT LB [J]
--[--]
--[--]
--[--]--[--]--[--] --[--]
TABLE OF FORCES AND MOMENTS DUE TO SEISMIC ACTION OF THE
STEAM LEAD AND VALVES
Fx
BOILER
NO.
------
Fy
Fz
Mx
My
Mz
LB [Kg] LB [Kg] LB [Kg] FT LB [J] FT LB [J] FT LB [J]
--[--]--[--]--[--] --[--]
--[--]
--[--]
NOTES:
1.
BOILERS SHALL BE DESIGNED TO WITHSTAND THE
FORCES AND MOMENTS SHOWN ABOVE.
2.
ADD ANY Fy FORCE (500 LB [230 Kg] MINIMUM) AS
AN ESTIMATION OF THE WEIGHT EFFECT OF THE
STEAM LEAD AND VALVE ON THE BOILER. BOILER AND
PIPE HANGER SUPPLIERS SHALL COORDINATE TO
DETERMINE THE EXACT Fy FORCE WHICH WILL BE
IMPOSED ON THE STEAM NOZZLES.
3.
DELETE THE SEISMIC TABLE ON NON-SEISMIC AREAS.
FORCES AND MOMENTS ON
#
BOILER STEAM NOZZLES
NTS
DETAIL TITLE / FORCES
AND MOMENTS ON
BOILER STEAM NOZZLES
SCALE : NONE
DATE ISSUED :FEBRUARY 2008
CADD DETAIL NO. :
SD230511-34.DWG
TYPICAL STRUCTURAL
STEEL MEMBER FOR
EQUIPMENT
MO
T
SH OR
AF
T
N
VE
I
DR
U
EQ
T
EN
M
IP
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE"B"
WELDED STEEL BASE
STRUCTURAL
STEEL FRAME
SLEEVE
ANCHOR
REINFORCING BARS
BOLT
SPRING
ISOLATOR
SECTION A-A
ALL WELDED
TYPICAL STRUCTURAL
STEEL FRAMEWORK
STEEL MEMBER FOR
EQUIPMENT
MO
T
SH OR
AF
T
A
EN
IV
DR
U
EQ
T
EN
M
IP
A
NUMBER OF ISOLATION
UNITS AS REQUIRED
TYPE "1"
CONCRETE INERTIA BASE
#
VIBRATION ISOLATION BASES
NTS
DETAIL TITLE / VIBRATION
ISOLATION BASES
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD230541-01.DWG
FAN INLET
FLEXIBLE DUCT
CONNECTIONS
FAN DISCHARGE
FLEXIBLE DUCT
CONNECTIONS
FAN SECTION
VIBRATORS ISOLATORS
AS SCHEDULED OR
SPECIFIED
COIL SECTION
THRUST RESTRAINT
OR DISCHARGE
DUCT
TYPE "THR"
NOTES:
1.
ATTACH THRUST RESTRAINTS SYMMETRICALLY ON BOTH SIDES OF THE FAN
DISCHARGE.
2.
ADJUST RESTRAINT TO ALLOW 1/4" [6 mm] MOVEMENT OF FAN AT START
AND STOP.
#
THRUST RESTRAINT FOR FANS
NTS
DESIGNER'S NOTE:
ON THE VIBRATION ISOLATION SCHEDULE OR UNDER THE TITLE OF THIS DETAIL
DESIGNATE FANS REQUIRING RESTRAINT. THIS IS USUALLY SEPARATELY MOUNTED
FAN SECTIONS FOR STATIC PRESSURE OVER 4" [100 mm] AND POSSIBLY FOR
AXIAL FLOW FANS FOR STATIC PRESSURE OVER 4" [100 mm].
DETAIL TITLE / THRUST
RESTRAINT FOR FANS
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD230541-02.DWG
B
W
PIPE SLEEVE (5D, 3"
[75mm] MIN.)
5D
A
B
BOLT (TYP)
1"
D
[25mm]
ANCHOR
L
2D
FLOOR
A
CONCRETE BASE
PLAN
5D
WELD HEAD TO PLATE
OR BEND OVER END 5D
SECTION B-B
EQUIPMENT BASE PLATE
TYPICAL ANCHOR
BOLT NUT & WASHER
16"
PROVIDE DOUBLE SLAB
[125mm]
L/10
5" MIN.
[400mm]
REINFORCING IN BASE AREA
SECTION A-A (BASE POURED WITH FLOOR SLAB)
TYPICAL ANCHOR
EQUIPMENT BASE PLATE
PROVIDE #3 BARS 12" [300mm]
[125mm]
L/10
5" MIN.
BOLT NUT & WASHER
O.C. EACH WAY IN THE BASE &
NOTE:
DOWEL BASE TO FLOOR
L & W DIMENSIONS
SHALL BE 6" [150mm]
SECTION A-A (BASE NOT POURED WITH SLAB)
GREATER THAN THE
EQUIPMENT BASE PLATE.
#
CONCRETE EQUIPMENT BASES
NTS
DESIGNER'S NOTE:
THIS DETAIL IS PRIMARILY FOR PUMPS WITHOUT ISOLATORS.
COORDINATE DETAIL
WITH ARCHITECTURAL AND STRUCTURAL.
DETAIL TITLE / CONCRETE
EQUIPMENT BASES
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD230541-03.DWG
DETAIL TITLE / SEISMIC BRACING FOR LIGHT SUSPENDED EQUIPMENT/
EQUIPMENT RESTRAINED BY RESILIENT PADS (TYPE DS)
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD230541-04.DWG
#
NTS
(TYP)
NUTS
LOCK
(TYP)
ROD
HANGER
AIR TERMINAL UNITS.
NOT REQUIRED FOR
NOTE:
SEISMIC BRACING FOR LIGHT
SUSPENDED EQUIPMENT
LESS
250 LBS. [114KG] OR
EQUIPMENT WEIGHT
CLAMP
SIDES
SEISMIC BRACING FOR EQUIPMENT
(TYPE DS)
FLOOR
RESILIENT PAD
PLATE
BONDED STEEL
& SLEEVE
NEOPRENE WASHER
ANCHOR BOLT
FLOOR MOUNT EQUIPMENT
RESTRAINED BY RESILIENT PADS
BASE
EQUIPMENT
CROSS BRACING
RODS ALL FOUR
STEEL EXPANSION SHIELD FOR EXISTING
CONSTRUCTION AND INSERTS FOR NEW
CONSTRICTION THIS TYPE SHALL BE
USED ONLY IN SLABS OR BEAMS OF 4"
[100mm] MIN DEPTH
CONCRETE
FLOOR SLAB
3/8" [10mm] MIN DIA EXPANSION
BOLTS FOR EXISTING CONSTRUCTION
AND INSERTS FOR NEW CONSTRUCTION
3/8" [10mm] MIN
CLIP
ANGLE
DIA INSERTS NEW
CONSTRUCTION ONLY.
NUTS & WASHERS
3/8" [10mm] MIN
DIA HANGER RODS
TURNBUCKLE
3/8" [10mm] MIN
DIA HANGER RODS
FOR PIPES UNDER 2" [50mm] IN SIZE USE
1 1/2"x1 1/2"x1/4" [40x40x6.4mm] ANGLE.
ALL PIPES 2" [50mm] & LARGER USE
3"x3"x1/4" [75x75x6.4mm] ANGLE
#
SECURING HANGER RODS IN CONCRETE
NTS
DETAIL TITLE / SECURING
HANGER RODS IN CONCRETE
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD230541-05.DWG
COLLAR DIA.
WIDTH OR LENGTH
COLLAR DIA.
WIDTH OR LENGTH
18" MIN.
18" MIN.
[450mm]
[450mm]
6" MIN.
6" MIN.
[150mm]
[150mm]
5/8" [18mm]
MINERAL FIBER
DUCT
CEILING
INSULATION
CEILING
AS SPECIFIED
CEILING DIFFUSER
OR REGISTER
SIDE VIEW
END VIEW
INSULATED DUCT TYPE
COLLAR DIA.
WIDTH OR LENGTH
6" MIN.
6" MIN.
[150mm]
6" MIN.
[150mm]
[150mm]
1-1/4" [32mm]
FIRE RESISTANT
DUCT INSULATION
DUCT
CEILING
EXTEND FROM
CEILING
CEILING TO TOP
OF DUCT
CEILING DIFFUSER
SIDE VIEW
OR REGISTER
END VIEW
NON-INSULATED DUCT TYPE
#
FIRE PROTECTION FOR CEILING OUTLETS
NTS
DESIGNER NOTES:
1.SHOW LOCATION ON FLOOR PLANS
DETAIL TITLE / FIRE
PROTECTION FOR CEILING OUTLETS
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD230711-01.DWG
1/2" [15mm] STEEL PIPE OR
STEEL TUBING TO SENSORS
DIFFERENTIAL PRESSURE
TRANSMITTER (FLOW, LEVEL)
PT
BLOWDOWN
ELEVATION
NOTES:
1.
INSTALLATION OF SENSORS AND TRANSMITTERS SHALL CONFORM TO
RECOMMENDATIONS OF MANUFACTURERS OF TRANSMITTERS.
#
PRESSURE TRANSMITTER INSTALLATION
NTS
DETAIL TITLE / PRESSURE
TRANSMITTER INSTALLATION
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230911-01.DWG
BYPASS
CW
OR
SW
N.C.
WATER METER
80 MESH
STRAINER
3'-6"
SUPPORT BRACKET
[1.1M]
ANCHORED TO WALL OR
FLOOR
COLUMN
ELEVATION
#
WATER METER INSTALLATION
NTS
DETAIL TITLE / WATER
METER INSTALLATION
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230911-02.DWG
DETAIL TITLE / BURNER
SCALE : NONE
DATE ISSUED :DECEMBER 2008
7
6
4
8
1
2
10
9
AB C D
5
3'-3"
[1M] MIN
[1.5M] MAX
5'-0"
ALARM BELL (WATER LEVEL)
BOILER WATER LEVEL CONTROL STATION
ECONOMIZER TEMPERATURE INDICATOR
SELECTOR SWITCH FOR ECONOMIZER TEMPERATURE INDICATOR
BURNER STOP SWITCH
9.
10.
11.
5.
4.
3.
2.
1.
TRIM CONTROL STATIONS MAY BE LOCATED ON THIS PANEL.
BOILER COMBUSTION CONTROL SUBMASTER, DRAFT CONTROL AND OXYGEN
SHOULD BE -1 IN (-25 mm) TO +1 IN (25 mm) WC.
WITH ECONOMIZER DRAFT LOSS. IF THERE IS NO ECONOMIZER, RANGE
SCALE RANGE OF BOILER OUTLET DRAFT GAGE MUST BE COORDINATED
BOILER AND BURNER MANUFACTURER.
WINDBOX AND FURNACE DRAFT GAGE SCALE RANGES RECOMMENDED BY
PANEL DIMENSIONS APPROX, 3'-0" (1 M) W x 1'-6" (0.5 M) D x 7'-6"
(2.3 M) H.
PANEL.
PROVIDE FRONT OR REAR ACCESS DOORS FULL HEIGHT AND WIDTH OF
NOTES:
INTERIOR OF PANEL SHALL BE UTILIZED FOR MOUNTING RELAYS, BURNER
CONTROL PROGRAMMER, AND OTHER DEVICES.
ROW OF BURNER CONTROL SWITCHES
8.
1.
ROW OF BURNER CYCLE PILOT-LIGHTS
7.
BURNER CONTROL SYSTEM ANNUNCIATOR
B.
A.
WINDBOX (0 IN (mm) WC) (SEE NOTE 4)
FURNACE (0 IN (mm) WC) (SEE NOTE 4)
C. BOILER OUTLET (TO +
IN (mm) WC) (SEE NOTE
2)
D.
ECONOMIZER OUTLET (-1 IN (-25 mm) TO +1 IN (25 mm) WC)
(SEE NOTE 5)
ALARM HORN (FLAME FAILURE, LOW WATER CUTOUT)
ROW OF ALARM PILOT LIGHTS (MAY BE COMBINED WITH ITEM 5)
2 DRAFT GAGES
6.
5.
4.
3.
2.
1.
ITEM
NO. DESCRIPTION
NTS
FOR WATER TUBE BOILERS
BURNER CONTROL PANEL
BOILER RM FL
CONC BASE
11
3
LIGHT CANOPY
#
CONTROL PANEL FOR
ELEVATION
WATER TUBE BOILERS
CADD DETAIL NO. :
SD230911-03.DWG
1.
BOILER OPERATION RECORDER
A. STEAM FLOW: INDICATE, RECORD, INTEGRATE, [0-____ LB/HR [kg/s])
B. BOILER OUTLET FLUE GAS TEMPERATURE: RECORD (0-1000 °F [0-500 °C])
C. FLUE GAS OXYGEN CONTENT: RECORD (0-10% OXYGEN)
STEEL DIVIDER FULL
DEPTH OF PANEL
2.
LIGHTING CANOPY 16 IN.
[406mm] DEEP
I
B D
F
H
I
1
2
1
10
I
A
D
8
3
9
12
C
3
2
5
B
14
STEAM FLOW RECORDER(S)
A. HIGH PRESS STEAM DIST: RECORD, INTEGRATE, (0-___ LB/HR [kg/s])
B. MED PRESS STEAM DIST: RECORD, INTEGRATE, (0-___ LB/HR [kg/s])
C. LAUNDRY STEAM DIST: RECORD, INTEGRATE, (0-___ LB/HR [kg/s])
D. BOILER PLANT STEAM: RECORD, INTEGRATE, (0-___ LB/HR [kg/s])
4.
BOILER PLANT OPERATION RECORDER
4
16
13
14
3.
14
CONCRETE BASE
A. STEAM HEADER PRESS: RECORD (0-300 PSIG [0-2000kPa])
B. BOILER FEEDWATER TEMP: RECORD (0-300°F [0-150°C])
C. OUTSIDE AIR TEMP: RECORD (-30°F [-35°C] TO +120°F [50°C])
5.
MASTER STEAM PRESSURE CONTROLLER
6.
CLOCK
7.
ALARM ANNUNCIATOR
A. CONDENSATE STORAGE TANK HIGH LEVEL
B. CONDENSATE STORAGE TANK LOW LEVEL
BOILER ROOM
C. FEEDWATER HEATER HIGH LEVEL
FLOOR
FLOOR SPACE FOR FUTURE PANEL
D. FEEDWATER HEATER LOW LEVEL
E. HIGH STEAM HEADER PRESS
EXTENSION FOR FUTURE BOILER
F. EMERGENCY GAS VALVE CLOSED
G. HIGH NATURAL GAS HEADER PRESS (SET AT 5 PSIG [35kPa] ABOVE MAIN REGULATOR SET PRESS)
H. LP IGNITER GAS IN USE-FOR EMERGENCY ONLY (PROVIDE HIGH PRESS SWITCH SET AT 2 PSIG [14kPa])
I. LOW EXCESS AIR BOILER NO. (PROVIDE ONE POINT FOR EACH BOILER, SET AT ___ % OXYGEN)
ELEVATION
ENGINEERING NOTES:
1.
PANEL APPROX. 12'-6"Wx2'-0"DX8'-0"H [3810x610x2438mm]. SHOW
ACTUAL SIZE ON DWGS.
2.
3.
IF GRAPHIC PAPERLESS RECORDERS ARE SPECIFIED (WITH 8 CHANNELS
MIN.) ITEMS 3 & 4 CAN BE COMBINED INTO ONE RECORDER.
SOME RECORDING & MONITORING FUNCTIONS MAY BE HANDLED BY A
COMPUTER WORK STATION & THEREFORE MAY BE DELETED FROM THIS
8.
ANNUNCIATOR ACKNOWLEDGE BUTTON
9.
ANNUNCIATOR TEST BUTTON
10.
ANNUNCIATOR BELL
11.
EMERGENCY GAS SAFETY SHUT OFF VALVE CONTROL
12.
PRESSURE GAGES
A.
B.
C.
D.
PANEL.
4.
ON SOME PROJECTS, IT MAY BE DESIRABLE TO LOCATE EMERGENCY
GENERATOR ANNUNCIATORS & METERS ON THIS PANEL.
5.
PROVIDE SMOKE DENSITY MONITORS ONLY ON PLANTS BURNING HEATED
OIL OR WHERE REQUIRED BY LOCAL CODES.
6.
ON PLANTS WHERE DRAFT CONTROL SYSTEMS ARE PROVIDED, CONSIDER
LOCATING THE DRAFT GAGES ON THIS PANEL ABOVE THE BOILER
OPERATION RECORDERS. THE GAGES ARE NORMALLY LOCATED ON THE
BURNER CONTROL PANELS.
7.
STEAM HEADER [0-200 PSIG (0-1500kPa])
NATURAL GAS HEADER (0-15 PSIG [0-100kPa])
FUEL OIL HEADER (0-200 PSIG [0-1500kPa])
BOILER FEEDWATER HEADER (0-300 PSIG [0-2000kPa]) (WHEN HEADER SERVING ALL BOILERS IS PROVIDED)
13.
START-STOP BUTTONS AND PILOT LIGHTS FOR PUMPS
14.
SMOKE DENSITY MONITOR (WHEN SPECIFIED)
15.
REMOTE REGISTER FOR GAS METER (WHEN SPECIFIED)
16.
FEEDWATER DEAERATOR TANK AND CONDENSATE STORAGE TANK WATER LEVEL CONTROL STATION
DELETE THE "ENGINEERING NOTES" FROM THE PROJECT DRAWINGS.
#
BOILER PLANT INSTRUMENTATION PANEL
NTS
SCALE : NONE
G
PLANT INSTRUMENTATION PANEL
2
E
DETAIL TITLE / BOILER
1
C
A
5' [1524mm]
11
A. COMBUSTION CONTROL SUBMASTER
B. DRAFT CONTROL (WHEN SPECIFIED)
C. OXYGEN TRIM (WHEN SPECIFIED)
6" [152mm]
7
6
BOILER CONTROL STATIONS (MANUAL/AUTOMATIC, BIAS)
(THESE CONTROL STATIONS MAY BE LOCATED ON THE BURNER CONTROL PANELS INSTEAD OF ON THE
INSTRUMENTATION PANEL.)
CAD DETAIL NO.:
FLUID PIPING FOR INSTRUMENTS
IN THIS SECTION OF PANEL ONLY
15
SD230911-04.DWG
DESCRIPTION
DATE ISSUED: DECEMBER 2008
ITEM
NO.
TO DISABLE RETURN FAN WHEN SMOKE
DAMPER IN RETURN DUCT CLOSES
PSL
H-1
FT
CS
ZC
VFD
ZC
SD
HS
SPD
DPS
MINIMUM
DIFFUSER
OUTSIDE
SECTION
TT
T-5
LIMIT SETPOINT IS REACHED
TSL
TT
TSL-1
T-3
[3000mm]
TT
TT
MPS
WATER, HOT
TT
WATER OR
T-2
SD
OUTSIDE UNDER
SUBSTITUTES
2C
V-3
STEAM HUMIDIFIER
2C
CHR
ARE
PERMISSIBLE
DETECTOR
ONLY WHERE REQUIRED
CHS
V-1
HHL
SMOKE
SST
V-2
ELECTRIC COILS
LOCATE SENSOR
HS
SPD
VARIABLE FREQUENCY
DRIVE, TYP.
SPS
FT
CS
VFD
HT
PSH
T-1
T-6
ZC
HOT GLYCOL
10' MIN.
SD
IT
D-1
SUPPLY AIR TO
TERMINAL UNIT
SUPPLY FAN
COIL COOLING
AIR
COIL PREHEAT
PRE- FILTER
AFMD
OUTSIDE
AFTER - FILTER
COMM
AIR
TO DISABLE FAN WHEN HIGH PRESSURE
DPS
DPS
AFMD
FT
PRESSURE SWITCH HIGH
SST
AIA
FINAL FILTER
D-4
V-4
LPS
SHIELD
#
VARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR CONTROL DIAGRAM
NTS
SCALE : NONE
HT
T4
AIR VOLUME AIR HANDLING UNIT
D-2
TT
WITH MINIMUM OUTSIDE AIR CONTROL DIAGRAM
ZC
DETAIL TITLE / VARIABLE
D-3
SD
RETURN
AIR
AFMD
RETURN FAN
CAD DETAIL NO.:
FAN STATUS ,TYP.
DATE ISSUED: DECEMBER 2008
TRANSMITTER FOR
EXHAUST AIR
SD230923-04.DWG
PRESSURE SWITCH LOW
CURRENT
ROOM
ELECTRIC
EXHAUST FAN
UNIT HEATER
PLENUM
D1
D2
EXHAUST
LOUVERS
INTAKE
T
T
T
T-1
T-2
T-3
LOUVER
FLEXIBLE
CONNECTION
EMERGENCY
GENERATOR
ACD
NOTES:
1.
EMERGENCY GENERATOR SHALL BE INTERLOCKED WITH D3.
GENERATOR IS ENERGIZED D3 SHALL OPEN.
WHEN EMERGENCY
WHEN EMERGENCY GENERATOR IS
DE-ENERGIZED D3 SHALL CLOSE, PROVIDED ROOM EXHAUST FAN IS OFF.
2.
ROOM EXHAUST FAN SHALL BE INTERLOCKED WITH D3 & ROOM THERMOSTAT T1.
WHEN ROOM THERMOSTAT RISES ABOVE 85°F [29°C] ROOM EXHAUST FAN SHALL RUN
& D3 SHALL OPEN. WHEN ROOM THERMOSTAT DROPS BELOW 80°F [27 C] ROOM
EXHAUST FAN SHALL STOP & D3 SHALL CLOSE, PROVIDED EMERGENCY GENERATOR
IS DE-ENERGIZED.
3.
POWER OPERATED, OPPOSED BLADE, DAMPERS D1 & D2 SHALL BE INTERLOCKED
WITH ROOM THERMOSTAT T2 SET AT 60°F [16°C]. ON A RISE IN ROOM
TEMPERATURE ABOVE 60°F [16°C] D1 SHALL MODULATE OPEN & D2 SHALL
MODULATE CLOSED. ON A DROP IN ROOM TEMPERATURE BELOW 60°F [16°C], D1
SHALL MODULATE CLOSED & D2 SHALL MODULATE OPEN.
4.
ELECTRIC UNIT HEATER SHALL BE INTERLOCKED WITH ROOM THERMOSTAT T3 SET AT
45°F [7.2°C]. ON A DROP IN ROOM TEMPERATURE BELOW 43°F [6.1°C] ELECTRIC UNIT
HEATER SHALL BE ENERGIZED & ON A RISE IN ROOM TEMPERATURE ABOVE 47°F [8.3°C].
#
EMERGENCY GENERATOR ROOM CONTROLS
DESIGNER'S
1.
NTS
NOTES:
IF THE PROJECT INVOLVES MULTIPLE EMERGENCY GENERATORS, EACH GENERATOR
SHALL HAVE A DEDICATED SECTION OF THE OUTSIDE AIR INTAKE LOUVER & DAMPER
MOTOR(S) ASSIGNED TO IT. THE DESIGNER SHALL SHOW A SCHEDULE OF THE
EMERGENCY GENERATORS & THE SPECIFIC INTERLOCKED LOUVER/DAMPER SECTIONS
ON THE FLOOR PLANS.
2.
WHEN THE ROOM EXHAUST FAN IS RUNNING ALONE, WITHOUT ANY EMERGENCY
GENERATOR, ONLY A DESIGNATED PORTION OF THE OUTSIDE AIR INTAKE LOUVER
SHALL OPEN.
THE DESIGNER SHALL SHOW THIS SECTION ON THE FLOOR PLANS.
DETAIL TITLE / EMERGENCY
GENERATOR ROOM CONTROLS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230923-07.DWG
HOIST WAY VENT LOUVERS
2
AT WALL OR ROOF
POSITION
M
HOIST WAY VENT DAMPER
TWO POSITION, N.O.
TO LOCAL 120 V
POWER
SPACE SMOKE
DETECTOR*
LOCATED AT TOP
TO FIRE ALARM CONTROL
OF HOISTWAY
PANEL (FACP)*
SD
TO FIRE ALARM* &
INITIATE PHASE 1 RECALL
*BY ELECTRICAL
ECC
NOTES:
1.
THE DAMPER SHALL REMAIN CLOSED DURING NORMAL OPERATION AND OPEN UPON
LOSS OF POWER FROM A SIGNAL FROM THE SMOKE DETECTOR, LOCATED AT THE
TOP OF THE HOISTWAY.
COORDINATE NUMBER OF CONTACTS WITH THE ELECTRICAL
AND FIRE PROTECTION DESIGNS.
2.
SHOW DAMPER LOCATION AND SIZE ON THE DRAWINGS.
3.
PROVIDE A BINARY DDC POINT TO SOUND AN ALARM AT ECC.
4.
REMOTE ALARM SHALL BE ACTIVATED WHEN THE HOISTWAY SMOKE DETECTOR
DETECTS SMOKE.
HOISTWAY VENT DAMPER (HVD)
#
CONTROLS
NTS
DESIGNER'S NOTES:
1.
THE AREA OF VENTS SHALL NOT BE LESS THAN 3.0% OF THE TOTAL HOISTWAY
AREA OR 3 SQUARE FEET (0.28 SQUARE METERS) FOR EACH ELEVATOR CAR,
WHICHEVER IS GREATER.
DETAIL TITLE / HOISTWAY VENT DAMPER (HVD) CONTROLS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230923-08.DWG
SMOKE PARTITION
DUCT TRANSITION
SMOKE DAMPER (N.C.)
AS REQUIRED
SEE SCHEDULE
SD
AIR
AIRFLOW
DUCT
AD
TO FIRE
ALARM CONTROL
PSH
PANEL (FACP)
120V
ZS
M
ELECTRICAL
POWER
2 POSITION
BINARY POINT
PRESSURE SWITCH HIGH
TO SHUT DOWN FAN UPON
DAMPER POSITION
REACHING HIGH PRESSURE
FEEDBACK TO
SETPOINT
ECC
NOTE:
UPON DETECTION OF SMOKE BY THE SMOKE DETECTOR, THE SMOKE DAMPER SHALL
CLOSE & SEND AN ALARM TO THE ECC.
#
SMOKE DAMPER CONTROL DIAGRAM
NTS
DESIGNER'S NOTE:
PROVIDE A DAMPER AND DETECTOR ONLY FOR PARTIALLY SPRINKLERED BUILDINGS
WHEN EITHER SIDE OF SMOKE PARTITION IS NOT SPRINKLED AND PROTECTED BY
QUICK RESPONSE SPRINKLER HEADS.
DETAIL TITLE / SMOKE
DAMPER
CONTROL DIAGRAM
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD230923-09.DWG
BUILDING INCOMING
MAIN STEAM
TT
TEMPERATURE
TRANSMITTER
PT
SHUTOFF VALVE
PRESSURE
TRANSMITTER
FLOW METER
DIFFERENTIAL PRESSURE (DP) CEL
INTERFACE
STEAM FLOW MEASUREMENT
WITH BACNET
SYSTEM
TO METERING
SYSTEM
NOTE:
1.
MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURES
#
STEAM METER DETAIL
NTS
DESIGNER'S NOTE:
1.
MODIFY DETAIL AS REQUIRED TO BE PROJECT SPECIFIC FOR THE TYPE OF METER BEING
USED.
DETAIL TITLE / STEAM
METER DETAIL
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD230923-10.DWG
CADD DETAIL NO. :SD231000-01.DWG
FILL CAP
[150mm]
GRADE
[300mm]
GRAVEL (ALL
AROUND)
3" [75mm]
#4 REBAR TOP
CONCRETE
AND BOTTOM
(SQUARE)
INTEGRAL DRAIN VALVE WITH
ACCESS COVER
FILL PIPE
ENCLOSURE SEALED WATER
TIGHT (TYP.)
2" [51mm] FILL
TYPE
ELEVATION
REINFORCED CONCRETE SLAB
CAP FOR SOUNDING
3" [76mm]
MANHOLE COVER
TANK
MAXIMUM
COMPRESSED
V
GRADE
-
SPILL CONTAINER
CONNECTED TO FILL LINE
42" [1067mm] DIA. MANWAY
VENT CAP
FILL BOX
FULL SIZE DISCHARGE
SEALED WATER TIGHT
FOAM BOARD
SECONDARY
SOIL SEPARATOR
CONTAINMENT
22" [559mm] DIA.
MANWAY (TYPICAL)
12"
[304mm]
LEAK DETECTOR
SENSOR
TANK
TYPICAL PIPE
FOR
HOLD-DOWN
STRAPS
SOUNDING ROD
[300mm]
WEAR PLATE
LADDER
1/4" [6mm]
THICK, 12"
[304mm] SQ
STEEL (TYP.)
12"
[300mm]
FOR - DOUBLE WALL TANK
TURN-BUCKLE
REINFORCED CONCRETE BALLAST PAD
DESIGN FOR BUOYANCY OF EMPTY
TANK WITH CREDIT FOR BACKFILL
UNDERGROUND FUEL OIL
END ELEVATION
6" [150mm]
12"
SIDE ELEVATION
NTS
FOOT VALVE
[150mm]
BEDDING MATERIAL
#
VALVE
6"
LEAK DETECTOR SENSOR
STORAGE TANK
PREVENT ON
FILL
12"
GAGE
OVERFILL
FOS
FOR
HANGER
LADDER
STEEL OR ALUMINUM 2 1/2"
[64mm] WIDE STRINGERS
3/4" [19mm] DIA. RUNGS
ANCHOR AT BOTTOM GUIDE AT
TOP
[300mm]
SCALE : NONE
PROJECT REQUIREMENTS.
FUEL OIL STORAGE TANK
THE PROJECT ENGINEER MUST PROVIDE A COMPLETE DESIGN WHICH CONFORMS TO
DETAIL TITLE / UNDERGROUND
DRAWINGS.
8" [200mm]
12"
NOTE: THIS DETAIL SHOWS BASIC REQUIREMENTS ONLY AND IS NOT INTENDED FOR USE ON PROJECT
DATE ISSUED :DECEMBER 2008
6"
DETAIL TITLE / STEAM
STEAM TRAP ASSEMBLY
LINE DRIP POCKET
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232111-01.DWG
[305mm]
[152mm]
12"
6"
MIN.
STEAM LINE DRIP POCKET
MIN.
SAME AS STEAM MAIN
#
NTS
STEAM TRAP ASSEMBLY
CONNECTION
RETURN
3/8" [10mm] TEST
DRIP
UNLESS OTHERWISE NOTED.
CONNECTION
STEAM LINE DRIP POCKET
TRAP (TYPICAL)
PIPE T0 STEAM
DRIP POCKET PIPE SIZE
NOTE:
CAP (TYPICAL)
FROM DRIP
STEAM TRAP ASSEMBLY
3/4" [20mm] MIN.
3/4" [20mm] DRAIN
(ALTERNATE LOCATIONS)
(TYPICAL)
DRIP LEG (TYP.)
(TYPICAL)
12"
6"
MIN.
STEAM LINE
MIN.
[305mm]
[152mm]
VENT PIPE THROUGH ROOF
VALVE HAS FLANGED OUTLET
SUPPORT AS INDICATED ON
SAFETY VALVE
DWGS. (NOTES 1, 2)
[25mm]
1" MIN.
PROVIDE UNION UNLESS SAFETY
PIPE THREADED INTO ELBOW
(SAME SIZE AS ELBOW)
DRIP PAN ELBOW
3"
(SECTIONAL VIEW)
[76mm]
D
OPEN DRAIN (NOTE 3)
CONNECTION TO PRESSURE
24" MAX.
VESSEL OR PIPE
FLEXIBLE
[610mm]
CONNECTOR
3/4" [20mm] DRAIN
ELEVATION
TO FLOOR DRAIN OR
OPEN SIGHT DRAIN
NOTES:
1.
(NOTE 4)
UNLESS OTHERWISE SHOWN ON THE DRAWINGS, SIZE THE VENT PIPE SO THAT STEAM
IS NOT BLOWN OUT AT THE VENT PIPE ENTRANCE. UTILIZE THE CALCULATION METHOD
CONTAINED IN ANSI B31.1. POWER PIPING CODE, APPENDIX II.
2.
VENT PIPE SHALL TERMINATE 6' [1829mm] MIN. ABOVE FINISHED ROOF.
3.
DISCHARGE OF DRAIN MUST BE DIRECTED AWAY FROM PLATFORMS OR OTHER AREAS
WHICH PERSONNEL MAY OCCUPY.
4.
DO NOT CONNECT ANY OTHER DRAIN TO THE DRIP PAN ELBOW DRAIN PIPE.
#
STEAM SAFETY VALVE
NTS
DETAIL TITLE / STEAM
SAFETY VALVE
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232111-02.DWG
6'
WHISTLE
ROOF
N.C.
HOLE DRILLED IN
WHISTLE
DEAERATOR VENTING
[0-1500kPa]
VACUUM
TO BLDG HEATING
HPS(
(CONVECTORS)
5 PSIG
LPS(
V
H-__
TO BLOWOFF TANK
T
FUEL
TEMP. CONTROL VALVE
OIL
0-200 PSIG
HEATER
LPR
0-15 PSIG
PRIMARY
[0-100kPa]
ELEMENT BOILER
[0-1500kPa]
FUEL OIL
FOS
TANK
PRV-___
0-15 PSIG
LPS(
SENSOR
[0-100kPa]
)
LPR
PRV-___
T-___
LPS(
PLANT FLOW
HPR
T-___
)
TO BLOWOFF
12"
LPR
[305mm]
LPS(
LPR
FEEDWATER DEAERATER
N.C.
TEMPERATURE
CONTROL VALVE
FOS
TANK
H
SV-__ (SET AT 15
PSIG [100kPa])
HPR
TO OIL PUMPS
30-300°F
[0-150°C]
)
THRU
LPS(15)
FOS
[0-150°C]
[35kPa]
ROOF
TO BLOWOFF
30-300°F
30" HG VAC-15 PSIG
[100kPa VAC-100kPa]
)
T-___
T-___
)
)
T-___
LPR
T-___
TO ADDITIONAL
TANK
FUEL OIL HEATERS
TO BLOWOFF
LPR
TANK
T-___
TO
HPS(
ENGINEERING NOTE: SIZE PRV
GLOBE - TYPE BYPASS VALVE
SO THAT MAX FLOW WILL NOT
EXCEED SV CAPY.
OIL TANKS
THRU
ROOF
ROOF
LATERAL CONNECTION
V
ADDITIONAL
(TYP.)(REQUIRED FOR
SOUND REDUCTION)
PRIMARY ELEMENT MPS DISTRIBUTION
SV-___
BOILERS
)
STRAIGHT PIPE AS
HPS(
THRU
RECOMMENDED
RECOMMENDED
BY FLOWMETER
BY FLOWMETER
MANUFACTURER (TYP.)
MANUFACTURER (TYP.)
HPS(
)
)
HPS(
0-200 PSIG
)
HPS(
)
HPS(
3' MAX
[914mm]
)
HPS(
)
)
HPS(
THREADED FOR CALORIMETER
CONNECTION (LOCATE TO ALLOW
SPACE FOR PROVIDED PLUG (TYP.)
CALORIMETER)
HPS(
[0-1500kPa]
3/4" [20mm] HALF-COUPLING
HPS(
)
)
HPS(
)
TO LAUNDRY
PRIMARY ELEMENT-HPS
PRESSURE
[0-1500kPa]
INSERT OPERATING
WATER - FILL CONNECTION
)
1" [25mm]
PANEL-MOUNTED
HEADER
HPS(
)
T-___
D
D
3/4" [20mm]
(TYP.)
3/4" [20mm] (TYP.)
FLOOR
FD
FD
FACTORY INSTALLED BYPASSES
ON VALVES 4" [102mm] &
LARGER
#
STANDARD STEAM BOILER PLANT PIPING DIAGRAM
NTS
HPR
BOILER ROOM
T-___
[762mm]
TRANSMITTER
2'-6"
HPR
MAIN STEAM
3.
ENGINEERING NOTES FOR MPS DISTRIBUTION PRV ARE TYP. FOR
4.
PRIMARY ELEMENT LOCATIONS SHALL CONFORM TO
ALL PRVS.
5.
DELETE "ENGINEERING NOTE" FROM PROJECT DRAWINGS.
6.
SHOW ALL PIPE SIZES.
7.
DO NOT SCHEDULE BOILER SAFETY VALVES.
8.
DO NOT SIZE VENT PIPES FROM BOILER SAFETY VALVES.
D
D
D
CONNECTION
HPR
SHOW VALVES THREADED OR FLANGED TO SUIT THE PROJECT.
INSTRUMENTS &
BOILER
T-___
CONFORMANCE.
2.
CONNECT TO
MASTER STEAM PRESSURE
CONNECTION/
FOR EMERGENCY
ATOMIZING
PROJECT DESIGN AND FLOW DIAGRAM SHALL BE IN
REQUIREMENTS OF INSTRUMENT MANUFACTURER.
HPS(
CONTROLS
FUTURE BOILER
OIL BURNER
1.
LAUNDRY FLOW SENSOR
BOILER
TO STEAM
ENGINEERING NOTES:
DISTRIBUTION
DISTRIBUTION FLOW SENSOR
S
0-200 PSIG
SIZE__
TO HPS
)
PRIMARY ELEMENT-HPS
& ADJUSTING)
ENGINEERING NOTE:
MPR
T-___
HPS(
BOILER-BURNER TESTING
HPS(
B
PRV-___
(TYP.)
(EXHAUST SYSTEM FOR
BURNER
T-___
HPR
PRV STATION
)
STOP-CHECK
3/4"
[20mm]
[0-400kPa]
(TYP.-ALL PRV STATIONS)
0-200 PSIG
7'
[2134mm]
V
V
V
NON-RETURN
)
0-60 PSIG
[0-1500kPa]
20
STEAM SILENCER
HPS(
3/4" [20mm]
(TYP.)
T-___
10
3/4"V
[20mm]
SV
T-___
STEAM FLOW SENSOR
BOILERS
MPS(
SV-___
0-200 PSIG
MPR
)
(UH. HV UNITS)
[0-700kPa]
DIAMETERS OF STRAIGHT PIPE
PRIMARY ELEMENT-BOILER
FROM OTHER
TO BLDG. HEATING
DISTRIBUTION
N.C.
T-___
ROOF
)
MPR
HPR
STRAIGHT PIPE AS
THRU
TO MPS
0-100 PSIG
PRV-___
PRV-___
[0-1500kPa]
FROM OTHER
HPS(
[0-1500kPa]
0-200 PSIG
ATOMIZING BURNERS
MPS(
BYPASS
PRV-___
V
6'
[1829mm]
(TYP. ALL
(FIRE-TUBE BOILER
VENTS)
ONLY)
TO ECONOMIZER
SOOT - BLOWER
TO OTHER STEAM
N.C.
SV-___
ROOF
FLOW SENSOR
ROOF
)
THRU
V
THERMAL BULB
V
)
HPS(
TO ADDITIONAL
FOOT VALVE
)
HEATING COIL
HPS(
FUEL OIL HEATERS
CONTRACTOR MUST DO THIS BASED ON VALVES FURNISHED.
DATE ISSUED: DECEMBER 2008
)
LPS(
ELL
HPR
LPR
HPS(
15 PSIG [100kPa]
CAD DETAIL NO.:
BREAKER
PRV-___
SCALE : NONE
[0-200kPa]
VALVE WEDGE FOR
VALVE
0-200 PSIG
STEAM BOILER PLANT PIPING DIAGRAM
0-30 PSIG
DETAIL TITLE / STANDARD
)
V
SV-__ (SET AT 10
PSIG [70kPa])
V
BLDG. WALL
LPS(
W
ROOF
[170kPa]
V
ROOF
SET AT 25 PSIG
[1829mm]
THRU
SV (SENTINEL)
SD232111-03.DWG
VENT PIPE - ALL VERTICAL
NO HORIZONTAL SECTIONS
EXPANDED RETURN MAIN
PERFORATED TUBE 1"x1/8"
[25x6mm] THICK GUIDE FINS
WELDED TO PERFORATED TUBE
SECTION A-A
A
WELD CAP
INCREASER
B
EXPANDED RETURN MAIN
CAP
RETURN
PERFORATED
REDUCER
MAIN
TUBE
A
FLOW
A
C
D
E
SECTION-EXPANDED RETURN MAIN
A
SIZE, TRAP DISCHARGE LINE
1/2" [15mm]
3/4" [20mm]
B
SIZE, 45° WELDING NIPPLE
1" [25mm]
1-1/4" [32mm]
C
LENGTH OF EXPANDED MAIN
7" [175mm]
7" [175mm]
AHEAD OF TRAP DISCHARGE PIPE
D
LENGTH OF PERFORATED PIPE
16-1/2" [415mm]
16-1/2" [415mm]
E
LENGTH OF EXPANDED MAIN OF
2" [50mm]
2" [50mm]
FOLLOWING PERFORATED PIPE
RETURN MAIN SIZE
UP TO 1-1/2"
[40mm]
EXPANDED RETURN MAIN SIZE
2" [50mm]
3" [75mm] &
2-1/2" [65mm]
SAME SIZE
OVER
NOTES:
1.
1/2" [15mm] PERFORATED TUBE SHALL HAVE 40 - 1/8" [16mm]
DIAMETER HOLES SPACED 1-1/2" [40mm] O.C. IN 4 ROWS.
2.
3/4" [20mm] PERFORATED TUBE SHALL HAVE 78 - 1/8" [6mm]
DIAMTER HOLES SPACED 1-1/2" [40mm] O.C. IN 6 ROWS.
3.
HOLES IN TUBE SHALL BE SPACED EQUALLY AROUND PERIMETER.
HIGH AND MEDIUM PRESSURE STEAM TRAP
#
DISCHARGE INTO PUMPED CONDENSATE RETURN LINE
NTS
DETAIL TITLE / HIGH
AND MEDIUM PRESSURE STEAM TRAP DISCHARGE
INTO PUMPED CONDENSATE RETURN LINE
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232111-09.DWG
DETAIL TITLE / WATER
FLOW MEASURING STATION
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232113-01.DWG
#
1.
FE
TEMPERATURE ELEMENT
TE
TE
INTERFACE
NTS
(WITH BTU METER)
WATER FLOW MEASURING STATION
MAINTAIN UPSTREAM AND DOWN STREAM DISTANCES RECOMMENDED BY METER MANUFACTURES
USED.
MODIFY DETAIL AS REQUIRED TO BE PROJECT SPECIFIC FOR THE TYPE OF METER BEING
DESIGNER'S NOTE:
1.
NOTE:
OUTLET
SUPPLY
FLOW ELEMENT
BACNET
METERING STATION
INTERFACE WITH
2 1/2" [65mm] DIA.
2" [50mm] DIA. & SMALLER
ABOVE 2" [50mm] DIA. PIPE
HORIZONTAL
2 1/2" [65mm] DIA.
2" [50mm] DIA. & SMALLER
ABOVE 2" [50mm] DIA. PIPE
VERTICAL
#
INSTALLATION OF THERMOMETER WELLS
NTS
DETAIL TITLE / INSTALLATION
OF THERMOMETER WELLS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232113-02.DWG
EXTERIOR SKIN
INTERIOR SKIN
PREFAB. WALL PANEL
AS SPECIFIED
MASTIC
GASKET
S.S. WALL PLATE
SECURED WITH S.S.
SCREWS
PIPE INSULATION
AS SPECIFIED
TUBING, PIPING
OR CONDUIT
S.S. WALL PLATE
SEAL INSULATION
SECURED WITH S.S.
AGAINST SKIN
SCREWS
OF WALL PANEL
FIELD APPLIED INSULATION
AFTER INSERTION OF
RESPECTIVE SERVICE FACILITY
THRU REFRIGERATOR OR
FREEZER WALL
TUBING, PIPING, AND CONDUITS PASSING
#
THROUGH PRE-FAB INSULATED WALL PANELS
NTS
DETAIL TITLE / TUBING,
PIPING, AND CONDUITS PASSING
THROUGH PRE-FAB INSULATED WALL PANELS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232113-03.DWG
#
NEAREST FD
LINE TO
SEE EXPANSION TANK
&
SET PRESSURE REDUCING VALVE SO PRESSURE AT HIGHEST POINT IN
5
MINIMUM OF 4 PSIG. [28kPa]
WHERE CHARGING
DATE ISSUED :DECEMBER 2008
SCALE : NONE
EXPANSION TANK PIPING CONNECTIONS
DETAIL TITLE / HORIZONTAL
CADD DETAIL NO. :SD232113-04.DWG
PROVIDE AND SHOW A
LOW WATER ALARM ON CHARGED SYSTEMS TO INDICATE NO WATER IN TANK.
OF TANK IS PROPOSED PROVIDE NECESSARY TAPPINGS.
BY CLOSENESS OF VALVES SERVING ADJACENT EQUIPMENT.
VALVES SHALL BE INDICATED ON EITHER SIDE OF AIR SEPARATOR AS REQUIRED
DESIGNER'S NOTE:
NTS
PIPING CONNECTIONS
HORIZONTAL EXPANSION TANK -
SYSTEM HAS A
SYSTEMS USE IN-LINE AIR PURGER IN LIEU OF AIR SEPARATOR.
FOR HOT WATER SYSTEMS 2" [50mm] AND SMALLER AND CHILLED WATER
SCHEDULE.
PROVIDE STRAINER IN AIR SEPARATOR WHEN INDICATED IN EXPANSION TANK
4.
3.
SHOWN ON HEAT EXCHANGER DETAIL & SYSTEM IS USED ONLY
FOR HOT WATER HEATING.
VALVE IS
SEE EXPANSION TANK SYSTEM SCHEDULE FOR COMPONENT SIZES.
4
RELIEF VALVE FOR CHILLED WATER SYSTEM IS SHOWN. OMIT WHEN RELIEF
DRAIN
3
SEE NOTES NO.
AIR SEPARATOR
FROM SYSTEM
D
OTHERWISE
UNLESS INDICATED
TO NEAREST F.D.
RUN DRAIN LINE
(REMOVE HANDLE)
VALVE IN VERTICAL
NORMALLY OPEN GATE
2.
VALVE
ISOLATION
OR BALL
BUTTERFLY
RODS (TYP)
HANGER
PI
AUTOMATIC AIR VENT
1.
NOTES
TO PUMP SUCTION
NC
PREVENTER
RUN DRAIN
SCHEDULE FOR SIZE
SLOPE (MIN.)
PITCH UP 1.6%
REDUCED PRESSURE BACKFLOW
COLD WATER FILL LINE.
D
TANK SADDLE
AV
CONNECTOR PIPE
SUPPORTS (TYPICAL)
EXPANSION
TANK
HANGER ROD
DIAPHRAGM
DETAIL TITLE / FLOOR
PIPING CONNECTIONS
MOUNTED EXPANSION TANK-
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232113-05.DWG
NC
NEAREST FD
LINE TO
RUN DRAIN
3
&
4
TO
PUMP
SEE NOTES
SEPARATOR
AIR
3.
2.
1.
CHILLED WATER SYSTEMS USE
[50mm] AND SMALLER AND
FOR HOT WATER SYSTEMS 2"
SIZES.
SCHEDULE FOR COMPONENT
SEE EXPANSION TANK SYSTEM
NEAREST FD UNLESS
INDICATED OTHERWISE
TANK
WITH DRAIN ACCESS OPENING
NTS
PIPING CONNECTIONS
PROVIDE AND SHOW A LOW WATER ALARM ON CHARGED SYSTEMS TO INDICATE NO WATER IN TANK.
SERVING ADJACENT EQUIPMENT. WHERE CHARGING OF TANK IS PROPOSED PROVIDE NECESSARY TAPPINGS.
GATE VALVES SHALL BE INDICATED ON EITHER SIDE OF AIR SEPARATOR AS REQUIRED BY CLOSENESS OF VALVES
DESIGNER'S NOTE:
#
[28kPa].
HAS A MINIMUM OF 4 PSIG
HIGHEST POINT IN SYSTEM
VALVE SO PRESSURE AT
SET PRESSURE REDUCING
FLOOR MOUNTED EXPANSION TANK -
MAY BE USED AS AN OPTION.
SHOWN. ANGLE IRON LEGS
FROM SYSTEM
RUN DRAIN LINE TO
BLADDER
VALVE
ISOLATION
OR BALL
BUTTERFLY
EXPANSION
FLOOR MOUNTING BASE RING
PAD
HOUSEKEEPING
[150mm]
6"
SHRAEDER VALVE
AIR CHARGING
SUCTION
OF AIR SEPARATOR.
DRAIN
RODS (TYP)
NOTE:
SCHEDULE FOR SIZE
PI
HANGER
CONNECTOR PIPE.
IN-LINE AIR PURGER IN LIEU
DRAIN
D
MV
AUTO. AIR VENT TO DRAIN
SEE EXPANSION TANK
COLD WATER FILL LINE.
D
PREVENTER
REDUCED PRESSURE BACKFLOW
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" [20mm] BALL VALVE
ADAPTER TO 3/4" [20mm] HOSE
THREAD-PROVIDE HOSE CAP NUT
ELEVATION
WELDED PIPING
ELEVATION
THREADED PIPING
TYPICAL CHILLED AND HOT WATER
PIPING DRAIN VALVE CONNECTIONS
NOTES:
1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.
2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
DESIGNER'S NOTE:
SHOW SCALE POCKETS ON MAJOR CIRCULATING WATER PIPING RISER
DIAGRAMS AND/OR PLANS.
MV
AIR VENT
OR
AV
1/2" [15mm]
1/4" [8mm]
COPPER TUBING
BALL VALVE
1/2" [15mm] x 4" [100mm]
NIPPLE
CIRCULATING WATER PIPING
ELEVATION
NOTES:
TYPICAL MANUAL AIR VENT
1. VENT ALL HIGH POINTS INDICATED ABOVE.
2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.
DRAIN VALVE AND AIR VENT CONNECTIONS
#
(HYDRONIC SYSTEMS)
NTS
DETAIL TITLE / DRAIN VALVE AND AIR
(HYDRONIC SYSTEMS)
VENT CONNECTIONS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232113-07.DWG
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR
TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
A
CLEAN OUT
DRAIN
B
1"
[25mm]
PAN
DIELECTRIC
FITTING
FLOOR SINK
NOTE:
1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY
LOCAL VA AND IS INDOORS AND DOES NOT PASS THROUGH
RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR
METALS ARE TO BE CONNECTED.
A
B
2" [50mm]
X
1" [25mm]
2X
UNIT TYPE
DRAW THRU
BLOW THRU
PLUS X
MINIMUM
WHERE X = STATIC PRESSURE IN PAN
#
AIR HANDLING UNIT DRAIN TRAP DETAIL
NTS
DETAIL TITLE / AIR
HANDLING UNIT DRAIN TRAP DETAIL
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232113-08.DWG
W
LONG RADIUS ELBOW
(TYPICAL)
PIPE ALIGNMENT GUIDES
(TYPICAL)
H
SUPPLY
W + 25 FT. [7.6m]
RETURN
APPROXIMATE MINIMUM
PLAN
EXPANSION LOOP
LOOP NO.
100-ELI
---
H
W
---
---
---
---
EXPANSION LOOP DETAIL
#
EXPANSION LOOP DETAIL
NTS
DETAIL TITLE / EXPANSION
LOOP DETAIL
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232113-09.DWG
SEQUENCE OF OPERATION:
70
1. STEAM CONTROL VALVE SHALL MODULATE TO MAINTAIN THE LEAVING
HOT WATER TEMPERATURE AT SET POINT.
O.A.
2. THE LEAVING HOT WATER TEMPERATURE SHALL BE RESET INVERSELY
30
WITH THE OUTDOOR TEMPERATURE AS SCHEDULED.
140°F (60°C)
(MIN.)
3. THE LEAD AND LAG PUMPS AND HEAT EXCHANGERS SHALL BE
SEQUENTIAL BY THE OPERATOR CONTROLS AT THE PRE-DETERMINED
INTERVAL (USUALLY 7 DAYS). IN THE EVENT THE PUMP FAILS TO START
WITHIN 30 SECONDS, AN ALARM SHALL BE INITIATED AND THE SECOND
180°F (82°C)
(MAX.)
TYP OSA RESET
PUMP SHALL START AUTOMATICALLY.
SCHEDULE
VALVE SEQUENCE:
1
1. V1 (3 CAPACITY) MODULATING FULLY OPEN TO MAINTAIN SET POINT
2
2 .V2 (3 CAPACITY) MODULATE FULLY OPEN TO MAINTAIN SET POINT.
3. BOTH V1 & V2 MODULATE TOGETHER TO MAINTAIN SET POINT.
AMBIENT TEMPERATURE TRANSMITTER WITH SUN
SHIELD
V1-C
V-1
CONTROL VALVES (N.C.). SIZE
VALVES IN 1/3 - 2/3 VALVE
V2-C
MPS
ARRANGEMENT
V-2
HEAT EXCHANGERS
TT
HWS
HX-1
TT
TC
TEMPERATURE
SENSOR (TYP)
PC
PUMP
HWR
TT
V3-C
HWP-1
CS
V-3
V4-C
HS
V-4
SST
PUMP
LPS
70
HX-2
HWP-2
CS
O.A.
30
CONTROL VALVES
140°F (60°C)
(MIN.)
180°F (82°C)
(MAX.)
HS
(N.C.). SIZE VALVES
IN 1/3 - 2/3
SST
VALVE ARRANGEMENT
DUAL HEAT EXCHANGER CONTROLS
#
(HEATING SYSTEM)
NTS
DETAIL TITLE / DUAL HEAT EXCHANGER CONTROLS (HEATING SYSTEM)
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232113-10.DWG
DETAIL TITLE /
HEAT EXCHANGER - STEAM TO HOT WATER
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232113-11.DWG
1/2" [15mm]
H
4.
3.
#
1
3
AND
2
3
SIZE ARRANGEMENT.
NTS
HEAT EXCHANGER - STEAM TO HOT WATER
CONTROL VALVES SHALL BE IN A
R
AI
MOUNTING HEIGHT SHALL
MAKE THE BYPASS THE SAME SIZE AS THE CONNECTIONS TO THE CONTROL VALVES.
BE ADJUSTED TO FACILITATE GRAVITY RETURN OF STEAM CONDENSATE.
PROVIDE SADDLE SUPPORTS AND LEGS OR HANGERS FOR HEAT EXCHANGER.
E
P.)
AL
SC
(TY
T
KE
C
PO
VEN
2.
D
AS
IC
TO P . )
AT
Y
T
R
T
S
MP K (
MO
P.)
N
Y
ER
A
T
H
T
T
T (
FL
THE ABOVE DETAIL SHOWS REQUIRED PIPING FOR TWO HEAT EXCHANGERS IN PARALLEL.
(TYP.)
TEST PLUG
(TYP.)
HEAT EXCHANGER
SI
PI
SUPPLY
STEAM
1/3
&
2/3YP.
P
N
BY
I T
ES ENT,
V
L
VA NGEM
L
O
TR ARRA
N
O
C ZE
S
AS
PI
MPS
1.
NOTE:
(TYP.)
THERMOMETER
(TYP.)
VACUUM BREAKER
D
CHECK VALVE
S
HW
FLOOR DRAIN. (TYP.)
RELIEF VALVE TO NEAREST
TEMPERATURE
-
TT
H
RUN DRAIN LINE FROM
SENSORS
DDC
-
TT
WR
VALVE SETTING
12"MIN.
6"MIN.
SEE SCHEDULES FOR RELIEF
[305mm]
(TYP.)
[152mm]
(TYP.)
MANUAL AIR VENT
REDUCER, IF REQUIRED
TEST PLUG (TYP.)
SHUT OFF VALVE
UNION CONNECTIONS
(TYP.)
MV
WATER RETURN
MODULATION CONTROL VALVE
COIL
WATER SUPPLY
DRAIN WITH HOSE
CONNECTION
TERMINAL UNIT WATER COILS -
PIPING CONNECTIONS
#
NTS
DESIGNER'S NOTE:
1.
THIS DETAIL IS APPLICABLE TO: 2-PIPE FAN COIL UNITS (CHILLED OR HOT WATER)
â—‹ VAV/CV AIR TERMINAL UNITS ( REHEAT COIL)
â—‹
â—‹
DUCT-MOUNTED REHEAT COIL
CABINET UNIT HEATERS
DETAIL TITLE / TERMINAL
UNIT WATER COILS -
PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232113-12.DWG
PLUG
1 1/2" [40mm]
FULL PORT BALL
VALVE
1 1/2"∅x2" LONG
[40x50mm] PIPE
°
0
9
1 1/2" [40mm]
FULL PORT BALL
VALVE
PLUG
WELD (TYP)
NOTE:
1.
2.
PROVIDE IN CHILLED WATER MAIN AND IN CONDENSER WATER MAIN.
LOCATE PILOT TUBE TAPS 20 PIPE DIAMETERS DOWNSTREAM AND
10 PIPE DIAMETERS UPSTREAM FROM THE NEAREST PIPE FITTING.
EITHER TOP OR SIDE LOCATION.
BOTH ARE NOT REQUIRED AT
SAME LOCATION.
#
PITOT TEST CONNECTIONS
NTS
DESIGNER'S NOTE:
SHOW LOCATION OF PILOT TEST CONNECTIONS ON FLOOR PLANS FOR
CONDENSER WATER PIPING TO COOLING TOWER. THIS IS REQUIRED FOR FLOW
MEASUREMENT BY ASME COOLING TOWERS TEST CODE.
DETAIL TITLE / PITOT
TEST CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232113-13.DWG
PIPE HANGERS - PROVIDE DOUBLE
DEFLECTION NEOPRENE (TYPE HN)
FOR FIRST TWO ON EACH SIDE OF
PUMP (SEE NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
BALANCING
DEVICE
FLEXIBLE
STRAINER
CONNECTION
BALL OR
BUTTERFLY
TYP.
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY.
DO NOT SUPPORT PUMP FROM
MOTOR.
#
IN-LINE PUMPS - CONNECTIONS
NTS
DESIGNER'S NOTE:
1.
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER PUMP.
2.
ELIMINATE BALANCING DEVICE WHEN PUMP CONTROLLED BY VARIABLE SPEED DRIVE.
DETAIL TITLE / IN-LINE
PUMPS - CONNECTIONS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232123-01.DWG
FIRST 3 HANGERS FOR EACH PIPE AND
BRANCH SHALL BE SPRING &
NEOPRENE
TYPE.
TYPE "H" FOR 4"
[100mm] DIA. PIPE & SMALLER. TYPE
"H-P" FOR 5" [125mm] DIA. PIPE &
LARGER.
RIGID PIPE
HANGER
RIGID PIPE
HANGER
BUTTERFLY OR BALL
INSTALL HANGER AS CLOSE
SHUT OFF VALVE, TYP.
TO PIPE ELBOW AS POSSIBLE
(TYPICAL)
OPTIONAL STRAINER
PRESSURE GAUGE
CHECK VALVE
1/2" [15mm]
1/2" [15mm]
SUCTION DIFFUSER
FLEXIBLE CONNECTOR (TYPICAL)
WITH BUILT IN STRAINER.
OPTIONAL: LONG RADIUS
PUMP
ELBOW AND INLET
STRAINER WITH 3XDIAM
STRAIGHT INLET TO PUMP
FLOOR
DRAIN
VIBRATION ISOLATOR
CONCRETE INERTIA
(TYPICAL)
BASE
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION
1" [25mm] MIN.
DIA. PIPE STAND
SINGLE SUCTION FLOOR-MOUNTED PUMPS #
CONNECTIONS WITH FLEXIBLE CONNECTORS
NTS
DESIGNER'S NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER PUMP.
DETAIL TITLE / SINGLE
SUCTION FLOOR-MOUNTED PUMPS -
CONNECTIONS WITH FLEXIBLE CONNECTORS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232123-02.DWG
FIRST 3 HANGERS FOR EACH PIPE
AND BRANCH SHALL BE SPRING &
NEOPRENE
TYPE.
TYPE "H" FOR 4"
[100mm] DIA. PIPE & SMALLER.
TYPE "H-P" FOR 5" [125mm] DIA.
PIPE & LARGER.
RIGID PIPE
RIGID PIPE
HANGER
HANGER
BUTTERFLY OR BALL
INSTALL HANGER AS CLOSE
SHUT OFF VALVE, TYP.
TO PIPE ELBOW AS
POSSIBLE (TYPICAL)
OPTIONAL STRAINER
PRESSURE
GAGE
1/2" [15mm]
1/2" [15mm]
SUCTION DIFFUSER
WITH BUILT IN STRAINER.
MECHANICAL COUPLING
OPTIONAL: LONG RADIUS
(6" MIN.[150 MM] SPACING)
(TYPICAL)
ELBOW AND INLET
PUMP
STRAIGHT INLET TO PUMP
STRAINER WITH 3XDIAM
FLOOR
DRAIN
1" [25mm] MIN.
DIA. PIPE STAND
CONCRETE BASE
(SEE DETAIL)
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION
SINGLE SUCTION FLOOR-MOUNTED PUMPS CONNECTIONS WITH MECHANICAL COUPLINGS
#
NTS
DESIGNER'S NOTE:
1.
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP, EXCEPT FOR COOLING TOWER
PUMP. USE THIS DETAIL ONLY FOR PUMPS IN A MECHANICAL BUILDING WHERE
POSSIBLE VIBRATION WILL NOT BE OBJECTIONABLE AND WHERE APPROVED BY VA.
2.
COUPLINGS SHALL NOT BE USED ON HOT WATER SYSTEMS.
DETAIL TITLE / SINGLE
SUCTION FLOOR-MOUNTED PUMPS -
CONNECTIONS WITH MECHANICAL COUPLINGS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232123-03.DWG
FIRST 3 HANGERS FOR EACH PIPE AND BRANCH
SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR
4" [100mm] DIA. PIPE AND SMALLER. TYPE "H-P"
FOR 5" [125mm] DIA. PIPE AND LARGER.
RIGID PIPE
HANGER
(TYPICAL)
BUTTER OR BALL
INSTALL HANGER AS CLOSE TO PIPE
SHUT OFF VALVE, TYP.
ELBOW AS POSSIBLE (TYPICAL)
CHECK VALVE
OPTIONAL STRAINER
1/2" [15mm]
PRESSURE GAUGE
FLEXIBLE CONNECTOR
FLEXIBLE CONNECTOR
PUMP
SUCTION DIFFUSER WITH
BUILT-IN STRAINER
1" [25mm] MIN. DIA.
PIPE STAND
DRAIN
FLOOR
1" [25mm] MIN. DIA. PIPE STAND
VIBRATION ISOLATOR
CONCRETE INERTIA BASE
(TYPICAL)
(SEE DETAIL)
NOTE:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION.
DESIGNER'S NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMPS, EXCEPT FOR COOLING TOWER PUMP.
DOUBLE SUCTION FLOOR-MOUNTED PUMPS #
CONNECTIONS WITH FLEXIBLE CONNECTORS
NTS
DETAIL TITLE / DOUBLE
SUCTION FLOOR-MOUNTED PUMPS -
CONNECTIONS WITH FLEXIBLE CONNECTORS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232123-04.DWG
FIRST 3 HANGERS FOR EACH PIPE AND
BRANCH SHALL BE SPRING & NEOPRENE
TYPE. TYPE "H" FOR 4" [100mm] DIA.
PIPE AND SMALLER. TYPE "H-P" FOR 5"
[125mm] DIA. PIPE AND LARGER.
RIGID PIPE
HANGER
(TYPICAL)
INSTALL HANGER AS CLOSE
TO PIPE ELBOW AS POSSIBLE
BUTTER OR BALL
(TYPICAL)
SHUT OFF VALVE, TYP.
CHECK VALVE
PRESSURE GAGE
OPTIONAL STRAINER
1/2" [15mm]
MECHANICAL COUPLINGS (6"
[150mm] MIN. SPACING)
(TYPICAL)
PUMP
SUCTION DIFFUSER WITH
BUILT-IN STRAINER
DRAIN
FLOOR
1" [25mm] MIN. DIA.
CONCRETE BASE
PIPE STAND
(SEE DETAIL)
NOTES:
SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION.
DOUBLE SUCTION FLOOR-MOUNTED PUMPS -
CONNECTIONS WITH MECHANICAL COUPLINGS
#
NTS
DESIGNER'S NOTE:
1.
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP EXCEPT FOR COOLING TOWER PUMP.
USE
THIS DETAIL ONLY FOR PUMPS IN A MECHANICAL BUILDING WHERE POSSIBLE VIBRATION
WILL NOT BE OBJECTIONABLE AND WHERE APPROVED BY VA.
2.
COUPLINGS SHALL NOT BE USED IN HOT WATER APPLICATIONS.
DETAIL TITLE / DOUBLE
SUCTION FLOOR-MOUNTED PUMPS -
CONNECTIONS WITH MECHANICAL COUPLINGS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232123-05.DWG
FIRST 3 HANGERS FOR EACH PIPE AND
BRANCH SHALL BE SPRING & NEOPRENE
TYPE. TYPE "H" FOR 4" [100mm] DIA.
PIPE AND SMALLER. TYPE "H-P" FOR 5"
[125mm] DIA. PIPE AND LARGER.
RIGID PIPE
HANGER
AV
(TYPICAL)
AV
INSTALL HANGER
BUTTER OR BALL
AS CLOSE TO
SHUT OFF VALVE, TYP.
PIPE ELBOW AS
POSSIBLE (TYPICAL)
NON SLAM CHECK VALVE
WITH COUNTER WEIGHT
PRESSURE GAGE
STRAINER
1/2" [15mm]
ECCENTRIC REDUCER
INLET TO PUMP SHALL BE
MINIMUM OF 3 PIPE
PUMP
DIAMETERS
FLEXIBLE CONNECTOR
TYP.
NOTE 3
FLOOR
1" [25mm] MIN. DIA.
CONCRETE BASE
PIPE STAND
(SEE DETAIL)
1.
Y TYPE STRAINER BLOWDOWN HEIGHT SHALL ACCOMMODATE 55 GALLON DRUM.
2.
PUMP INSTALLATION IS DIAGRAMMATIC AND INTENDED TO SHOW THE MAJOR COMPONENTS
REQUIRED FOR INSTALLATION.
ACTUAL PUMP PROVIDED.
THE INSTALLED PIPING CONFIGURATION SHALL BE BASED ON THE
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL A COORDINATION
DRAWING SHOWING PUMP, PIPING, AND ACCESSORIES AS REQUIRED BY THIS INSTALLATION DETAIL.
3.
ALL PAD, PUMP, AND PIPING DRAINS SHALL BE HARD PIPED TO NEAREST FLOOR DRAIN,
TYPICAL.
HORIZONTAL SPLIT CASE PUMP #
FLEXIBLE CONNECTORS
NTS
DESIGNER'S NOTE:
CHECK VALVE IS OPTIONAL FOR SINGLE PUMP EXCEPT FOR COOLING TOWER PUMP.
USE THIS
DETAIL ONLY FOR PUMPS IN A MECHANICAL BUILDING WHERE POSSIBLE VIBRATION WILL NOT
BE OBJECTIONABLE OR WHERE APPROVED BY VA.
DETAIL TITLE / HORIZONTAL
SPLIT CASE PUMP -
FLEXIBLE CONNECTORS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232123-06.DWG
PUMP DISCHARGE
TO PLANT
SCHEDULE 80 STEEL PIPE
GRAVITY RETURN
CONTROL CABINET
FROM FLASH TANK
VENT
IF SHOWN ON
FLOOR PLAN
RECEIVER
THERMOMETER
WATER LEVEL GAUGE
LPR
THERMOMETER
5" [127mm] THICK
CONCRETE HOUSEKEEPING
FLOOR
FLUSHING
3/4" [20mm] DRAIN,
CONNECTION
DISCHARGE INTO NEAREST
PAD
#
FLOOR DRAIN, NC.
CONDENSATE PUMPS - PIPING CONNECTIONS
NTS
DETAIL TITLE / CONDENSATE
PUMPS - PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232123-07.DWG
V
NOTE 3
REDUCER (TYP.)
IF REQUIRED.
VENT TO ATMOSPHERE
PSV
PILOT CONTROL LINE
NOTE 1
N.C.
NOTE 1
D2
SIPHON
(TYP.)
D1
D2
INVERTER
4 D2 MIN.
BUCKET TRAP
ASSEMBLY TYP.
10 D1 MIN.
20 D2 MIN.
NOTE:
1.
2.
SEE FLOOR PLANS FOR PIPE SIZES.
SEE EQUIPMENT SCHEDULES FOR VALVE DATA AND PIPE SIZES D1 AND D2.
INSTALL VALVES AS RECOMMENDED BY MANUFACTURER.
3.
MAKE BYPASS VALVE DISCHARGE PIPE THE SAME SIZE AS D2 FOR THE LARGEST
PRV.
4.
PROVIDE NECESSARY UNIONS FOR THE REMOVAL OF VALVE WITH SCREWED
CONNECTIONS.
STEAM PRESSURE REDUCING STATION
DOUBLE VALVE (1/3 AND 2/3)
1
NTS
DESIGNER'S NOTES:
1.
DESIGNATE LOWER VALVE A AND UPPER VALVE B (1-PRV1A, 1-PRV1B).
USE SYSTEM PRESSURE FOR 1-PRV1A AND SET PRESSURE 2 PSIG [13.8kPa]
HIGHER
2.
USE DUAL VALVE PRESSURE REDUCING STATION WHEN THE MINIMUM LOAD IS
10% OR LESS THAN PEAK LOAD.
3.
SAFETY VALVES SHALL BE SIZED SO AS TO RELIEVE AT PRESSURES OF 5-10
PSIG [35-70kPa] IN EXCESS OF DELIVERED PRESSURES OF PRV'S AND TO HAVE
A CAPACITY EQUAL TO THE MAXIMUM CAPACITY OF PRV IT IS TO RELIEVE. VENT
PIPE SHALL BE NO LESS THAN ONE PIPE SIZE LARGER THAN SAFETY VALVE
DISCHARGE AND SHALL FURTHER BE SIZED SO THAT FRICTIONAL RESISTANCE OR
VENT DOES NOT EXCEED VELOCITY PRESSURE AT SAFETY VALVE OUTLET. VENTS
FROM SAFETY VALVES SHALL RUN THE SHORTEST AND MOST DIRECT ROUTE TO
OUTDOOR THRU THE ROOF. WHERE VENTS RUN IN FINISHED SPACE THEY SHALL
BE FURRED IN TO MATCH ADJACENT BUILDING CONSTRUCTION; IN UNFINISHED
SPACE, PIPE TO BE COVERED ONLY. SAFETY VALVES SHALL BE LOCATED AS
SHOWN ON THE FLOOR PLANS.
DETAIL TITLE / STEAM PRESSURE REDUCING STATION
DOUBLE VALVE (1/3 AND 2/3)
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232213-01.DWG
H.P. & M.P. DRIP RETURNS.
(SEE FLOOR PLANS)
2" VENT TO OUTSIDE OF BUILDING
30°-300°F
4"
GRAVITY RETURN TO
[102 MM]
CONDENSATE PUMP
RETURN
DIELECTRIC FITTING
FLASH TANK
(WHEN RETURN IS COPPER)
PIPE WITH 1/4" PERFORATIONS SHALL
EXTEND FULL LENGTH OF TANK AND SHALL
HEIGHT DEPENDING
BE SAME DIAMETER OF CONDENSATE RETURN
ON INLET OR PUMP
CONNECTION
TO BE INSTALLED.
1/4" PERFORATIONS SHALL BE EQUIVALENT
TO TANK.
TOTAL AREA OF ALL
TO THE TRANSVERSE AREA OF THE PIPE.
FLOOR
PROVIDE PIPE SUPPORT
AND SADDLES.
FLASH TANK SCHEDULE
#
CONDENSATE PUMP
APPROX. CAPACITY OF
CAPACITY- GPM
FLASH TANK- GALLONS
0 THRU 15
16
14 DIA.
X
24 LONG
SIZE OF FLASH TANK-
INCHES
16
"
22
24
14 DIA.
X
36 LONG
23
"
30
31
16 DIA.
X
36 LONG
31
"
37
37
16 DIA.
X
42 LONG
38
"
45
42
16 DIA.
X
48 LONG
46
"
60
61
18 DIA.
X
54 LONG
61
"
75
75
18 DIA.
X
66 LONG
76
"
97
95
24 DIA.
X
54 LONG
98
"
150
155
24 DIA.
X
78 LONG
TYPICAL CONNECTIONS TO FLASH TANK
NTS
DESIGNER'S NOTE:
INDICATE THE HEIGHT ON FLOOR PLANS AND/OR SECTIONS.
PROVIDE A FLASH TANK FOR EACH CONDENSATE PUMP, WHICH SERVES MPR OR HPR
CONDENSATE.
DETAIL TITLE / TYPICAL
CONNECTIONS TO FLASH TANK
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232213-06.DWG
RETURN OR
EXHAUST AIR
ON/OFF
CONTROL
STEAM
SUPPLY
RAH
VALVE
V-2
ZC
V-1
TSH
PC
STEAM
CONDENSATE
HHL
AFS
RETURN
SUPPLY
AIR
10'-0" MIN.
[3000 mm]
STEAM HUMIDIFIER
RETURN (OR EXHAUST) AIR HUMIDITY SHALL BE MONITORED. ON A CALL FOR HUMIDIFICATION,
HUMIDIFIER VALVE V-1 SHALL MODULATE TO MAINTAIN THE RETURN (OR EXHAUST) AIR
HUMIDITY SET POINT TO 30% (ADJUSTABLE). PRIOR TO ACTIVATION OF V-1, THE ON/OFF
CONTROL VALVE V-2 SHALL BE ENABLED THROUGH ECC AND JACKET TEMPERATURE SENSED
BY TSH SHALL BE WARM ENOUGH TO PREVENT CONDENSATION. THE HIGH LIMIT HUMIDITY
SENSOR, LOCATED IN THE SUPPLY AIR DUCT 10 FEET AWAY FROM THE HUMIDIFIER SHALL
DISABLE THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE ECC, IF THE SUPPLY AIR
HUMIDITY EXCEEDS 90% RH (ADJUSTABLE). THE AIRFLOW SWITCH SHALL PROVE AIRFLOW
BEFORE HUMIDITY CONTROLS ARE ACTIVATED.
#
STEAM HUMIDIFIER CONTROLS
NTS
DETAIL TITLE / STEAM
HUMIDIFIER CONTROLS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232213-08.DWG
3/4" [20mm]
AIR LOOP
DOOR
UNION (TYP)
[25mm]
1"
RETURN MAIN
RETURN MAIN
FLOOR
PLUGGED TEE
FOR DRAINING
REMOVABLE COVER PLATE
TRENCH
MAKE ONE PIPE SIZE LARGER
THAN RETURN MAIN
3/4" [20mm]
AIR LOOP
UNION (TYP)
DOOR
1"
[25mm]
REMOVABLE COVER
RETURN MAIN
PLATE
RETURN MAIN
FLOOR
PLUGGED TEE
FOR DRAINING
TERRA COTTA SLEEVE
PIT
MAKE TWO PIPE SIZE LARGER
THAN RETURN MAIN
CONDENSATE RETURN
#
PIPING AROUND OPENINGS
NTS
DETAIL TITLE / CONDENSATE
RETURN PIPING
AROUND OPENINGS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD232213-09.DWG
TO OUTSIDE AIR VENT MANIFOLD
PRESSURE
MIST ELIMINATOR
SAFETY VALVE
SET @20 PSIG
PC
SHUTOFF VALVE
PT
SET @15 PSIG
LPS
LT
STEAM CONTROL
TO HUMIDIFIER(S)
LC
VALVE
MPS
MODULATING LEVEL
OR
CONTROL VALVE
HPS
WATER LEVEL
REVERSE
F&T TRAP ASSEMBLY
OSMOSIS
FEED
WATER
RO FEEDWATER
PREHEATED
SEE PLUMBING
DWG FOR R.O.
PREHEAT PLATE & FRAME HEAT EXCHANGER
SYSTEM
TO CONDENSATE RETURN
#
CLEAN STEAM GENERATOR
NTS
DESIGNER NOTES:
1.PREHEAT HEAT EXCHANGER IS OPTIONAL.
DETAIL TITLE / CLEAN
STEAM GENERATOR
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232213-10.DWG
FROM PUMP DISCHARGE
1.
SIZE WATER FILTER FOR
5% OF TOTAL SYSTEM
FLOW
PRESSURE
1/2" [15mm]
GAUGE
TO PUMP SUCTION
NOTE:
AUTOMATIC FLOW CONTROL
DEVICE SEE NOTE 2
WATER
FILTER
LOW POINT
DRAIN
DRAIN
CONNECTION
WATER FILTERS #
CLOSED LOOP HYDRONIC SYSTEMS
NTS
DESIGNER'S NOTE:
1.
PROVIDE SEDIMENT WATER FILTER ON EACH CHILLED WATER, HOT WATER AND GLYCOL
WATER HEATING SYSTEM.
CIRCULATING FLOW.
CAPACITY SHALL BE APPROXIMATELY 5% OF THE TOTAL
SHOW FILTER LOCATIONS ON THE DRAWINGS. INCLUDE THE FILTER
FLOW RATE IN PUMP CAPACITIES.
2.
SIZE PIPES TO WATER FILTER.
SELECT PRESSURE RANGE PER PROJECT NEED. SPECIFY PRESSURE RANGE ON DRAWINGS.
DETAIL TITLE / WATER
FILTERS -
CLOSED LOOP HYDRONIC SYSTEMS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232500-01.DWG
AUTOMATIC FLOW
CONTROL AND
BALANCE DEVICE
1" [25mm]
FUNNEL
CHEMICAL POT
FEEDERMINIMUM CAPACITY 5
3/4" [20mm]
GALLONS [19L]
1" [25mm]
TO
FROM PUMP DISCHARGE
TO PUMP SUCTION
DRAIN
NOTE:
TOP OF CHEMICAL POT
FEEDER TANK SHALL NOT BE
MORE THAN 4'-0" [1200mm]
ABOVE FINISHED FLOOR.
WATER TREATMENT - CLOSED SYSTEMS
#
NTS
DESIGNER'S NOTE:
1.
SHOW LOCATION OF ALL CHEMICAL POT FEEDER TANKS ON PIPING DIAGRAMS
FOR EACH CHILLED WATER AND HEATING HOT WATER SYSTEM. FEEDER MAY
ALSO BE USED FOR MAKE-UP FOR SMALL GLYCOL-WATER SYSTEMS (UNDER
50 GPM [190 LPM] IN LIEU OF A TANK/PUMP MAKE-UP SYSTEM.
DETAIL TITLE / WATER
TREATMENT - CLOSED SYSTEMS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232500-02.DWG
TOWER
TOWER
TOWER
CAD DETAIL NO.:
LC
~
REDUCED
CONDENSER WATER SUPPLY
PRESSURE
BACK FLOW
(FROM TOWER)
PREVENTER
SIDE STREAM SOLID
DWG
MAKE UP
MODULATING LEVEL
METER
CONTROL VALVE
CHEMICAL
FEED
PUMP
NO. 1
CHEMICAL
FEED
PUMP
NO. 2
HS
HS
CHEMICAL
FEED
PUMP
NO. 3
PH TRANSMITTER
CONDENSERS
PHT
PUMP
TYP.
HS
CT
OPTIONAL
SIDE STREAM
SAMPLE
SEPARATOR
TYP.
CONDUCTIVITY
CONDENSERS
TRANSMITTER
TYP.
CHEMICAL FEED
CONTROLLER
CONDENSER WATER RETURN
(TO TOWER)
STORAGE TANK NO. 1
CHILLED WATER SCALE
STORAGE TANK NO. 2
AND CORROSION
TOWER BIOCIDE
INHIBITOR
STORAGE TANK NO. 3 STORAGE TANK NO. 4
TOWER SCALE AND
DESIGNERS NOTES:
BROMINE FEEDER
1.DESIGN WATER TREATMENT SYSTEM BASED ON THE AVAILABLE
M
CORROSION INHIBITOR
WATER SAMPLE ANALYSIS AND RECOMMENDATIONS OF THE WATER
TREATMENT CONSULTANT.
WATER TREATMENT SYSTEM -
COOLING TOWER
NTS
FLOOR
BLOW
SINK
VALVE
METER
DOWN
2.PROVIDE INTERFACE BETWEEN CHEMICAL FEED CONTROLLER
AND ECC.
3.CHILLED WATER WATER TREATMENT SYSTEM SHALL BE OPERATED
MANUALLY.
4.ADDITIONAL STORAGE TANKS AND FEED PUMPS MAY BE REQUIRED
BASED ON THE OUTCOME OF THE WATER SAMPLE ANALYSIS.
5.ENSURE CLOSE COORDINATION BETWEEN THE CONTRACT
SPECIFICATIONS AND DETAILS.
DATE ISSUED: DECEMBER 2008
PLUMBING
VALVE TYP.
SCALE : NONE
M
TREATMENT SYSTEM -
RELIEF BYPASS
~
SEE
COOLING TOWER
SEPARATOR WITH PUMP
DCW
DETAIL TITLE / WATER
~
#
SD232500-03.DWG
CHILLED WATER
RETURN HEADER
WATER
LEVEL
CWS
CWS
CONDENSER
WATER PUMP
SEE PUMP
SIDESTREAM
SIDESTREAM
SCHEDULE
SEPARATOR
SEPARATOR
AND DETAIL
SOLIDS
RECOVERY
RECOVERY
SEPARATOR
SEPARATOR
CWS
CWS
CONDENSER
SOLIDS
FD
FD
SEPARATOR DETAIL WITHOUT
SIDESTREAM PUMP
SEPARATOR DETAIL WITH
SIDESTREAM PUMP
DESIGNER'S NOTE:
1. PROVIDE EITHER A COMMON SIDESTREAM SOLID SEPARATOR WITH PUMP OR A DEDICATED
SEPARATOR FOR EACH CONDENSER WATER SYSTEM.
2. INCREASE CONDENSER WATER PUMP CAPACITY 5%-8% FOR A DEDICATED SIDESTREAM
SEPARATOR.
#
SIDESTREAM SOLID SEPARATOR
NTS
DETAIL TITLE / SIDE
STREAM SOLID SEPARATOR
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD232500-04.DWG
W2
W1
NOTE:
1.
ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY
SMACNA.
2.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE
REGARDLESS OF W DIMENSION.
3.
4.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2"
[40mm] MAXIMUM SPACE BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE
DOUBLE VANE TYPE.
#
DUCTWORK SQUARE VANE ELBOWS
NTS
DETAIL TITLE / DUCTWORK
SQUARE VANED ELBOWS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-01.DWG
#
R
THAN W.
GREATER
OR BE
DETAIL TITLE / DUCTWORK
3W
1/3W
1/3W.
THAN
GREATER
OR BE
EQUAL
R SHALL
DATE ISSUED: DECEMBER 2008
2W
ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS
2.
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
CAD DETAIL NO.:
15 DEGREES ON DRAWINGS.
DO NOT SHOW MITERED ELBOWS AND MITERED OFFSETS (TRANSITIONS) GREATER THAN
DESIGNER'S NOTE:
NTS
DUCTWORK RADIUS ELBOWS
1/6W.
THAN
GREATER
OR BE
EQUAL
R SHALL
SHORT RADIUS ELBOW
WITH TWO VANES
W
1/6W
VANE
1/
1.
SHORT RADIUS ELBOW
WITH ONE VANE
W
VANE
2/
R
NOTE:
STANDARD RADIUS OR
LONG RADIUS ELBOW
W
EQUAL
R SHALL
1/3W
R
RADIUS ELBOWS
SCALE : NONE
SD233100-02.DWG
#
.
X
A
M
30°
MAX
.
EQUIPMENT
15°
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
FLOW
AIR
.
°
5
X
1
A
M
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
15
°
X.
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
NTS
(WITH EQUIPMENT MOUNTED IN DUCT)
DUCTWORK TRANSITIONS
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
FLOW
AIR
MAX.
15
°
MA
X.
°
0
3
MA
DETAIL TITLE / DUCTWORK TRANSITIONS
(WITH EQUIPMENT MOUNTED IN DUCT)
SCALE : NONE
SD233100-03.DWG
AIR
#
DATE ISSUED: DECEMBER 2008
AIR
MAIN
DAMPER
SUPPLY
CAD DETAIL NO.:
NTS
2.
1.
AIR
FLOW
BRANCH DUCT TAKE-OFF PLAN VIEW
W
DAMPER
PROVIDE VOLUME
DUCT
MAIN SUPPLY
SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.
OTHER CASES AND MAY BE USED AT ANYTIME.
FPM [5.1 M/S] OR LESS. THE AIR SPLIT DUCT TAKE-OFF SHALL BE USED IN ALL
MAIN DUCT CFM ANYTIME AND UP TO 40% WHEN THE MAIN DUCT VELOCITY IS 1000
DUCT CFM. THE BRANCH DUCT TAKE-OFF MAY BE USED FOR UP TO 15% OF THE
THE SUPPLY REGISTER TAKE-OFF MAY BE USED FOR UP UP TO 25% OF THE MAIN
DESIGNER'S NOTES:
FLOW
SUPPLY REGISTER TAKE-OFF
PLAN VIEW
TOP REGISTER
DUCT
1/4 W OR 4"
[100mm] MIN.
PROVIDE VOLUME
AIR
FLOW
AIR
FLOW
AIR
OR LINKAGE
CFM NOTED ON FLOOR PLANS
SUPPLY DUCTWORK TAKE-OFFS
OR BRANCH DUCT
FLOW
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
FLOW
SUPPLY REGISTER
DUCT
SUPPLY
MAIN
SPLIT DIMENSION
SEE FLOOR PLAN FOR
ADJUSTABLE
METAL ROD
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
AIR
TURNING VANES
FLOW
DETAIL TITLE / SUPPLY
DUCTWORK TAKE-OFFS
SCALE : NONE
SD233100-04.DWG
MAIN SUPPLY
X.
A
°M
45
ROUND SHEET METAL
"D
"
DUCT.
RIGID DUCT TO AIR TERMINAL
UNIT.
PLAN VIEW
#
SUPPLY DUCT TAKEOFF - AIR TERMINAL UNIT
NTS
DETAIL TITLE / SUPPLY
DUCT TAKEOFF- AIR TERMINAL UNITS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-05.DWG
FLOW
MAIN SUPPLY
FLOW
SMACNA FIGURE 4-6
45° LEED IN
RIGID DUCT TO AIR TERMINAL
UNIT.
PLAN VIEW
ALTERNATE SUPPLY DUCT TAKEOFF #
AIR TERMINAL UNITS
NTS
DETAIL TITLE / ALTERNATE
SUPPLY DUCT TAKEOFF -
AIR TERMINAL UNITS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-06.DWG
AIR
MAIN EXHAUST OR RETURN
FLOW
AIR
FLOW
1/4W OR 4"
[100mm] MIN.
VD
PROVIDE VOLUME DAMPER
BRANCH DUCT
AT EACH BRANCH DUCT
W
PLAN VIEW
#
EXHAUST OR RETURN BRANCH DUCTWORK
NTS
DESIGNER'S NOTE:
1.
SHOW ALL VOLUME DAMPERS ON FLOOR PLANS.
DETAIL TITLE / EXHAUST
OR RETURN BRANCH DUCTWORK
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-07.DWG
INSULATION SEE
1/2" [15mm]
SPECIFICATION
ROUND ROD PIN
STIFFEN BLADE
AS REQUIRED
DUCT
OUTSIDE END BEARING
INSULATION
STAND-OFF
DAMPER BLADE
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
1/8" [6mm]
CLEARANCE
SIDE ELEVATION
ALL AROUND
SECTION
NOTE:
1.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
#
VOLUME DAMPER DETAIL
NTS
DETAIL TITLE / VOLUME
DAMPER DETAIL
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-08.DWG
"A"
"A"
INSULATION
DUCT
GASKET
INSULATION
SECTION "A-A"
ACCESS PANEL
CASING
GASKET
"B"
HANDLE INSIDE
"B"
INSULATION
FLEXIBLE
WASHER
NOTES:
SECTION "B-B"
ACCESS DOOR
FACTORY
FABRICATED
1.
LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS
2.
HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE
LATCH
TIGHTLY.
PINS.
3.
SEE SMACNA 2005, FIGURE 9-15
ACCESS PANEL AND DOOR DETAIL
#
NTS
DESIGNERS NOTES:
1.
USE ACCESS DOORS ON AIR HANDLING UNITS AND DUCTWORK INSTALLED IN EQUIPMENT
ROOMS.
2.
USE ACCESS PANELS ON ALL EQUIPMENT AND DUCTWORK INSTALLED ABOVE FINISHED
CEILINGS.
DETAIL TITLE / ACCESS
PANEL AND DOOR DETAIL
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD233100-09.DWG
HOUSING WELDED
ROUND
TO DUCT SECTION
FLAT OVAL
OR
DUCT SECTION
COVER WITH HANDLE
AND CHAIN RETAINER
GASKETED AND
PRESSURE SEALED
#
ACCESS SECTION FOR ROUND/OVAL DUCT
NTS
DETAIL TITLE / ACCESS SECTION FOR ROUND/OVAL DUCT
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-10.DWG
SHEET METAL AS
ALTERNATE
POSITION
OF BOLT
SPECIFIED FOR
1" [25mm] FLANGE & HEM
DUCTWORK.
BOLT ON 4" [100mm] CENTERS
1 1/2" [40mm]
1"x1/8" [25x3mm] BAND IRON
POCKET SLIP
FLEXIBLE MATERIAL
AS SPECIFIED
WASHER
FLANGED
CONNECTION
ON FAN SIDE
DUCT
1 1/2" [40mm] MIN. TO 3" [75mm]
MAX. INSTALLED. 6" [150mm]
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
NOMINAL WITH MATERIAL TAUT
RECTANGULAR FLEXIBLE CONNECTION
5/16" [8mm] FLANGE
BOLT ON 4" [100mm] CENTERS
1"x1/8" [25x3mm] BAND IRON
1"x1/8" [25x3mm] DRAW BAND
SHEET METAL SCREWS ON
12" [300mm] CENTERS
FLEXIBLE
RIVET ON 4"
MATERIAL AS
[100mm]
SPECIFIED
1/2"
[15mm]
CENTERS
1/2"
[15mm]
WASHER
FLANGED CONNECTION
ON FAN SIDE
DUCT
1 1/2"
[40mm]
1-1/2" [40mm] MIN. TO 3" [75mm]
MAX. INSTALLED. 6" [150mm]
NOMINAL WITH MATERIAL TAUT
ROUND FLEXIBLE CONNECTION
#
FLEXIBLE DUCT CONNECTIONS
NTS
DETAIL TITLE / FLEXIBLE
DUCT CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-11.DWG
NOTE 6
FIRE BARRIER
SLEEVE, NOTE 2
[25mm]
TYPICAL DUCT
INSULATION
1"
PARTITION OR CHASE
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
DAMPER,
NOTE 1
ACCESS
DUCT
PANEL
CONNECTION
NOTE 5
NOTE 4
SLEEVE, NOTE 2
PERIMETER ANGLE, NOTE 3
(NOTE FASTENED TO PARTITION)
NOTE:
1.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, 1S SIMILAR.
FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND
GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN
THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.
2.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO
DAMPER FRAME AND TO PERIMETER ANGLES.
3.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm],
14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.
4.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.
ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR
LINKS.
5.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN
SPACE WITH ROCK WOOL FIRESTOP FIBER.
6.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
7.
AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH
CONCRETE CURB AROUND OPENING FOR DUCT.
SECTION THRU
#
FIRE DAMPER INSTALLATION
NTS
DETAIL TITLE / SECTION
THRU
FIRE DAMPER INSTALLATION
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-12.DWG
ALL THREAD ROD.
MINIMUM 3/8"
[10mm]∅
INSULATION
GALVANIZED ANGLE
IRON OR EQUIVALENT
STRENGTH CHANNEL
NOTE:
1.
PROVIDE BRACING TO LIMIT THE AMPLITUDE OF WALL VIBRATION AND WALL
DEFLECTION TO SPECIFIED MAXIMUMS.
2.
MINIMUM BRACING REQUIREMENTS:
MAXIMUM DUCT WIDTH
MAXIMUM SIZE ANGLE
UP
27
41
61
1-1/2x1-1/2x3/16 [40x40x7]
2x2x3/16 [50x50x7]
2x2x3/16 [50x50x7]
IN. [mm]
3.
#
MAXIMUM SPACING
IN. [mm]
TO 26 [650]
[675] TO 40 [1000]
[1000] TO 60 [1500]
[1500] TO 72 [1800]
IN. [mm]
NONE
72 [1800]
48 [1200]
24 [600]
INSULATION: FOR COLD DUCTS INSULATE BRACES AND PROVIDE VAPOR BARRIER.
FLAT OVAL DUCT HANGERS/REINFORCEMENT
NTS
DETAIL TITLE / FLAT OVAL DUCT HANGERS/REINFORCEMENT
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-13.DWG
DETAIL TITLE / ROUND
DUCT HANGERS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-14.DWG
UNDER
#
26
36
50
60
84
[650]
[900]
[1250]
[1500]
[2100]
IN. [mm]
MAX. DUCT Ø
1 [25] x 22 GA STRAP
1 [25] x 18 GA STRAP
1 [25] x 16 GA STRAP
3/8 [10]Ø. RODS
1/2 [13]Ø RODS
ALLOWS FOR DUCT REINFORCING AND
INSULATION, BUT NO EXTERNAL LOAD.
PROJECTS.
DESCRIBE OR DETAIL UPPER ATTACHMENTS APPLICABLE TO PARTICULAR
DESIGNER'S NOTE:
NTS
260 [119]
420 [190]
700 [317]
1320 [598]
2500 [1133]
LBS. [kg]
MAX. LOAD
TABULATED DATA FROM SMACNA
NOTE:
ONE
ONE
ONE
TWO
TWO
QUANTITY/SIZE
IN. [mm]
HANGER STRAPS OR RODS
ROUND DUCT HANGERS
[1250mm]∅
OVER 50"
BAND
HANGER RODS
&
[1250mm]∅
50"
STRAP
SIZE AS HANGER
BAND OF SAME
FASTENERS
LOAD RATED
144
144
144
144
144
[3600]
[3600]
[3600]
[3600]
[3600]
IN. [mm]
MAX.
SPACING
DUCT RISER - SEE FLOOR
SHEET METAL SCREWS 4"
PLANS FOR SIZES
[100mm] ON CENTER
EXTEND ANGLE 3"
1 1/2"x1 1/2"x1/8" [40x40x3mm]
[75mm] BEYOND DUCT
ANGLE INSTALL ON BOTH LONG
DIMENSION SIDES OF DUCT. FOR
DUCTS OVER 60" [1500mm] USE
2"x2"x1/8" [50x50x3mm] ANGLE.
FLOOR
SEAL HOLE WITH FIREPROOFING
HOLE IN STRUCTURAL FLOOR
MATERIAL AFTER DUCT INSTALLATION
DUCT RISER
0.5 INCH WG [125Pa] TO 2 INCHES WG [500Pa] DUCT RISER SUPPORT
DUCT RISER - SEE FLOOR
ARRANGE RISER SO
PLANS FOR DETAILS
REINFORCER TRANSVERSE JOINT
IS AT RISER SUPPORT POINT
2"x2"x1/4" [50x50x6mm]
ANGLE INSTALL ON BOTH LONG
DIMENSION SIDES OF DUCT.
FLOOR
HOLE IN STRUCTURAL FLOOR
SEAL HOLE WITH FIREPROOFING
MATERIAL AFTER DUCT INSTALLATION
DUCT RISER
2 INCHES WG [500Pa] TO 4 INCHES WG [1000Pa] DUCT RISER SUPPORT
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND FAN ROOM FLOORS SHALL BE PROVIDED WITH A 3" [75mm] HIGH CONCRETE
CURB AROUND OPENING FOR DUCT.
#
DUCT RISER SUPPORTS
NTS
DESIGNER'S NOTE:
INDICATE ON DRAWING THE DUCT PRESSURE CLASS 2" WG [500Pa] WG, 3" WG
[750Pa] OR 4" WG [100OPa].
DETAIL TITLE / DUCT
RISER SUPPORTS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-15.DWG
SIZE TO MAINTAIN 3500 FPM
°
15
[17.8 M/S] OUTLET VELOCITY
AS REQUIRED
WELDED STAINLESS STEEL
EXHAUST STACK
1" [25mm] GALVANIZED
STEEL STRAP SECURED
TO EXHAUST STACK
GUY WIRE (4 REQUIRED)
WELDED
10'-0" MIN.
TRANSITION
(AS REQUIRED)
F.C.
EXHAUST
FAN
[3000mm]
JOINT
DRIP LIP
DRAIN,
1/2"
[15mm]
WELDED
COUPLING
BLANK PLATE
SECURE
SECURE GUY
STACK TO
ROOF
WIRE TO
ROOF
ROOF (TYP.)
(TYP.)
#
EXHAUST STACK DETAIL
NTS
DESIGNER'S NOTE:
1.
10 FEET MINIMUM HEIGHT IS SHOWN.
INCREASE THE HEIGHT, AS
REQUIRED, TO COMPLY WITH THE RECOMMENDATIONS OF THE
DISPERSION ANALYSIS.
2.
USE THIS DETAIL FOR FUME HOODS,BIOLOGICAL SAFETY CABINETS,
ISOLATION ROOM EXHAUST AND ANY OTHER APPLICABLE AREA.
DETAIL TITLE / EXHAUST
STACK DETAIL
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-16.DWG
CONNECT TO GENERAL EXHAUST
EXHAUST DUCT
CEILING
2"
[50mm]
CEILING REGISTER
50 CFM, 4" [100mm] DIA.
STAINLESS
STEEL DUCT PER
MANUFACTURER'S
RECOMMENDATION
FILM
PROCESSOR
PROVIDE DUCT TRANSITION
FITTING IF REQUIRED
BETWEEN 4" AND
FILM PROCESSOR
NOTE:
1.
USE THIS DETAIL ONLY IF THE FILM PROCESSING INVOLVES USE OF
CHEMICALS.
#
DUCTWORK CONNECTION - FILM PROCESSOR
NTS
DETAIL TITLE / DUCTWORK
CONNECTION - FILM PROCESSOR
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD233100-18.DWG
SUPPORT ANGLES OR STANDING
"A"
SEAMS SECURE TO STRUCTURE TO
EXHAUST DUCT
ABOVE AS RECOMMENDED BY
WIDTH
SMACNA
SEE NOTE 1
"A"
LENGTH
PLAN
HIGH CLG.
-
CLG. SUPPORT
ANGLE-SEE
SEE NOTE 4
ARCHITECTURAL
SPECIFICATIONS
-
NORMAL 9'-0"
"B"
[2740mm] CLG.
32" [800mm] MIN.
"B"
SEE NOTE 2
FRONT ELEVATION
3/4" [20mm] LAP ALL
AROUND MITER AND WELD
1"
CORNERS SEE NOTE 3
[25mm]
SECTION "A-A"
CONTINUOUS
WELD
1"x1/8"[25x6mm]
STIFFENING BAR-
1/2"
[12.71mm]
3/4"
[20mm]
SEE NOTE 3
SECTION
"B-B"
NOTES:
1. HOODS SHALL BE STAINLESS STEEL, SEE SPECIFICATIONS. FOR HOOD SIZE &
LOCATION SEE EQUIPMENT SCHEDULE. FOR EXHAUST DUCT CONNECTIONS - SEE FLOOR
PLANS.
2. ALL HOODS SHALL BE 6'-6" [2m] ABOVE FINISHED FLOOR UNLESS OTHERWISE
NOTED. HOODS OVER URNS SHALL BE 7'-6" [2.3m] MINIMUM ABOVE FINISHED FLOOR.
3. HOODS OVER 6'-0" [1.9m] LONG WITH 2 OR MORE SECTIONS, SHALL HAVE INSIDE
STANDING SEAM AND 1"x1/8" [25x6mm] STIFFENING BAR - SEE SECTION "B-B".
4. EXTEND SIDE & END SHEET TO SUIT HIGH CEILING WHEN REQUIRED.
5. DETAIL SHOWS HOOD IN OPEN SPACE. WHEN HOOD IS INSTALLED AT WALL OR
PARTITION
#
SECURE TO WALL OR PARTITION WITH EXPANSION BOLTS.
HOOD TYPE "A"
NTS
DESIGNER'S NOTE:
VERIFY ALL DIMENSIONS. SEE ARCHITECTURAL FLOOR PLANS FOR REQUIRED HOOD
LOCATIONS.
DETAIL TITLE / HOOD
TYPE "A"
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD233100-19.DWG
SUPPORT ANGLES OR
RECESSED STERILIZERS IN
STANDING SEAMS. SECURE
MECHANICAL EQUIP AREA
TO STRUCTURE ABOVE AS
RECOMMENDED BY SMACNA
A
NORMAL 9'-0"
[2400mm] CEILING
LENGTH
PLAN
PROVIDE A STAINLESS
[300mm]
12"
A
STEEL COLLAR FOR
EACH OPENING
PARTITION
STAINLESS STEEL
SCREWS 16"
20"x8" [500x200mm]
OPENINGS SEE NOTE 4
[400mm] O.C.
NORMAL 9'-0"
SECTION A
[2400mm]
[813mm]
1/2"
[13mm]
1"
[25mm]
CONTINUOUS
WELD OR
SOLDER
B
FRONT ELEVATION
SEE
B
1"x1/8" [25x3mm]
NOTE 2
32" MIN.
CEILING
3/4"
[19mm]
STIFFENING BAR,
SEE NOTE 3
SECTION B
NOTE:
1.
HOODS SHALL BE STAINLESS STEEL. SEE SPECIFICATIONS. FOR HOOD SIZES &
LOCATIONS SEE EQUIPMENT SCHEDULE OR FLOOR PLANS.
2.
HOODS SHALL BE 6'-6" [1950mm] ABOVE FINISHED FLOOR.
3.
HOODS OVER 6'-0" [1800mm] LONG WITH 2 OR MORE SECTIONS SHALL HAVE
INSIDE STANDING SEAM AND 1"x1/8" [25x3mm] STIFFENING BAR. SEE SECTION B.
4.
PROVIDE A 20"x8" [500x200mm] OPENING OVER EACH STERILIZER. LOCATE
OPENING AS HIGH AS POSSIBLE IN HOOD, BUT BELOW CEILING IN MECHANICAL
EQUIPMENT AREA IF ROOM HAS A CEILING.
#
HOOD TYPE "B"
NTS
DESIGNER'S NOTE:
1.
SEE ARCHITECTURAL PLANS FOR REQUIRED HOOD LOCATIONS. USE TYPE
"B" HOOD FOR RECESSED STERILIZERS, WHEN STERILIZERS ARE
INSTALLED IN A MECHANICAL EQUIPMENT AREA.
DETAIL TITLE / HOOD
TYPE "B"
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-20.DWG
"WET" EXHAUST DUCT
TO DEDICATED
(STAINLESS STEEL)
EXHAUST SYSTEM
MANUAL VOLUME
DAMPER
CEILING
EXHAUST HOOD (TYPE "A")
UNDUCTED WASHER
EXHAUST VENT
OPENING
1'-0" [300mm] MIN. FRONT
AND 6" [150mm] MIN.
WALL
CLEARANCE ON BOTH SIDES
WASHER
DOOR
GLASSWARE WASHER
(SEE ARCHITECTURAL
FLOOR PLANS)
FLOOR
6'-0" [1800mm] MINIMUM-EXACT HEIGHT
SHALL BE BASED ON EQUIPMENT FURNISHED
#
EXHAUST DUCTWORK- GLASSWARE WASHER
NTS
DESIGNER'S NOTES:
1.
SEE VA STANDARD DETAIL 23 31 00-20 FOR CONSTRUCTION & INSTALLATION DETAILS.
2.
COORDINATE HOOD DIMENSIONS AND EXHAUST AIR VOLUME SHOWN ON THE EQUIPMENT
DRAWINGS.
EXHAUST AIR VOLUME SHALL BE BASED ON THE 100 FPM [.5 M/sec]
VELOCITY THRU THE FACE AREA OF THE HOOD.
DETAIL TITLE / EXHAUST
DUCTWORK - GLASSWARE WASHER
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD233100-21.DWG
OUTSIDE AIR
LOUVER
NOTE:1
NOTE 2
EXTERIOR
CMU WALL
[1400mm]
4'-8"
WALL
24"x24" [600mmx600mm]
BOLTED 1/2" [15mm]
STEEL ACCESS PANEL
FLOOR DRAIN (TYP.)
OUTSIDE AIR
ACCESS SECTION
DAMPER
(WALK-IN)
DETAIL KEYNOTES:
1.
THE DESIGN AND SUPPORTING DOCUMENTATION FOR THE BLAST
RESISTANT CONCRETE WALL SHALL BE COORDINATED AND APPROVED
BY A REGISTERED PROFESSIONAL STRUCTURAL ENGINEER SPECIALIZING
IN BLAST RESISTANT CONSTRUCTION.
2.
LIMIT AIR VELOCITY TO 800 FPM [4.0 m/s] THRU PLENUM.
OUTSIDE AIR INTAKE FOR AIR HANDLER
#
UNIT FOR MISSION CRITICAL FACILITY
NTS
DETAIL TITLE / OUTSIDE
AIR INTAKE FOR AIR HANDLER
UNIT FOR MISSION CRITICAL FACILITY
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-23.DWG
SEE SPECIFICATIONS FOR CLAMPS
AND SEALANT (TYP.)
THERMAL INSULATION
SEE SPECIFICATIONS
SUPPORT SADDLE
FROM STRUCTURE
CONICAL OUTLET
FLEXIBLE DUCT SIZE
SAME AS DIFFUSER
BRANCH DUCT
INLET: 5'-0" MAX
LENGTH.
USE RIGID ELBOWS
FOR CHANGE OF
DIRECTION GREATER
THAN 45°
12"
SHEET METAL
SADDLE
[300mm]
TYPICAL
DIFFUSER OR
VOLUME DAMPER W/
LOCKING QUAD
CEILING
REGISTER IN
LAY-IN CLG.
NOTE:
THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED
FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
#
FLEXIBLE AIR DUCT CONNECTOR
NTS
DETAIL TITLE / FLEXIBLE
AIR DUCT CONNECTOR
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD233100-24.DWG
LOCATED IN OPERATING ROOM
SURGICAL
SUITE
SUPPLY
DIFFUSER
SYSTEM
HEPA FILTRATION
AIR VELOCITY
MAX. 400 FPM
[2.0 M/sec]
ACCESS DOOR
MIN.24x36
4'-0"
[1200mm]
MIN.
2-POSITION
TERMINAL UNIT
ELBOW
WITH REHEAT
S.S.
DUCT
RH
WELDED S.S. DRAIN PAN
~
STEAM HUMIDIFIER
HWS
HWR
~
~
TU
D
LOCATED IN CORRIDOR
~
~
LPS
LPR
INDIRECT WASTE
TO FLOOR DRAIN
NOTES:
1.ALL DUCTWORK IS STAINLESS STEEL
#
SUPPLY DUCT DETAIL OPERATING ROOM
NTS
DESIGNERS NOTES:
1.PROVIDE 2 FULL CROSS SECTIONS THRU EACH OR.
DETAIL TITLE / SUPPLY
DUCT TAKEOFF DETAIL - OPERATING ROOM
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD233100-25.DWG
ACTIVE LENGTH
PLENUM WITH
INTERNALLY LINED
INACTIVE LENGTHS
INSULATION
TYP.
ROUND OR OVAL
INLET COLLAR
MINIMUM 2"
EXTENSION
VOLUME
DAMPER
BRANCH DUCT
INSULATED FLEXIBLE AIR DUCT
CONNECTOR LENGTH NOT TO
EXCEED 3' [900 MM]
NOTES:
1.COORDINATE
SLOT DIFFUSER FRAME/BORDER
TYPE AND END BORDER CONFIGURATION WITH
CEILING TYPE.
INLET COLLAR
PLENUM
LINEAR
DIFFUSER
CEILING
#
LINEAR SLOT DIFFUSER
NTS
DETAIL TITLE / LINEAR
SLOT DIFFUSERS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233100-26.DWG
MOTOR HOUSING
ELECTRICAL
CONDUIT GUIDE
WOOD NAILING
STRIP
CURB CAP
PREFABRICATED
ROOF
SEE NOTE 1
CURB
SEE NOTE 2
SEE NOTE 2
ROOF
RIGID CONDUIT TO
TRANSITION DUCT TO
ACCOMMODATE
FULL SIZE OF DAMPER
ELECTRICAL WIRES
SUPPLIED WITH ROOF
VENTILATOR
GRAVITY BACKDRAFT DAMPER
DUCT
NOTE:
1.
2.
SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED
LAG BOLTS NOT OVER 12" [300mm] ON CENTER.
SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST
ROOF).
3.
RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER,
THEN THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.
#
POWER ROOF VENTILATOR
NTS
DESIGNERS NOTES:
1.PROVIDE A MOTORIZED DAMPER, IF APPLICABLE.
2.PROVIDE DIRECT DRIVE FANS FOR LOCATIONS NOT
EASILY ACCESSIBLE. AS ATTIC OR PIPE BASEMENT AND
LESS THAN 2 HP.
3.MINIMUM CURB HEIGHT SHALL BE 12 INCHES [300
mm]. INCREASE HEIGHT, IF REQUIRED, TO OVERCOME
SNOW DRIFT.
DETAIL TITLE / POWER
ROOF VENTILATOR
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233400-01.DWG
WOOD NAILING
STRIP
FACTORY ASSEMBLED
HINGED HOOD WITH
PREFABRICATED
ROOF
LATCH & BIRD SCREEN
CURB
SEE NOTE 1
SEE NOTE 2
CURB CAP
ROOF
SEE NOTE 2
GRAVITY BACKDRAFT
DAMPER.
TRANSITION DUCT TO
FULL SIZE OF DAMPER
DUCT (WHEN SHOWN)
SUPPLIED WITH HOOD
NOTE:
1.
2.
SECURE HOOD TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG
BOLTS NOT OVER 12" [300mm] ON CENTER.
SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (MENTAL DECK & BAR JOIST
ROOF).
#
LOW-SILHOUETTE EXHAUST OR INTAKE HOOD
NTS
DESIGNER'S NOTE:
1.PROVIDE A MOTORIZED DAMPER, WHERE APPLICABLE.
2.MINIMUM CURB HEIGHT SHALL BE 12" [300 MM]. INCREASE HEIGHT, IF REQUIRED,
TO OVER COME SNOW DRIFT
DETAIL TITLE / LOW-SILHOUETTE
EXHAUST OR INTAKE HOOD
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233400-02.DWG
BELOW SET POINT VALVE V-1 WILL
MODULATE TO MAINTAIN SET POINT +
.5°,THE ADJUSTABLE TOLERANCE OF +
.5° HAS BEEN SELECTED TO PREVENT
VALVE HUNTING
C. THE REVERSE SHALL OCCUR ON RISE
IN SPACE TEMPERATURE.
TE
A. UPON FALL IN SPACE
A. SET POINTS SHALL SET AS FOLLOWS:
TEMPERATURE BELOW SET POINT VALVE V-1
COOLING 75° F (ADJ)
HEATING 70° F (ADJ)
WILL MODULATE TO MAINTAIN SET POINT +
.5°, THE ADJUSTABLE TOLERANCE OF + .5°
DEADBAND OF 5° F BETWEEN HEATING
HAS BEEN SELECTED TO PREVENT VALVE
AND COOLING SET POINT WILL BE
HUNTING
MAINTAINED
B. VALVE V-2 SHALL BE ENABLED WHEN
B. UPON FALL IN SPACE TEMPERATURE
OUTSIDE AIR FALLS BELOW 40° F (ADJ) AND
BELOW SET POINT VALVE V-1 WILL
VALVE V-1 HAS BEEN MODULATED OPEN
MODULATE TO MAINTAIN SET POINT +
ABOVE 30% (ADJ) V-2 SHALL THEN BE
.5°,
MODULATED TO MAINTAIN
THE ADJUSTABLE TOLERANCE OF + .5°
HAS BEEN SELECTED TO PREVENT
SET POINT + .5° F. THE ADJUSTABLE
TOLERANCE OF .5° F HAS BEEN SELECTED TO
VALVE HUNTING
PREVENT VALVE HUNTING.
C. VALVE V-2 SHALL BE ENABLED WHEN
SPACE TEMPERATURE.
REHEAT
TERMINAL
COIL
UNIT
TERMINAL
UNIT
TE
POINT + .5° F. THE ADJUSTABLE
TOLERANCE OF .5° F HAS BEEN
SELECTED TO PREVENT VALVE HUNTING.
D. THE REVERSE SHALL OCCUR ON RISE
FLOW
IN SPACE TEMPERATURE.
TU
HWR
AND VALVE V-1 HAS BEEN MODULATED
OPEN ABOVE 30% (ADJ) V-2 SHALL
AIR
RHC
HWS
OUTSIDE AIR FALLS BELOW 40° F (ADJ)
THEN BE MODULATED TO MAINTAIN SET
REHEAT
COIL
TU
SD233600-01.DWG
CV BOX CONTROL SEQUENCE
W/DEADBAND
NO DEADBAND
C. THE REVERSE SHALL OCCUR ON RISE IN AIR
AIR
AIR
FLOW
FE
HWS
V-1
RHC
FE
HWR
V-1
PC
HWS
ATU
PC
CONTROLLER
ROOM THERMOSTAT/SENSOR
WALL MOUNTED
SUPPLEMENTAL
48" [1200mm] AFF.
HWR
TE
ROOM THERMOSTAT/SENSOR
WALL MOUNTED
WITH SUPPLEMENTAL HEATING
CONSTANT VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM
NTS
ATU
CONTROLLER
48" [1200mm] AFF.
HEAT
NO SUPPLEMENTAL HEATING
#
V-2
TE
CAD DETAIL NO.:
CV BOX CONTROL SEQUENCE
SCALE : NONE
IN SPACE TEMPERATURE.
ROOM TEMPERATURE (°F)
VOLUME AIR TERMINAL UNIT
MAINTAINED
B. UPON FALL IN SPACE TEMPERATURE
ROOM TEMPERATURE (°F)
CONTROL DIAGRAM
VALVE HUNTING
B. THE REVERSE SHALL OCCUR ON RISE
SP
SP
DATE ISSUED: DECEMBER 2008
CFM
DETAIL TITLE / CONSTANT
AND COOLING SET POINT WILL BE
W
DEADBAND OF 5° F BETWEEN HEATING
.5° HAS BEEN SELECTED TO PREVENT
O
COOLING 75° F (ADJ)
HEATING 70° F (ADJ)
L
A. SET POINTS SHALL SET AS FOLLOWS:
F
CV BOX CONTROL SEQUENCE
W/DEADBAND
.5°, THE ADJUSTABLE TOLERANCE OF +
(CFM)
(CFM)
AIR FLOW
(CFM)
AIR FLOW
(CFM)
AIR FLOW
T
CV BOX CONTROL SEQUENCE
MODULATE TO MAINTAIN SET POINT +
A
ROOM TEMPERATURE (°F)
BELOW SET POINT VALVE V-1 WILL
W
O
L
F
ROOM TEMPERATURE (°F)
A. UPON FALL IN SPACE TEMPERATURE
E
W
CV
SP
NO DEADBAND
H
O
L
CV
CFM
SP
E
F
W
CFM
R
T
A
E
H
E
O
CV
CFM
P
P
U
S
W
O
L
F
R
L
F
AIR FLOW
P
P
U
S
T
A
W
O
L
F
E
H
E
R
T
A
E
H
E
R
CV
HEATING
HEATING
HEATING
HEATING
MINIMUM
MINIMUM
MINIMUM
MINIMUM
SP
ROOM TEMPERATURE (°F)
VAV BOX CONTROL SEQUENCE
ROOM TEMPERATURE (°F)
VAV BOX CONTROL SEQUENCE
W/DEADBAND
NO DEADBAND
A. SET POINTS SHALL BE SET AS FOLLOWS:
A. UPON FALL IN SPACE TEMPERATURE THE
COOLING 75°F (ADJ)
HEATING 70°F(ADJ)
VAV DAMPER WILL MODULATE TO MINIMUM
POSITION.
B. UPON FURTHER DROP IN SPACE
DEADBAND OF 5° F BETWEEN HEATING AND
TEMPERATURE VALVE V-1 WILL MODULATE
COOLING SET POINTS WILL BE MAINTAINED.
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
HUNTING
IN SPACE TEMPERATURE.
BEEN SELECTED TO PREVENT VALVE
HUNTING
D. THE REVERSE SHALL OCCUR ON THE RISE
IN SPACE TEMPERATURE.
POSITION.
B. UPON FURTHER DROP IN SPACE
COOLING SET POINTS WILL BE MAINTAINED.
B. UPON FALL IN SPACE TEMPERATURE THE
VAV DAMPER WILL MODULATE TO MINIMUM
POSITION.
HUNTING
C. UPON FURTHER DROP IN SPACE
C. VALVE V-2 SHALL BE ENABLED WHEN
TEMPERATURE VALVE V-1 WILL MODULATE
OUTSIDE AIR FALLS BELOW 40° F (ADJ)
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
AND VALVE V-1 HAS BEEN MODULATED
BEEN SELECTED TO PREVENT VALVE
OPEN ABOVE 30% (ADJ). VALVE V-2
HUNTING
SHALL MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5°F HAS
D. VALVE V-2 SHALL BE ENABLED WHEN
OUTSIDE AIR FALLS BELOW 40° F (ADJ)
BEEN SELECTED TO PREVENT VALVE
AND VALVE V-1 HAS BEEN MODULATED
REHEAT
AIR
TERMINAL
COIL
TERMINAL
UNIT
TE
UNIT
OPEN ABOVE 30% (ADJ). VALVE V-2
SHALL MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5°F HAS
REHEAT
BEEN SELECTED TO PREVENT VALVE
COIL
HUNTING.
E. THE REVERSE SHALL OCCUR ON THE RISE
AIR
TU
IN SPACE TEMPERATURE.
FLOW
AIR
TU
FLOW
RHC
HWS
HWR
FE
V-1
HWS
RHC
FE
HWR
V-1
PC
ATU
HWS
PC
CONTROLLER
V-2
ROOM THERMOSTAT/SENSOR
TE
WALL MOUNTED
48" [1200mm] AFF.
SUPPLEMENTAL
HWR
TE
HEAT
NO SUPPLEMENTAL HEATING
#
WITH SUPPLEMENTAL
VARIABLE VOLUME AIR TERMINAL UNIT CONTROL DIAGRAM
NTS
SD233600-02.DWG
W
O
L
F
R
DEADBAND OF 5° F BETWEEN HEATING AND
TEMPERATURE VALVE V-1 WILL MODULATE
HUNTING. THE REVERSE SHALL OCCUR ON
AIR
A RISE IN SPACE TEMPERATURE.
TE
I
COOLING 75°F (ADJ)
HEATING 70°F(ADJ)
VAV DAMPER WILL MODULATE TO MINIMUM
BEEN SELECTED TO PREVENT VALVE
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
A. SET POINTS SHALL BE SET AS FOLLOWS:
A. UPON FALL IN SPACE TEMPERATURE THE
POSITION.
TEMPERATURE VALVE V-1 WILL MODULATE
ROOM TEMPERATURE (°F)
VAV BOX CONTROL SEQUENCE
W/DEADBAND
NO DEADBAND
TO MAINTAIN SET POINT + .5° F. THE
ADJUSTABLE TOLERANCE OF + .5° F HAS
C. UPON FURTHER DROP IN SPACE
C. THE REVERSE SHALL OCCUR ON THE RISE
ROOM TEMPERATURE (°F)
VAV BOX CONTROL SEQUENCE
VAV DAMPER WILL MODULATE TO MINIMUM
B. UPON FALL IN SPACE TEMPERATURE THE
BEEN SELECTED TO PREVENT VALVE
SP
ATU
CONTROLLER
ROOM THERMOSTAT/SENSOR
WALL MOUNTED
48" [1200mm] AFF.
HEATING
SCALE : NONE
SP
VOLUME AIR TERMINAL UNIT
SP
CAD DETAIL NO.:
W
DATE ISSUED: DECEMBER 2008
O
CONTROL DIAGRAM
L
DETAIL TITLE / VARIABLE
F
A
T
A
I
R
W
A
V
O
E
A
L
H
AIR FLOW
F
E
V
A
V
(CFM)
AIR FLOW
F
L
O
W
W
P
R
V
P
(CFM)
U
O
L
F
R
I
A
V
A
V
AIR FLOW
(CFM)
F
L
O
W
A
I
R
V
A
V
(CFM)
100%
S
W
O
L
W
F
O
L
T
F
A
E
H
E
R
W
O
L
F
W
O
L
F
T
A
E
H
E
R
T
A
E
H
E
R
AIR FLOW
100%
P
P
U
S
100%
100%
FAN POWERED,
AIR TERMINAL UNIT
M
PC
FT
ROOM THERMOSTAT/SENSOR
SST
TT
S/A
FAN
FILTER
T
R/A OR
RECIRCULATED
WALL MOUNTED 48"
[1200 MM] AFF.
SOUND
HWR
BAFFLE
HWS
NOTES:
A. TERMINAL UNIT SHALL OPERATE ON A SCHEDULE SET BY THE ECC.
THE SERIES FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS.
THE SPACE TEMPERATURE SHALL BE MAINTAINED BETWEEN 70° (ADJ)
AND 75°F (ADJ) BY MODULATING PRIMARY AIR VOLUME AND HOT WATER
CONTROL VALVE IN SEQUENCE.
B. UPON FALL IN SPACE TEMPERATURE THE PRIMARY AIR DAMPER SHALL
MODULATE TO PRESET MINIMUM AIR VOLUME. UPON FURTHER FALL IN
SPACE TEMPERATURE BELOW 70° F THE HOT WATER VALVE SHALL
MODULATE TO OPEN POSITION TO MAINTAIN SET POINT WITHIN +.5°
(ADJ). THE TOLERANCE RANGE OF
+ .5° F HAS BEEN SELECTED TO
PREVENT VALVE HUNTING.
C. THE REVERSE SHALL OCCUR ON A RISE IN SPACE TEMPERATURE.
SERIES FAN POWERED AIR TERMINAL UNIT
#
CONTROL DIAGRAM
NTS
DETAIL TITLE / FAN
POWERED AIR TERMINAL UNIT
CONTROL DIAGRAM
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD233600-03.DWG
DIFFUSER (TYP.)
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
SOUND ATTENUATOR
SEE EQUIPMENT
SCHEDULE
SEE NOTE 1
REHEAT COIL
SEE NOTE 2
SEE NOTE 3
SEE NOTE 4
AIR TERMINAL UNIT
(CV OR VAV)
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
SEE NOTE 5
NOTE:
1.
RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A
MINIMUM OF 3 TIMES THE DIAMETER OF INLET
2.
A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO
THIS BOX, BUT ALLOWED TO ACCOMMODATE MINOR OFFSETS. MAXIMUM
LENGTH 3'-0" [900mm].
3.
A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE
AS THE BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE
BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS).
FOR LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A
DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT
OR BELOW 0.2"/100' [1.64Pa/m].
4.
FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT
SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0"
[1500mm].
THAN 45°.
5.
USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER
COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION W/VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
6.
USE OF THE FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED
FOR THE DEDICATED AHU SERVING THE SURGICAL SUITE.
#
DUCT CONNECTIONS - AIR TERMINAL UNITS
NTS
DESIGNER'S NOTE: 1.INDICATE SOUND ATTENUATOR AS REQUIRED BY ACOUSTICAL
ANALYSIS
DETAIL TITLE / DUCT
CONNECTIONS - AIR TERMINAL UNITS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD233600-04.DWG
DETAIL TITLE / FLASH
TANK
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD235011-01.DWG
#
D
[0-150°C]
(TYPICAL)
30-300°F
TRAPS
FROM STEAM
OPEN SIGHT DRAIN
3/4"
[20mm]
V
NTS
FLASH TANK
= PIPE AREA
1/8" [6mm] HOLES
PERFORATED PIPE
RETURN PUMP SET
CONDENSATE
GRAVITY FLOW TO
C-TANK
L
FLASH TANK
[0-100 kPa]
0-15 PSIG
THRU ROOF
2.
TANK SHELL
PIPE EXTRACTOR
BUSHING
30 [207]
1.34 [0.13]
2.23 [0.21]
3.00 [0.28]
100 [689]
60 [414]
3.15 [0.29]
3.40 [0.32]
110 [758]
125 [862]
150 [1034]
NOTE 1
3.71 [0.35]
SQ. FT.[SQ.
M] NOTE 2
PSIG [kPa]
TANK AREA
STEAM
PRESSURE
ATMOSPHERIC PRESSURE.
CONDENSATE. TANK AT
THOUSAND POUNDS OF
CENTER OF TANK PER
LENGTH x DIAMETER AT
STEAM TRAP.
PRESSURE UPSTREAM OF
NOTES
1.
DOUBLE-THREADED
PIPE
HALF-COUPLING
MPR
HPR
3/4" [20mm] TO
3/4" [2Omm]
(SEE PLUMBING
DRAWINGS)
CW HW
BOILER, DEAERATOR,
OR STEAM HEADER
CF
USE FWPD FOR
TANK
NOTES
1.
ON SYSTEM WHICH
SERVES DEAERATOR
2.
PURGING CF LINE TO
DO NOT PROVIDE FWPD
PROVIDE A SEPARATE
CHEMICAL FEED SYSTEM
BOILER (NOTE 1)
FOR EACH BOILER, FOR
MOTOR-DRIVEN
THE DEAERATOR AND FOR
AGITATOR
MAIN STEAM.
V
FWPD
3/4" [20mm]
3/4"
[20mm]
TO FD
CF
0-300 PSIG
D
[0-2000 kPa]
BASE
PUMP
MOTOR
BOILER
ROOM
FLOOR
ELEVATION
1
CHEMICAL FEED SYSTEM - PUMPED TYPE
NTS
DETAIL TITLE / CHEMICAL
FEED SYSTEM - PUMPED TYPE
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD235011-02.DWG
AUTO VALVE
FLEX CONN.
AIR COMPRESSOR
AC
1
CW
AND RECEIVER
AFTERCOOLER
CONDENSATE
0-300 PSIG
A
TRAP
[0-2000 kPa]
RV
A
FLEX
D
CONN
D
1/2 " [15mm]
D
OSD
A
1/2 " [15mm]
D
CONDENSATE TRAP
COMPRESSED AIR
SYSTEM SEE NOTE
A
FROM DUPLICATE
COMPRESSED AIR
SYSTEM (SEE NOTE)
FILTER
AD AIR
1 DRYER
TO STEAM ATOMIZING
OIL BURNER FOR
A
COLD START (TYPICAL)
D
1/2" [15mm]
CONDENSATE TRAP
NOTE:
PROVIDE DUPLICATE
D
D
OSD
1/2"
[15mm]
PRV
A
"COMPRESSED AIR
SYSTEM" IF PNEUMATIC
A
CONTROLS ARE
FURNISHED
A
FOR PLANT USE
FILTER
TO INSTRUMENT
OR CONTROL
SYSTEM
(TYPICAL FOR
EACH SYSTEM)
COMPRESSED AIR SYSTEM #
STANDARD PIPING DIAGRAM
NTS
DETAIL TITLE / COMPRESSED
AIR SYSTEM - STANDARD PIPING DIAGRAM
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD235011-03.DWG
VARIABLE SPRING HANGERS
VENT THRU
ROOF
NOTE TO DESIGNER:
)
V
HPS (
PRESSURE
LPS (
)
INSERT NOMINAL
5 PSIG
TURBINE
0-200 PSIG
[35kPa]
[0-1500kPa]
SV
[0-100kPa]
12" [300mm]
1/2"
[15mm]
MIN.
HPR
D
FLOOR
MIN.
D
12" [300mm]
LPR
D
D
1 1/2" [40mm]
OPEN SIGHT DRAIN
GRAVITY RETURN
CONCRETE PAD
TO RECEIVER
GRAVITY RETURN
FROM TURBINE
ELEVATION (END VIEW)
TO RECEIVER
#
0-15 PSIG
CASING
STEAM TURBINE DRIVE
NTS
DETAIL TITLE / STEAM
TURBINE DRIVE
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD235011-04.DWG
TANK DESIGN SHALL
BE IN CONFORMANCE
1 1/4"
[32mm]
BO
CW
NOTE:
WITH NATIONAL BOARD
HPR
"BOILER BLOWOFF
EQUIPMENT"
OFL
LEG (4 REQD.)
WEAR PLATE
PLAN VIEW
3/4" [20mm]
OPENING (SYPHON
BREAKER)
12" [305mm]
1 1/4" [32mm]
COUPLING (TYP)
TEMPERATURE CONTROL
WEAR PLATE
2" [50mm]
PLUGGED
VENT THRU ROOF
FROM STEAM ATOMIZING
BURNER AND OIL HEATER
TRAPS
V
VALVE (TCV-1)
HPR
THERMAL BULB
3" [76mm]
1 1/4" [32mm]
0-30 PSIG [0-200 kPa]
CW
3/4" [20mm]
BO
THERMAL BULB
FROM
BOILERS
C
L TANK (NORMAL WATER LEVEL)
6" [152mm]
2" [50mm] PIPE
SIZE IN AREA OF
6" [152mm]
CW
GAGE GLASS (1/2"[25mm] MIN.DIA)
30-300°F
MANHOLE 12"x16" [305x406mm]
[0-150°C] (TYP)
INTERNAL OFL PIPE (WATER SEAL)
6" [152mm]
WELL
CROSS
OFL
OPEN SIGHT DRAIN
STEEL
PLATE
ANGLES
GROUT
2" [50mm] DRAIN
FLOOR
PLUGS
ELEVATION
#
BOILER BLOWOFF TANK
NTS
DETAIL TITLE / BOILER
BLOWOFF TANK
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD235011-05.DWG
1/2" [15mm] FROM EACH
BOILER
1/4" [8mm] FROM
BWS
COOLING WATER
BWS
3/4" [20mm]
BWS
FWS
DEAERATOR
SW
30-180°F
[0-83°C]
1/4" [8mm]
SAMPLE
SAMPLE COOLER
OUTLET
AND FWS. MOUNT BWS COOLER 4'
SW
3/4" [20mm]
PROVIDE SEPARATE COOLERS FOR BWS
[1.2M]
COLUMN.
ABOVE FLOOR ON WALL OR
MOUNT FWS COOLER 2'
[0.6M] ± ABOVE MEZZANINE FLOOR
ANTI-SYPHON
AT DEAERATOR.
VACUUM BREAKER
D
1/2" [15mm]
FD
ELEVATION
WATER SAMPLE COOLERS BOILER
#
WATER AND FEEDWATER
NTS
DETAIL TITLE / WATER
SAMPLE COOLERS
BOILER WATER AND FEEDWATER
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD235011-06.DWG
DETAIL TITLE / CONTINUOUS
STANDARD PIPING DIAGRAM
BLOWDOWN HEAT RECOVERY
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD235011-07.DWG
#
CBD
NC
BO
1/2"
[15mm]
DRUM
MUD
BURNER
CBD
2" [50mm]
TANK
BLOWOFF
FLOW: _____ LBS/HR [kg/s]
P:100 PSIG [689kPa]
CBD CONTROL
50-400°F [10-205°C]
(TYPICAL)
1/2" [15mm]
BOILER
TYP. WATERTUBE
STEAM DRUM
NTS
BOILER
BOILER
TYPICAL FOR EACH
BWS/CBD PIPING IS
NOTE:
BURNER
TYP. FIRETUBE
BWS/CBD
RECOVERY STANDARD PIPING DIAGRAM
CONTINUOUS BLOWDOWN HEAT
BOTTOM BLOWOFF
FROM BOILER
EXCHANGERS
FROM OTHER HEAT
1/2"[15mm] (TYP.)
STORAGE TANK
CONDENSATE
TANK DIA.
25% OF
(MIN. WATER LEVEL)
30% OF TANK DIA.
FOR EACH BOILER
(TUBE BUNDLE) ONE
HEAT EXCHANGER
TO SAMPLE COOLER
BWS/CBD
BWS
1/2" [15mm]
BWS
CBD
FUNNEL (5"x2"
[125x50mm]
WELDING
REDUCER)
BALL VALVE
3/4" [20mm] TO
DRUM
1/2"
[15mm]
1/2"
[15mm]
CF
12" [300mm]
CAP
V
3'-8" [1.1M] MAX.
BOILER STEAM
TO FLOOR
12" [300mm]
DRAIN
PIPE
3/4"
[20mm]
3/4" [20mm]
12" [300mm] CAP
4" [100mm] LEGS ((2"x2"x1/4")
[50x50x8mm] WELDED TO TANK
FROM BF
LINE
& BASE PLATES
D
3/4" [20mm] TO FLOOR
DRAIN
GROUT
1/2" [15mm]
BOILER ROOM FLOOR
BASE PLATE (4"x4"x1/4"
[100x100x8mm])
ELEVATION
EXP. BOLT
(TYP)
NOTE: NORMAL CHEMICAL FEED SHALL BE WITH A PUMP
TYPE SYSTEM. SHOT TYPE SHALL BE USED ONLY FOR
BOILER LAYUP.
BOILER CHEMICAL FEED SYSTEM #
SHOT TYPE
NTS
DETAIL TITLE / BOILER
CHEMICAL FEED SYSTEM
SHOT TYPE
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD235011-08.DWG
AIR STORAGE TANK
OR DRYER
3/8" [10mm]
MANUAL VALVE
3/8" [10mm] O.D.
DRAIN TRAP
COPPER TUBING
FURNISHED WITH
RUN TO NEAREST
EQUIPMENT
FLOOR DRAIN
TYPICAL DRAIN FOR AIR
#
COMPRESSOR AND DRYER
NTS
DETAIL TITLE / TYPICAL
DRAIN FOR AIR
COMPRESSOR AND DRYER
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD235011-09.DWG
DETAIL TITLE / EQUIPMENT
DAEERATOR AND CONDENSATE STORAGE TANKS
ANCHORING-PACKAGED BOILER AND
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD235011-10.DWG
#
FRAME
BOILER BASE
REBAR
FOUNDATION
CONC.
PLATE
ANCHOR BOLT
BOILER FURNISHED
CONTRACTOR BASED ON
QUANTITY DETERMINED BY
ANCHOR BOLTS SIZE AND
(PLATE DESIGNED BY BOILER
FRAME MANUFACTURER)
PLATE WELDED TO BASE
FRAME
BOILER BASE
BEAMS
BY STEEL
SUPPORTED
FOR TANKS
ALTERNATE
PLATES
REINFORCEMENT
BOLTS
ELEVATION
REBAR
ANCHOR BOLT
FLOOR
PLAN
(TYPICAL)
BOLTS
ANCHOR
SADDLES
TANK
PIERS
SLOTTED HOLE
STEEL PLATE
BEAM
SADDLE
PIER
CONCRETE
SADDLE
TANK
BOLTED TO PIER
3/8" [10mm] THK.
EACH SIDE
SIZE +0.5" [15mm]
LENGTH = BOLT
NTS
DEAERATOR AND CONDENSATE STORAGE TANKS
EQUIPMENT ANCHORING - PACKAGED BOILER AND
ELEVATION
BOILER
PLAN
CONCRETE
FOUNDATION
CONC.
PROVIDE SLOTTED HOLES IN PLATES TO ALLOW THERMAL EXPANSION IF
RECOMMENDED BY BOILER MANUFACTURER
REFER TO SYMBOL AND SCHEDULE SHEETS FOR SEISMIC FORCE DESIGN INFORMATION
2.
NOTES:
1.
DETAIL TITLE / WATER
TUBE BOILER
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD235233-01.DWG
2" [50mm]
AREA FOR FUEL OIL AND
CONCRETE PAD
#
GAS FUEL TRAIN
FLOOR
D
NTS
WATER TUBE BOILER
FRONT ELEVATION
ATOMIZING MEDIA TRAIN
AREA FOR NATURAL
3/4"
[20mm]
HPS
BOILER ROOM
WINDBOX
GAS TRAIN
(PILOT)
IGNITER
AREA FOR
BOILER
ATTENUATOR
8'-0"
SOUND
MOTOR
[2438mm]
FORCED DRAFT FAN
STEAM DRUM
ANGLE VALVE
D
SOOTBLOWER
[1219mm]
4'-0" MAX.
BREECHING
ECONOMIZER
WITH ROTOR (WINDOWS
TO FACE UP AND DOWN)
TO BLOWOFF
LINE
3/4" [20mm]
DRAIN VALVES (TYPICAL)
FROM DRAIN VALVES
SWITCH 3' [914mm] MAX.
LOW WATER CUTOUT SHUNT
WHEEL
SOOTBLOWER WITH CHAIN
FEEDWATER CONTROLLER
WATER LEVEL SENSOR FOR
3/4" [20mm] DRAIN FROM
(0-300 PSIG (0-2000 kPa)
STEAM PRESSURE GAGE
CUTOFFS
HIGH STEAM PRESSURE
FROM PLATFORM
CONTROL VALVE OPERABLE
BREECHING
D
2" [50mm]
3/4"
[20mm]
WATER CUTOFF
AUXILIARY LOW
GAGE GLASS
WATER LEVEL
HPS
DRUM
SIGHT FLOW INDICATOR
MUD
D
D
D
D
WATER COLUMN WITH PROBES
D
ECONOMIZER
ECONOMIZER
VENT THRU ROOF
ACCESS PANEL
STACK
SAFETY VALVE
ECONOMIZER VALVES
STEAM DRUM
PLATFORM
NON-RETURN
3'-6"
STOP-CHECK
[1067mm]
VALVE
VENT
BURNER
12"
VALVE PLATFORM
HANDRAIL (TYP.)
[300mm]
C
L
LADDER
STEAM DRUM
BOILER
PLAN VIEW
STEAM LINE
TO HEADER
ACCESS PANEL
STACK
ECONOMIZER
ECONOMIZER
[25mm]
1"
VALVES
HANDRAIL
NON-RETURN
VALVE
STOP-CHECK
PLATFORM
VALVE
TOP OF BOILER CASING
STEAM DRUM
MANWAY
BREECHING
STEAM
DRUM
REAR OF
BOILER
LADDER
WATER DRUM
CONCRETE PAD
9'-0"
SUPPORT PLATFORMS
FROM FLOOR
[2743mm]
PLATFORM
NOTE:
BOILER ROOM
FLOOR
ELEVATION
ACCESS PLATFORM
#
ARRANGEMENT WATER TUBE BOILER
NTS
DETAIL TITLE / ACCESS
PLATFORM ARRANGEMENT
WATER TUBE BOILER
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD235233-02.DWG
DETAIL TITLE / FIRE
TUBE BOILER
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD235239-01.DWG
3/4" [20mm] TO
BLOWOFF LINE
2' [600mm] MAX.
UP AND DOWN)
WINDOWS TO FACE
#
FLOOR
NTS
FIRE TUBE BOILER
ELEVATION
BASE
ROOM
BOILER
MAX.
2' [600mm]
AND DOWN)
WINDOWS TO FACE UP
WITH ROTOR (ORIENT
CONCRETE
1/2"
[15mm]
WITH ROTOR (ORIENT
[25mm]
1"
VALVES)
BALL VALVES NOT PERMITTED (TYP)
SIGHTFLOW INDICATOR
[25mm]
1"
BURNER
LWCO AND GAGE GLASS DRAIN
(LOCATE WITHIN 3' [900mm] OF
LOW WATER CUTOFF SHUNT SWITCH
1 1/4" [32mm]
GAGE GLASS
UNIT LOW WATER CUTOFF
FEEDWATER LEVEL CONTROL
HIGH PRESSURE CUTOUTS
STEAM PRESSURE GAGE (0-300
PSIG [0-2000kPa])
SIGHTFLOW INDICATOR
TO BLOWOFF LINE
3/4" [20mm]
SHUNT SWITCH (LOCATE WITHIN 3'
[900mm] OF ALWCO DRAIN VALVE)
AUXILIARY LOW WATER CUTOFF
1 1/4" [32mm]
ALARM
ALARM HIGH WATER
CUTOFF LOW WATER
AUXILIARY LOW WATER
PLUGGED CROSS (TYPICAL)
1 1/4" [32mm]
BOILER
LADDER
BOILER
HANDRAIL
ACCESS PANEL
2'-6"
[0.8M]
STACK
PLATFORM
12"
[300mm]
BURNER
C
L
VENT
MANWAY
ECONOMIZER
NON-RETURN
SAFETY VALVE
STOP-CHECK VALVE
VENT THRU
PLAN VIEW
ROOF
HANDRAIL
STEAM LEAD
PLATFORM
NON-RETURN
1"
STOP-CHECK VALVE
[25mm]
BOILER
TOP OF BOILER
CASING
LADDER
BURNER
CONCRETE PAD
BOILER ROOM FLOOR
ELEVATION
NOTE: SUPPORT PLATFORM FROM FLOOR OR FROM BOILER IF BOILER MANUFACTURER
PROVIDES BOILER ATTACHMENTS AND APPROVES INSTALLATION.
#
ACCESS PLATFORM ARRANGEMENT
NTS
DETAIL TITLE / ACCESS
PLATFORM ARRANGEMENT
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD235239-02.DWG
[0-200kPa]
(ANNUNCIATOR)
1
0-160°F
VALVE
__PSIG [__kPa]
M
G
FILTER
G
G
TO OTHER
BOILERS
LPF(I)
FLOW
METER
STRAIGHTENING VANES AS REQUIRED
ROOF
1/2" [15mm] TO PRESSURE
GAGE (INSTRUMENTATION PANEL)
M-__
FROM GAS MAIN
FOR EMERGENCY BOILER
CONNECTION
1/2" [50mm]V
[0-70°C]
VENT CAP (TYP.)
CONNECTION TO OUTSIDE BUILDING
TYPICAL BURNER MAIN GAS &
IGNITER (PILOT) GAS PIPING
1" [25mm]
BY MFGR OF GAS FLOW METER
V
[0-200kPa]
MAY BE INSTALLED BY GAS
CO. ON SOME PROJECTS
BLDG. WALL
0-300 PSIG
[0-2000kPa]
3/8"
[10mm]V
0-300 PSIG
[0-2000kPa]
1" [25mm]
LOCKABLE
3/8" [10mm]V
3/4"
[20mm]
FILTER
SET PRESS.
PRV
1" [25mm]
3/8"
[10mm]V
LOW PRESS.
CUTOUT SW.
IGNITER (PILOT)
POCKET
FLEX. CONN.
LPG(I)
G/LPG(I)
FILTER
1" [25mm]
EV
4
SAFETY SHUT-OFF
VALVE
EARTHQUAKE AUTOMATIC
GAS SHUT-OFF VALVE
FOR EMERGENCY ONLY"
HIGH PRESSURE SW. SET
AT 2 PSIG [14kPa]
(ANNUNCIATOR)
3/8" V
[10mm]
SEE NOTE 1
3-WAY
SEE NOTE 2
SAFETY SHUT-OFF VALVES
1" [25mm] FROM PRV
G(I)
2
PRV
"LP IGNITER GAS IN USE
G
EV
EMERGENCY GAS
SEE NOTE 2
AUTOMATIC VENT VALVE
0-1.5xPRV
DIRT
3/4" [20mm]
V
INTERNAL RELIEF VENTS
3/4" [20mm]
V
OUT SIDE
GAS SHUT-OFF VALVE
1" [25mm] FROM PRV
0-30 PSIG
V
3
ENGINEERING NOTE:
EARTHQUAKE AUTOMATIC
LPF(I)
EV
MAIN GAS METERING & REGULATING AREA
CASING PILOT VENTS
V
M
V
LPG TANKS
VA FURNISHED
EMERGENCY FUEL FOR
IGNITIORS (PILOTS)
PRV - OUTLET PRESS:
3/4" [20mm]
5 PSIG [35kPa] INTERNAL RELIEF SET
AT 10 PSIG [70kPa] (NOTE: TWO
PRVS IN SERIES MAY BE NECESSARY)
SEE NOTE 2
DIRT POCKETS
AUTOMATIC
LOCKABLE
VENT VALVE
0-30 PSIG
3/8" [10mm]V
[0-200kPa]
0-1.5xMAX.
BURNER PRESS
0-1.5xPRV
1/2" [15mm]V
SET PRESS.
3/4"
[20mm]V
HIGH PRESS.
CUTOUT SW.
CUTOUT SW.
FILTER
PRV
SEE NOTE 1
BURNER
SAFETY SHUT-OFF VALVES
2.
SHOW VALVES FLANGED OR THREADED AS DICTATED BY PIPE SIZES.
3.
SHOW ALL PIPE SIZES.
4.
IN SOME LOCATIONS, IT MY BE NECESSARY TO PROVIDE "FIRM" GAS
DIRT
POCKET
1.
1/2-1 1/2 [15-40]
COMPANY.
DELETE "ENGINEERING NOTE" FROM PROJECT DRAWINGS.
6.
EARTHQUAKE VALVES REQUIRED IN SEISMIC AREAS ONLY. REFER TO
VA PROGRAM GUIDE, "NATURAL DISASTERS NON-STRUCTURAL
RESISTIVE DESIGN"
3.
#
SIZE AUTOMATIC VENT VALVES & VENT PIPING AS FOLLOWS:
FUEL SSO VALVE SIZE IN. [mm]
SERVICE TO THE IGNITERS. COORDINATE THIS WITH THE GAS
5.
PIPING SIZED BY BURNER MFGR. TO SUIT FLOW
REQUIREMENTS & AVAILABLE PRESSURE.
2.
VENT SIZE IN. [mm]
3/4 [20]
2 [50]
1 [25]
2 1/2-3 [65-75]
1 1/4 [32]
4-5 [100-125]
2 [50]
6 [150]
2 1/2 [65]
VENT HEADER SAME SIZE AS MAIN BURNER VENT.
NATURAL GAS AND LIQUEFIED PETROLEUM GAS - BURNER AND IGNITER FUEL STANDARD PIPING DIAGRAM
NTS
FUEL PLOW
CONTROL VALVE
NOTES:
PROJECT DESIGN AND FLOW DIAGRAM SHALL BE IN CONFORMANCE.
(IN. WC)
MAIN
G
ENGINEERING NOTES :
1.
LOW PRESS.
4' MAX.
[1219mm] MAX.
SD235239-03.DWG
CAD DETAIL NO.:
PRESS
HIGH PRESSURE SW.
SAFETY SHUT-OFF
DATE ISSUED: DECEMBER 2008
0-30 PSIG
EMERGENCY GAS
SCALE : NONE
0-1.5xLINE
EV
GAS AND LIQUEFIED PETROLEUM GAS - BURNER AND IGNITER FUEL
1/2" [50mm]V
SCREENED OUTLET OR
1/2" [50mm]V
___PSIG [___kPa]
2'
PRV - OUTLET PRESS:
STANDARD PIPING DIAGRAM
5 PSIG [35kPa] FOR FIRE TUBE BOILERS
10 PSIG [70kPa] FOR WATER TUBE BOILERS
(HIGHER PRESSURE MAY BE REQUIRED FOR
LOW-NOX BURNERS)
[610mm]
SET PRESSURE:
DETAIL TITLE / NATURAL
ENGINEERING NOTE:
THERMOMETER
UNDER CANOPY
PRESSURE
GAUGE
DDC
TEMPERATURE
SENSOR TO ECC
FLOW SWITCH
FLEXIBLE
CONNECTORS
IF REQUIRED
TT
FS
TEST PLUGS
TT
CHR
CHS
EVAPORATOR
AIR COOLED CHILLER - PIPING CONNECTIONS
#
NTS
DESIGNER NOTE:
1.
PROVIDE HEAT TRACING WHEN THE EXPOSED PIPING CARRYING CHILLED
WATER IS NOT MIXED WITH PROPYLENE CLYCOL. ALL VALVES, STRAINER,
FLOW SWITCH, FLEXIBLE CONNECTORS, ETC., SHALL BE WRAPPED WITH
ELECTRIC HEAT TRACE CABLE UNDER INSULATION.
2.
VERIFY NEED FOR FLEXIBLE CONNECTOR.
3.
PROVIDE ALUMINUM JACKETING ON ALL EXPOSED, INSULATED PIPING.
DETAIL TITLE / AIR
COOLED CHILLER -
PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD236400-01.DWG
DETAIL TITLE / WATER
PIPING CONNECTIONS
COOLED CHILLER -
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD236400-02.DWG
DRAIN
FLOOR
BOX TYP.
WATER
MARINE
#
EVAPORATOR END
EVAP
COND
VENT PIPE
SWITCH, TYP
FLOW
CHR
DEVICE
RELIEF
PRESSURE
(TYP.)
CONCRETE PAD
6" [150mm] HIGH
FS
PIPING CONNECTIONS
NTS
4.
5.
METHOD.
IS THE ONLY APPROVED JOINING
ABOVE 6", WELDED PIPE WITH FLANGES
MECHANICAL COUPLINGS ARE OPTIONAL.
FOR PIPING 6" AND BELOW,
VALVES CONTROLLED BY ECC.
VALVES ON BOTH CHWR & CWR.
PROVIDE MODULATING BUTTERFLY
DEVICES CONNECTED TO THE HEADER.
TO EQUAL OR EXCEED TOTAL AREA OF
ASHRAE STANDARD 15. HEADER SIZE
BUILDING IN ACCORDANCE WITH
DEVICES AND EXTEND TO EXTERIOR OF
TOWER
COLLECT VENT PIPES FROM ALL
BOTH CONDENSER AND EVAPORATOR.
PROVIDE MARINE WATER BOXES FOR
TO NEAREST FLOOR DRAIN.
DRAIN ALL LOW POINTS OF SYSTEMS
REFRIGERANT PRESSURE RELIEF
CHS
3.
2.
1.
NOTE:
FROM COOLING
(TYP)
PIPE HANGERS
TOWER
TO COOLING
VALVE, TYP.
BUTTERFLY CONTROL
WATER COOLED CHILLER -
DRAIN
FLOOR
SPECIFIED
ISOLATION AS
VIBRATION
CONDENSER END
EVAP
COND
(TYP.)
THERMOMETER
FS
CWS
CWR
WATER FLOW
MEASURING DEVICE
DETAIL TITLE / MULTIPLE
PIPING CONNECTIONS
CELL COOLING TOWER -
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD236500-01.DWG
LC
TYP.
1.
M
M
M
VFD
M
THE BASINS SHALL BE INTERCONNECTED BY FLUMES.
(TO TOWER)
WATER RETURN
CONDENSATE
PI
M
VFD
PIPING
EQUALIZING
#
M
VALVE N.C.
MIN. 2" BALL
MULTIPLE CELL COOLING TOWER PIPING CONNECTIONS
4.COORDINATE WITH ELECTRICAL ON BASIN HEATER.
3.SEE HVAC DESIGN MANUAL.
EACH FAN MOTOR.
2.PROVIDE ACCESS FOR ALL ELEVATED VALVES AND CONTROL DEVICES AND TO
GRADE PROVIDE A PLATFORM AROUND THE PERIMETER.
1.IF TOWER IS INSTALLED MORE THAN 5 FT [1500 MM] ABOVE THE ROOF OR
DESIGNERS NOTES:
NTS
BASIN TYP.
COLD WATER
3" OVERFLOW
WATER LEVEL
WITH TOWER TYP.
VALVE FURNISHING
MANUAL BALANCING
EACH CELL SHALL BE
VFD
PROVIDED WITH ITS OWN SUMP AND ANTI-CAVITATION PLATE.
NOTE:
TO PUMP SUCTION
(FROM TOWER)
WATER SUPPLY
CONDENSATE
SEWER
SANITARY
TO
VALVE
CONTROL
LEVEL
MODULATING
TO
INLET
SCREEN
BASIN TYP
HOT WATER
HS
TT
ECC
HS
EXHAUST AIR
PUMP
SUPPLY AIR
T
HEAT
TT
PROVIDE VA
ECC
RECOVERY
GRADE A
COIL
PREFILTER ON
UP STREAM SIDE
OF COIL
NOTES:
1.TO PREVENT ICING ON EXHAUST COIL MAINTAIN TEMPERATURE OF SOLUTION ENTERING
EXHAUST AIR COIL > 35° F BY MODULATING 3 WAY VALVE.
2.DISCONTINUE HEAT RECOVERY IF OUTSIDE AIR TEMPERATURE > BETWEEN 60 TO 80° F
(ADJUSTABLE)
3.FOR SYSTEMS WITH WINTER DESIGN CONDITIONS < 32° F, PROVIDE APPROPRIATE
PROPYLENE GLYCOL SOLUTION.
#
RUN AROUND HEAT RECOVERY COIL DETAIL
NTS
DETAIL TITLE / RUN
AROUND ENERGY RECOVERY DETAIL
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD237200-01.DWG
AIR INTAKE FOR MISSION
SD237300-01.DWG
CRITICAL FACILITIES, SEE
VA STANDARD DETAILS.
MIN CLEARANCE - 36"
4
5
6
7
8
9
10
11
12
13
14
15
16
17
COIL PULL DISTANCE
MINIMUM OUTSIDE
MINIMUM OUTSIDE
100% OUTSIDE
100% OUTSIDE
ITEM
OF FILTERS VAV
FILTERS CV
OF FILTERS CV
OF FILTERS CV
*
MIXING BOX
1
YES
YES
NO
NO
*
BLENDER SECTION
2
YES
YES
NO
NO
PRE-FILTERS (SIDE
ACCESS)
3
YES
YES
YES
YES
4
YES
YES
YES
YES
5
YES
YES
YES
YES
6
YES
YES
YES
YES
7
NO
NO
YES
YES
8
NO
NO
YES
YES
9
YES
YES
YES
YES
10
YES
YES
YES
YES
HUMIDIFIER
11
YES
YES
YES
YES
COOLING COIL
12
YES
YES
YES
YES
FAN
13
YES
YES
YES
YES
DIFFUSER PLATE
14
NO
NO
NO
YES
15
NO
NO
YES
YES
1.
ACCESS DOORS SHALL BE GASKETED AND HINGED TO OPEN
16
NO
NO
NO
YES
2.
MINIMUM ACCESS DOOR WIDTH SHALL BE 24" [600mm].
17
YES
YES
YES
YES
SMALL
AFTER FILTER (SIDE
ACCESS)
ACCESS SECTION,
MED-LARGE
*
*
*
*
*
*
*
*
HEAT RECOVERY COIL
ACCESS SECTION,
MED-LARGE
PRE-HEAT COIL
INSPECTION
SECTION,SMALL
ACCESS
SECTION,MED-LARGE
HEPA FILTER
DISCHARGE PLENUM
(VERTICAL)
AIR THREE BEDS OF AIR TWO BEDS AIR THREE BEDS
* AS REQUIRED
DETAIL TITLE / ACCESS
AIR HANDLING UNIT
INSPECTION SECTION,
AIR TWO BEDS
NOTE:
AGAINST FAN OPERATING PRESSURE TO PREVENT AIR LEAKAGE.
3.
4.
5.
ACCESS DOOR HEIGHT SHALL BE DETERMINED BY UNIT CASING
BUT NOT TO EXCEED 6'-0" [1800mm].
ACCESS DOORS ON FAN SUCTION SHALL OPEN OUTWARD.
ACCESS DOORS ON FAN DISCHARGE SIZE SHALL OPEN INWARD.
ACCESS DOOR SWING DETAIL FOR AIR HANDLING UNITS
#
NTS
DESIGNER'S NOTES:
1.
ALL AHU SECTIONS SHOWN IN THIS DETAIL MAY NOT BE APPLICABLE TO EACH AIR HANDLING UNIT INCLUDED IN THE PROJECT.
2.
SEE DETAIL FOR AIR INTAKE FOR MISSION CRITICAL FACILITIES.
3.
USING THIS FORMAT, DESIGNER SHALL DEVELOP A SIMILAR VIEW OF EACH AHU INCLUDED IN THE PROJECT.
SECTIONS SHALL BE APPLICATION SPECIFIC.
EACH AIR HANDLING UNIT.
SELECTION OF THE AHU
EACH VIEW SHALL INCLUDE OVERALL DIMENSIONS AND AVAILABLE ACCESS SPACE FOR
NOTE THAT THESE VIEWS DO NOT NEGATE THE NEED TO PROVIDE CROSS-SECTIONS/ELEVATIONS OF THE
MECHANICAL ROOMS, SHOWING EQUIPMENT SECTIONS AND DETAILS OF EACH AHU.
CAD DETAIL NO.:
3
DATE ISSUED: DECEMBER 2008
2
SCALE : NONE
1
DOOR SWING DETAIL FOR AIR HANDLING UNITS
RETURN AIR INTAKE.
SPRING LOADED VACUUM BREAKER
VB
VENTED TO ATMOSPHERE TYPICAL
ON BOTH THE STEAM SUPPLY
AND THE CONDENSATE LINES.
MPS
(30 PSIG)
ON/OFF CONTROL VALVE
INTEGRAL FACE AND
BYPASS DAMPER
VB
FLEXIBLE CONNECTOR INSTALLED PARALLEL
TO COIL HEADER AND AS CLOSE AS POSSIBLE
TO COIL CONDENSATE CONNECTION.
MPR
FLOAT AND THERMOSTATIC TRAP ASSEMBLY
INTEGRAL FACE
#
AND BYPASS STEAM COIL DETAIL
NTS
DESIGNER'S NOTE:
1. USE THIS DETAIL FOR UNIT MOUNTED PREHEAT COIL.
DETAIL TITLE / INTEGRAL
FACE AND BYPASS STEAM COIL
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD237300-02.DWG
FAN COIL SEQUENCE OF OPERATION (COOLING ONLY)
1. FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE DCC.
2. MODULATE V-1 TO MAINTAIN SPACE SET POINT AND FAN SHALL CYCLE W/TEMPERATURE.
3. ALARM IF SPACE TEMPERATURE OUTSIDE OF RANGES.
COOLING COIL
RA
FAN
FILTER
V-1
CHR
HS
SST
CHS
PC
SHARED ARRANGEMENT IF FEASIBLE
TT
T-1
ROOM TEMPERATURE SENSOR, WALL MOUNTED
48" [1200mm] AFF.
#
COOLING ONLY FAN COIL UNIT CONTROLS
NTS
DESIGNER'S NOTE
1. MODIFY THE DETAIL IF DCC IS NOT USED.
DETAIL TITLE / COOLING
ONLY FAN COIL UNIT CONTROLS
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD238200-01.DWG
FAN COIL SEQUENCE OF OPERATION (HEATING ONLY)
1. FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE DCC.
2. MODULATE V-1 TO MAINTAIN SPACE SET POINT AND FAN SHALL CYCLE W/TEMPERATURE.
3. ALARM IF SPACE TEMPERATURE OUTSIDE OF RANGES.
HEATING COIL
RA
FAN
FILTER
V-1
HWR
HS
ZC
SST
HWS
PC
TT
SHARED ARRANGEMENT IF FEASIBLE
T-1
ROOM TEMPERATURE SENSOR, WALL MOUNTED
48" [1200mm] AFF.
#
HEATING ONLY FAN COIL UNIT CONTROLS
NTS
DESIGNER'S NOTE
MODIFY DETAIL IF DCC IS NOT USED.
DETAIL TITLE / HEATING
ONLY FAN COIL UNIT CONTROLS
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD238200-02.DWG
FAN COIL SEQUENCE OF OPERATION (PATIENT ROOMS)
FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE ECC.
FAN SHALL
RUN CONTINUOUSLY. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL
BE GENERATED IN THE EVENT THE UNIT FAILS TO RUN.
THE ADJUSTABLE ROOM TEMP
SET POINT WILL BE 70°-75° WITH 0.5° HEATING/COOLING OFFSETS.
VALVE V-1 & V-2
WILL NOT BE OPEN SIMULTANEOUSLY. ROOM OCCUPANT WILL HAVE ABILITY OF ADJUSTING
ROOM TEMPERATURE BETWEEN 70°-75°.
FAN COIL SEQUENCE OF OPERATION (NONPATIENT ROOMS)
FAN COIL SHALL OPERATE ON A SCHEDULE AS SET BY ECC. FAN SHALL RUN CONTINUOUSLY
IN OCCUPIED MODE. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE
GENERATED IN THE EVENT THE UNIT FAILS TO RUN BETWEEN THE RANGE OF 70°-75° SPACE
TEMPERATURE BOTH V-1 & V-2 SHALL BE CLOSED. UPON RISE IN TEMPERATURE ABOVE 75°
V-2 SHALL MODULATE OPEN TO MAINTAIN 75° F. UPON FALL IN TEMPERATURE BELOW 70° F.
HEATING VALVE V-1 SHALL MODULATE TO OPEN TO MAINTAIN 70° F.
HEATING COIL
COOLING COIL
FAN
RA
CS
FILTER
HS
V-1
TT
SST
V-2
HWR
CHR
HWS
CHS
PC
T
T-1
ROOM TEMPERATURE SENSOR WITH SPACE ADJUSTABLE WALL MOUNTED
48" [1200mm] AFF.
#
FOUR PIPE FAN COIL UNIT CONTROLS
NTS
DETAIL TITLE / FOUR
PIPE FAN COIL UNIT CONTROLS
SCALE : NONE
DATE ISSUED : DECEMBER 2008
CADD DETAIL NO. :
SD238200-03.DWG
HOT WATER CABINET UNIT HEATER SEQUENCE
1.
CABINET HEATER SHALL OPERATE ON A SCHEDULE AS SET BY THE ECC.
FAN
STATUS SHALL BE MONITORED AND AN ALARM MESSAGE GENERATED IN THE EVENT THE
UNIT FAILS TO RUN. THE ROOM TEMP SETPOINT WILL BE 74° (ADJ). THE HOT WATER
VALVE WILL BE ENABLED AS REQUIRED TO MAINTAIN SPACE TEMP SETPOINT. HI/LO/OFF
SWITCH WILL ALLOW LOCAL FAN SPEED ADJUSTMENT.
CABINET UNIT
HEATER
HEATING COIL
FAN
FILTER
120V
STT
HS
HI
LO
EMCS
OFF
ENABLE
PC
FAN MOTOR
V-1
HWR
T
HWS
T-1
ROOM THERMOSTAT WALL MTD OR RETURN AIR MTD
48" [1200mm] AFF.
#
HOT WATER CABINET UNIT CONTROLS
NTS
DESIGNER'S NOTES:
1.
CONNECT TO ECC NETWORK IS OPTIONAL.
2.
PROVIDE NON-DDC CLOSED LOOP AUTOMATIC TEMPERATURE CONTROLS FOR THE HOT WATER
CABINET UNIT HEATER.
COORDINATE THE INTERFACE, IF ANY, WITH THE DDC SYSTEM FOR
APPLICATIONS SUCH AS ALARM INDICATION WITH PROJECT SCOPE OF WORK.
3.
PROVIDE A STEP CONTROL FOR NON-CRITICAL APPLICATIONS.
WHEN TEMPERATURE FALLS
BELOW SET POINT, THE CABINET UNIT HEATER SHALL BE ENERGIZED AND THE
TWO-POSITION, TWO-WAY VALVE SHALL OPEN.
DETAIL TITLE / HOT
WATER CABINET UNIT
CONTROLS
SCALE : NONE
DATE ISSUED :DECEMBER 2008
CADD DETAIL NO. :
SD238200-04.DWG
RUNOUT & INTERCONNECTING
PIPING. PROVIDE DIELECTRIC
FITTINGS AS REQUIRED. CIRCUIT TO
COMPLY WITH SPECIFIED CAPACITY
& PRESSURE DROP. (TYP.)
HWR
HWS
NOTE:
1.
HEATING ONLY PANELS
MINIMUM FLOW SHALL BE NO
LESS THAN 0.5 GPM [1.9 LPM]
HYDRONIC RADIANT CEILING PANELS #
PIPING CONNECTIONS
NTS
DETAIL TITLE / HYDRONIC
RADIANT CEILING PANELS -
PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238200-05.DWG
AUTOMATIC FLOW
CONTROL VALVE
MV
R
TE
WA
T
N
HO TUR
R
E
TE
R
WA
T
Y
HO PPL
U
S
UNIT HEATER
NOTE: UNIT MOUNTED
THERMOSTAT SHALL
MAINTAIN SPACE
TEMPERATURE BY
CYCLING
TYPICAL CONNECTIONS TO
HORIZONTAL HOT WATER UNIT HEATER
R
TE
WA
T
N
HO TUR
R
E
TE
R
WA
T
Y
HO PPL
U
S
AUTOMATIC FLOW
CONTROL VALVE
AIR VENT
TEST PLUG,
UNIT HEATER
MV
TYP.
SHUTOFF BALL
VALVE, TYP.
WYE STRAINER,
TYP.
TYPICAL CONNECTIONS TO
VERTICAL HOT WATER UNIT HEATER
UNIT HEATERS (HOT WATER) #
PIPING CONNECTIONS
NTS
DETAIL TITLE / UNIT HEATERS (HOT WATER) PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238200-06.DWG
STEAM SUPPLY
STEAM CONTROL
VALVE, 2
STEAM CONDENSATE
[150mm]
6" MIN.
UNIT HEATER
BUCKET TRAP
[300mm]
INVERTED
12" MIN.
POSITION
SCALE POCKET
RETURN
PIPING CONNECTIONS TO HORIZONTAL TYPE STEAM UNIT HEATER
STEAM CONTROL VALVE
BUCKET TRAP
[150mm]
INVERTED
6" MIN.
12" MIN.
STEAM SUPPLY
[300mm]
UNIT
HEATER
STEAM
CONDENSATE
SCALE POCKET
RETURN
PIPING CONNECTIONS TO VERTICAL TYPE STEAM UNIT HEATER
NOTES:
1.UNIT MOUNTED THERMOSTAT SHALL MAINTAIN SPACE TEMPERATURE
BY CYCLING THE FAN. THE CONTROL VALVE SHALL BE INTERLOCK WITH THE FAN.
UNIT HEATERS (STEAM)
#
PIPING CONNECTIONS
NTS
DETAIL TITLE / UNIT HEATERS (STEAM)
PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238200-07.DWG
CABINET
HEATING ELEMENT
CONTROL VALVE
SEE SEQUENCE
12" MIN.
OF CONTROL
SHUTOFF VALVE
FLOOR
LPS
PIPE SLEEVE
THERMOSTATIC TRAP
LPR
ASSEMBLY
#
FLOOR PLATE
CONVECTOR-STEAM PIPING CONNECTION
NTS
DESIGNER'S NOTE:
USE THIS DETAIL WHEN THE CONVECTOR (OR STEAM RADIATOR) IS USED IN
CONJUNCTION WITH AN AIR TERMINAL UNIT TO SERVE AN OCCUPY SPACE, REPLACE
RADIATOR VALVE WITH A STEAM CONTROL VALVE AND CONTROL SPACE WITH COMMON
THERMOSTAT.
DETAIL TITLE / CONVECTOR-STEAM
PIPING CONNECTION
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238200-08.DWG
GASKET ALL AROUND WHEN MOUNTED
HANGER ROD SUPPORTS
AGAINST CEILING AND/OR WALL
SECURE TO STRUCTURE
ABOVE (TYP)
COIL
FINISHED
CEILING
FAN
4-WAY DEFLECTION
SUPPLY AIR GRILLE
DRAIN PAN & PIPE CONNECTION
RETURN AIR
GRILLE & FILTER
ACCESS
DOOR
&
FINISHED
CEILING
GRILLS
NOTE:
UNLESS OTHERWISE NOTED,
ALL UNITS SHALL BE MOUNTED
AGAINST FINISHED CEILING.
#
FAN COIL UNIT - HORIZONTAL EXPOSED
NTS
DETAIL TITLE / FAN
COIL UNIT - HORIZONTAL EXPOSED
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238200-09.DWG
HANGER ROD
SUPPORTS SECURE
TO STRUCTURE
ABOVE WITH
DUCT SIZE TO SUIT
SUPPLY AIR GRILLE
COIL
SPRING ISOLATORS
(TYP)
6" PLENUM
[150mm]
FINISHED
CEILING
FAN
ACCESS DOOR
4-WAY DEFLECTION
SUPPLY AIR GRILLE
304 SS DRAIN
PAN & PIPE
CONNECTION
FILTER
FOR SOFFIT SEE
ARCH. DRAWINGS
ACCESS DOOR
RETURN AIR
SIZED TO ALLOW
GRILLE
INSULATE FULL
ACCESS TO
LENGTH OF THE
ELECTRICAL AND
CONDENSATE DRAIN
COIL CONNECTIONS
PIPING
AND ALLOW FOR
TERMINATE OVERFLOW
DRAIN ABOVE
LAVATORY, SINK, OR
MOTOR/FAN
ASSEMBLY
REMOVAL
FLOOR DRAIN
NOTES:
SIX INCH [150mm]
1.
PLENUM AS SHOWN SHALL BE SUPPLIED BY MANUFACTURER OF
FAN COIL UNIT.
2.
SEE DETAIL FOR SUPPLY & RETURN PIPING CONNECTIONS.
PROVIDE ACCESS FOR FILTER REMOVAL.
3.
4.
SEE FAN COIL UNIT SCHEDULE FOR PIPE SIZES.
SUPPLY & RETURN GRILLES SHALL BE SIZED TO SUIT CONNECTIONS ON FAN COIL UNIT.
DUCTWORK SHALL SUIT GRILLES AND FAN COIL UNIT FURNISHED.
#
FAN COIL UNIT - HORIZONTAL CONCEALED
NTS
DETAIL TITLE / FAN
COIL UNIT - HORIZONTAL CONCEALED
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238200-10.DWG
PIPE HANGER SHALL SUPPORT
REDUCER, IF REQUIRED
PIPING INDEPENDENT OF COIL
AIR VENT
MV
WHEN COIL
IS NOT
TEST PLUG
MV
MV
FE
(TYP.)
TI
SELF-VENTING
TEMPERATURE
INDICATION TO ECC
WATER COIL
SEE CONTROL
DIAGRAM
DRAIN
SINGLE COIL
DRAIN WHEN COIL IS
NOT SELF-DRAINING
REDUCER, IF REQUIRED
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
MV
AIR VENT
MV
TEST PLUG
FE
(TYP.)
MV
TI
WHEN COIL
FLOW ELEMENT
IS NOT
SELF-VENTING
WATER COIL
MV
WATER COIL
DRAIN
DRAIN WHEN COIL IS
NOT SELF-DRAINING
DOUBLE COIL
NOTE:
1.
WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST
2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR
4" [100mm]∅ PIPE & SMALLER. TYPE "H-P" FOR 5" [125mm]∅ PIPE & LARGER.
2.
PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE
SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE
SERVICING OF FILTERS, VALES, OR EQUIPMENT.
3.
THE FLOW ELEMENT MAY BE INSTALLED IN THE SUPPLY PIPING IF THE REQUIRED
MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE OBTAINED IN THE
RETURN PIPING.
#
WATER COILS - PIPING CONNECTIONS
NTS
DESIGNER'S NOTE:
BALANCING VALUES MAY BE OMITTED IF REVERSE PIPING PROVIDED.
DETAIL TITLE / WATER
COILS - PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238216-01.DWG
DETAIL TITLE / PREHEAT COIL (HOT WATER) - PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238216-02.DWG
#
COIL
PREHEAT
AV
FEET PER SECOND
TUBE WATER VELOCITY OF 3.0
SIZE AND SELECT COIL FOR
PARALLEL FLOW AND MINIMUM
TAPPINGS
NOTE:
SHUTOFF VALVE
VALVE
BYPASS
MANUAL
HWS/GHS
HWR/GHR
TO ALL COIL HEADER 1
CONNECTIONS
FULL SIZE
DEVICE
BALANCING
VALVE
MODULATING CONTROL
1.COORDINATE WITH HVAC DESIGN MANUAL.
DESIGNERS NOTE:
NTS
PREHEAT COIL (HOT WATER) - PIPING CONNECTIONS
AIR
AV
INLINE PUMP
AUTO. AIR VENT TO DRAIN, TYP
MANUAL BYPASS VALVE
DETAIL TITLE / STEAM
COIL - PIPING CONNECTIONS
SCALE : NONE
DATE ISSUED: DECEMBER 2008
CAD DETAIL NO.:
SD238216-03.DWG
SUPPORT PIPING
SCALE POCKET
RETURN
STEAM CONDENSATE
NO. 4
SEE NOTE
VA AKE
E
BR
CK
CHE
m]
15mCUUM
[
A
"
1/2 LVE V R
IF REQUIRED
INCREASER,
IF REQUIRED
REDUCER,
GAGE
PRESSURE
STEAM SUPPLY
SWING JOINTS TO ALLOW FOR THE VIBRATION.
CONNECTIONS TO COIL SHALL BE INSTALLED WITH
VIBRATION ISOLATOR UNITS, THE RUNOUT PIPING FOR
WHEN COIL IS INCLUDED IN CASING MOUNTED ON
PIPES FROM OPPOSITE ENDS.
END. REHEAT COIL MAY HAVE SUPPLY & RETURN
5. SUPPLY & RETURN PIPES ARE SHOWN FROM SAME
5,000 LBS/HR [2400 KG/HR] OR GREATER.
TWO TRAPS REQUIRED WHEN CONDENSATE LOAD IS
4. TWO TRAP ASSEMBLIES IN PARALLEL ARE SHOWN.
SEPARATE VACUUM BREAKER FOR EACH COIL.
BANK OF TWO OR MORE HIGH. ALSO PROVIDE
3. TRAP EACH COIL SEPARATELY WHEN INSTALLED IN A
DOORS OR PANELS; NEITHER SHALL IT BLOCK THE
SERVICING OF FILTERS, VALVES, OR EQUIPMENT.
IT WILL NOT BLOCK THE SWING OR USE OF ACCESS
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT
1.
NOTE:
NTS
STEAM COIL - PIPING CONNECTIONS
DISCHARGE SIDE OF TRAP SET. CHANGE F & T TRAP SET TO SHOW PIPING LOCATION CONNECTION.
FOR VACUUM RETURN SYSTEMS CONNECT 1/2" [15mm] CHECK VALVE VACUUM BREAKER INTO
DESIGNER'S NOTE:
#
TAPPING
FULL SIZE
OUTLET
CONDENSATE
12"MIN.
FOOT TO
[300mm]
1/4" [8mm] PER
PITCH COIL DOWN
COIL (TYP.)
INDEPENDENT OF
6"MIN.
PIPE HANGER SHALL
[150mm]