United States A T B C B AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES CHECKLIST FOR BUILDINGS AND FACILITIES United States Architectural and Transportation Barriers Compliance Board 1331 F Street N.W., Suite 1000 Washington, D.C. 20004-1111 Notice This checklist has been prepared to assist individuals and entities with rights or duties under Title II, and Title III of the Americans with Disabilities Act (ADA) in applying the requirements of the Americans with Disabilities Act Accessibility Guidelines (ADAAG) to buildings and facilities subject to the law. The checklist presents information in summary form on the Department of Transportation (DOT) and the Department of Justice (DOJ) regulations implementing the ADA. The checklist must be used with the DOT and DOJ regulations and ADAAG to ensure accuracy. This checklist is intended for technical assistance purposes only. Individuals who use this checklist should be aware that the Department of Justice and the Department of Transportation, not the U.S. Architectural and Transportation Barriers Compliance Board (Access Board), are responsible for the enforcement of Titles II and III of the ADA. Use of this checklist does not constitute a determination of your legal rights or responsibilities under the ADA, and it is not binding on the Department of Justice, Department of Transportation, or the Access Board. Use of this checklist is voluntary. Individuals who use this checklist are not required to send the survey forms to DOJ, DOT, or the Access Board. While ADAAG may be amended in the future, this checklist is based on ADAAG as published on July 26, 1991 (sections 1 through 4.35 and special application sections 5 through 9) and September 6, 1991 (section 10). See 56 FR 35408 (July 26, 1991) and 56 FR 45500 (September 6, 1991) as corrected at 57 FR 1393 (January 14, 1992). Americans with Disabilities Act Accessibility Guidelines Checklist for Buildings and Facilities PREPARED BY: U.S. Architectural & Transportation Barriers Compliance Board 1331 F Street N.W., Suite 1000 Washington, D.C. 20004-1111 1-800-USA-ABLE October 1992 Table of Contents INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 1 Purpose New Construction Alterations Historic Preservation Barrier Removal in Existing Facilities Key Stations What Are "Places of Public Accommodation" and "Commercial Facilities" How the Checklist is Organized to Assist You How Differences in Requirements for New Construction, Alterations, and Historic Properties are Addressed SURVEY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . .Page 6 Approach to Surveying Preparing to Survey Step 1: Identify the Type of Facility or Building Use Step 2: Determine Minimum Requirements Step 3: Copy and Assemble the Survey Forms Step 4: Survey BUILDING IDENTIFICATION AND DATA SHEET MINIMUM REQUIREMENTS AND SUMMARY SHEETS A: B: C: D: E: F: G: H: I: J: Parking and Passenger Loading Zones Site Accessible Routes and Elements Entrances Building Accessible Route Rooms and Spaces (Including Assembly Areas and Dressing and Fitting Rooms) Toilet Rooms and Bathrooms Special Features Ä Signage, Alarms, Detectable Warnings, and Automated Teller Machines (ATMs) Special Types of Facilities Accessible Buildings Ä Additions and Alterations Accessible Buildings Ä Historic Preservation TECHNICAL REQUIREMENTS SURVEY FORMS General Requirements Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Survey Form 1: Parking Form 2: Passenger Loading Zone Form 3: Exterior Accessible Routes Form 4: Curb Ramps Form 5: Drinking Fountains Form 6: Telephones Form 7: Ramps Form 8: Stairs Form 9: Platform Lifts Form 10: Entrances and Exits (Areas of Rescue Assistance) Form 11: Doors and Gates Form 12: Building Lobbies and Corridors (Interior Accessible Route) Form 13: Elevators Form 14: Rooms and Spaces Form 15: Assembly Areas Form 16: Toilet Rooms and Bathrooms Form 17: Bathtubs and Showers Form 18: Dressing and Fitting Rooms Form 19: Signage Form 20: Alarms Form 21: Detectable Warnings Form 22: Automated Teller Machines (ATMs) Special Facility Types Survey Survey Survey Survey Survey Form Form Form Form Form Survey Form Survey Form Survey Form Survey Form 23: 24: 25: 26: 27: Restaurants and Cafeterias Medical Care Facilities Mercantile Facilities Libraries Transient Lodging - Hotels, Motels, Inns, Boarding Houses, Dormitories, and Similar Places 28: Transient Lodging in Homeless Shelters, Halfway Houses, Transient Group Homes, and Other Social Services Establishments 29a: Transportation Facilities - Bus Stops 29b: Transportation Facilities - Fixed Facilities, Terminals and Stations 29c: Transportation Facilities - Airports INTRODUCTION Purpose The Americans with Disabilities Act (ADA), signed by President Bush on July 26, 1990, is landmark legislation to extend civil rights protection to people with disabilities. The ADA prohibits discrimination on the basis of disability in employment, State and local government services, public transportation, public accommodations, commercial facilities, and telecommunications. The ADA required the U.S. Architectural and Transportation Barriers Compliance Board (Access Board) to supplement its Minimum Guidelines and Requirements for Accessible Design to serve as the basis for regulations to be issued by the Department of Justice and the Department of Transportation under Title II and Title III of the Act. On July 26, 1991, the Access Board published its ADA Accessibility Guidelines for Buildings and Facilities (ADAAG). These guidelines were amended and supplemented with provisions for transportation facilities on September 6, 1991. ADAAG is applicable to buildings and facilities covered by Title II and Title III of the ADA to the extent required by regulations issued by the Department of Justice and the Department of Transportation under the ADA. The purpose of this checklist is to enable people to survey places of public accommodation, commercial facilities, and transportation facilities for compliance with the new construction and alterations requirements of Title II, Subtitle B (Public Transportation) and Title III of the ADA. It can also be used to identify barriers in existing buildings. No special training is needed to use this checklist. It can be used by businesses, building owners and managers, State and local governments, design professionals, or concerned citizens. The checklist must be used in conjunction with the Department of Justice's regulations in 28 CFR Part 36, the Department of Transportation's regulations in 49 CFR Part 37, and the Americans with Disabilities Act Accessibility Guidelines which are reprinted in the appendices to those regulations. Appendix A of the Department of Transportation's regulations includes section 10 of ADAAG, which specifies additional provisions for transportation facilities. Buildings and facilities constructed or altered by, on behalf of, or for the use of State and local governments covered by Title II, Subtitle A of the ADA, (other than transportation facilities covered by the Department of Transportation's regulation), are allowed by 28 CFR 35.151 to follow either ADAAG without the elevator exception or the Uniform Federal Accessibility Standards (UFAS). A similar checklist, the UFAS Accessibility Checklist, is available from the Access Board. New Construction Places of public accommodation and commercial facilities covered by Title III of the ADA are required by 28 CFR 36.401 and 36.406 to comply with ADAAG if the facilities are designed and constructed for first occupancy after January 26, 1993. This requirement applies only if: (1) the last application for a building permit or permit extension for the facility is certified to be completed by a State, county, or local government after January 26, 1992 and (2) the first certificate of occupancy for the facility is issued after January 26, 1993. Full compliance with the new construction requirements is not required where an entity can demonstrate that it is structurally impracticable. The exception for structural impracticability, a very narrow one, is discussed in 28 CFR 36.401(c) and ADAAG 4.1.1(5)(a). Other exceptions for certain temporary structures, specific building areas and features (including elevators) are discussed in ADAAG 4.1.1(4), 4.1.1(5)(b) and 4.1.3(5) and, where applicable, on the Minimum Requirements Summary Sheets or the Technical Requirements Survey Forms. Transportation facilities covered by Title II, Subtitle B of the ADA are required by 49 CFR 37.9 and 37.41 to comply with ADAAG, including section 10, if a notice to proceed is issued after January 25, 1992, for bus, light rail or rapid rail facilities; or after October 7, 1991, for intercity or commuter rail stations. 1 Employee Work Areas Areas that are used only by employees as work areas must be designed and constructed so that individuals with disabilities can approach, enter, and exit the areas as required in ADAAG 4.1.1(3). The guidelines do not require that any areas used only by employees as work areas be constructed to permit maneuvering within the work area or be constructed or equipped (i.e., with racks or shelves) to be accessible. Equivalent Facilitation Departures from the ADAAG technical and scoping provisions are permitted where the alternative designs and technologies used will provide substantially equivalent or greater access to and usability of the facility. See ADAAG 2.2 and other sections referenced in Appendix A2.2 of ADAAG for specific examples of equivalent facilitation. For transportation facilities covered by Title II, Subtitle B of the ADA, a determination of equivalent facilitation must be made by the Administrator of the Federal Transit Administration or the Federal Railroad Administration, as applicable. The specific procedure for applying for such a determination is included in 49 CFR 37.9(d). Alterations Alterations to a place of public accommodation or commercial facility covered by Title III of the ADA that are undertaken after January 26, 1992 are required by 28 CFR 36.402 and 36.406 to be done in a manner so as to ensure that, to the maximum extent feasible, the altered portions of the facility comply with ADAAG. For transportation facilities covered by Title II, Subtitle B of the ADA, 49 CFR 37.9 and 37.4 require that alterations must follow ADAAG if a notice to proceed or work order is issued after January 25, 1992, for bus, light or rapid rail facilities; or after October 7, 1991, for intercity or commuter rail stations. In general, alterations of specific elements or portions of a facility must be completed in compliance with the requirements for new construction. However, full compliance with the alterations requirements is not required where it is technically infeasible. The exception for technical infeasibility is discussed in ADAAG 4.1.6(1)(j). This and other special provisions and exceptions for alterations contained in ADAAG 4.1.6 are discussed on the Minimum Requirements Summary Sheet I: Accessible Buildings - Additions and Alterations. Additional special provisions and exceptions for alterations for special facility types are found in ADAAG 5, 6, 7, 9 and 10 and on the Technical Requirements Survey Forms for the special facility types. If an alteration affects or could affect the usability of or access to an area of a facility that contains a "primary function," an accessible path of travel must be provided to the altered area. In addition, restrooms, telephones, and drinking fountains serving the altered area must also be made accessible to the extent that the cost is not "disproportionate" to the cost of the overall alteration. Disproportionality is defined in 28 CFR 36.403 (f) and 49 CFR 37.43(e) as a sum not to exceed 20% of the cost of the alteration to the primary function area. Historic Preservation Alterations to a qualified historic building or facility must comply with ADAAG unless it is determined in accordance with procedures described in ADAAG 4.1.7(2) that compliance with certain requirements would threaten or destroy the historic significance of the building or facility. In such a case, alternative requirements may be used. The alternative requirements are discussed in 28 CFR 36.405 and ADAAG 4.1.7(3) and on the Minimum Requirements Summary Sheet J: Accessible Buildings - Historic Preservation. Barrier Removal in Existing Facilities Public accommodations covered by Title III of the ADA must remove architectural barriers in existing facilities, including communication barriers that are structural in nature, where such removal is readily achievable. The ADA 2 generally defines readily achievable as "easily accomplishable and able to be carried out without much difficulty or expense." The requirement to remove architectural barriers where readily achievable is discussed in 28 CFR 36.304. Measures taken to comply with readily achievable barrier removal must comply with ADAAG unless it would not be readily achievable. Then, other readily achievable measures that do not fully comply with ADAAG may be taken. However, no measure shall be taken that poses a significant risk to the health or safety of individuals with disabilities or others. Key Stations Existing rapid rail, light rail, and commuter rail transportation systems covered by Title II, Subtitle B of the ADA must identify "key stations", in accordance with requirements of 49 CFR 37.47 and 37.51. Generally, "key stations" must comply with ADAAG 10.3.2. Under some conditions, previously altered elements which conform to UFAS (when done by a public entity) or ANSI A117.1-1980 (when done by a private entity without Federal funds) may meet the key station requirements. This "grandfather" provision applies only to "key stations" and is discussed in 49 CFR 37.9(b) and the corresponding explanatory material in Appendix D to the Department of Transportation's regulations. All existing intercity rail stations must comply with ADAAG 10.3.2. The timeframes for making "key stations" and existing intercity rail stations accessible are specified in the Department of Transportation's regulations at 49 CFR 37.47, 37.51, and 37.55. What Are "Places of Public Accommodation" and "Commercial Facilities"? ADAAG applies to new construction and alterations of "places of public accommodation and commercial facilities." A "place of public accommodation" is a facility, operated by a private entity, whose operations affect commerce and which falls within at least one of the twelve categories listed below: 1. An inn, hotel, motel, or other place of lodging, except for an establishment located within a building that contains not more than five rooms for rent or hire and that is actually occupied by the proprietor of the establishment as the residence of the proprietor; 2. A restaurant, bar or other establishment serving food or drink; 3. A motion picture house, theater, concert hall, stadium, or other place of exhibition or entertainment; 4. An auditorium, convention center, lecture hall, or other place of public gathering; 5. A bakery, grocery store, clothing store, hardware store, shopping center, or other sales or rental establishment; 6. A laundromat, dry cleaner, bank, barber shop, beauty shop, travel service, shoe repair service, funeral parlor, gas station, office of an accountant or lawyer, pharmacy, insurance office, professional office of a health care provider, hospital, or other service establishment; 7. A terminal, depot, or other station used for specified public transportation; 8. A museum, library, gallery, or other place of public display or collection; 9. A park, zoo, amusement park, or other place of recreation; 10. A nursery, elementary, secondary, undergraduate, or postgraduate private school, or other place of education; 3 11. A day care center, senior citizen center, homeless shelter, food bank, adoption agency, or other social service center establishment; 12. A gymnasium, health spa, bowling alley, golf course, or other place of exercise or recreation. "Commercial facilities" are facilities whose operations will affect commerce and that are intended for nonresidential use by a private entity (e.g., factories and warehouses). "Commercial facilities" do not include facilities that are covered or expressly exempted from coverage under the Fair Housing Act of 1968, as amended; aircraft; and certain railroad equipment listed in 28 CFR 36.104. How the Checklist is Organized to Assist You This checklist presents the minimum scoping and technical requirements contained in ADAAG for newly constructed facilities in the logical progression of traveling to and through a building. The Minimum Requirements Summary Sheets tell you what to survey, such as an accessible route, an entry, or a bathroom. The Technical Requirements Survey Forms give you the specific features those elements must have. There are 29 survey forms to represent elements on the site and in the building. Many of ADAAG's general requirements are repeated on different forms because they apply to more than one element. Some survey forms may refer you to others for detailed provisions. In general, the Minimum Requirements Summary Sheets and the Technical Requirements Survey Forms contain the ADAAG requirements for new construction. In alterations one must first attempt to meet the requirements for new construction unless it is technically infeasible or special provisions apply. The survey process moves through a parallel structure in three steps using the following sheets and forms: Step 1: Building/Facility Identification and Data Sheet Step 2: Minimum Requirements Summary Sheets Sheet Sheet Sheet Sheet Sheet A: B: C: D: E: Sheet F: Sheet G: Sheet H: Sheet I: Sheet J: Step 3: Parking and Passenger Loading Zones Site Accessible Routes and Elements Entrances Building Accessible Route Rooms and Spaces (Including Assembly Areas and Dressing and Fitting Rooms) Toilet Rooms and Bathrooms Special Features - Signage, Alarms, Detectable Warnings, and Automated Teller Machines (ATMs) Special Types of Facilities Accessible Buildings - Additions and Alterations Accessible Buildings - Historic Preservation Technical Requirements Survey Forms Form Form Form Form Form Form Form 1: 2: 3: 4: 5: 6: 7: Parking Passenger Loading Zones Exterior Accessible Routes Curb Ramps Drinking Fountains Telephones Ramps Form 8: Stairs 4 Form Form Form Form 9: 10: 11: 12: Form Form Form Form Form Form Form Form Form Form 13: 14: 15: 16: 17: 18: 19: 20: 21: 22: Platform Lifts Entrances and Exits (Areas of Rescue Assistance) Doors and Gates Building Lobbies and Corridors (Interior Accessible Route) Elevators Rooms and Spaces Assembly Areas Toilet Rooms and Bathrooms Bathtubs and Showers Dressing and Fitting Rooms Signage Alarms Detectable Warnings Automated Teller Machines (ATMs) Special Facility Types -Form Form Form Form Form 23: 24: 25: 26: 27: Form 28: Form 29: Restaurants and Cafeterias Medical Care Facilities Mercantile Facilities Libraries Transient Lodging (Hotels, Motels, Inns, Boarding Houses, Dormitories, and Other Similar Places) Transient Lodging in Homeless Shelters, Halfway Houses, Transient Group Homes, and Other Social Service Establishments Transportation Facilities How Differences in Requirements for New Construction, Alterations, and Historic Properties are Addressed Special provisions and exceptions allowed in alterations of buildings, including historic properties, are addressed in Minimum Requirements Summary Sheet I: Accessible Buildings - Additions and Alterations, and Sheet J: Accessible Buildings - Historic Preservation. Special provisions and exceptions allowed in special facility types such as hotels, motels, hospitals, mercantile facilities, libraries, restaurants and cafeterias are addressed in Survey Forms 23 through 29. 5 SURVEY INSTRUCTIONS Approach to Surveying This checklist is designed to be used in full or in part, depending on the facility and your available time. If you are surveying a facility with which you are familiar, you may already know what the general access problems are and will want to use specific survey forms to check the details. If you are unfamiliar with the facility, it is helpful to make an initial tour through the building to orient yourself and to obtain information to help you compile your survey document. Although this checklist is structured for use on site, it can also be used by architects, facility managers or others to review architectural plans. Preparing to Survey Make contact with the building management and advise them that you will be surveying the building and that you will be glad to share your information with them. If you do not have a building plan, ask the management if they can provide you with one. A plan can be very helpful, particularly if you are surveying a large facility. You can assign numbers to areas or elements on the plan and use the same numbers to correlate the Survey Forms. Take a copy of ADAAG with you when you do in this checklist are fairly brief, it is gain a thorough understanding of the full Also, not every illustration in the ADAAG the survey. Since the questions helpful to have ADAAG with you to requirements of the Guidelines. has been included in this survey. Illustrations are provided in the checklist only for those survey questions which cannot easily be stated or understood using words alone. Step 1: Identify the Type of Facility or Building Use Complete the Building Identification and Data Sheet to document the name and address of the facility, dates of construction and alteration, type of facility or building use, number of stories and size of each, name of surveyor and date of survey. Before surveying the facility it is essential to determine whether the provisions of ADAAG apply to the facility or portion of the facility and to identify certain attributes about the facility which might trigger or disallow certain exceptions contained in ADAAG. To determine which provisions of ADAAG apply, you must consult the Department of Justice regulations or Department of Transportation regulations as explained in the introduction. To determine the exceptions that apply you must also consult the DOJ or DOT regulations. Exceptions within ADAAG are noted on the Technical Requirements Survey Forms. An example of an exception is the elevator exemption contained in ADAAG 4.1.3(5) Exception 1. Elevators are not required in places of public accommodation and commercial facilities that are less than three stories or that have less than 3,000 square feet per story unless the building is a shopping center or mall, the professional office of a health care provider, or a transportation facility. Step 2: Determine Minimum Requirements The Minimum Requirements Summary Sheets tell you which elements are required to be accessible, such as a toilet room or an accessible route between the entrance and parking. Use the Summary Sheets to identify the specific elements of your facility which must be accessible. With the Summary Sheets in hand, take a quick tour of the facility and/or look at the building plans. As you go through the facility, complete each Summary Sheet in the order in which it is presented. The Summary Sheets will ask you to inventory the elements of your facility which must be accessible. 6 The principle of an "accessible route" is key to the Summary Sheets. An "accessible route" is simply a path of travel which a person in a wheelchair, an elderly person, or someone with another mobility limitation would find safe and easy to use. (See ADAAG 3.5 Definitions.) The Summary Sheets define where these accessible routes must be. Step 3: Copy and Assemble the Survey Forms Return to your workplace with the completed Summary Sheets. Using the completed Summary Sheets you can determine how many copies to make of each Technical Requirements Survey Form. Some forms will be needed more than once, others will not be needed at all. Some forms will reference other forms. Two forms that are referenced quite often are Form 11: Doors and Gates and Form 12: Building Lobbies and Corridors. Where forms are cross referenced you will always need to have a copy of the form for reference. In some multi-story buildings, you will find that certain elements required to be accessible are duplicated in the details of installation and you may be able to develop a "shorthand" method of surveying these elements. For instance, you might find that accessible drinking fountains are installed in the same location in a corridor and in the same way on the first through the tenth floor of a ten story building. It may be sufficient to use only one form (Form 5: Drinking Fountains) to assess compliance in detail for a typical fountain on the first floor, and then note that each fountain on the second through the tenth floor is the same. All elevators are required to be accessible but where there are three elevators in a bank, you will often find that the three elevators are the same. If this is true, you may be able to use a single form (Form 13: Elevators) to survey three elevators in the same bank. Copy the necessary Survey Forms and attach them to the Summary Sheet which called for them. When you are finished, you will have a series of Survey Forms which progress logically through the facility and are divided by the Minimum Requirements Summary Sheets. If you are working with a team, you can give team members a complete section covered by a Summary Sheet. Cover the entire package with the Building Identification and Data Sheet. If you are surveying an alteration to a facility or an alteration which falls under historic preservation provisions, you will also need those Summary Sheets. Step 4: Survey Bring a copy of ADAAG, a clipboard, a pencil or a pen, a flexible measuring tape, and a stick of chalk for marking distances on surfaces. You may also want a line level or other device to measure ramp slopes, and a fish scale for determining door pull force. Each Survey Form has a title block which allows you to identify the specific element you are inspecting. Be sure to fill in the location of the element and the facility name on each Survey Form. Each survey question or series of questions has an ADAAG section number. Some questions have more than one ADAAG section number. If you do not understand the question, look up the section(s) in ADAAG. Illustrations referenced in the survey forms are printed on subsequent pages. If you have a question about a term, refer to ADAAG 3.5 (Definitions). Check off whether the element complies or not. whether or not it complies, put a question mark blank boxes because it will confuse someone who If the element does not exist, write "N/A" (Not If you cannot determine in the box. Do not leave later reviews the forms. Applicable). Each Survey Form has boxes for you to check for each question, either "yes" or "no." Please also notice that extra space is provided for you to elaborate where a simple "yes" or "no" is insufficient. You should note as precisely as possible what the problem is; for example, "clear opening width only 29 inches," "hand rail diameter 4 inches," or "ramp slope 1:10." This information will assist those using the survey at a later date to make modifications to evaluate which changes might be more critical in providing access. 7 BUILDING IDENTIFICATION AND DATA SHEET Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Address: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Date(s) of Construction: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Date(s) of Alteration: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Type of Facility of Building Use: (In this space, provide information about the facility that will help you in applying the provisions of ADAAG and in using the survey data in the future. For example, is the building a place of public accommodation or commercial facility? Is it owned by a State or local government? Is it the professional office of a health care provider, a shopping center or a shopping mall, or a transportation facility?) ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Number of Stories and Size of Each: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄName(s) of Surveyors: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Date(s) of Survey: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ 8 A: PARKING AND PASSENGER LOADING ZONES (Attach Needed Survey Forms to this Summary Sheet.) Parking - Minimum Number: 4.1.2(5)(a) and (b) General Use Parking: If self parking is provided for employees or visitors, each parking area/lot or structure is required to have accessible parking spaces complying with the following table and with 4.6. Note: Spaces required by the table need not be provided in the particular area/lot or structure. They may be provided at a different location if equivalent or greater accessibility, in terms of distance from an accessible entrance, cost and convenience, is ensured. Total Parking Area/Lot or Structure 1 to 25 26 to 50 51 to 75 76 to 100 101 to 150 151 to 200 201 to 300 301 to 400 401 to 500 501 to 1000 1001 and over Required Minimum Number of Accessible Spaces 1 2 3 4 5 6 7 8 9 2 percent of total 20 plus 1 for each 100 over 1000 In addition, one in every eight accessible parking spaces (but not less than one) must be served by an access aisle at least 96 inches wide and must be designated "van accessible." Exception: Provision of all required spaces in conformance with the "Universal Parking Space Design" which accommodates both cars and vans is permitted (see Appendix A4.6.3 of ADAAG). Parking at Health Care Facilities: 4.1.2(5)(a), (b) and (d) Employee and visitor parking at general health care facilities must comply with the table above, except as follows. At outpatient units and facilities, 10 percent of the total number of parking spaces provided serving each such outpatient unit or facility must be accessible. At units and facilities specializing in treatment or services for people with mobility impairments, 20 percent of the total number of spaces provided serving each such unit or facility must be accessible. List parking areas/lots or structures to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄSurvey each parking area/lot or structure with Form 1: Parking and Passenger Loading Zones and Form 3: Exterior Accessible Routes. For parking structures which have doors or gates, or elevators, use Form 11: Doors and Gates and Form 13: Elevators. If direct access is provided for pedestrians from an enclosed parking garage to a building, use Form 10: Entrances and Exits (Areas of Rescue Assistance). If the parking structure has public telephones or drinking fountains, use Form 5: Drinking Fountains and Form 6: Telephones. If the parking structure has toilet rooms, use Minimum Requirements Summary Sheet F: Toilet Rooms and Bathrooms. A-1 Valet Parking: 4.1.2(5)(e) Valet parking facilities must provide a passenger loading zone complying with 4.6.6 located on an accessible route to the entrance of the facility. Note: Valet parking facilities are not required to provide accessible parking spaces. List valet parking facilities to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each valet parking facility with Form 2: Passenger Loading Zones. Survey the accessible route from the passenger loading zone to the entrance to the facility with Form 3: Exterior Accessible Routes, or Form 12: Building Lobbies and Corridors. You may also need Form 4: Curb Ramps and Form 21: Detectable Warnings. Passenger Loading Zones: 4.1.2(5)(c) Where passenger loading zones are provided, at least one must be accessible. You can usually identify the accessible passenger loading zone by a sign bearing the International Symbol of Accessibility. If no sign is present, survey existing passenger loading zones to identify ones that may be accessible. Begin with the passenger loading zone closest to an accessible entrance. List passenger loading zones to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each passenger loading zone with Form 2: Passenger Loading Zones. You may also need Form 4: Curb Ramps and Form 21: Detectable Warnings. Number of Copies: Form 1: Parking ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 2: Passenger Loading Zones ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 3: Exterior Accessible Routes ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 4: Curb Ramps ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 5: Drinking Fountains ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 6: Telephones ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 10: Entrances and Exits (Areas of Rescue Assistance) ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 11: Doors and Gates ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 12: Building Lobbies and Corridors ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 13: Elevators ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 21: Detectable Warnings ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ A-2 B: SITE ACCESSIBLE ROUTES AND ELEMENTS (Attach Needed Survey Forms to this Summary Sheet.) Site Accessible Routes and Elements: 4.1.2(1), 4.1.2(2), 4.1.2(3), and 4.1.2(4) At least one accessible route must be provided within the boundary of the site connecting the following elements, where provided on the site, to an accessible building entrance. From: public transportation stops accessible parking spaces accessible passenger loading zones public streets and sidewalks To: accessible accessible accessible accessible entrance entrance entrance entrance If you are using a plan drawing, you may want to mark each of these routes with a colored pencil. In addition, at least one accessible route must connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site. Accessible routes must connect these elements. If they do exist, then the completed survey form will reveal their complying and non-complying features. The accessible route to an accessible entrance must, to the maximum extent feasible, coincide with the route for the general public. All objects that protrude from surfaces or posts into circulation paths must comply with the requirements of 4.4; and the sidewalks, ramps and other walking surfaces that make up the accessible routes and spaces must comply with 4.5. List accessible routes to be surveyed: From: To: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each accessible route with Form 3: Exterior Accessible Routes. You may also need Form 4: Curb Ramps; Form 7: Ramps; Form 8: Stairs*; Form 9: Platform Lifts*; Form 13: Elevators; Form 19: Signage; and Form 21: Detectable Warnings where these elements are part of an accessible route. If drinking fountains, public telephones, or automated teller machines are located on the site, use Form 5: Drinking Fountains; Form 6: Telephones; and Form 22: Automated Teller Machines (ATMs). If a toilet facility or bathing facility is located on a site, use Minimum Requirements Summary Sheet F: Toilet Rooms and Bathrooms. *Note: The use of stairs and platform lifts to provide access is limited in new construction. Stairs: 4.1.3(4) Interior and exterior stairs connecting levels that are not connected by an elevator, ramp, or other accessible means of vertical access must comply with 4.9. In new construction, this condition may occur in facilities subject to the elevator exemption (see 4.1.3(5) Exception 1), or where mezzanines are exempt in restaurants (see 5.4). B-1 List stairs to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey stairs with Form 8: Stairs in those buildings and facilities only where the levels are not connected by an elevator, ramp, or other accessible means of vertical access. Platform Lifts: 4.1.3(5) Exception 4 In new construction, platform lifts complying with 4.11 and applicable State or local codes may be used in place of an elevator only under the following conditions: (a) To provide an accessible route to a performing area in an assembly occupancy. (b) To comply with the wheelchair viewing position, line-of-sight, and dispersion requirements of 4.33.3. (c) To provide access to incidental occupiable spaces and rooms which are not open to the general public and which house no more than five persons, including but not limited to equipment control rooms and projection booths. (d) To provide access where existing site constraints or other constraints make use of a ramp or an elevator infeasible. List platform lifts to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each platform lift with Form 9: Platform Lifts. Number of Copies: Form 3: Exterior Accessible Routes ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 4: Curb Ramps ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 5: Drinking Fountains ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 6: Telephones ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 7: Ramps ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 8: Stairs ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 9: Platform Lifts ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 13: Elevators ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 19: Signage ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 21: Detectable Warnings ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 22: Automated Teller Machines (ATMs) ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ C: ENTRANCES (Attach Needed Survey Forms to this Summary Sheet.) Entrances: 4.1.3(8) At least 50% of all public entrances must be accessible. If the number of exits required by the applicable building/fire code is greater than 50% of public entrances, the number of accessible entrances must be at least equal to the number of required exits up to the total number of entrances planned. (See examples below.) In addition: Each separate tenancy must have an accessible entrance. Where an entrance is provided from an enclosed parking structure, an accessible entrance must be provided. Where access is provided from a pedestrian tunnel or elevated walkway, an accessible entrance must be provided. Examples: A facility has six (6) public entrances planned and four (4) fire exits are required. Four (4) of the six (6) public entrances must be accessible. A facility has one (1) public entrance planned, and two (2) fire exits are required. Only the one (1) public entrance must be accessible. A facility has three (3) public entrances planned, and two (2) fire exits are required. Two (2) of the three (3) public entrances must be accessible. List accessible entrances to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each accessible entrance with Form 10: Entrances and Exits (Areas of Rescue Assistance); Form 11: Doors and Gates; and Form 3: Exterior Accessible Routes. You may also need Form 7: Ramps; Form 8: Stairs*; Form 9: Platform Lifts*; Form 13: Elevators; and Form 19: Signage, where these elements are part of an entrance. *Note: Use of stairs and platform lifts to provide accessibility is limited in new construction. (See Minimum Requirements Summary Sheet B: Site Accessible Routes and Elements.) Number of Copies: Form 3: Exterior Accessible Routes ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 7: Ramps ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 8: Stairs ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 9: Platform Lifts ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 13: Elevators ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 19: Signage ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ C-1 D: BUILDING ACCESSIBLE ROUTE (Attach Needed Survey Forms to this Summary Sheet.) Building Accessible Route: 4.1.3(1), 4.1.3(3), 4.1.3(4), and 4.1.3(5) At least one accessible route complying with 4.3 must connect accessible building or facility entrances with all accessible spaces and elements within the building or facility. In a multi-story building, an accessible elevator must provide access to each level unless a ramp complying with 4.8 is provided. Use of stairs or platform lifts to provide access in new construction is limited. If the building is less than three stories, or has less than 3,000 square feet per story, an elevator is not required unless the building is the professional office of a health care provider, a shopping center or shopping mall, or a transportation facility. These terms are defined in 36 CFR S36.401(d). All objects that overhang or protrude into circulation paths must comply with 4.4; and ground and floor surfaces along accessible routes must comply with 4.5. List building lobbies and corridors to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each building lobby and corridor with Form 12: Building Lobbies and Corridors. You may also need Form 19: Signage and Form 20: Alarms. If a door or gate is across an accessible route, use Form 11: Doors and Gates. If drinking fountains, public telephones, or automated teller machines are located in a building lobby or corridor, use Form 5: Drinking Fountains; Form 6: Telephones; and Form 22: Automated Teller Machines (ATMs). List ramps to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each ramp with Form 7: Ramps. List elevators to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each elevator or bank of elevators with Form 13: Elevators. Stairs: 4.1.3(4) Interior and exterior stairs connecting levels that are not connected by an elevator, ramp, or other accessible means of vertical access must comply with 4.9. In new construction, this condition may occur in facilities subject to the elevator exemption (see 4.1.3(5) Exception 1), or where mezzanines are exempt in restaurants (see 5.4). List stairs to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey stairs with Form 8: Stairs in those buildings and facilities only where the levels are not connected by an elevator, ramp, or other accessible means of vertical access. Platform Lifts: 4.1.3(5) Exception 4 In new construction, platform lifts complying with 4.11 and applicable State or local codes may be used in lieu of an elevator only under the following conditions: (a) To provide an accessible route to a performing area in an assembly occupancy. (b) To comply with the wheelchair viewing position, line-of-sight, and dispersion requirements of 4.33.3. (c) To provide access to incidental occupiable spaces and rooms which are not open to the general public and which house no more than five persons, including but not limited to equipment control rooms and projection booths. (d) To provide access where existing site constraints or other constraints make use of a ramp or an elevator infeasible. List platform lifts to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each platform lift with Form 9: Platform Lifts. Number of Copies: Form 5: Drinking Fountains ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 6: Telephones ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 7: Ramps ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 8: Stairs ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 9: Platform Lifts ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 11: Doors and Gates ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 12: Building Lobbies and Corridors ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 13: Elevators ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 19: Signage ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 20: Alarms ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 22: Automated Teller Machines (ATMs) ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ E: ROOMS AND SPACES (Including Assembly Areas and Dressing and Fitting Rooms) (Attach Needed Survey Forms to this Summary Sheet.) Public and Common Use Areas: 4.1.1 Rooms and spaces which are not specifically exempt or which are not used solely as work areas must be fully accessible. Note: Accessibility is not required to: (i) observation galleries used primarily for security purposes; or (ii) non-occupiable spaces accessed only by ladders, catwalks, crawl spaces, very narrow passageways, or freight (non-passenger) elevators and frequented only by service personnel for repair purposes (e.g., elevator pits, elevator penthouses, piping or equipment catwalks). Work Areas: 4.1.1(3) Areas that are used only by employees as work areas must be designed and constructed so that individuals with disabilities can approach, enter, and exit the areas. The guidelines do not require that areas used only by employees as work areas be constructed to permit maneuvering within the work area or be constructed or equipped (i.e., with racks or shelves) to be accessible. List rooms and spaces which must be accessible: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each room and space with Form 14: Rooms and Spaces. You may also need Form 11: Doors and Gates; Form 19: Signage; and Form 20: Alarms. If ramps, stairs*, or lifts* are part of a room or space, use Form 7: Ramps; Form 8: Stairs*; and Form 9: Platform Lifts*. If drinking fountains or public telephones are located in a room or space, use Form 5: Drinking Fountains and Form 6: Telephones. Note: Use of stairs and platform lifts to provide accessibility is limited in new construction. (See Minimum Requirements Summary Sheet D: Building Accessible Route.) List rooms and spaces that are used solely as work areas: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey the door area with Form 11: Doors and Gates and survey the accessible route with Form 12: Building Lobbies and Corridors. E-1 Assembly Areas: An assembly area is defined as a room or space accommodating a group of individuals for recreational, educational, political, social, or amusement purposes, or for the consumption of food and drink. List assembly areas to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each assembly area with Form 15: Assembly Areas. Dressing and Fitting Rooms: 4.1.3(21) Where dressing and fitting rooms are provided for use by the general public, patients, customers or employees, 5 percent (but not less than one) of dressing rooms for each type of use in each cluster of dressing and fitting rooms must comply with 4.35. List dressing rooms to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each dressing room with Form 18: Dressing and Fitting Rooms. Number of Copies: Form 5: Drinking Fountains ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 6: Telephones ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 7: Ramps ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 8: Stairs ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 9: Platform Lifts ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 11: Doors and Gates ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 12: Building Lobbies and Corridors ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 14: Rooms and Spaces ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 15: Assembly Areas ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 18: Dressing and Fitting Rooms ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 19: Signage ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 20: Alarms ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ F: TOILET ROOMS AND BATHROOMS (Attach Needed Survey Forms to this Summary Sheet.) Toilet Rooms/Facilities and Bathrooms/Bathing Facilities: 4.1.2(6) & 4.1.3(11) In a building or facility, each public and common use toilet room/facility, and bathroom/bathing facility must be accessible. Employee toilet rooms are considered to be "common use" toilet rooms. Other toilet rooms and bathrooms must be adaptable in that all space and door requirements must be satisfied. For single user portable toilet or bathing units clustered at a single location (where not associated with construction sites), at least 5% (but no less than one) accessible toilet units or bathing units must be installed at each cluster whenever typical inaccessible units are provided. Accessible units must be identified by the International Symbol of Accessibility. List the toilet rooms/facilities and bathrooms/bathing facilities to be surveyed (include portable units on a site): ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each toilet room/facility with Form 16: Toilet Rooms and Bathrooms and Form 19: Signage. Survey each bathroom/bathing facility with Form 16: Toilet Rooms and Bathrooms; Form 17: Bathtubs and Showers, and Form 19: Signage. You may also need Form 11: Doors and Gates and Form 20: Alarms. If a drinking fountain is located in the toilet room/facility or bathroom/bathing facility, use Form 5: Drinking Fountains. Number of Copies: Form 5: Drinking Fountains ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 11: Doors and Gates ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 16: Toilet Rooms and Bathrooms ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 17: Bathtubs and Showers ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 20: Alarms ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ F-1 G: SPECIAL FEATURES - SIGNAGE, ALARMS, DETECTABLE WARNINGS, AND AUTOMATED TELLER MACHINES (ATMs) (Attach Needed Survey Forms to this Summary Sheet.) Signage: 4.1.2(7) and 4.1.3(16) Signs which designate permanent rooms and spaces must comply with 4.30.1, 4.30.4, 4.30.5, and 4.30.6. Other signs which provide direction to, or information about, functional spaces of the building must comply with 4.30.1, 4.30.2, 4.30.3, and 4.30.5. Exception: Building directories, menus, and all other signs which are temporary are not required to comply. List signs to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each sign with Form 19: Signage. Form 19: Signage is also used with Form 3: Exterior Accessible Routes; Form 6: Telephones; Form 10: Entrances and Exits (Areas of Rescue Assistance); Form 12: Building Lobbies and Corridors; Form 14: Rooms and Spaces; Form 16: Toilet Rooms and Bathrooms; and Form 29: Transportation Facilities. Alarms: 4.1.3(14) If emergency warning systems are provided, then they must include both audible alarms and visual alarms complying with 4.28. Sleeping accommodations required to comply with 9.3 must have an auxiliary visual alarm complying with 4.28.4. Emergency warning systems in medical care facilities may be modified to suit standard health care alarm design practice. List alarms to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each alarm with Form 20: Alarms. Form 20: Alarms is also used with Form 12: Building Lobbies and Corridors; Form 14: Rooms and Spaces; Form 15: Assembly Areas; and Form 16: Toilet Rooms and Bathrooms. Detectable Warnings: 4.1.3(15) Detectable warnings must be provided at reflecting pools that are not protected by railings, walks, or curbs. At hazardous vehicular areas on a site, if a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings, or other elements between the pedestrian areas and vehicular areas, then the boundary between the areas must be defined by a continuous detectable warning. Detectable warnings must also be provided on curb ramps on a site. List detectable warnings to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each detectable warning with Form 21: Detectable Warnings. Detectable warnings on curb ramps are included on Form 4: Curb Ramps. Form 21: Detectable Warnings is also used with Form 2: Passenger Loading Zones and Form 3: Accessible Routes. Automated Teller Machines (ATMs): 4.1.3(20) Where one or more automated teller machines is provided at a location, at least one ATM at that location must comply with 4.34. Exception: Drive-up-only automated teller machines are not required to comply with 4.27.2, 4.27.3 and 4.34.3. List ATMs to be surveyed: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Survey each ATM with Form 22: Automated Teller Machine (ATMs). Form 22: Automated Teller Machines (ATMs) is also used with Form 3: Exterior Accessible Routes and Form 12: Building Lobbies and Corridors. Number of Copies: Form 19: Signage ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 20: Alarms ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 21: Detectable Warnings ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Form 22: Automated Teller Machines (ATMs) ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ G-2 H: SPECIAL TYPES OF FACILITIES (Attach Needed Survey Forms to this Summary Sheet.) The facilities listed below have further specific requirements in addition to those of 4.1 to 4.35. If you are surveying one of these special facilities, you will also need the appropriate form for the type of facility. For instance, if you are surveying a hotel or motel, use Minimum Requirements Summary Sheets A - G to identify which Forms (1 - 22) are needed to survey the facility for compliance with 4.1 to 4.35 and then use Form 27: Transient Lodging to survey for compliance with 9.0. If the facility also has a gift shop and a restaurant, you will also need Form 25: Mercantile Facilities to survey for compliance with 7.0 and Form 23: Restaurants and Cafeterias to survey for compliance with 5.0. Special Facilities: Form 23: Restaurants and Cafeterias Form 24: Medical Care Facilities Form 25: Mercantile Facilities Form 26: Libraries Form 27: Transient Lodging (Hotels, Motels, Inns, Boarding Houses, Dormitories, Resorts, and Other Similar Places) Form 28: Transient Lodging in Homeless Shelters, Halfway Houses, Transient Group Homes, and Other Social Service Establishments. Form 29: Transportation Facilities H-1 I: ACCESSIBLE BUILDINGS ÄÄ ADDITIONS AND ALTERATIONS Additions 4.1.5: Additions must meet the applicable minimum requirements for new construction in 4.1.1 to 4.1.3 and the applicable technical provisions in 4.2 through 4.35 and 5.0 through 10.0 for each space or element added to the existing building or facility. Use the applicable survey forms for new construction for each altered element or space. Additions to an existing building or facility also are regarded as alterations. An addition that affects an area of primary function must also comply with 4.1.6(2) and 28 CFR S36.403. Alterations 4.1.6(1): No alteration may decrease accessibility below the requirements for new construction. Alterations are not required to provide greater accessibility than that in new construction. In existing buildings or facilities, alterations must comply with the following: Each element, space, feature, or area that is altered must comply with the applicable minimum requirements for new construction in 4.1.1 through 4.1.3 and the applicable technical provisions in 4.2 through 4.35 and 5.0 through 10.0. (Use Forms 1-29.) If the applicable requirements for new construction require that an element, space, feature, or area be on an accessible route, an accessible route is not required except as provided in 4.1.6(2) (Alterations to an Area Containing Primary Function). When alterations of single elements amount to an alteration of a room or space, the entire space must be made accessible. If full compliance with the technical provisions (4.2 through 4.35 and 5.0 through 10.0) of an altered element, space, feature, or area is technically infeasible, the special technical provisions in 4.1.6(3) may be utilized. If there is no special technical provision in 4.1.6(3) for an altered element, space, feature, or area, or if full compliance with the special technical provision is technically infeasible, the alteration must provide accessibility to the maximum extent feasible. Any elements or features of the building or facility that are being altered and can be made accessible, must be made accessible within the scope of the alteration. Special Technical Provisions 4.1.6(3): modified only as described below. The following elements may be Curb Ramps and Ramps - Slope and Rise: Where space limitations prohibit the use of a 1:12 slope, a slope between 1:10 and 1:12 is allowed for a maximum rise of 6 inches; and a slope between 1:8 and 1:10 is allowed for a maximum rise of 3 inches. Stairs - Handrail Extensions: Where handrail extensions would be hazardous (e.g., protruding into pedestrian traffic perpendicular to the stair) or impossible due to plan configuration, full extension of handrails is not required. Elevators - Safety Edges and Car Dimensions: If safety edges are provided in an existing automatic elevator, automatic door opening devices may be omitted. Where existing shaft configuration or technical infeasibility prohibits full compliance with 4.10.9, the car plan dimensions may be reduced by the minimum amount necessary, but in no case shall the inside car area be less than 48 inches by 48 inches. Equivalent facilitation may be provided with an elevator car of different dimensions when usability can be demonstrated and when all other accessible elements comply with 4.10. Doors - Clear Opening and Thresholds: Where it is technically infeasible to comply with the 32 inch clear opening width requirement, a maximum projection of 5/8 inch will be permitted for the latch side stop. existing I-1 If thresholds are no more than 3/4 inch high, and have (or are modified to have) a beveled edge on each side, they may remain. Toilet/Bath Rooms - Unisex, Alternate Stall, Directional Signage: Where it is technically infeasible to modify both men's and women's toilets/bath rooms in compliance with 4.22 or 4.23, a unisex toilet/bath room is permitted. Each unisex toilet room must contain one water closet complying with 4.16 and one lavatory complying with 4.19, and the door must have a privacy latch. Where it is technically infeasible to install a required standard stall (Fig. 30(a)), or where other codes prohibit reduction of the fixture count, either alternate stall (Fig. 30(b)) may be provided. Where existing toilet/bath rooms are not altered to be accessible, signage must be provided indicating the location of the nearest accessible toilet/bath room within the facility. Assembly Areas - Dispersal of Seating and Performing Areas: Where it is technically infeasible to meet dispersal requirements, accessible seating may be clustered. Each accessible seating area must have provisions for companion seating and must be located on an accessible route usable as a means of emergency egress. Where it is technically infeasible to alter all performing areas to be on an accessible route, at least one of each type of performing area must be made accessible. Lifts - Conditions for Use: In alterations, the use of lifts is not limited to the four conditions in 4.1.3(5) Exception 4. Lifts must comply with 4.11 and applicable State and local codes. Dressing/Fitting Rooms - Minimum Number: Where technically infeasible to provide the minimum number of dressing/fitting rooms required in 4.1.3(21), one dressing room for each sex (or one unisex room if typical) on each level must be made accessible. Additional Requirements and Exceptions (4.1.6(1)): Text Telephones - At least one interior public text telephone complying with 4.31.9 must be provided where: (i) Alterations to existing buildings or facilities with fewer than four exterior or interior public pay telephones would increase the total number to four or more telephones with at least one in an interior location; or (ii) Alterations to one or more exterior or interior public pay telephones occur in an existing building or facility with four or more public telephones with at least one in an interior location. Accessible Vertical Access - If an escalator or stair is planned or installed where none existed previously and major structural modifications are necessary for such installation, then a means of accessible vertical access must be provided that complies with the applicable provisions of 4.7 Curb Ramps, 4.8 Ramps, 4.10 Elevators, or 4.11 Lifts. Areas of Rescue Assistance - In alterations, areas of rescue assistance are not required because the new construction requirements of 4.1.3(9), 4.3.10 and 4.3.11 do not apply. Entrances - If a planned alteration entails alterations to an entrance, and the building has an accessible entrance, the entrance being altered is not required to comply with 4.1.3(8), except to the extent required by 4.1.6(2). If a particular entrance is not made accessible, appropriate accessible signage indicating the location of the nearest accessible entrance(s) must be installed at or near the inaccessible entrance, such that a person with a disability will not be required to retrace the approach route from the inaccessible entrance. Alterations Not Affecting Accessibility - If the alteration work is limited solely to the electrical, mechanical, or plumbing system, or to hazardous material abatement, or automatic sprinkler retrofitting, and does not involve the alteration of any elements or spaces required to be accessible under ADAAG then 4.1.6(2) does not apply. Elevator Exception - If a building is less than three stories or has less than 3,000 square feet per story, an elevator is not required unless the building is a shopping center or shopping mall, the professional office of a health care provider, or a transportation facility. These terms are defined in 28 CFR S36.404(a). I-2 Alterations to an Area Containing a Primary Function (4.1.6(2)): In addition to the requirements of 4.1.6(1), an alteration that affects or could affect the usability of or access to an area containing a primary function must be made so as to ensure that, to the maximum extent feasible, the path of travel to the altered area and the restrooms, telephones, and drinking fountains serving the altered area, are readily accessible to and usable by individuals with disabilities, unless such alterations are disproportionate to the overall alterations in terms of cost and scope (as determined under criteria established by the Attorney General). These terms are further defined in 28 CFR S36.403. I-3 J: ACCESSIBLE BUILDINGS ÄÄ HISTORIC PRESERVATION Alterations to a qualified historic building or facility must comply with the minimum requirements for alterations in 4.1.6. Use the applicable survey forms for new construction for each altered element or space. If it is determined, in accordance with the required procedures in 4.1.7(2), that the proposed alterations would threaten or destroy the historic significance of the building or facility, the following alternative requirements in 4.1.7(3) may be utilized: Site Accessible Route - Minimum Number: At least one accessible route complying with 4.3 must be provided from a site access point to an accessible entrance. Ramps - Slope and Rise: A ramp with a slope no steeper than 1:6 may be used as part of an accessible route to an entrance but the run must not exceed 2 feet. Entrances - Minimum Number and Primary Entrance: At least one accessible entrance complying with 4.14 and which is used by the public must be provided. If no public entrance can be made accessible, then access may be provided at any entrance which is open (unlocked) when directional signage is provided at the primary public entrance. The alternative accessible entrance must have a notification system, and where security is a concern, remote monitoring may be used. Building Accessible Route - Access to Other Floors: Accessible routes from an accessible entrance to all publicly used spaces must be provided at least on the accessible entrance level. Access must be provided in compliance with 4.1 to all levels of a building and facility whenever practicable. Toilet Rooms - Unisex: If toilets are provided, then at least one toilet facility, which may be unisex in design, complying with 4.22 and 4.1.6, must be provided on an accessible route. Displays: Displays and written information should be located so as to be seen by a seated person. If it is determined, in accordance with the required procedures in 4.1.7(2), that it is not feasible to provide physical access to a qualified historic building or facility using the alternative requirements in 4.1.7(3) without threatening or destroying the historic significance of the building or facility, alternative methods of access must be provided. See 36 CFR S36.405(b). J-1 SURVEY FORM 1: PARKING Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Parking Area/Lot Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ General Use: (Use table in 4.1.2(5)(a)) Total Parking Spaces in Number Number Van Area/Lot: Accessible: Accessible: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Outpatient Unit/Facility (10% required) ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Specialized Unit/Facility Serving or Treating Persons with Mobility Impairments (20% required) ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³ Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(5) ³Number ³Where parking spaces are ³ ³ ³ ³ ³4.6.1 ³Accessible ³provided for self-parking by ³ ³ ³ ³ ³ ³Parking Spaces ³employees or visitors or both, ³ ³ ³ ³ ³ ³ ³are the required number of ³ ³ ³ ³ ³ ³ ³accessible parking spaces ³ ³ ³ ³ ³ ³ ³complying with 4.6 (see below) ³ ³ ³ ³ ³ ³ ³provided? (See Minimum ³ ³ ³ ³ ³ ³ ³Requirements Summary Sheet A) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(All or some of the accessible ³ ³ ³ ³ ³ ³ ³parking spaces may be in a ³ ³ ³ ³ ³ ³ ³different location if ³ ³ ³ ³ ³ ³ ³equivalent or greater ³ ³ ³ ³ ³ ³ ³accessibility is ensured.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Each Area/Lot: ³Are the accessible parking ³ ³ ³ ³ ³ ³ ³spaces located in each ³ ³ ³ ³ ³ ³ ³specific area/lot? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³If the accessible parking ³ ³ ³ ³ ³ ³ ³spaces are in a different ³ ³ ³ ³ ³ ³ ³location, is equivalent or ³ ³ ³ ³ ³ ³ ³greater accessibility provided ³ ³ ³ ³ ³ ³ ³in terms of distance from the ³ ³ ³ ³ ³ ³ ³accessible entrance, cost and ³ ³ ³ ³ ³ ³ ³convenience? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Van Accessible ³Is one in every eight ³ ³ ³ ³ ³ ³Spaces ³accessible parking spaces (but ³ ³ ³ ³ ³ ³ ³not less than one) designated ³ ³ ³ ³ ³ ³ ³"van accessible?" ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.2 ³Location ³Are accessible parking spaces ³ ³ ³ ³ ³ ³Serving ³which serve a particular ³ ³ ³ ³ ³ ³Accessible ³building on the shortest ³ ³ ³ ³ ³ ³Entrance ³accessible route of travel ³ ³ ³ ³ ³ ³ ³from adjacent parking to the ³ ³ ³ ³ ³ ³ ³building's accessible entrance?³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 1-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Serving ³If the building has multiple ³ ³ ³ ³ ³ ³Multiple ³accessible entrances with ³ ³ ³ ³ ³ ³Accessible ³adjacent parking, are the ³ ³ ³ ³ ³ ³Entrances ³accessible parking spaces ³ ³ ³ ³ ³ ³ ³on the shortest accessible ³ ³ ³ ³ ³ ³ ³route of travel to the parking ³ ³ ³ ³ ³ ³ ³facility's accessible ³ ³ ³ ³ ³ ³ ³pedestrian entrance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Separate ³Where a parking facility does ³ ³ ³ ³ ³ ³Parking ³not serve a particular ³ ³ ³ ³ ³ ³Facility ³building, are the accessible ³ ³ ³ ³ ³ ³ ³parking spaces on the shortest ³ ³ ³ ³ ³ ³ ³accessible route of travel to ³ ³ ³ ³ ³ ³ ³the parking facility's ³ ³ ³ ³ ³ ³ ³accessible pedestrian ³ ³ ³ ³ ³ ³ ³entrance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.3 ³Parking ³Are accessible parking spaces, ³ ³ ³ ³ ³ ³Spaces and ³including van spaces, at least ³ ³ ³ ³ ³ ³Access ³96 inches wide with a Aisles - ³ ³ ³ ³ ³ ³Width ³demarcated access aisle? ³ ³ ³ ³ ³ ³of Parking ³ ³ ³ ³ ³ ³ ³Space ³(Two spaces may share a common ³ ³ ³ ³ ³ ³ ³aisle. See Figure 9) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(5)(a)³Width of Car ³Are all other access aisles at ³ ³ ³ ³ ³ ³Access Aisles ³least 60 inches wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(5)(b)³Width of Van ³If the parking space is ³ ³ ³ ³ ³ ³Accessible ³designated as "van accessible,"³ ³ ³ ³ ³ ³Access Aisle ³is the adjacent access aisle at³ ³ ³ ³ ³ ³ ³least 96 inches wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.3 ³Level ³Are the accessible parking ³ ³ ³ ³ ³ ³ ³spaces and access aisles level ³ ³ ³ ³ ³ ³ ³with no slope greater than 1:50³ ³ ³ ³ ³ ³ ³in all directions? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(This means a curb ramp cannot ³ ³ ³ ³ ³ ³ ³project into the access aisle.)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.3 ³Surface ³Are access aisles stable, firm,³ ³ ³ ³ ³4.3.6 ³ ³and slip resistant? ³ ³ ³ ³ ³4.5.1 ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.3 ³Access Aisle ³Does each access aisle connect ³ ³ ³ ³ ³4.3 ³and ³directly to an accessible route³ ³ ³ ³ ³ ³Accessible ³complying with 4.3? (Use Form ³ ³ ³ ³ ³ ³Route ³3: Exterior Accessible Route) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.3 ³ ³Is the accessible route a full ³ ³ ³ ³ ³ ³ ³36 inches wide and not reduced ³ ³ ³ ³ ³ ³ ³in width by vehicles ³ ³ ³ ³ ³ ³ ³overhanging parking space? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.4 ³Signs ³Does each accessible parking ³ ³ ³ ³ ³ ³Accessible ³space have a vertical sign, ³ ³ ³ ³ ³ ³Parking Spaces ³which is unobscured by a parked³ ³ ³ ³ ³ ³ ³vehicle, showing the ³ ³ ³ ³ ³ ³ ³International Symbol of ³ ³ ³ ³ ³ ³ ³Accessibility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.4 ³Van Accessible ³Do van accessible spaces have ³ ³ ³ ³ ³ ³Spaces ³a vertical sign, which is ³ ³ ³ ³ ³ ³ ³unobscured by a parked vehicle,³ ³ ³ ³ ³ ³ ³showing the International ³ ³ ³ ³ ³ ³ ³Symbol of Accessibility with an³ ³ ³ ³ ³ ³ ³additional sign ³ ³ ³ ³ ³ ³ ³"Van-Accessible" mounted below ³ ³ ³ ³ ³ ³ ³the symbol of accessibility? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: "Van-Accessible" ³ ³ ³ ³ ³ ³ ³sign is not required if all ³ ³ ³ ³ ³ ³ ³accessible parking spaces are ³ ³ ³ ³ ³ ³ ³Universal Parking Design. (See ³ ³ ³ ³ ³ ³ ³Figure A5) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 1-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.5 ³Van ³Do van accessible spaces have ³ ³ ³ ³ ³ ³Accessible ³a vertical clearance of at ³ ³ ³ ³ ³ ³Vertical ³least 98 inches? ³ ³ ³ ³ ³ ³Spaces ³ ³ ³ ³ ³ ³ ³Clearance ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does one vehicular access route³ ³ ³ ³ ³ ³ ³to and from van accessible ³ ³ ³ ³ ³ ³ ³spaces have a vertical ³ ³ ³ ³ ³ ³ ³clearance of at least 98 ³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(Van accessible spaces may be ³ ³ ³ ³ ³ ³ ³grouped on one level of ³ ³ ³ ³ ³ ³ ³a parking structure.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 1-3 1-4 SURVEY FORM 2: PASSENGER LOADING ZONE Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Passenger Zone Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(5)(c)³Loading ³Are passenger loading zones ³ ³ ³ ³ ³4.6.1 ³Zones ³provided? If so, at least one ³ ³ ³ ³ ³ ³ ³must meet all of the following ³ ³ ³ ³ ³ ³ ³requirements: ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.6 ³Access Aisle ³Is there an access aisle ³ ³ ³ ³ ³ ³ ³adjacent and parallel to the ³ ³ ³ ³ ³ ³ ³vehicle pull-up space? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Aisle ³Is the access aisle at least 60³ ³ ³ ³ ³ ³Size ³inches wide by 20 feet long? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Level ³Is the access aisle level, with³ ³ ³ ³ ³ ³Aisle ³no slope greater than 1:50 in ³ ³ ³ ³ ³ ³ ³all directions? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Level ³Is the vehicle pull-up space ³ ³ ³ ³ ³ ³Space ³level, with no slope greater ³ ³ ³ ³ ³ ³ ³than 1:50 in all directions? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.6 ³Aisle ³Is the access aisle surface ³ ³ ³ ³ ³4.3.6 ³Surface ³stable, firm and ³ ³ ³ ³ ³4.5.1 ³ ³slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.6 ³Curbs ³If there are curbs between the ³ ³ ³ ³ ³4.7 ³ ³access aisle and the vehicle ³ ³ ³ ³ ³ ³ ³pull-up space, is there a curb ³ ³ ³ ³ ³ ³ ³ramp complying with 4.7? (Use ³ ³ ³ ³ ³ ³ ³Form 4: Curb Ramps) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.5 ³Hazardous ³If a walk crosses or adjoins ³ ³ ³ ³ ³ ³Vehicular ³the vehicular way and the ³ ³ ³ ³ ³ ³Area ³walking surface is not ³ ³ ³ ³ ³ ³Detectable ³separated by curbs, railings, ³ ³ ³ ³ ³ ³Warnings ³or other elements between the ³ ³ ³ ³ ³ ³ ³pedestrian areas and vehicular ³ ³ ³ ³ ³ ³ ³areas, is the boundary between ³ ³ ³ ³ ³ ³ ³the areas defined by a ³ ³ ³ ³ ³ ³ ³continuous detectable warning ³ ³ ³ ³ ³ ³ ³at least 36 inches wide ³ ³ ³ ³ ³ ³ ³complying with 4.29.2? (Use ³ ³ ³ ³ ³ ³ ³Form 21: Detectable Warnings) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.6.5 ³Vertical ³Is there at least 114 inches ³ ³ ³ ³ ³ ³Clearance ³vertical clearance along the ³ ³ ³ ³ ³ ³ ³vehicle route to the vehicle ³ ³ ³ ³ ³ ³ ³pull-up space of the accessible³ ³ ³ ³ ³ ³ ³passenger loading zone from ³ ³ ³ ³ ³ ³ ³site entrance(s) and exit(s)? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 2-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there at least 114 inches ³ ³ ³ ³ ³ ³ ³vertical clearance at the ³ ³ ³ ³ ³ ³ ³accessible passenger loading ³ ³ ³ ³ ³ ³ ³zone (including vehicle pull-up³ ³ ³ ³ ³ ³ ³space and access aisle)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(7)(b)³Sign ³Is there a sign displaying the ³ ³ ³ ³ ³ ³ ³International Symbol of ³ ³ ³ ³ ³ ³ ³Accessibility at the accessible³ ³ ³ ³ ³ ³ ³passenger loading zone? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 2-2 SURVEY FORM 3: EXTERIOR ACCESSIBLE ROUTES Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Accessible Route to be Surveyed: From: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ To: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(1) ³Accessible ³Is there an accessible route ³ ³ ³ ³ ³4.3.2(1) ³Route Site ³within the boundary of the site³ ³ ³ ³ ³ ³Public ³linking an accessible building ³ ³ ³ ³ ³ ³Transportation ³entrance with the following, if³ ³ ³ ³ ³ ³ ³provided: public ³ ³ ³ ³ ³ ³ ³transportation stops; passenger³ ³ ³ ³ ³ ³ ³loading zones; public streets ³ ³ ³ ³ ³ ³ ³and sidewalks? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Route for ³Does the accessible route ³ ³ ³ ³ ³ ³General Public ³generally coincide with the ³ ³ ³ ³ ³ ³ ³route for the general public, ³ ³ ³ ³ ³ ³ ³to the maximum extent feasible?³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(2) ³Buildings ³Is there an accessible route ³ ³ ³ ³ ³4.3.2(2) ³Connected ³connecting accessible ³ ³ ³ ³ ³ ³ ³buildings, facilities, elements³ ³ ³ ³ ³ ³ ³and spaces on the same site? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.3 ³Accessible ³Is the accessible route at ³ ³ ³ ³ ³ ³Route Size ³least 36 inches wide except ³ ³ ³ ³ ³ ³Width ³at doorways or gates? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³U-Turn ³Where the accessible route ³ ³ ³ ³ ³ ³ ³makes a U-turn around an ³ ³ ³ ³ ³ ³ ³obstacle less than 48 inches ³ ³ ³ ³ ³ ³ ³wide, is the pathway width at ³ ³ ³ ³ ³ ³ ³least 42 inches on approaches ³ ³ ³ ³ ³ ³ ³and 48 inches in the turn? ³ ³ ³ ³ ³ ³ ³(See Figure 7(b)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.4 ³Passing ³If the accessible route is ³ ³ ³ ³ ³ ³Spaces ³less than 60 inches wide, are ³ ³ ³ ³ ³ ³ ³there passing spaces at least ³ ³ ³ ³ ³ ³ ³60 inches wide and 60 inches ³ ³ ³ ³ ³ ³ ³long or intersecting walks ³ ³ ³ ³ ³ ³ ³allowing passing at reasonable ³ ³ ³ ³ ³ ³ ³intervals not exceeding 200 ³ ³ ³ ³ ³ ³ ³feet? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.5 ³Provisions for ³Is there at least 80 inches ³ ³ ³ ³ ³4.4.2 ³Persons Who ³clear head room on an ³ ³ ³ ³ ³ ³Are Blind ³accessible route? ³ ³ ³ ³ ³ ³Head Room ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.4.2 ³Cane ³If there is less than 80 ³ ³ ³ ³ ³ ³Detectable ³inches clear head room in an ³ ³ ³ ³ ³ ³Barrier Where ³area adjoining an accessible ³ ³ ³ ³ ³ ³Head Room is ³route, is there a cane ³ ³ ³ ³ ³ ³Less Than 80 ³detectable barrier within 27 ³ ³ ³ ³ ³ ³Inches ³inches of the floor? (See ³ ³ ³ ³ ³ ³ ³Figure 8(c-1)) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 3-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.4.1 ³Protruding ³If objects mounted to the wall ³ ³ ³ ³ ³ ³Objects ³have leading edges between 27 ³ ³ ³ ³ ³ ³ ³and 80 inches from the floor, ³ ³ ³ ³ ³ ³ ³do they project less than 4 ³ ³ ³ ³ ³ ³ ³inches into the pathway? (Wall³ ³ ³ ³ ³ ³ ³mounted objects with leading ³ ³ ³ ³ ³ ³ ³edges at or below 27 inches may³ ³ ³ ³ ³ ³ ³project any amount so long as ³ ³ ³ ³ ³ ³ ³the required clear width of an ³ ³ ³ ³ ³ ³ ³accessible route is not ³ ³ ³ ³ ³ ³ ³reduced.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do free standing objects ³ ³ ³ ³ ³ ³ ³mounted on posts with leading ³ ³ ³ ³ ³ ³ ³edges between 27 and 80 inches ³ ³ ³ ³ ³ ³ ³high (such as a sign or ³ ³ ³ ³ ³ ³ ³telephone) project less than 12³ ³ ³ ³ ³ ³ ³inches into the perpendicular ³ ³ ³ ³ ³ ³ ³route of travel? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there an accessible path at ³ ³ ³ ³ ³ ³ ³least 36 inches clear alongside³ ³ ³ ³ ³ ³ ³the protruding object? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.7 ³Slopes ³Is the cross slope of the ³ ³ ³ ³ ³ ³Cross Slope ³accessible route no greater ³ ³ ³ ³ ³ ³ ³than 1:50? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Walkway Slope ³Is the slope of the accessible ³ ³ ³ ³ ³ ³ ³route no greater than 1:20? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.1 ³ ³Where the slope is greater than³ ³ ³ ³ ³ ³ ³1:20, does it comply with the ³ ³ ³ ³ ³ ³ ³requirements for ramps? (Use ³ ³ ³ ³ ³ ³ ³Form 7: Ramps) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.8 ³Changes in ³When walkway levels change, is ³ ³ ³ ³ ³4.5.2 ³Level ³the vertical difference between³ ³ ³ ³ ³ ³ ³them less than 1/4 inch? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are changes in level between ³ ³ ³ ³ ³ ³ ³1/4 inch and 1/2 inch beveled ³ ³ ³ ³ ³ ³ ³with a slope no greater than ³ ³ ³ ³ ³ ³ ³1:2? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are curb ramps, ramps, or ³ ³ ³ ³ ³ ³ ³elevators used for changes in ³ ³ ³ ³ ³ ³ ³level greater than 1/2 inch? ³ ³ ³ ³ ³ ³ ³(Lifts may only be used in ³ ³ ³ ³ ³ ³ ³certain limited situations in ³ ³ ³ ³ ³ ³ ³new construction. See Minimum ³ ³ ³ ³ ³ ³ ³Requirements Summary Sheet B ³ ³ ³ ³ ³ ³ ³and ADAAG 4.1.3(5)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the curb ramp, ramp, or ³ ³ ³ ³ ³ ³ ³elevator comply with 4.7, 4.8, ³ ³ ³ ³ ³ ³ ³or 4.10? (Use Form 4: Curb ³ ³ ³ ³ ³ ³ ³Ramps; Form 7: Ramps; or Form ³ ³ ³ ³ ³ ³ ³13: Elevators) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.6 ³Surface ³Are accessible route surfaces ³ ³ ³ ³ ³4.5.1 ³ ³stable, firm and ³ ³ ³ ³ ³ ³ ³slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.5.4 ³Grates ³Is the smaller dimension of ³ ³ ³ ³ ³ ³ ³grate openings no more than ³ ³ ³ ³ ³ ³ ³1/2 inch, and are long ³ ³ ³ ³ ³ ³ ³dimensions of rectangular gaps ³ ³ ³ ³ ³ ³ ³placed perpendicular to the ³ ³ ³ ³ ³ ³ ³usual direction of travel? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 3-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(7) ³Directional ³Do signs which provide ³ ³ ³ ³ ³4.30.1 ³and ³direction to, or information ³ ³ ³ ³ ³ ³Informational ³about, functional spaces of the³ ³ ³ ³ ³ ³Signs ³building, comply with 4.30.2, ³ ³ ³ ³ ³ ³ ³4.30.3, and 4.30.5? (Use Form ³ ³ ³ ³ ³ ³ ³19: Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(7) ³Room ³Do signs which designate ³ ³ ³ ³ ³4.30.1 ³Identification ³permanent rooms and spaces ³ ³ ³ ³ ³ ³Signs ³comply with 4.30.4, 4.30.5, and³ ³ ³ ³ ³ ³ ³4.30.6? (Use Form 19: Signage)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(7) ³Symbols ³If provided, are the following ³ ³ ³ ³ ³4.30.7 ³ ³elements identified by the ³ ³ ³ ³ ³ ³ ³International Symbol of ³ ³ ³ ³ ³ ³ ³Accessibility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³(a) accessible parking spaces; ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(b) accessible passenger ³ ³ ³ ³ ³ ³ ³loading zones; ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(c) accessible entrances when ³ ³ ³ ³ ³ ³ ³not all are accessible; ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(d) accessible toilet and ³ ³ ³ ³ ³ ³ ³bathing facilities when not all³ ³ ³ ³ ³ ³ ³are accessible ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(8)(d)³Directions to ³When not all entrances are ³ ³ ³ ³ ³ ³Accessible ³accessible, is there ³ ³ ³ ³ ³ ³Entrance ³directional signage ³ ³ ³ ³ ³ ³ ³indicating the accessible ³ ³ ³ ³ ³ ³ ³route to an accessible ³ ³ ³ ³ ³ ³ ³entrance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.5 ³Hazardous ³If a walk crosses or adjoins a ³ ³ ³ ³ ³ ³Vehicular ³vehicular way, and the walking ³ ³ ³ ³ ³ ³Areas ³surfaces are not separated by ³ ³ ³ ³ ³ ³Detectable ³curbs, railings, or other ³ ³ ³ ³ ³ ³Warnings ³elements between the pedestrian³ ³ ³ ³ ³ ³ ³areas and vehicular areas, is ³ ³ ³ ³ ³ ³ ³the boundary between the areas ³ ³ ³ ³ ³ ³ ³defined by a continuous ³ ³ ³ ³ ³ ³ ³detectable warning at least 36 ³ ³ ³ ³ ³ ³ ³inches wide complying with ³ ³ ³ ³ ³ ³ ³4.29.2? (Use Form 21: ³ ³ ³ ³ ³ ³ ³Detectable Warnings) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 3-3 SURVEY FORM 4: CURB RAMPS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Curb Ramp Location: See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.1 ³Curb Ramp ³Is there a curb ramp wherever ³ ³ ³ ³ ³ ³Location ³an accessible route crosses a ³ ³ ³ ³ ³ ³ ³curb? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.2 ³Slope ³Is the slope of the curb ramp ³ ³ ³ ³ ³4.8.2 ³ ³1:12 or less in new ³ ³ ³ ³ ³ ³ ³construction? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.2 ³Transition ³Is the transition from the curb³ ³ ³ ³ ³ ³ ³ramp to the walkway and to the ³ ³ ³ ³ ³ ³ ³road or gutter flush and free ³ ³ ³ ³ ³ ³ ³of abrupt changes? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Counter Slope ³Are the running slopes of the ³ ³ ³ ³ ³ ³ ³road, gutter or accessible ³ ³ ³ ³ ³ ³ ³route adjoining the ramp no ³ ³ ³ ³ ³ ³ ³greater than 1:20? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.3 ³Width ³Is the width of the curb ramp, ³ ³ ³ ³ ³ ³ ³not including the flared sides,³ ³ ³ ³ ³ ³ ³at least 36 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.4 ³Surface ³Is the surface of the curb ramp³ ³ ³ ³ ³4.5.1 ³ ³stable, firm and ³ ³ ³ ³ ³ ³ ³slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.5 ³Side Flares ³If the curb ramp is located ³ ³ ³ ³ ³ ³ ³where pedestrians must walk ³ ³ ³ ³ ³ ³ ³across it or where it is not ³ ³ ³ ³ ³ ³ ³protected by handrails or guard³ ³ ³ ³ ³ ³ ³rails, does it have flared ³ ³ ³ ³ ³ ³ ³sides? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Side Flare ³Do these flared sides have a ³ ³ ³ ³ ³ ³Slope ³slope of 1:10 or less? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where the space at the top of ³ ³ ³ ³ ³ ³ ³the ramp is less than 48 inches³ ³ ³ ³ ³ ³ ³and wheelchair users must use ³ ³ ³ ³ ³ ³ ³the side flares for access, do ³ ³ ³ ³ ³ ³ ³the flared sides have a slope ³ ³ ³ ³ ³ ³ ³of 1:12 or less? (See Figure ³ ³ ³ ³ ³ ³ ³12(a)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.5 ³Returned ³If sharp return curb cuts are ³ ³ ³ ³ ³ ³Curbs ³present, is pedestrian cross ³ ³ ³ ³ ³ ³ ³traffic prohibited by walls, ³ ³ ³ ³ ³ ³ ³guardrails, shrubbery, or other³ ³ ³ ³ ³ ³ ³elements? (See Figure 12(b)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.6 ³Built-up Curb ³Are built-up curb ramps located³ ³ ³ ³ ³4.6.3 ³Ramps ³so that they do not project ³ ³ ³ ³ ³ ³ ³into vehicular traffic lanes or³ ³ ³ ³ ³ ³ ³parking access aisles? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 4-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.7 ³Detectable ³Does the curb ramp have a ³ ³ ³ ³ ³ ³Warning ³detectable warning? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.2 ³Domes ³Does the detectable warning ³ ³ ³ ³ ³ ³ ³consist of raised truncated ³ ³ ³ ³ ³ ³ ³domes? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Size and ³Are the truncated domes 0.9 ³ ³ ³ ³ ³ ³Spacing ³inches in diameter and 0.2 ³ ³ ³ ³ ³ ³ ³inches in height with a ³ ³ ³ ³ ³ ³ ³center-to-center spacing of ³ ³ ³ ³ ³ ³ ³2.35 inches? All measurements ³ ³ ³ ³ ³ ³ ³are nominal. (See Figures ³ ³ ³ ³ ³ ³ ³below) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Visual ³Does the detectable warning ³ ³ ³ ³ ³ ³Contrast ³contrast visually with ³ ³ ³ ³ ³ ³ ³adjoining surfaces ³ ³ ³ ³ ³ ³ ³(light-on-dark or ³ ³ ³ ³ ³ ³ ³dark-on-light)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the material used to provide³ ³ ³ ³ ³ ³ ³contrast an integral part of ³ ³ ³ ³ ³ ³ ³the walking surface? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.8 ³Parked ³Are curb ramps located or ³ ³ ³ ³ ³ ³Vehicles ³protected so that they will not³ ³ ³ ³ ³ ³ ³be obstructed by parked ³ ³ ³ ³ ³ ³ ³vehicles? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.9 ³Curb Ramps ³Are curb ramps at crosswalks ³ ³ ³ ³ ³ ³at Crosswalks ³wholly contained within the ³ ³ ³ ³ ³ ³ ³crosswalk lines, except for the³ ³ ³ ³ ³ ³ ³flared sides? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.10 ³Diagonal Curb ³If diagonal (or corner-type) ³ ³ ³ ³ ³ ³Ramps ³curb ramps have returned curbs ³ ³ ³ ³ ³ ³ ³or other well-defined edges, ³ ³ ³ ³ ³ ³ ³are these edges parallel to the³ ³ ³ ³ ³ ³ ³direction of the pedestrian ³ ³ ³ ³ ³ ³ ³traffic flow? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Bottom of ³Is there at least 48 inches ³ ³ ³ ³ ³ ³Diagonal ³clear space within the ³ ³ ³ ³ ³ ³ ³crosswalk lines at the bottom ³ ³ ³ ³ ³ ³ ³of a diagonal curb ramp? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Straight ³If the diagonal curb ramp has ³ ³ ³ ³ ³ ³Curb ³flared sides, is there at least³ ³ ³ ³ ³ ³ ³a 24 inch segment of straight ³ ³ ³ ³ ³ ³ ³curb located on each side of ³ ³ ³ ³ ³ ³ ³the curb ramp within the ³ ³ ³ ³ ³ ³ ³crosswalk lines? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.11 ³Island ³Where an accessible pathway ³ ³ ³ ³ ³ ³ ³crosses an island, is the ³ ³ ³ ³ ³ ³ ³island cut through at street ³ ³ ³ ³ ³ ³ ³level? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are there curb ramps on both ³ ³ ³ ³ ³ ³ ³sides and a level area at least³ ³ ³ ³ ³ ³ ³48 inches long between them? ³ ³ ³ ³ ³ ³ ³(With a 6 inch high curb, the ³ ³ ³ ³ ³ ³ ³island will be at least 16 feet³ ³ ³ ³ ³ ³ ³wide.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 4-2 4-3 Section] SURVEY FORM 5: DRINKING FOUNTAINS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Fountain Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(10)(a)³Water ³Where there is only one ³ ³ ³ ³ ³4.15.1 ³Fountains ³drinking fountain on a floor, ³ ³ ³ ³ ³ ³ ³is there one accessible to ³ ³ ³ ³ ³ ³ ³wheelchair users in accordance ³ ³ ³ ³ ³ ³ ³with 4.15 (see below) and one ³ ³ ³ ³ ³ ³ ³accessible to persons who have ³ ³ ³ ³ ³ ³ ³difficulty bending or stooping ³ ³ ³ ³ ³ ³ ³(e.g., drinking fountains ³ ³ ³ ³ ³ ³ ³mounted at standard height or a³ ³ ³ ³ ³ ³ ³water cooler)? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(10)(b)³ ³Where there is more than one ³ ³ ³ ³ ³4.15.1 ³ ³drinking fountain on a floor, ³ ³ ³ ³ ³ ³ ³do 50% comply with 4.15 (See ³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(10) ³Accessible ³Is the accessible drinking ³ ³ ³ ³ ³ ³Route ³fountain on an accessible ³ ³ ³ ³ ³ ³ ³route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.15.5(2) ³Clearance ³If the unit is free-standing or³ ³ ³ ³ ³ ³Fountains ³built-in and does not have a ³ ³ ³ ³ ³ ³Without Knee ³clear space underneath it, does³ ³ ³ ³ ³ ³Space ³it have a clear floor space ³ ³ ³ ³ ³ ³ ³alongside it at least 30 by 48 ³ ³ ³ ³ ³ ³ ³inches which allows a ³ ³ ³ ³ ³ ³ ³wheelchair user to make a ³ ³ ³ ³ ³ ³ ³parallel approach? (See Figures³ ³ ³ ³ ³ ³ ³27(c) and (d)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.15.5(1) ³Fountains With ³If the unit is wall- or ³ ³ ³ ³ ³ ³Knee Space ³post-mounted, is there a clear ³ ³ ³ ³ ³ ³ ³knee space between the bottom ³ ³ ³ ³ ³ ³ ³of the apron and the floor ³ ³ ³ ³ ³ ³ ³which is at least 27 inches ³ ³ ³ ³ ³ ³ ³high, 30 inches wide, and 17 to³ ³ ³ ³ ³ ³ ³19 inches deep? (See Figures ³ ³ ³ ³ ³ ³ ³27(a) and (b)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does such a unit also have a ³ ³ ³ ³ ³ ³ ³clear floor space at least 30 ³ ³ ³ ³ ³ ³ ³by 48 inches perpendicular to ³ ³ ³ ³ ³ ³ ³the unit allowing a forward ³ ³ ³ ³ ³ ³ ³approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.4.1 ³Protruding ³If a wall mounted drinking ³ ³ ³ ³ ³ ³Objects ³fountain has a leading edge ³ ³ ³ ³ ³ ³ ³between 27 and 80 inches from ³ ³ ³ ³ ³ ³ ³the floor, does it project less³ ³ ³ ³ ³ ³ ³than 4 inches into the pathway?³ ³ ³ ³ ³ ³ ³(Wall mounted fountains with ³ ³ ³ ³ ³ ³ ³leading edges at or below 27 ³ ³ ³ ³ ³ ³ ³inches may project any amount ³ ³ ³ ³ ³ ³ ³so long as the required clear ³ ³ ³ ³ ³ ³ ³width of an accessible route is³ ³ ³ ³ ³ ³ ³not reduced). ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 5-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.15.2 ³Spout - Height ³Is the spout outlet no higher ³ ³ ³ ³ ³ ³ ³than 36 inches from the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.15.3 ³Location ³Is the spout at the front of ³ ³ ³ ³ ³ ³ ³the unit, with a water flow ³ ³ ³ ³ ³ ³ ³trajectory parallel or nearly ³ ³ ³ ³ ³ ³ ³parallel to the front edge? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Water Flow ³If the fountain has a round or ³ ³ ³ ³ ³ ³ ³oval bowl, is the water flow ³ ³ ³ ³ ³ ³ ³within 3 inches of the front ³ ³ ³ ³ ³ ³ ³edge of the fountain? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the water flow at least 4 ³ ³ ³ ³ ³ ³ ³inches high to allow the ³ ³ ³ ³ ³ ³ ³insertion of a cup under the ³ ³ ³ ³ ³ ³ ³flow? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.15.4 ³Controls ³Are the controls located on the³ ³ ³ ³ ³ ³Location ³front or the side near the ³ ³ ³ ³ ³ ³ ³front edge? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.15.4 ³Operation ³Are the controls operable with ³ ³ ³ ³ ³4.27.4 ³ ³one hand? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the controls operable ³ ³ ³ ³ ³ ³ ³without tight grasping, ³ ³ ³ ³ ³ ³ ³pinching, or twisting of the ³ ³ ³ ³ ³ ³ ³wrist? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force to operate the ³ ³ ³ ³ ³ ³ ³controls no greater than 5 lbf?³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 5-2 5-3 SURVEY FORM 6: TELEPHONES Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Telephone Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(17)(a)³Telephones ³At each bank of public pay ³ ³ ³ ³ ³4.31.1 ³ ³telephones, is there at least ³ ³ ³ ³ ³ ³ ³one telephone per bank ³ ³ ³ ³ ³ ³ ³accessible to wheelchair users ³ ³ ³ ³ ³ ³ ³complying with 4.31.2 through ³ ³ ³ ³ ³ ³ ³4.31.8 (See below)? If there ³ ³ ³ ³ ³ ³ ³is only one public pay ³ ³ ³ ³ ³ ³ ³telephone per floor, does it ³ ³ ³ ³ ³ ³ ³comply with 4.31.2 through ³ ³ ³ ³ ³ ³ ³4.31.8? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where two or more banks of ³ ³ ³ ³ ³ ³ ³public pay telephones are ³ ³ ³ ³ ³ ³ ³provided on a floor, does at ³ ³ ³ ³ ³ ³ ³least one telephone per floor ³ ³ ³ ³ ³ ³ ³provide for a forward reach ³ ³ ³ ³ ³ ³ ³complying with 4.2.5 (See ³ ³ ³ ³ ³ ³ ³below)? (For exterior ³ ³ ³ ³ ³ ³ ³installations only, if dial ³ ³ ³ ³ ³ ³ ³tone first service is ³ ³ ³ ³ ³ ³ ³available, a side reach ³ ³ ³ ³ ³ ³ ³telephone may be installed ³ ³ ³ ³ ³ ³ ³instead of a forward reach ³ ³ ³ ³ ³ ³ ³telephone.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.17(a) ³Clear Floor ³Does the accessible telephone ³ ³ ³ ³ ³4.31.2 ³Space ³have at least 30 by 48 inches ³ ³ ³ ³ ³4.2.4 ³ ³clear floor space that allows ³ ³ ³ ³ ³ ³ ³either a forward or parallel ³ ³ ³ ³ ³ ³ ³approach by wheelchair users? ³ ³ ³ ³ ³ ³ ³(Where two or more banks of ³ ³ ³ ³ ³ ³ ³public telephones are provided ³ ³ ³ ³ ³ ³ ³on a floor, at least one ³ ³ ³ ³ ³ ³ ³telephone per floor must allow ³ ³ ³ ³ ³ ³ ³a forward approach and be ³ ³ ³ ³ ³ ³ ³mounted so the highest operable³ ³ ³ ³ ³ ³ ³part is no higher than 48 ³ ³ ³ ³ ³ ³ ³inches.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Accessible ³Is there an accessible route at³ ³ ³ ³ ³ ³Route ³least 36 inches wide adjoining ³ ³ ³ ³ ³ ³ ³or overlapping the clear floor ³ ³ ³ ³ ³ ³ ³space? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.3 ³Forward ³If the clear floor space allows³ ³ ³ ³ ³4.2.5 ³Reach ³only a forward approach, is the³ ³ ³ ³ ³ ³Telephone ³highest operable part of the ³ ³ ³ ³ ³ ³ ³telephone no more than 48 ³ ³ ³ ³ ³ ³ ³inches from the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.3 ³Side Reach ³If the clear floor space allows³ ³ ³ ³ ³4.2.6 ³Telephone ³only a parallel approach, is ³ ³ ³ ³ ³ ³ ³the highest operable part of ³ ³ ³ ³ ³ ³ ³the telephone no more than 54 ³ ³ ³ ³ ³ ³ ³inches from the floor? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 6-1 ÚÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.7 ³Directories ³Are telephone books also within³ ³ ³ ³ ³ ³ ³these reach ranges? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.6 ³Controls ³Does the telephone have ³ ³ ³ ³ ³ ³ ³pushbutton controls unless such³ ³ ³ ³ ³ ³ ³service is unavailable? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.8 ³Cord ³Is the cord from the telephone ³ ³ ³ ³ ³ ³ ³to the handset at least 29 ³ ³ ³ ³ ³ ³ ³inches long? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(17)(b)³Volume ³Is each accessible telephone ³ ³ ³ ³ ³ ³Controls ³equipped with a volume control?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are 25% of all other public ³ ³ ³ ³ ³ ³ ³telephones equipped with volume³ ³ ³ ³ ³ ³ ³controls and dispersed among ³ ³ ³ ³ ³ ³ ³all types of public telephones?³ ³ ³ ³ ³ ³ ³(Public telephones include ³ ³ ³ ³ ³ ³ ³public pay telephones and ³ ³ ³ ³ ³ ³ ³public closed-circuit ³ ³ ³ ³ ³ ³ ³telephones.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.7(2) ³Signs ³Are volume controlled ³ ³ ³ ³ ³ ³ ³telephones identified by a sign³ ³ ³ ³ ³ ³ ³showing a handset with ³ ³ ³ ³ ³ ³ ³radiating sound waves? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.5 ³Amplification ³Are volume controls capable of ³ ³ ³ ³ ³ ³ ³amplification between 12 dbA ³ ³ ³ ³ ³ ³ ³and 18 dbA above normal? (If ³ ³ ³ ³ ³ ³ ³an automatic reset button is ³ ³ ³ ³ ³ ³ ³provided, the maximum of 18 dbA³ ³ ³ ³ ³ ³ ³may be exceeded.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Hearing Aid ³Are telephones hearing aid ³ ³ ³ ³ ³ ³Compatible ³compatible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(17)(c)³Text ³If there are 4 or more public ³ ³ ³ ³ ³ ³Telephones/ ³pay telephones (with at least ³ ³ ³ ³ ³ ³TDDs ³one in an interior location), ³ ³ ³ ³ ³ ³General ³is there at least one interior ³ ³ ³ ³ ³ ³ ³public text telephone? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Specific ³If an interior public pay ³ ³ ³ ³ ³ ³Facilities ³telephone is provided in a ³ ³ ³ ³ ³ ³ ³stadium or arena, convention ³ ³ ³ ³ ³ ³ ³center, a hotel with a ³ ³ ³ ³ ³ ³ ³convention center, or a covered³ ³ ³ ³ ³ ³ ³mall, is there at least one ³ ³ ³ ³ ³ ³ ³interior public text telephone ³ ³ ³ ³ ³ ³ ³in the facility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Hospitals ³If there is a public pay ³ ³ ³ ³ ³ ³ ³telephone in or adjacent to a ³ ³ ³ ³ ³ ³ ³hospital emergency room, a ³ ³ ³ ³ ³ ³ ³hospital recovery room, or a ³ ³ ³ ³ ³ ³ ³hospital waiting room, is there³ ³ ³ ³ ³ ³ ³a public text telephone in each³ ³ ³ ³ ³ ³ ³such location? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 6-2 ÚÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.9(3) ³Equivalent ³If a required text telephone is³ ³ ³ ³ ³ ³Facilitation ³not provided, is equivalent ³ ³ ³ ³ ³ ³ ³facilitation provided? (e.g., ³ ³ ³ ³ ³ ³ ³A portable text telephone may ³ ³ ³ ³ ³ ³ ³be made available in a hotel at³ ³ ³ ³ ³ ³ ³the registration desk if it is ³ ³ ³ ³ ³ ³ ³available on a 24-hour basis ³ ³ ³ ³ ³ ³ ³for use with nearby public pay ³ ³ ³ ³ ³ ³ ³telephones. In this instance, ³ ³ ³ ³ ³ ³ ³at least one public pay ³ ³ ³ ³ ³ ³ ³telephone must have a shelf and³ ³ ³ ³ ³ ³ ³outlet complying with 4.31.9(2)³ ³ ³ ³ ³ ³ ³(see below) to accommodate a ³ ³ ³ ³ ³ ³ ³portable text telephone. In ³ ³ ³ ³ ³ ³ ³addition, if an acoustic ³ ³ ³ ³ ³ ³ ³coupler is used, the telephone ³ ³ ³ ³ ³ ³ ³handset cord must be ³ ³ ³ ³ ³ ³ ³sufficiently long so as to ³ ³ ³ ³ ³ ³ ³allow connection of the text ³ ³ ³ ³ ³ ³ ³telephone and the telephone ³ ³ ³ ³ ³ ³ ³receiver. Directional signage ³ ³ ³ ³ ³ ³ ³must be provided in compliance ³ ³ ³ ³ ³ ³ ³with 4.30.7.) (See below) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.9 ³Mounting ³Is a required text telephone ³ ³ ³ ³ ³ ³Location ³permanently mounted within, or ³ ³ ³ ³ ³ ³ ³adjacent to, the telephone ³ ³ ³ ³ ³ ³ ³enclosure? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Cord Length ³If an acoustic coupler is used,³ ³ ³ ³ ³ ³ ³is the telephone cord ³ ³ ³ ³ ³ ³ ³sufficiently long enough to ³ ³ ³ ³ ³ ³ ³allow connection of the text ³ ³ ³ ³ ³ ³ ³telephone to the telephone ³ ³ ³ ³ ³ ³ ³receiver? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.7(3) ³TDD Symbol ³Are required text telephones ³ ³ ³ ³ ³ ³ ³identified by the international³ ³ ³ ³ ³ ³ ³TDD symbol? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³Directional ³Is the directional signage ³ ³ ³ ³ ³4.30.1 ³Signs ³complying with 4.30.2, 4.30.3, ³ ³ ³ ³ ³4.30.7 ³ ³and 4.30.5 provided to indicate³ ³ ³ ³ ³ ³ ³the location of the text ³ ³ ³ ³ ³ ³ ³telephone? (Use Form 19: ³ ³ ³ ³ ³ ³ ³Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the directional signage ³ ³ ³ ³ ³ ³ ³placed adjacent to all ³ ³ ³ ³ ³ ³ ³telephone banks which do not ³ ³ ³ ³ ³ ³ ³contain a text telephone? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(If the facility does not have ³ ³ ³ ³ ³ ³ ³any telephone banks, the ³ ³ ³ ³ ³ ³ ³directional signage must be ³ ³ ³ ³ ³ ³ ³provided at the entrance (e.g.,³ ³ ³ ³ ³ ³ ³in a building directory.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(17)(d)³Text ³If there are 3 or more ³ ³ ³ ³ ³4.31.9(2) ³Telephone, ³telephones in an interior bank ³ ³ ³ ³ ³ ³Shelves ³of telephones, does at least ³ ³ ³ ³ ³ ³& Outlets ³one telephone have a shelf and ³ ³ ³ ³ ³ ³ ³electrical outlet for use with ³ ³ ³ ³ ³ ³ ³a portable text telephone? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the shelf large enough to ³ ³ ³ ³ ³ ³ ³accommodate a text telephone ³ ³ ³ ³ ³ ³ ³and does it provide at least 6 ³ ³ ³ ³ ³ ³ ³inches of vertical clearance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the telephone handset ³ ³ ³ ³ ³ ³ ³capable of being placed flush ³ ³ ³ ³ ³ ³ ³on the surface of the shelf? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 6-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the directional signage ³ ³ ³ ³ ³ ³ ³placed adjacent to all ³ ³ ³ ³ ³ ³ ³telephone banks which do not ³ ³ ³ ³ ³ ³ ³contain a text telephone? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³(If the facility does not have ³ ³ ³ ³ ³ ³ ³any telephone banks, the ³ ³ ³ ³ ³ ³ ³directional signage must be ³ ³ ³ ³ ³ ³ ³provided at the entrance (e.g.,³ ³ ³ ³ ³ ³ ³in a building directory.)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.31.4 ³Protruding ³If a wall-mounted telephone has³ ³ ³ ³ ³4.4.1 ³Objects ³leading edges between 27 and 80³ ³ ³ ³ ³ ³ ³inches from the floor, does it ³ ³ ³ ³ ³ ³ ³project less than 4 inches into³ ³ ³ ³ ³ ³ ³the pathway? (Wall mounted ³ ³ ³ ³ ³ ³ ³telephones or their enclosures ³ ³ ³ ³ ³ ³ ³with leading edges at or below ³ ³ ³ ³ ³ ³ ³27 inches may project any ³ ³ ³ ³ ³ ³ ³amount so long as the required ³ ³ ³ ³ ³ ³ ³clear width of an accessible ³ ³ ³ ³ ³ ³ ³route is not reduced.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If a telephone is mounted on a ³ ³ ³ ³ ³ ³ ³post with leading edges between³ ³ ³ ³ ³ ³ ³27 and 80 inches high, does it ³ ³ ³ ³ ³ ³ ³project less than 12 inches ³ ³ ³ ³ ³ ³ ³into a perpendicular route of ³ ³ ³ ³ ³ ³ ³travel? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there an accessible route at³ ³ ³ ³ ³ ³ ³least 36 inches wide alongside ³ ³ ³ ³ ³ ³ ³the telephone? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 6-4 SURVEY FORM 7: RAMPS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Ramp Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.1 ³Ramps ³Does each part of an accessible³ ³ ³ ³ ³ ³ ³route with a slope greater than³ ³ ³ ³ ³ ³ ³1:20 comply with 4.8 (See ³ ³ ³ ³ ³ ³ ³below)? (For curb ramps use ³ ³ ³ ³ ³ ³ ³Form 4: Curb Ramps) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.2 ³Running ³Is the ramp slope 1:12 or less?³ ³ ³ ³ ³ ³Slope ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Maximum ³Is the rise for any run a ³ ³ ³ ³ ³ ³Rise ³maximum of 30 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.6 ³Cross Slope ³Is the cross slope of the ramp ³ ³ ³ ³ ³ ³ ³surface no greater than 1:50? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.6 ³Surface ³Is the ramp surface stable, ³ ³ ³ ³ ³4.5 ³ ³firm and slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Grates ³Is the smaller dimension of ³ ³ ³ ³ ³ ³ ³grate openings no more than 1/2³ ³ ³ ³ ³ ³ ³inch, and are long dimensions ³ ³ ³ ³ ³ ³ ³of rectangular gaps placed ³ ³ ³ ³ ³ ³ ³perpendicular to the usual ³ ³ ³ ³ ³ ³ ³direction of travel? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.3 ³Clear Width ³Is the clear width (between ³ ³ ³ ³ ³ ³ ³handrails) of the ramp at least³ ³ ³ ³ ³ ³ ³36 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.4 ³Landings ³Is there a level landing at the³ ³ ³ ³ ³ ³ ³top and bottom of each ramp and³ ³ ³ ³ ³ ³ ³each ramp run? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Size ³Is each landing at least as ³ ³ ³ ³ ³ ³ ³wide as the ramp and at least ³ ³ ³ ³ ³ ³ ³60 inches long? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where the ramp changes ³ ³ ³ ³ ³ ³ ³direction, is there a landing ³ ³ ³ ³ ³ ³ ³of at least 60 by 60 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Landings with ³If a doorway is located on a ³ ³ ³ ³ ³ ³Doors ³landing, does the area in front³ ³ ³ ³ ³ ³ ³of the door comply with the ³ ³ ³ ³ ³ ³ ³maneuvering space requirements ³ ³ ³ ³ ³ ³ ³for doors? (Use Form 11: Doors ³ ³ ³ ³ ³ ³ ³and Gates) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 7-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.7 ³Edge ³If a ramp or landing has a drop³ ³ ³ ³ ³ ³Protection ³off, does it have a minimum 2 ³ ³ ³ ³ ³ ³ ³inch curb, a wall, railings, or³ ³ ³ ³ ³ ³ ³projecting surfaces which ³ ³ ³ ³ ³ ³ ³prevent people from falling ³ ³ ³ ³ ³ ³ ³off? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.8 ³Drainage ³Are outside ramps and their ³ ³ ³ ³ ³ ³ ³approaches designed so that ³ ³ ³ ³ ³ ³ ³water will not accumulate on ³ ³ ³ ³ ³ ³ ³walking surfaces? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.5 ³Handrails ³If the ramp rises more than 6 ³ ³ ³ ³ ³ ³ ³inches or is longer than 72 ³ ³ ³ ³ ³ ³ ³inches, does it have a handrail³ ³ ³ ³ ³ ³ ³on each side? (Handrails are ³ ³ ³ ³ ³ ³ ³not required on curb ramps or ³ ³ ³ ³ ³ ³ ³adjacent to seating in assembly³ ³ ³ ³ ³ ³ ³areas.) On dogleg or ³ ³ ³ ³ ³ ³ ³switchback ramps, is the inside³ ³ ³ ³ ³ ³ ³handrail continuous? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Gripping ³Are the gripping surfaces ³ ³ ³ ³ ³ ³Surface ³continuous? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Mounting ³Are handrails fixed so that ³ ³ ³ ³ ³ ³ ³they do not rotate within their³ ³ ³ ³ ³ ³ ³fittings? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Height ³Is the top of the handrail ³ ³ ³ ³ ³ ³ ³between 34 and 38 inches above ³ ³ ³ ³ ³ ³ ³the ramp surface? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Handrail ³At ends of handrails, are there³ ³ ³ ³ ³ ³Extension ³at least 12 inches of handrail,³ ³ ³ ³ ³ ³ ³parallel to the floor or ground³ ³ ³ ³ ³ ³ ³surface, extending beyond the ³ ³ ³ ³ ³ ³ ³top and bottom of the ramp ³ ³ ³ ³ ³ ³ ³segment? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Ends of ³Are the ends of handrails ³ ³ ³ ³ ³ ³Handrails ³rounded or returned smoothly to³ ³ ³ ³ ³ ³ ³the floor, wall, or post? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.5 ³Diameter ³Is the diameter of the handrail³ ³ ³ ³ ³4.26.2 ³ ³between 1-1/4 and 1-1/2 inches?³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Does the shape provide an ³ ³ ³ ³ ³ ³ ³equivalent gripping surface? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Standard pipe sizes ³ ³ ³ ³ ³ ³ ³designated by the industry as ³ ³ ³ ³ ³ ³ ³1-1/4 to 1-1/2 inches are ³ ³ ³ ³ ³ ³ ³acceptable for purposes of this³ ³ ³ ³ ³ ³ ³section. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.5 ³Clearance ³Is the clear space between ³ ³ ³ ³ ³4.26.2 ³ ³handrails and walls exactly ³ ³ ³ ³ ³ ³ ³1-1/2 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.5 ³Clearance in ³If a handrail is located in a ³ ³ ³ ³ ³4.26.2 ³Recess ³recess, is the recess no more ³ ³ ³ ³ ³ ³ ³than 3 inches deep extending at³ ³ ³ ³ ³ ³ ³least 18 inches above the top ³ ³ ³ ³ ³ ³ ³of the rail? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.5 ³Structural ³Do the handrails meet the ³ ³ ³ ³ ³4.26.3 ³Strength ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for bending stress³ ³ ³ ³ ³ ³ ³and shear stress? (See 4.26.3) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 7-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.5 ³ ³Do the fasteners meet the ³ ³ ³ ³ ³4.26.3 ³ ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for shear force ³ ³ ³ ³ ³ ³ ³and tensile force? (See 4.26.3)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.8.5 ³Hazards ³Are handrail edges free of ³ ³ ³ ³ ³4.26.4 ³ ³sharp or abrasive elements and ³ ³ ³ ³ ³ ³ ³do they have edges with a ³ ³ ³ ³ ³ ³ ³minimum radius of 1/8 inch? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 7-3 SURVEY FORM 8: STAIRS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Stair Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(4) ³Stairs ³Do interior and exterior stairs³ ³ ³ ³ ³4.9.1 ³ ³connecting levels that are not ³ ³ ³ ³ ³ ³ ³connected by an elevator, ramp,³ ³ ³ ³ ³ ³ ³or other accessible means of ³ ³ ³ ³ ³ ³ ³vertical access comply with 4.9³ ³ ³ ³ ³ ³ ³(See below)? (In new ³ ³ ³ ³ ³ ³ ³construction, this condition ³ ³ ³ ³ ³ ³ ³may occur in facilities subject³ ³ ³ ³ ³ ³ ³to the elevator exemption (see ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 1) or where ³ ³ ³ ³ ³ ³ ³mezzanines are exempt in ³ ³ ³ ³ ³ ³ ³restaurants (See 5.4).) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.2 ³Risers/Treads ³In any one flight of stairs, do³ ³ ³ ³ ³ ³ ³all the steps have uniform ³ ³ ³ ³ ³ ³ ³riser heights and tread widths?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the risers closed? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the treads at least 11 ³ ³ ³ ³ ³ ³ ³inches measured from riser to ³ ³ ³ ³ ³ ³ ³riser? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.3 ³Nosings ³Do the nosings project no more ³ ³ ³ ³ ³ ³ ³than 1-1/2 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If nosings do project, do the ³ ³ ³ ³ ³ ³ ³risers slope toward the nosings³ ³ ³ ³ ³ ³ ³or are nosings angled not less ³ ³ ³ ³ ³ ³ ³than 60 degrees from horizontal³ ³ ³ ³ ³ ³ ³to prevent tripping in an ³ ³ ³ ³ ³ ³ ³ascending direction? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the radius of the curvature ³ ³ ³ ³ ³ ³ ³at the leading edge of the ³ ³ ³ ³ ³ ³ ³tread no more than 1/2 inch? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4 ³Handrails ³Do stairways have continuous ³ ³ ³ ³ ³4.26 ³ ³handrails along both sides? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(1) ³ ³On dogleg or switchback stairs,³ ³ ³ ³ ³ ³ ³is the inside handrail ³ ³ ³ ³ ³ ³ ³continuous at landings? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(2) ³ ³At ends of handrails, is there ³ ³ ³ ³ ³ ³ ³at least 12 inches of handrail ³ ³ ³ ³ ³ ³ ³parallel to the floor beyond ³ ³ ³ ³ ³ ³ ³the top riser? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 8-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(2) ³ ³At ends of handrails, is there ³ ³ ³ ³ ³ ³ ³at least one tread width of ³ ³ ³ ³ ³ ³ ³sloping handrail plus at least ³ ³ ³ ³ ³ ³ ³12 inches of horizontal ³ ³ ³ ³ ³ ³ ³handrail beyond the bottom ³ ³ ³ ³ ³ ³ ³riser? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(2) ³ ³If the handrail extension ³ ³ ³ ³ ³ ³ ³protrudes into an accessible ³ ³ ³ ³ ³ ³ ³route, is the handrail ³ ³ ³ ³ ³ ³ ³extension rounded to be 27 ³ ³ ³ ³ ³ ³ ³inches or less from the floor ³ ³ ³ ³ ³ ³ ³in compliance with 4.4? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(3) ³ ³Is the clearance between walls ³ ³ ³ ³ ³ ³ ³and handrails exactly 1-1/2 ³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(4) ³ ³Is the gripping surface ³ ³ ³ ³ ³ ³ ³uninterrupted by newel posts or³ ³ ³ ³ ³ ³ ³other obstructions? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(5) ³ ³Are the tops of handrails ³ ³ ³ ³ ³ ³ ³between 34 and 38 inches above ³ ³ ³ ³ ³ ³ ³the stair nosings? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(6) ³ ³Are the ends of handrails ³ ³ ³ ³ ³ ³ ³rounded or returned smoothly to³ ³ ³ ³ ³ ³ ³the floor, wall or post? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4(7) ³ ³Are handrails fixed so that ³ ³ ³ ³ ³ ³ ³they do not rotate within their³ ³ ³ ³ ³ ³ ³fittings? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4 ³ ³Is the outside diameter of the ³ ³ ³ ³ ³4.26.2 ³ ³handrail between 1-1/4 inches ³ ³ ³ ³ ³ ³ ³and 1-1/2 inches? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Does the shape provide an ³ ³ ³ ³ ³ ³ ³equivalent gripping surface? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Standard pipe sizes ³ ³ ³ ³ ³ ³ ³designated by the industry ³ ³ ³ ³ ³ ³ ³1-1/4 to as 1-1/2 inches are ³ ³ ³ ³ ³ ³ ³acceptable for purposes of this³ ³ ³ ³ ³ ³ ³section. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4 ³Clearance in ³If a handrail is located in a ³ ³ ³ ³ ³4.26.2 ³Recess ³recess, is the recess no more ³ ³ ³ ³ ³ ³ ³than 3 inches deep extending at³ ³ ³ ³ ³ ³ ³least 18 inches above the top ³ ³ ³ ³ ³ ³ ³of the rail? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4 ³Structural ³Do the handrails meet the ³ ³ ³ ³ ³4.26.3 ³Strength ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for bending stress³ ³ ³ ³ ³ ³ ³and shear stress? (See 4.26.3)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4 ³ ³Do the fasteners meet the ³ ³ ³ ³ ³4.26.3 ³ ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for shear force ³ ³ ³ ³ ³ ³ ³and tensile force? (See ³ ³ ³ ³ ³ ³ ³4.26.3) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.4 ³Hazards ³Are handrail edges free of ³ ³ ³ ³ ³4.26.4 ³ ³sharp or abrasive elements and ³ ³ ³ ³ ³ ³ ³do they have edges with a ³ ³ ³ ³ ³ ³ ³minimum radius of 1/8 inch? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 8-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.9.6 ³Drainage ³Are outdoor stairs and their ³ ³ ³ ³ ³ ³ ³approaches designed so that ³ ³ ³ ³ ³ ³ ³water does not accumulate on ³ ³ ³ ³ ³ ³ ³walking surfaces? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 8-3 SURVEY FORM 9: PLATFORM LIFTS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Lift Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. 4.1.3(5) EXCEPTION 4: ÄÄ In new construction, platform lifts may be used in lieu of an elevator only under the following conditions and where State and local codes permit. Ä To provide an accessible route to a performing area in an assembly occupancy. Ä To comply with the wheelchair viewing position, line-of-sight, and dispersion requirements in assembly areas with fixed seating. Ä To provide access to incidental occupiable rooms and spaces that are not open to the general public and which house no more than five persons. (This includes, but is not limited to, equipment control rooms and projection booths.) Ä To provide access where existing site constraints or other constraints make use of a ramp or an elevator infeasible. 4.1.6(3)(g): ÄÄ In alterations, the use of platform lifts is not limited to the above conditions. Platform lifts may be used as part of an accessible route in alterations. ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(5) ³Lifts ³In new construction, if a lift ³ ³ ³ ³ ³Exception 4³ ³is installed in lieu of an ³ ³ ³ ³ ³ ³ ³elevator or ramp, was it ³ ³ ³ ³ ³ ³ ³installed consistent with ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 4 (above) ³ ³ ³ ³ ³ ³ ³and in compliance with ³ ³ ³ ³ ³ ³ ³applicable State and local ³ ³ ³ ³ ³ ³ ³codes? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.3 ³Independent ³Can the lift be entered, ³ ³ ³ ³ ³ ³Use ³operated and exited without ³ ³ ³ ³ ³ ³ ³assistance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Platform ³Is the lift platform at least ³ ³ ³ ³ ³4.2.4 ³Size ³30 by 48 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Clear Space ³Is there at least a 30 by 48 ³ ³ ³ ³ ³4.2.4 ³Outside Lift ³inch clear space outside the ³ ³ ³ ³ ³ ³ ³lift positioned for a ³ ³ ³ ³ ³ ³ ³wheelchair user to reach the ³ ³ ³ ³ ³ ³ ³controls from a parallel or ³ ³ ³ ³ ³ ³ ³forward approach and to enter ³ ³ ³ ³ ³ ³ ³the lift? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Controls ³Where a forward reach is ³ ³ ³ ³ ³4.27.3 ³Forward ³provided, is the height of the ³ ³ ³ ³ ³4.2.5 ³Reach ³lift control no more than 48 ³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Side Reach ³Where a side reach is provided,³ ³ ³ ³ ³4.27.3 ³ ³is the height of the lift ³ ³ ³ ³ ³4.2.6 ³ ³control no more than 54 inches?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Operation ³Are the controls operable with ³ ³ ³ ³ ³4.27.4 ³ ³one hand and without tight ³ ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³ ³of the wrist? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³operate the controls no greater³ ³ ³ ³ ³ ³ ³than 5 lbf? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 9-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(1) ³Accessible ³Is the lift on an accessible ³ ³ ³ ³ ³4.3.2 ³Route ³route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Surface ³Is the surface of the lift, as ³ ³ ³ ³ ³4.3.6 ³ ³well as the accessible route to³ ³ ³ ³ ³4.5.1 ³ ³which it connects, stable, firm³ ³ ³ ³ ³ ³ ³and slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Edge Bevel ³If there is a change in level ³ ³ ³ ³ ³4.5.2 ³ ³of between 1/4 and 1/2 inch, is³ ³ ³ ³ ³ ³ ³the edge beveled with a slope ³ ³ ³ ³ ³ ³ ³of 1:2 or less? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.11.2 ³Safety Code ³Does the lift meet the ASME ³ ³ ³ ³ ³ ³ ³A17.1 Safety Code for Elevators³ ³ ³ ³ ³ ³ ³and Escalators, Section XX, ³ ³ ³ ³ ³ ³ ³1990? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 9-2 SURVEY FORM 10: ENTRANCES AND EXITS (AREAS OF RESCUE ASSISTANCE) Use with the Minimum Requirements Summary Sheet and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Entrance and Exit Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Area of Rescue Assistance Location: Total Number of Entrances: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Number of Accessible Entrances: Number of Exits Required by Building/Fire Code: ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(8)(a)³Entrances ³Are at least 50% of all public ³ ³ ³ ³ ³ ³Number ³entrances accessible? ³ ³ ³ ³ ³ ³Accessible: ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Ground Floor ³Is at least one accessible ³ ³ ³ ³ ³ ³Entrance ³entrance on the ground floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Separate Tenant ³Does each separate tenancy have³ ³ ³ ³ ³ ³Entrances ³an accessible entrance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Equivalent to ³Is the number of accessible ³ ³ ³ ³ ³ ³Required Exits ³entrances at least equivalent ³ ³ ³ ³ ³ ³ ³to the number of exits required³ ³ ³ ³ ³ ³ ³by the applicable building/fire³ ³ ³ ³ ³ ³ ³codes? (Use Minimum ³ ³ ³ ³ ³ ³ ³Requirements Summary Sheet C: ³ ³ ³ ³ ³ ³ ³Entrances) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(This does not require an ³ ³ ³ ³ ³ ³ ³increase in the total number of³ ³ ³ ³ ³ ³ ³entrances planned for the ³ ³ ³ ³ ³ ³ ³facility.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Primary ³Where feasible, are the ³ ³ ³ ³ ³ ³Entrance ³accessible entrances the ³ ³ ³ ³ ³ ³ ³entrances used by the majority ³ ³ ³ ³ ³ ³ ³of the people visiting or ³ ³ ³ ³ ³ ³ ³working in the building? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(8)(b)³Pedestrian ³If access is provided for ³ ³ ³ ³ ³ ³Tunnels and ³pedestrians through a ³ ³ ³ ³ ³ ³Elevated ³pedestrian tunnel or elevated ³ ³ ³ ³ ³ ³Walkways ³walkway, is one entrance to the³ ³ ³ ³ ³ ³ ³building from each tunnel or ³ ³ ³ ³ ³ ³ ³walkway accessible? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 10-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Direct Entrance ³If direct access is provided ³ ³ ³ ³ ³ ³From Parking ³for pedestrians from an ³ ³ ³ ³ ³ ³Garage ³enclosed parking garage to the ³ ³ ³ ³ ³ ³ ³building, is at least one ³ ³ ³ ³ ³ ³ ³direct entrance from the garage³ ³ ³ ³ ³ ³ ³to the building accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(8)(c)³Public ³If the only entrance is a ³ ³ ³ ³ ³4.14.2 ³Entrance ³service entrance, is it ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(7) ³Directional ³If an entrance is not ³ ³ ³ ³ ³4.30.1 ³Signs ³accessible, are there ³ ³ ³ ³ ³ ³ ³directional signs indicating ³ ³ ³ ³ ³ ³ ³the location of the nearest ³ ³ ³ ³ ³ ³ ³accessible entrance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the directional signs ³ ³ ³ ³ ³ ³ ³comply with 4.30.2, 4.30.3, ³ ³ ³ ³ ³ ³ ³and 4.30.5? (Use Form 19: ³ ³ ³ ³ ³ ³ ³Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.14.1 ³Accessible ³Within the boundaries of the ³ ³ ³ ³ ³4.3.2(1) ³Route ³site, is the accessible ³ ³ ³ ³ ³4.3 ³ ³entrance connected by an ³ ³ ³ ³ ³ ³ ³accessible route to existing ³ ³ ³ ³ ³ ³ ³public transportation stops, ³ ³ ³ ³ ³ ³ ³accessible parking and ³ ³ ³ ³ ³ ³ ³passenger loading zones, and to³ ³ ³ ³ ³ ³ ³public streets or sidewalks? ³ ³ ³ ³ ³ ³ ³(Use Form 3: Exterior ³ ³ ³ ³ ³ ³ ³Accessible Routes) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the accessible entrance ³ ³ ³ ³ ³ ³ ³connected by an accessible ³ ³ ³ ³ ³ ³ ³route to all accessible ³ ³ ³ ³ ³ ³ ³elements or spaces within the ³ ³ ³ ³ ³ ³ ³building or facility? (Use ³ ³ ³ ³ ³ ³ ³Form 12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.14.1 ³Level Change ³If there is a vertical level ³ ³ ³ ³ ³4.3.8 ³ ³change between 1/4 inch and 1/2³ ³ ³ ³ ³ ³ ³inch at or along the route to ³ ³ ³ ³ ³ ³ ³the entrance, is the edge ³ ³ ³ ³ ³ ³ ³beveled with a slope of 1:2 or ³ ³ ³ ³ ³ ³ ³less? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If there is a vertical level ³ ³ ³ ³ ³ ³ ³change greater than 1/2 inch at³ ³ ³ ³ ³ ³ ³the entrance, is a curb ramp, ³ ³ ³ ³ ³ ³ ³ramp, or elevator complying ³ ³ ³ ³ ³ ³ ³with 4.7, 4.8, or 4.10 ³ ³ ³ ³ ³ ³ ³provided? (Use Form 4: Curb ³ ³ ³ ³ ³ ³ ³Ramps; Form 7: Ramps; or Form ³ ³ ³ ³ ³ ³ ³13: Elevators) (Lifts may be ³ ³ ³ ³ ³ ³ ³used in certain limited ³ ³ ³ ³ ³ ³ ³situations in new construction.³ ³ ³ ³ ³ ³ ³See Minimum Requirements ³ ³ ³ ³ ³ ³ ³Summary Sheet D and ADAAG ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 4) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(7)(a)³Doors ³At each accessible entrance to ³ ³ ³ ³ ³4.13.1 ³ ³a building or facility, is ³ ³ ³ ³ ³ ³ ³there at least one accessible ³ ³ ³ ³ ³ ³ ³door meeting the requirements ³ ³ ³ ³ ³ ³ ³of 4.13? (Use Form 11: Doors ³ ³ ³ ³ ³ ³ ³and Gates) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 10-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.2 ³Turnstiles ³If turnstiles or revolving ³ ³ ³ ³ ³ ³ ³doors are used on an accessible³ ³ ³ ³ ³ ³ ³route, is there an accessible ³ ³ ³ ³ ³ ³ ³gate or door provided adjacent ³ ³ ³ ³ ³ ³ ³to the turnstile or revolving ³ ³ ³ ³ ³ ³ ³door to facilitate the same use³ ³ ³ ³ ³ ³ ³pattern? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.3 ³Gates ³Do all gates, including ticket ³ ³ ³ ³ ³ ³ ³gates, comply with the ³ ³ ³ ³ ³ ³ ³applicable specifications of ³ ³ ³ ³ ³ ³ ³4.13? (Use Form 11: Doors and ³ ³ ³ ³ ³ ³ ³Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(9) ³Exits and ³Does each occupiable level of a³ ³ ³ ³ ³ ³Areas of ³building or facility which is ³ ³ ³ ³ ³ ³Rescue ³required to be accessible have ³ ³ ³ ³ ³ ³Assistance ³accessible means of egress ³ ³ ³ ³ ³ ³ ³equal to the number of exits ³ ³ ³ ³ ³ ³ ³required by local building/life³ ³ ³ ³ ³ ³ ³safety regulations? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Where a required exit is not ³ ³ ³ ³ ³ ³ ³accessible, are there areas of ³ ³ ³ ³ ³ ³ ³rescue assistance complying ³ ³ ³ ³ ³ ³ ³with 4.3.11 (see below) equal ³ ³ ³ ³ ³ ³ ³to the number of inaccessible ³ ³ ³ ³ ³ ³ ³required exits? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is there a horizontal exit ³ ³ ³ ³ ³ ³ ³complying with local ³ ³ ³ ³ ³ ³ ³building/life safety ³ ³ ³ ³ ³ ³ ³regulations provided in lieu of³ ³ ³ ³ ³ ³ ³an area of rescue assistance? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Does the building or facility ³ ³ ³ ³ ³ ³ ³have a supervised automatic ³ ³ ³ ³ ³ ³ ³sprinkler system? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³Exit Door Signs ³Do signs which designate exit ³ ³ ³ ³ ³4.30.1 ³ ³doors comply with 4.30.4, ³ ³ ³ ³ ³ ³ ³4.30.5, and 4.30.6? (Use Form ³ ³ ³ ³ ³ ³ ³19: Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.1 ³Location and ³Are each of the required areas ³ ³ ³ ³ ³ ³Construction of ³of rescue assistance located ³ ³ ³ ³ ³ ³Areas of Rescue ³and constructed in compliance ³ ³ ³ ³ ³ ³Assistance ³with one of the following: ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÄÄ A portion of a stairway ³ ³ ³ ³ ³ ³ ³landing in a smokeproof ³ ³ ³ ³ ³ ³ ³enclosure complying with local ³ ³ ³ ³ ³ ³ ³building requirements? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÄÄ A portion of an exterior ³ ³ ³ ³ ³ ³ ³exit balcony, complying with ³ ³ ³ ³ ³ ³ ³local requirements, immediately³ ³ ³ ³ ³ ³ ³adjacent to an exit stairway? ³ ³ ³ ³ ³ ³ ³Openings to the interior of the³ ³ ³ ³ ³ ³ ³building located within 20 feet³ ³ ³ ³ ³ ³ ³of the area of rescue ³ ³ ³ ³ ³ ³ ³assistance must have fire ³ ³ ³ ³ ³ ³ ³assemblies with 3/4 hour fire ³ ³ ³ ³ ³ ³ ³protection rating. ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 10-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³ ÄÄ A portion of a one-hour ³ ³ ³ ³ ³ ³ ³fire-resistive corridor, ³ ³ ³ ³ ³ ³ ³complying with local ³ ³ ³ ³ ³ ³ ³requirements for fire-resistive³ ³ ³ ³ ³ ³ ³construction and for openings, ³ ³ ³ ³ ³ ³ ³immediately adjacent to an exit³ ³ ³ ³ ³ ³ ³enclosure? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÄÄ A vestibule immediately ³ ³ ³ ³ ³ ³ ³adjacent to an exit enclosure ³ ³ ³ ³ ³ ³ ³constructed to the same ³ ³ ³ ³ ³ ³ ³fire-resistive standards ³ ³ ³ ³ ³ ³ ³required for corridors and ³ ³ ³ ³ ³ ³ ³openings? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÄÄ A portion of a stairway ³ ³ ³ ³ ³ ³ ³landing within an exit ³ ³ ³ ³ ³ ³ ³enclosure which is vented to ³ ³ ³ ³ ³ ³ ³the exterior and is separated ³ ³ ³ ³ ³ ³ ³from the interior of the ³ ³ ³ ³ ³ ³ ³building with not less than a ³ ³ ³ ³ ³ ³ ³one hour fire resistive doors? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÄÄ When approved by local ³ ³ ³ ³ ³ ³ ³authorities, an area or room ³ ³ ³ ³ ³ ³ ³separated by a smoke barrier ³ ³ ³ ³ ³ ³ ³from other portions of the ³ ³ ³ ³ ³ ³ ³building, and which has an exit³ ³ ³ ³ ³ ³ ³directly into an exit ³ ³ ³ ³ ³ ³ ³enclosure, where smoke barriers³ ³ ³ ³ ³ ³ ³completely enclose the area or ³ ³ ³ ³ ³ ³ ³room and have a fire resistive ³ ³ ³ ³ ³ ³ ³rating of not less than one ³ ³ ³ ³ ³ ³ ³hour? Doors in the smoke ³ ³ ³ ³ ³ ³ ³barrier must be tight-fitting ³ ³ ³ ³ ³ ³ ³smoke-and draft-control ³ ³ ³ ³ ³ ³ ³assemblies with a fire rating ³ ³ ³ ³ ³ ³ ³of not less than 20 minutes, ³ ³ ³ ³ ³ ³ ³and must also be self-closing ³ ³ ³ ³ ³ ³ ³or automatic closing. Where ³ ³ ³ ³ ³ ³ ³the room or area exits into an ³ ³ ³ ³ ³ ³ ³exit enclosure which is ³ ³ ³ ³ ³ ³ ³required to be of more than one³ ³ ³ ³ ³ ³ ³hour fire-resistive ³ ³ ³ ³ ³ ³ ³construction, the room or area ³ ³ ³ ³ ³ ³ ³must have the same ³ ³ ³ ³ ³ ³ ³fire-resistive construction, ³ ³ ³ ³ ³ ³ ³including the same opening ³ ³ ³ ³ ³ ³ ³protection, as required for the³ ³ ³ ³ ³ ³ ³adjacent exit enclosure. ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÄÄ An elevator lobby when ³ ³ ³ ³ ³ ³ ³elevator shafts and adjacent ³ ³ ³ ³ ³ ³ ³lobbies are pressurized as ³ ³ ³ ³ ³ ³ ³required for a smokeproof ³ ³ ³ ³ ³ ³ ³enclosure by local regulations ³ ³ ³ ³ ³ ³ ³and when complying with the ³ ³ ³ ³ ³ ³ ³requirements in 4.3.11 (see ³ ³ ³ ³ ³ ³ ³below) for size, communication,³ ³ ³ ³ ³ ³ ³and signage? The ³ ³ ³ ³ ³ ³ ³pressurization system must be ³ ³ ³ ³ ³ ³ ³activated by smoke detectors on³ ³ ³ ³ ³ ³ ³each floor and the ³ ³ ³ ³ ³ ³ ³pressurization system and its ³ ³ ³ ³ ³ ³ ³duct work must be separated ³ ³ ³ ³ ³ ³ ³from other portions of the ³ ³ ³ ³ ³ ³ ³building by a minimum two hour ³ ³ ³ ³ ³ ³ ³fire resistive construction. ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 10-4 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.2 ³Wheelchair ³Does each area of rescue ³ ³ ³ ³ ³ ³Spaces in Areas ³assistance provide at least 2 ³ ³ ³ ³ ³ ³of Rescue ³spaces no less than 30 by 48 ³ ³ ³ ³ ³ ³Assistance ³inches which do not encroach on³ ³ ³ ³ ³ ³Size ³any required exit width? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Required ³Is the total number of ³ ³ ³ ³ ³ ³Number of ³wheelchair spaces per story at ³ ³ ³ ³ ³ ³Wheelchair ³least equal to one for every ³ ³ ³ ³ ³ ³Spaces ³200 persons of calculated ³ ³ ³ ³ ³ ³ ³occupant load served by the ³ ³ ³ ³ ³ ³ ³area of rescue assistance? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: The appropriate ³ ³ ³ ³ ³ ³ ³local authority may reduce the ³ ³ ³ ³ ³ ³ ³minimum number of such spaces ³ ³ ³ ³ ³ ³ ³to one for each area of rescue ³ ³ ³ ³ ³ ³ ³assistance on floors where the ³ ³ ³ ³ ³ ³ ³occupant load is less than 200.³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.3 ³Stairway Width ³Is each stairway serving an ³ ³ ³ ³ ³ ³ ³area of rescue assistance at ³ ³ ³ ³ ³ ³ ³least 48 inches wide between ³ ³ ³ ³ ³ ³ ³handrails? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.4 ³Two-Way ³Is there a method of two-way ³ ³ ³ ³ ³ ³Communication ³communication (using both ³ ³ ³ ³ ³ ³ ³visible and audible signals) ³ ³ ³ ³ ³ ³ ³between each area of rescue ³ ³ ³ ³ ³ ³ ³assistance and the primary ³ ³ ³ ³ ³ ³ ³entry? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(The fire department or other ³ ³ ³ ³ ³ ³ ³local authority may approve a ³ ³ ³ ³ ³ ³ ³location other than a primary ³ ³ ³ ³ ³ ³ ³entry.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.5 ³Instructions ³Are there instructions for the ³ ³ ³ ³ ³ ³for Use ³use of the area of rescue ³ ³ ³ ³ ³ ³ ³assistance during an emergency ³ ³ ³ ³ ³ ³ ³posted adjacent to the ³ ³ ³ ³ ³ ³ ³communication system? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.5 ³Identification ³Is each area of rescue ³ ³ ³ ³ ³ ³Signs ³assistance identified by a sign³ ³ ³ ³ ³ ³ ³which states "Area of Rescue ³ ³ ³ ³ ³ ³ ³Assistance," and which also ³ ³ ³ ³ ³ ³ ³displays the International ³ ³ ³ ³ ³ ³ ³Symbol of Accessibility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.5 ³ ³Is the sign illuminated ³ ³ ³ ³ ³ ³ ³when/where exit signs are ³ ³ ³ ³ ³ ³ ³required to be illuminated? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.11.5 ³Directional ³Is there directional signage ³ ³ ³ ³ ³ ³Signs ³posted at all inaccessible ³ ³ ³ ³ ³ ³ ³exits indicating the direction ³ ³ ³ ³ ³ ³ ³to areas of rescue assistance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³ ³Does the directional signage ³ ³ ³ ³ ³4.30.1 ³ ³comply with 4.30.2, 4.30.3, and³ ³ ³ ³ ³ ³ ³4.30.5? (Use Form 19: Signage)³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 10-5 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.10 ³Accessible ³Do accessible routes also serve³ ³ ³ ³ ³ ³Routes ³as a means of egress or connect³ ³ ³ ³ ³ ³ ³to areas of rescue assistance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(7)(d)³Doors ³Is each door along a means of ³ ³ ³ ³ ³ ³ ³egress an accessible door ³ ³ ³ ³ ³ ³ ³meeting the requirements of ³ ³ ³ ³ ³ ³ ³4.13? (Use Form 11: Doors and ³ ³ ³ ³ ³ ³ ³Gates) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 10-6 SURVEY FORM 11: DOORS AND GATES Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Door Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(7) ³Doors ³Is there at least one ³ ³ ³ ³ ³4.13.1 ³Accessible ³accessible door complying with ³ ³ ³ ³ ³ ³Entrances ³4.13 (see below) at each ³ ³ ³ ³ ³ ³ ³accessible entrance to the ³ ³ ³ ³ ³ ³ ³building or facility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Accessible ³Is there at least one ³ ³ ³ ³ ³ ³Spaces ³accessible door complying with ³ ³ ³ ³ ³ ³ ³4.13 (see below) at each ³ ³ ³ ³ ³ ³ ³accessible space in the ³ ³ ³ ³ ³ ³ ³facility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Accessible ³Does each door that is an ³ ³ ³ ³ ³ ³Routes ³element of an accessible route ³ ³ ³ ³ ³ ³ ³comply with 4.13 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Egress Door and ³Does each door that is an ³ ³ ³ ³ ³ ³Areas of Rescue ³element of an accessible means ³ ³ ³ ³ ³ ³Assistance: ³of egress or that connects to ³ ³ ³ ³ ³ ³ ³an area of rescue assistance ³ ³ ³ ³ ³ ³ ³comply with 4.13 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.2 ³Revolving ³If a revolving door or ³ ³ ³ ³ ³ ³Doors and ³turnstile is used on an ³ ³ ³ ³ ³ ³Turnstiles: ³accessible route, is an ³ ³ ³ ³ ³ ³ ³accessible door or gate ³ ³ ³ ³ ³ ³ ³provided adjacent to the ³ ³ ³ ³ ³ ³ ³turnstile or revolving door to ³ ³ ³ ³ ³ ³ ³facilitate the same use ³ ³ ³ ³ ³ ³ ³pattern? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.3 ³Gates ³Do gates, including ticket ³ ³ ³ ³ ³ ³ ³gates, meet the applicable ³ ³ ³ ³ ³ ³ ³specifications of 4.13 (See ³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.5 ³Clear Opening ³When a door is open 90 degrees,³ ³ ³ ³ ³ ³ ³is there a clear opening width ³ ³ ³ ³ ³ ³ ³at least 32 inches measured ³ ³ ³ ³ ³ ³ ³between the face of the door ³ ³ ³ ³ ³ ³ ³and the door stop on the latch ³ ³ ³ ³ ³ ³ ³side? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Closets ³If the door does not require ³ ³ ³ ³ ³ ³ ³full-user passage, such as that³ ³ ³ ³ ³ ³ ³to a shallow closet, is the ³ ³ ³ ³ ³ ³ ³clear opening width at least 20³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.4 ³Double Leaf ³If the doorway has two ³ ³ ³ ³ ³ ³Doors ³independently operated door ³ ³ ³ ³ ³ ³ ³leaves, does at least one ³ ³ ³ ³ ³ ³ ³active leaf provide at least a ³ ³ ³ ³ ³ ³ ³32 inch clear opening width? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 11-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.6 ³Maneuvering ³If the door is not automatic or³ ³ ³ ³ ³ ³Space ³power assisted, does it have ³ ³ ³ ³ ³ ³ ³maneuvering space relative to ³ ³ ³ ³ ³ ³ ³the direction of approach as ³ ³ ³ ³ ³ ³ ³shown in Figure 25? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Entry doors to ³ ³ ³ ³ ³ ³ ³acute care hospital bedrooms ³ ³ ³ ³ ³ ³ ³are exempt from the requirement³ ³ ³ ³ ³ ³ ³for the 18 inch space at the ³ ³ ³ ³ ³ ³ ³latch side of the door if the ³ ³ ³ ³ ³ ³ ³door is at least 44 inches ³ ³ ³ ³ ³ ³ ³wide. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the floor level and clear ³ ³ ³ ³ ³ ³ ³within the required ³ ³ ³ ³ ³ ³ ³maneuvering space? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.7 ³Vestibules ³If there are two doors in a ³ ³ ³ ³ ³ ³Doors in Series:³series, is the clear space ³ ³ ³ ³ ³ ³ ³between doors in a vestibule at³ ³ ³ ³ ³ ³ ³least 48 inches plus the width ³ ³ ³ ³ ³ ³ ³of any door swinging into the ³ ³ ³ ³ ³ ³ ³space? (See Figure 26) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do doors in a series swing in ³ ³ ³ ³ ³ ³ ³the same direction? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Do they swing away from the ³ ³ ³ ³ ³ ³ ³space between the doors? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.8 ³Thresholds ³Is the threshold at doorways no³ ³ ³ ³ ³ ³ ³higher than 3/4 inch in height ³ ³ ³ ³ ³ ³ ³for exterior sliding doors? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the threshold no higher than³ ³ ³ ³ ³ ³ ³1/2 inch for other doors? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If there is a raised threshold,³ ³ ³ ³ ³ ³ ³is it beveled at 1:2 or less? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.9 ³Hardware ³Are all handles, locks, and ³ ³ ³ ³ ³ ³ ³latches or other operative ³ ³ ³ ³ ³ ³ ³devices operable with one hand?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are they operable without tight³ ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³ ³of the wrist? (U-shaped ³ ³ ³ ³ ³ ³ ³handles, levers, and push type ³ ³ ³ ³ ³ ³ ³mechanisms are acceptable ³ ³ ³ ³ ³ ³ ³designs.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If there are sliding doors, is ³ ³ ³ ³ ³ ³ ³the operating hardware exposed ³ ³ ³ ³ ³ ³ ³and usable from both sides when³ ³ ³ ³ ³ ³ ³the doors are fully open? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³operate the controls no greater³ ³ ³ ³ ³ ³ ³than 5 lbf? (This does not ³ ³ ³ ³ ³ ³ ³apply to the force required to ³ ³ ³ ³ ³ ³ ³retract latch bolts or to ³ ³ ³ ³ ³ ³ ³disengage other devices that ³ ³ ³ ³ ³ ³ ³only hold the door in a closed ³ ³ ³ ³ ³ ³ ³position.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the operating hardware ³ ³ ³ ³ ³ ³ ³mounted no higher than 48 ³ ³ ³ ³ ³ ³ ³inches above the floor? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 11-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.10 ³Door Closers ³If the door has a closer, is ³ ³ ³ ³ ³ ³ ³the closer adjusted so that ³ ³ ³ ³ ³ ³ ³from an open position of 70 ³ ³ ³ ³ ³ ³ ³degrees, the door will take at ³ ³ ³ ³ ³ ³ ³least 3 seconds to move to a ³ ³ ³ ³ ³ ³ ³point 3 inches from the latch ³ ³ ³ ³ ³ ³ ³(measured to the leading edge ³ ³ ³ ³ ³ ³ ³of the door)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.11 ³Opening Force - ³Do fire doors have the minimum ³ ³ ³ ³ ³ ³Fire Doors: ³opening force allowable by the ³ ³ ³ ³ ³ ³ ³appropriate local authority? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Interior Doors ³Do interior hinged doors, and ³ ³ ³ ³ ³ ³ ³sliding or folding doors, have ³ ³ ³ ³ ³ ³ ³an opening force of 5 lbf or ³ ³ ³ ³ ³ ³ ³less? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.12 ³Automatic ³If an automatic door is used, ³ ³ ³ ³ ³ ³Doors ³does it comply with ANSI/BHMA ³ ³ ³ ³ ³ ³ ³A156.10-1985? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Low Powered ³If there is a slow-opening, ³ ³ ³ ³ ³ ³Doors ³low-powered automatic door, ³ ³ ³ ³ ³ ³ ³does it comply with ANSI ³ ³ ³ ³ ³ ³ ³A156.19-1984 and does it take ³ ³ ³ ³ ³ ³ ³at least 3 seconds to open to ³ ³ ³ ³ ³ ³ ³back check? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do such doors require no more ³ ³ ³ ³ ³ ³ ³than 15 lbf to stop door ³ ³ ³ ³ ³ ³ ³movement? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Power Assisted ³If a power assisted door is ³ ³ ³ ³ ³ ³Doors ³used, does it have an opening ³ ³ ³ ³ ³ ³ ³force of 5 lbf or less and does³ ³ ³ ³ ³ ³ ³its closing conform to the ³ ³ ³ ³ ³ ³ ³requirements in ANSI ³ ³ ³ ³ ³ ³ ³A156.19-1984? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 11-3 11-5 SURVEY FORM 12: BUILDING LOBBIES AND CORRIDORS (INTERIOR ACCESSIBLE ROUTE) Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Lobby or Corridor Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(1) ³Accessible ³Is there an accessible route ³ ³ ³ ³ ³4.3.2(3) ³Route ³connecting accessible entrances³ ³ ³ ³ ³ ³ ³with all accessible elements ³ ³ ³ ³ ³ ³ ³and spaces within the building?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.3 ³Width ³Is the accessible route at ³ ³ ³ ³ ³ ³General ³least 36 inches wide except at ³ ³ ³ ³ ³ ³ ³doorways? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³U-Turn: ³Where the accessible route ³ ³ ³ ³ ³ ³ ³makes a U-turn around an ³ ³ ³ ³ ³ ³ ³obstacle which is less than 48 ³ ³ ³ ³ ³ ³ ³inches wide, does the pathway ³ ³ ³ ³ ³ ³ ³width increase to at least 42 ³ ³ ³ ³ ³ ³ ³inches on the approaches and 48³ ³ ³ ³ ³ ³ ³inches in the turn? (See ³ ³ ³ ³ ³ ³ ³Figure 7(b)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.4 ³Passing ³If the accessible route is less³ ³ ³ ³ ³ ³Spaces ³than 60 inches wide, are there ³ ³ ³ ³ ³ ³ ³passing spaces at least 60 ³ ³ ³ ³ ³ ³ ³inches wide and 60 inches long ³ ³ ³ ³ ³ ³ ³or intersecting corridors ³ ³ ³ ³ ³ ³ ³allowing passing at reasonable ³ ³ ³ ³ ³ ³ ³intervals not exceeding 200 ³ ³ ³ ³ ³ ³ ³feet? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.5 ³Provisions ³If objects mounted to the wall ³ ³ ³ ³ ³4.4.1 ³for Persons ³have leading edges between 27 ³ ³ ³ ³ ³ ³Who are ³and 80 inches from the floor, ³ ³ ³ ³ ³ ³Blind ³do they project less than 4 ³ ³ ³ ³ ³ ³Protruding ³inches into the pathway? (Wall³ ³ ³ ³ ³ ³Objects ³mounted objects with leading ³ ³ ³ ³ ³ ³ ³edges at or below 27 inches may³ ³ ³ ³ ³ ³ ³project any amount so long as ³ ³ ³ ³ ³ ³ ³the required clear width of an ³ ³ ³ ³ ³ ³ ³accessible route is not ³ ³ ³ ³ ³ ³ ³reduced.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do free-standing objects ³ ³ ³ ³ ³ ³ ³mounted on posts with leading ³ ³ ³ ³ ³ ³ ³edges between 27 and 80 inches ³ ³ ³ ³ ³ ³ ³high project less than 12 ³ ³ ³ ³ ³ ³ ³inches into the perpendicular ³ ³ ³ ³ ³ ³ ³route of travel? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there an accessible path at ³ ³ ³ ³ ³ ³ ³least 36 inches clear alongside³ ³ ³ ³ ³ ³ ³the protruding object? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 12-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.4.2 ³Headroom ³Is there at least 80 inches ³ ³ ³ ³ ³ ³ ³clear head room on an ³ ³ ³ ³ ³ ³ ³accessible route? If there is ³ ³ ³ ³ ³ ³ ³less than 80 inches clear head ³ ³ ³ ³ ³ ³ ³room in an area adjoining an ³ ³ ³ ³ ³ ³ ³accessible route, is there a ³ ³ ³ ³ ³ ³ ³cane detectable barrier within³ ³ ³ ³ ³ ³ ³27 inches of the floor? (See ³ ³ ³ ³ ³ ³ ³Figure 8(c-1)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.5.1 ³Floor ³Are the floor surfaces on ³ ³ ³ ³ ³ ³Surface ³accessible routes stable, firm,³ ³ ³ ³ ³ ³ ³and slip- resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.7 ³Slope ³Is the slope of the accessible ³ ³ ³ ³ ³4.8.1 ³ ³route no greater than 1:20? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Where the slope is greater than³ ³ ³ ³ ³ ³ ³1:20, does it comply with the ³ ³ ³ ³ ³ ³ ³requirements for ramps? (Use ³ ³ ³ ³ ³ ³ ³Form 7: Ramps) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.7 ³Cross Slope ³Is the cross slope no greater ³ ³ ³ ³ ³4.8.1 ³ ³than 1:50? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.8 ³Changes in ³Are ramps or elevators used for³ ³ ³ ³ ³4.5.2 ³Level ³changes in level greater than ³ ³ ³ ³ ³ ³ ³1/2 inch? (Lifts may only be ³ ³ ³ ³ ³ ³ ³used in certain limited ³ ³ ³ ³ ³ ³ ³situations in new construction.³ ³ ³ ³ ³ ³ ³See Minimum Requirements ³ ³ ³ ³ ³ ³ ³Summary Sheet D and ADAAG ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 4.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the ramp or elevator ³ ³ ³ ³ ³ ³ ³comply with 4.8 or 4.10? (Use ³ ³ ³ ³ ³ ³ ³Form 7: Ramps or Form 13: ³ ³ ³ ³ ³ ³ ³Elevators) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³When walkway levels change, is ³ ³ ³ ³ ³ ³ ³the vertical difference less ³ ³ ³ ³ ³ ³ ³than 1/4 inch? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are changes in level between ³ ³ ³ ³ ³ ³ ³1/4 inch and 1/2 inch beveled ³ ³ ³ ³ ³ ³ ³with a slope no greater than ³ ³ ³ ³ ³ ³ ³1:2? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³When floor materials change, ³ ³ ³ ³ ³ ³ ³does the vertical difference ³ ³ ³ ³ ³ ³ ³between them meet the above ³ ³ ³ ³ ³ ³ ³requirements? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.5.3 ³Carpet ³If carpet or carpet tile is ³ ³ ³ ³ ³ ³ ³used on the floor, is it ³ ³ ³ ³ ³ ³ ³securely attached? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are exposed edges of carpet ³ ³ ³ ³ ³ ³ ³fastened to the floor and have ³ ³ ³ ³ ³ ³ ³trim along their entire length?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is it a low pile type of carpet³ ³ ³ ³ ³ ³ ³(1/2 inch maximum) with a firm ³ ³ ³ ³ ³ ³ ³pad or no pad underneath it? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(7)(e)³Doors ³Does each door that is an ³ ³ ³ ³ ³4.13 ³ ³element of an accessible route ³ ³ ³ ³ ³ ³ ³comply with 4.13? (Use Form ³ ³ ³ ³ ³ ³ ³11: Doors and Gates) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 12-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.2 ³Revolving ³If a revolving door or ³ ³ ³ ³ ³ ³Door ³turnstile is used on an ³ ³ ³ ³ ³ ³ ³accessible route, is an ³ ³ ³ ³ ³ ³ ³accessible door or gate ³ ³ ³ ³ ³ ³ ³provided adjacent to the ³ ³ ³ ³ ³ ³ ³revolving door or turnstile to ³ ³ ³ ³ ³ ³ ³facilitate the same use ³ ³ ³ ³ ³ ³ ³pattern? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.3 ³Gates ³Do gates, including ticket ³ ³ ³ ³ ³ ³ ³gates, meet all the applicable ³ ³ ³ ³ ³ ³ ³specifications of 4.13? (Use ³ ³ ³ ³ ³ ³ ³Form 11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³Directional ³Do signs which provide ³ ³ ³ ³ ³4.30.1 ³and ³direction to, or information ³ ³ ³ ³ ³ ³Informational ³about, functional spaces of the³ ³ ³ ³ ³ ³Signs ³building comply with 4.30.2, ³ ³ ³ ³ ³ ³ ³4.30.3, and 4.30.5? (Use Form ³ ³ ³ ³ ³ ³ ³19: Signage) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Building ³ ³ ³ ³ ³ ³ ³directories, menus, and all ³ ³ ³ ³ ³ ³ ³other signs which are temporary³ ³ ³ ³ ³ ³ ³are not required to comply. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³Room ³Do signs which identify ³ ³ ³ ³ ³4.30.1 ³Identification ³permanent rooms and spaces ³ ³ ³ ³ ³ ³Signs ³comply with 4.30.4, 4.30.5, and³ ³ ³ ³ ³ ³ ³4.30.6? (Use Form 19: Signage)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(14) ³Alarms ³If emergency warning systems ³ ³ ³ ³ ³4.28 ³ ³are provided, do they include ³ ³ ³ ³ ³ ³ ³both audible alarms and visual ³ ³ ³ ³ ³ ³ ³alarms complying with 4.28? ³ ³ ³ ³ ³ ³ ³(Use Form 20: Alarms) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 12-3 SURVEY FORM 13: ELEVATORS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Elevator Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Elevator Location: 4.1.3(5) EXCEPTION 1: Elevators are not required in facilities that are less than three stories or that have less than 3,000 square feet per story unless the building is a shopping center, a shopping mall, or the professional office of a health care provider, or another type of facility as determined by the Attorney General.* The elevator exemption set forth in this paragraph does not obviate or limit in any way the obligation to comply with the other accessibility requirements established in section 4.1.3. For example, floors above or below the accessible ground floor must meet the requirements of this section except for elevator service. If toilet or bathing facilities are provided on a level not served by an elevator, then toilet or bathing facilities must be provided on the accessible ground floor. In new construction if a building or facility is eligible for this exemption, but a full passenger elevator is nonetheless planned, that elevator shall meet the requirements of 4.10 and shall serve each level in the building. A full passenger elevator that provides service from a garage to only one level of a building or facility is not required to serve other levels. *Note: The term "professional office of a health care provider" and "shopping center or shopping mall" are further defined in the Department of Justice regulations at 28 CFR Section 36.401(d)(1) for new construction and 28 CFR Section 36.404(a) for alterations. The Attorney General has also designated any terminal, depot, or other station used for specified public transportation, or an airport passenger terminal as not eligible for the elevator exception. (See 28 CFR Sections 36.401(d)(2) and 36.404(a).) In such a facility, any area housing passenger services, including boarding and debarking, loading and unloading, baggage claim, dining facilities, and other common areas open to the public, must be on an accessible route from an accessible entrance. ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(5) ³Elevator ³Is the building eligible for ³ ³ ³ ³ ³Exception 1³Exception ³the elevator exception in ³ ³ ³ ³ ³ ³ ³4.1.3(5) above? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Eligible ³If the building is eligible for³ ³ ³ ³ ³ ³Building ³the elevator exception, does ³ ³ ³ ³ ³ ³ ³the floor above or below the ³ ³ ³ ³ ³ ³ ³accessible ground floor comply ³ ³ ³ ³ ³ ³ ³with all the other requirements³ ³ ³ ³ ³ ³ ³in 4.1.3 for new construction? ³ ³ ³ ³ ³ ³ ³(See Minimum Requirements ³ ³ ³ ³ ³ ³ ³Summary Sheets D through G) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 13-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If the building is eligible for³ ³ ³ ³ ³ ³ ³the elevator exception and ³ ³ ³ ³ ³ ³ ³toilet rooms or bathrooms are ³ ³ ³ ³ ³ ³ ³provided at a level not served ³ ³ ³ ³ ³ ³ ³by an elevator, are toilet ³ ³ ³ ³ ³ ³ ³rooms or bathrooms also ³ ³ ³ ³ ³ ³ ³provided on the accessible ³ ³ ³ ³ ³ ³ ³floor? (See Minimum ³ ³ ³ ³ ³ ³ ³Requirements Summary Sheet F: ³ ³ ³ ³ ³ ³ ³Toilet Rooms and Bathrooms) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If the building is eligible for³ ³ ³ ³ ³ ³ ³the elevator exception but a ³ ³ ³ ³ ³ ³ ³full passenger elevator is ³ ³ ³ ³ ³ ³ ³nonetheless planned, does the ³ ³ ³ ³ ³ ³ ³elevator comply with 4.10 (see ³ ³ ³ ³ ³ ³ ³below) and serve each level in ³ ³ ³ ³ ³ ³ ³the building? (A full ³ ³ ³ ³ ³ ³ ³passenger elevator that ³ ³ ³ ³ ³ ³ ³provides service from a garage ³ ³ ³ ³ ³ ³ ³to only one level of a building³ ³ ³ ³ ³ ³ ³is not required to serve other ³ ³ ³ ³ ³ ³ ³levels.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(5) ³Ineligible ³If the building is not eligible³ ³ ³ ³ ³4.10.1 ³Building ³for the elevator exception, ³ ³ ³ ³ ³ ³ ³does an elevator serve each ³ ³ ³ ³ ³ ³ ³level, including mezzanines, ³ ³ ³ ³ ³ ³ ³unless otherwise noted below? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If more than one elevator is ³ ³ ³ ³ ³ ³ ³provided in a building not ³ ³ ³ ³ ³ ³ ³eligible for the elevator ³ ³ ³ ³ ³ ³ ³exemption, does each full ³ ³ ³ ³ ³ ³ ³passenger elevator comply with ³ ³ ³ ³ ³ ³ ³4.10 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Shopping ³In a facility housing a ³ ³ ³ ³ ³ ³Center or ³shopping center or a shopping ³ ³ ³ ³ ³ ³Shopping ³mall, does an elevator serve ³ ³ ³ ³ ³ ³Mall ³each floor level housing (or ³ ³ ³ ³ ³ ³ ³designed or intended for use ³ ³ ³ ³ ³ ³ ³by) at least one sales or ³ ³ ³ ³ ³ ³ ³rental establishment? (See 28 ³ ³ ³ ³ ³ ³ ³CFR Sections 36.401(d)(1)(ii) ³ ³ ³ ³ ³ ³ ³and 36.404(a)(2)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Professional ³In a facility housing the ³ ³ ³ ³ ³ ³Office of ³professional office of a health³ ³ ³ ³ ³ ³Health Care ³care provider, does an elevator³ ³ ³ ³ ³ ³Provider ³serve each floor level housing ³ ³ ³ ³ ³ ³ ³(or designed or intended for ³ ³ ³ ³ ³ ³ ³use by) at least one health ³ ³ ³ ³ ³ ³ ³care provider? (See 28 CFR ³ ³ ³ ³ ³ ³ ³Sections 36.401(d)(1)(i) and ³ ³ ³ ³ ³ ³ ³36.404(a)(1)) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 13-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Transportation ³In a terminal, depot, or other ³ ³ ³ ³ ³ ³Facility ³station used for specified ³ ³ ³ ³ ³ ³ ³public transportation, or an ³ ³ ³ ³ ³ ³ ³airport passenger terminal, is ³ ³ ³ ³ ³ ³ ³each area housing passenger ³ ³ ³ ³ ³ ³ ³services, including boarding ³ ³ ³ ³ ³ ³ ³and debarking, loading and ³ ³ ³ ³ ³ ³ ³unloading, baggage claim, ³ ³ ³ ³ ³ ³ ³dining facilities, and other ³ ³ ³ ³ ³ ³ ³common areas open to the public³ ³ ³ ³ ³ ³ ³connected by an accessible ³ ³ ³ ³ ³ ³ ³route from an accessible ³ ³ ³ ³ ³ ³ ³entrance? (See 28 CFR Section ³ ³ ³ ³ ³ ³ ³36.401(d)(1)(iii)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.2 ³Automatic ³Is the elevator operation ³ ³ ³ ³ ³ ³Operation ³automatic? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.2 ³Self-leveling ³Is the elevator self-leveling ³ ³ ³ ³ ³ ³ ³and does the floor of the ³ ³ ³ ³ ³ ³ ³elevator automatically come ³ ³ ³ ³ ³ ³ ³within 1/2 inch of the floor ³ ³ ³ ³ ³ ³ ³landing at each stop? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.9 ³Horizontal ³Is the horizontal gap between ³ ³ ³ ³ ³ ³Gap ³the car floor platform and the ³ ³ ³ ³ ³ ³ ³landing edge no greater than ³ ³ ³ ³ ³ ³ ³1-1/4 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.3 ³Hallway Call ³Are the hallway call buttons ³ ³ ³ ³ ³ ³Buttons ³centered at 42 inches above the³ ³ ³ ³ ³ ³ ³floor? Are the buttons at least³ ³ ³ ³ ³ ³ ³3/4 inches in the smallest ³ ³ ³ ³ ³ ³ ³dimension? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Visual ³Do the buttons have visual ³ ³ ³ ³ ³ ³Indicators ³signals to indicate when each ³ ³ ³ ³ ³ ³ ³call is registered and ³ ³ ³ ³ ³ ³ ³answered? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the button designating the ³ ³ ³ ³ ³ ³ ³"up" direction above the "down"³ ³ ³ ³ ³ ³ ³button? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the buttons raised or flush³ ³ ³ ³ ³ ³ ³(not recessed)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Clearance ³If there is an object below the³ ³ ³ ³ ³ ³ ³buttons, does it project no ³ ³ ³ ³ ³ ³ ³more than 4 inches into the ³ ³ ³ ³ ³ ³ ³elevator lobby? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.4 ³Hall Lanterns ³Is there a visible and audible ³ ³ ³ ³ ³ ³ ³signal at each hoistway ³ ³ ³ ³ ³ ³ ³entrance to indicate which car ³ ³ ³ ³ ³ ³ ³is answering a call? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 13-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Audible ³Do audible signals sound once ³ ³ ³ ³ ³ ³Signals ³for "up" and twice for "down," ³ ³ ³ ³ ³ ³ ³or do they have verbal ³ ³ ³ ³ ³ ³ ³annunciators that say "up" or ³ ³ ³ ³ ³ ³ ³"down"? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Visible Signals ³Are visible signals also ³ ³ ³ ³ ³ ³ ³provided and are they: ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Mounted so that the centerline ³ ³ ³ ³ ³ ³ ³is at least 72 inches above ³ ³ ³ ³ ³ ³ ³the floor; ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³At least 2-1/2 inches in the ³ ³ ³ ³ ³ ³ ³smallest dimension; and, ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Visible from the vicinity of ³ ³ ³ ³ ³ ³ ³the hall call button? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.5 ³Raised and ³Does each elevator hoistway ³ ³ ³ ³ ³ ³Braille Floor ³entrance have raised floor ³ ³ ³ ³ ³ ³Designations ³designations on each door jamb ³ ³ ³ ³ ³ ³ ³centered 60 inches above the ³ ³ ³ ³ ³ ³ ³floor? Are the floor ³ ³ ³ ³ ³ ³ ³designation letters or numerals³ ³ ³ ³ ³ ³ ³2 inches high? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.5 ³Raised ³Are the letters or numerals ³ ³ ³ ³ ³4.30.4 ³Characters ³raised at least 1/32 inch upper³ ³ ³ ³ ³ ³ ³case, and sans serif or simple ³ ³ ³ ³ ³ ³ ³serif type? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Braille ³Are the letters or numerals ³ ³ ³ ³ ³ ³ ³accompanied with Grade II ³ ³ ³ ³ ³ ³ ³Braille? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.6 ³Doors ³Do the elevator doors open and ³ ³ ³ ³ ³ ³ ³close automatically? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do they re-open automatically ³ ³ ³ ³ ³ ³ ³without contact if an ³ ³ ³ ³ ³ ³ ³obstruction passes through the ³ ³ ³ ³ ³ ³ ³opening between 5 inches and 29³ ³ ³ ³ ³ ³ ³inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does this reopening device ³ ³ ³ ³ ³ ³ ³remain effective for at least ³ ³ ³ ³ ³ ³ ³20 seconds? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.7 ³Door and ³Is the time from when the ³ ³ ³ ³ ³ ³Signal Delay ³elevator's arrival is signaled ³ ³ ³ ³ ³ ³ ³until the doors begin to close ³ ³ ³ ³ ³ ³ ³at least 5 seconds? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If any hoistway door is farther³ ³ ³ ³ ³ ³ ³than 7.5 feet from the hall ³ ³ ³ ³ ³ ³ ³call button, does the time ³ ³ ³ ³ ³ ³ ³increase according to Figure ³ ³ ³ ³ ³ ³ ³21? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 13-4 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.8 ³ ³Do the elevator doors remain ³ ³ ³ ³ ³ ³ ³fully open for at least 3 ³ ³ ³ ³ ³ ³ ³seconds? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.9 ³Floor ³Does the floor area of the car ³ ³ ³ ³ ³ ³Surfaces ³allow maneuvering room for ³ ³ ³ ³ ³ ³ ³wheelchair users to enter the ³ ³ ³ ³ ³ ³ ³car, reach the controls, and ³ ³ ³ ³ ³ ³ ³exit? (See Figure 22) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.10 ³ ³Are the floors in and adjacent ³ ³ ³ ³ ³4.5 ³ ³to the elevator stable, firm, ³ ³ ³ ³ ³ ³ ³and slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.11 ³Illumination ³Is the illumination level at ³ ³ ³ ³ ³ ³Levels ³the car controls, the platform,³ ³ ³ ³ ³ ³ ³and the car threshold and ³ ³ ³ ³ ³ ³ ³landing sill at least 5 ³ ³ ³ ³ ³ ³ ³footcandles? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.12(1) ³Car Controls ³Are the car control buttons at ³ ³ ³ ³ ³ ³ ³least 3/4 inch in their ³ ³ ³ ³ ³ ³ ³smallest dimension? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the controls raised or ³ ³ ³ ³ ³ ³ ³flush? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.12(2) ³Raised ³Are the controls designated by ³ ³ ³ ³ ³4.30.4 ³Characters ³raised standard alphabet ³ ³ ³ ³ ³ ³ ³characters, arabic numerals, or³ ³ ³ ³ ³ ³ ³standard elevator symbols that ³ ³ ³ ³ ³ ³ ³are placed immediately to the ³ ³ ³ ³ ³ ³ ³left of the buttons? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Character ³Are the raised characters and ³ ³ ³ ³ ³ ³Height ³numbers at least 5/8 inch high ³ ³ ³ ³ ³ ³ ³and raised at least 1/32 inch? ³ ³ ³ ³ ³ ³ ³Are the raised characters and ³ ³ ³ ³ ³ ³ ³numbers upper case, and sans ³ ³ ³ ³ ³ ³ ³serif or simple serif? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Braille ³Do the controls also have ³ ³ ³ ³ ³ ³ ³Braille designations in Grade ³ ³ ³ ³ ³ ³ ³II Braille? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.12(2) ³Contrast ³Do the numbers and characters ³ ³ ³ ³ ³4.30.5 ³ ³contrast with the background ³ ³ ³ ³ ³ ³ ³(light-on-dark or ³ ³ ³ ³ ³ ³ ³dark-on-light)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Main Entry ³Is the button for the main ³ ³ ³ ³ ³ ³Designation ³entry floor designated by a ³ ³ ³ ³ ³ ³ ³raised star? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.12(2) ³Visual ³Do the floor buttons have ³ ³ ³ ³ ³ ³Indicators ³visual indicators to show when ³ ³ ³ ³ ³ ³ ³each call is registered and are³ ³ ³ ³ ³ ³ ³they extinguished when each ³ ³ ³ ³ ³ ³ ³call is answered? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 13-5 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.12(3) ³Height of ³Are the floor buttons no higher³ ³ ³ ³ ³ ³Controls ³than 54 inches above the floor ³ ³ ³ ³ ³ ³ ³for side approach and no higher³ ³ ³ ³ ³ ³ ³than 48 inches for front ³ ³ ³ ³ ³ ³ ³approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Emergency ³Are the emergency controls ³ ³ ³ ³ ³ ³Controls ³grouped at the bottom of the ³ ³ ³ ³ ³ ³ ³panel with centerlines no less ³ ³ ³ ³ ³ ³ ³than 35 inches above the floor?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Control ³If the cars have side opening ³ ³ ³ ³ ³ ³Location ³doors are the controls located ³ ³ ³ ³ ³ ³ ³on the side or front wall ³ ³ ³ ³ ³ ³ ³adjacent to the doors? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If the cars have center opening³ ³ ³ ³ ³ ³ ³doors, are the controls located³ ³ ³ ³ ³ ³ ³on the front wall? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.13 ³Car Position ³Is there a visual car position ³ ³ ³ ³ ³ ³Indicators ³indicator above the car control³ ³ ³ ³ ³ ³ ³panel or over the door to ³ ³ ³ ³ ³ ³ ³indicate the floor level? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Size ³Are the numerals at least 1/2 ³ ³ ³ ³ ³ ³ ³inch high? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Visible Signals ³Do the numerals illuminate? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Audible ³Does an audible signal sound as³ ³ ³ ³ ³ ³Signals ³the car passes or stops at a ³ ³ ³ ³ ³ ³ ³floor or is there an automatic ³ ³ ³ ³ ³ ³ ³verbal announcement? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the audible signal at least ³ ³ ³ ³ ³ ³ ³20 decibels and the frequency ³ ³ ³ ³ ³ ³ ³no higher than 1500 Hz? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.14 ³Emergency ³If an emergency two-way ³ ³ ³ ³ ³ ³Communications ³communication system between ³ ³ ³ ³ ³ ³ ³the elevator and a point ³ ³ ³ ³ ³ ³ ³outside the hoistway is ³ ³ ³ ³ ³ ³ ³provided, does it comply with ³ ³ ³ ³ ³ ³ ³ASME A17.1-1990? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Height ³Is the highest operable part of³ ³ ³ ³ ³ ³ ³the communication system no ³ ³ ³ ³ ³ ³ ³higher than 48 inches above the³ ³ ³ ³ ³ ³ ³floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.14 ³Raised ³Is the communication system ³ ³ ³ ³ ³4.30.4 ³Characters ³identified by a raised symbol ³ ³ ³ ³ ³ ³and Braille ³and lettering located adjacent ³ ³ ³ ³ ³ ³ ³to the device? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the raised symbol and ³ ³ ³ ³ ³ ³ ³lettering between 5/8 inch and ³ ³ ³ ³ ³ ³ ³2 inches high and raised at ³ ³ ³ ³ ³ ³ ³least 1/32 inch? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 13-6 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the raised lettering upper ³ ³ ³ ³ ³ ³ ³case, and sans serif or simple ³ ³ ³ ³ ³ ³ ³serif? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the raised lettering ³ ³ ³ ³ ³ ³ ³accompanied by Grade II ³ ³ ³ ³ ³ ³ ³Braille? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.14 ³ ³Do the symbol and lettering ³ ³ ³ ³ ³4.30.5 ³ ³contrast with the background ³ ³ ³ ³ ³ ³ ³(light-on-dark or ³ ³ ³ ³ ³ ³ ³dark-on-light)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If the system uses a handset, ³ ³ ³ ³ ³ ³ ³is the length of the cord from ³ ³ ³ ³ ³ ³ ³the panel to the handset at ³ ³ ³ ³ ³ ³ ³least 29 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the communication system ³ ³ ³ ³ ³ ³ ³usable without voice ³ ³ ³ ³ ³ ³ ³communication? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.10.14 ³Controls ³If the communication system is ³ ³ ³ ³ ³4.27 ³ ³in a closed compartment, is ³ ³ ³ ³ ³ ³ ³the hardware on the compartment³ ³ ³ ³ ³ ³ ³door operable with one hand, ³ ³ ³ ³ ³ ³ ³and without tight grasping, ³ ³ ³ ³ ³ ³ ³pinching, or twisting of the ³ ³ ³ ³ ³ ³ ³wrist? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³operate controls no greater ³ ³ ³ ³ ³ ³ ³than 5 lbf? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 13-7 SURVEY FORM 14: ROOMS AND SPACES Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Room or Space Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(7)(b)³Doors ³Do the doors comply with 4.13? ³ ³ ³ ³ ³4.13.1 ³ ³(Use Form 11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.3 ³Aisles ³Are aisles between permanently ³ ³ ³ ³ ³ ³ ³built-in case work or ³ ³ ³ ³ ³ ³ ³partitions at least 36 inches ³ ³ ³ ³ ³ ³ ³wide (or at least 32 inches ³ ³ ³ ³ ³ ³ ³wide for a length not to exceed³ ³ ³ ³ ³ ³ ³24 inches)? (See Figure 8(e)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where the aisle makes a U-turn ³ ³ ³ ³ ³ ³ ³around an obstacle which is ³ ³ ³ ³ ³ ³ ³less than 48 inches wide, is ³ ³ ³ ³ ³ ³ ³the pathway width at least 42 ³ ³ ³ ³ ³ ³ ³inches on the approach and 48 ³ ³ ³ ³ ³ ³ ³inches in the turn? (See ³ ³ ³ ³ ³ ³ ³Figure 7(b)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.4 ³Passing Space ³If the aisles between ³ ³ ³ ³ ³ ³ ³permanently built-in casework ³ ³ ³ ³ ³ ³ ³or partitions are less than 60 ³ ³ ³ ³ ³ ³ ³inches wide, are there passing ³ ³ ³ ³ ³ ³ ³spaces at least 60 inches wide ³ ³ ³ ³ ³ ³ ³and 60 inches long or ³ ³ ³ ³ ³ ³ ³intersecting aisles allowing ³ ³ ³ ³ ³ ³ ³passing at reasonable intervals³ ³ ³ ³ ³ ³ ³not exceeding 200 feet? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.5 ³Headroom ³Is there at least 80 inches ³ ³ ³ ³ ³4.4.2 ³ ³clear head room in the ³ ³ ³ ³ ³ ³ ³accessible space? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If there is less than 80 inches³ ³ ³ ³ ³ ³ ³clear head room in part of an ³ ³ ³ ³ ³ ³ ³accessible space, is there a ³ ³ ³ ³ ³ ³ ³cane detectable barrier within ³ ³ ³ ³ ³ ³ ³27 inches of the floor? (See ³ ³ ³ ³ ³ ³ ³Figure 8(c-1)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.4.1 ³Protruding ³If objects mounted to the wall ³ ³ ³ ³ ³ ³Objects ³have leading edges between 27 ³ ³ ³ ³ ³ ³ ³and 80 inches from the floor, ³ ³ ³ ³ ³ ³ ³do they project less than 4 ³ ³ ³ ³ ³ ³ ³inches into the accessible ³ ³ ³ ³ ³ ³ ³space? (Wall mounted objects ³ ³ ³ ³ ³ ³ ³with leading edges at or below ³ ³ ³ ³ ³ ³ ³27 inches may project any ³ ³ ³ ³ ³ ³ ³amount so long as they do not ³ ³ ³ ³ ³ ³ ³reduce the required clear width³ ³ ³ ³ ³ ³ ³of an accessible route.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 14-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do free-standing objects, ³ ³ ³ ³ ³ ³ ³mounted on posts with leading ³ ³ ³ ³ ³ ³ ³edges between 27 and 80 inches ³ ³ ³ ³ ³ ³ ³high (such as drinking ³ ³ ³ ³ ³ ³ ³fountains or telephones) ³ ³ ³ ³ ³ ³ ³project less than 12 inches ³ ³ ³ ³ ³ ³ ³into the perpendicular route of³ ³ ³ ³ ³ ³ ³travel? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there an accessible route at³ ³ ³ ³ ³ ³ ³least 36 inches clear alongside³ ³ ³ ³ ³ ³ ³the protruding object? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.5.1 ³Floors ³Are the floor surfaces in all ³ ³ ³ ³ ³ ³ ³accessible rooms and spaces ³ ³ ³ ³ ³ ³ ³stable, firm, and ³ ³ ³ ³ ³ ³ ³slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(5) ³Level Changes ³Are ramps or elevators used for³ ³ ³ ³ ³4.3.8 ³ ³any change in level greater ³ ³ ³ ³ ³4.5.2 ³ ³than 1/2 inch? (Lifts may only ³ ³ ³ ³ ³ ³ ³be used in certain limited ³ ³ ³ ³ ³ ³ ³situations in new construction.³ ³ ³ ³ ³ ³ ³See Minimum Requirements ³ ³ ³ ³ ³ ³ ³Summary Sheet D and ADAAG ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 4) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the ramps or elevators ³ ³ ³ ³ ³ ³ ³comply with 4.8 or 4.10? (Use ³ ³ ³ ³ ³ ³ ³Form 7: Ramps or Form 13: ³ ³ ³ ³ ³ ³ ³Elevators) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³When walkway levels change, is ³ ³ ³ ³ ³ ³ ³the vertical difference less ³ ³ ³ ³ ³ ³ ³than 1/4 inch? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are changes in level between ³ ³ ³ ³ ³ ³ ³1/4 inch and 1/2 inch beveled ³ ³ ³ ³ ³ ³ ³with a slope no greater than ³ ³ ³ ³ ³ ³ ³1:2? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³When floor materials change, ³ ³ ³ ³ ³ ³ ³does the vertical difference ³ ³ ³ ³ ³ ³ ³between them meet the above ³ ³ ³ ³ ³ ³ ³requirement? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.5.3 ³Carpet ³If carpet or carpet tile is ³ ³ ³ ³ ³ ³ ³used on the floor, is it ³ ³ ³ ³ ³ ³ ³securely attached? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is it a low pile type of carpet³ ³ ³ ³ ³ ³ ³(1/2 inch or less) with a firm ³ ³ ³ ³ ³ ³ ³pad or no pad underneath? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³Directional ³Do signs which provide ³ ³ ³ ³ ³4.30.1 ³and ³direction to, or information ³ ³ ³ ³ ³ ³Informational ³about, functional spaces of the³ ³ ³ ³ ³ ³Signage ³building comply with 4.30.2, ³ ³ ³ ³ ³ ³ ³4.30.3, and 4.30.5? (Use Form ³ ³ ³ ³ ³ ³ ³19: Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³Room ³Do signs which designate ³ ³ ³ ³ ³4.30.1 ³Identification ³permanent rooms and spaces ³ ³ ³ ³ ³ ³Signage ³comply with 4.30.4, 4.30.5, and³ ³ ³ ³ ³ ³ ³4.30.6? (Use Form 19: Signage)³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 14-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(12) ³Storage ³Does at least one of each type ³ ³ ³ ³ ³4.25.1 ³ ³of fixed or built-in storage ³ ³ ³ ³ ³ ³ ³facilities (e.g., cabinets, ³ ³ ³ ³ ³ ³ ³shelves, closets, and drawers) ³ ³ ³ ³ ³ ³ ³comply with 4.25 (See below)? ³ ³ ³ ³ ³ ³ ³(Additional storage may be ³ ³ ³ ³ ³ ³ ³provided outside the dimensions³ ³ ³ ³ ³ ³ ³required by 4.25. Accessible ³ ³ ³ ³ ³ ³ ³reach range requirements do not³ ³ ³ ³ ³ ³ ³apply to shelves or display ³ ³ ³ ³ ³ ³ ³units allowing self-service by ³ ³ ³ ³ ³ ³ ³customers in mercantile ³ ³ ³ ³ ³ ³ ³occupancies but they must be ³ ³ ³ ³ ³ ³ ³located on an accessible ³ ³ ³ ³ ³ ³ ³route.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.25.2 ³Clear Floor ³Is there a clear floor space ³ ³ ³ ³ ³4.2.4 ³Space ³at least 30 by 48 inches at ³ ³ ³ ³ ³ ³ ³fixed or built-in storage ³ ³ ³ ³ ³ ³ ³facilities which allows for ³ ³ ³ ³ ³ ³ ³either a forward or parallel ³ ³ ³ ³ ³ ³ ³approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.25.3 ³Side Reach ³If a parallel approach is ³ ³ ³ ³ ³4.2.5 ³ ³provided, are clothes rods and ³ ³ ³ ³ ³4.2.6 ³ ³shelves between 9 and 54 inches³ ³ ³ ³ ³ ³ ³from the floor? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.25.3 ³ ³Where the distance between a ³ ³ ³ ³ ³ ³ ³wheelchair and clothes rod or ³ ³ ³ ³ ³ ³ ³shelve is between 10 - 21 ³ ³ ³ ³ ³ ³ ³inches (e.g., closets without ³ ³ ³ ³ ³ ³ ³accessible doors) is the ³ ³ ³ ³ ³ ³ ³accessible shelf no more than ³ ³ ³ ³ ³ ³ ³48 inches from the floor and ³ ³ ³ ³ ³ ³ ³the reach no more than 21 ³ ³ ³ ³ ³ ³ ³inches? (See Figure 38) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Forward Reach ³If a front approach is ³ ³ ³ ³ ³ ³ ³provided, are clothes rods and ³ ³ ³ ³ ³ ³ ³shelves between 15 and 48 ³ ³ ³ ³ ³ ³ ³inches from the floor? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.5 ³Closet Doors ³Where passage is not required ³ ³ ³ ³ ³ ³ ³to access storage, does the ³ ³ ³ ³ ³ ³ ³door have at least 20 inches ³ ³ ³ ³ ³ ³ ³clear opening width? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.25.4 ³Hardware ³Is the hardware on the storage ³ ³ ³ ³ ³.27.4 ³ ³space doors operable with one ³ ³ ³ ³ ³ ³ ³hand, and without tight ³ ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³ ³of the wrist? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³activate the hardware less than³ ³ ³ ³ ³ ³ ³5 lbf? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(18) ³Fixed/Built-in ³Do 5% (but not less than one) ³ ³ ³ ³ ³4.32.1 ³Seating, ³of fixed or built-in seating, ³ ³ ³ ³ ³ ³Tables or ³tables, or counters (e.g., ³ ³ ³ ³ ³ ³Counters ³study carrels and student ³ ³ ³ ³ ³ ³ ³laboratory stations) comply ³ ³ ³ ³ ³ ³ ³with 4.32 (See below)? (For ³ ³ ³ ³ ³ ³ ³specific requirements for ³ ³ ³ ³ ³ ³ ³restaurants and cafeterias, use³ ³ ³ ³ ³ ³ ³Form 23: Restaurants and ³ ³ ³ ³ ³ ³ ³Cafeterias.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 14-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.2 ³Clear Space ³Do seating spaces which are ³ ³ ³ ³ ³4.2.4 ³Seating ³provided for wheelchair users ³ ³ ³ ³ ³ ³ ³have a 30 by 48 inch clear ³ ³ ³ ³ ³ ³ ³space which overlaps an ³ ³ ³ ³ ³ ³ ³accessible route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Knee Space ³Is no more than 19 inches of ³ ³ ³ ³ ³ ³ ³the 30 by 48 inch clear space ³ ³ ³ ³ ³ ³ ³measured under the table? (See³ ³ ³ ³ ³ ³ ³Figure 45) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.3 ³ ³Is the knee space at least 27 ³ ³ ³ ³ ³ ³ ³inches high, 30 inches wide, ³ ³ ³ ³ ³ ³ ³and 19 inches deep? (See ³ ³ ³ ³ ³ ³ ³Figure 45) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.4 ³ ³Is the top of the table or ³ ³ ³ ³ ³ ³ ³counter between 28 and 34 ³ ³ ³ ³ ³ ³ ³inches from the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.3 ³Aisles ³Are the aisles leading up to ³ ³ ³ ³ ³ ³ ³and between tables at least 36 ³ ³ ³ ³ ³ ³ ³inches wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(13) ³Controls ³Are light switches, controls, ³ ³ ³ ³ ³4.27.1 ³ ³dispensers, and similar devices³ ³ ³ ³ ³4.27.2 ³ ³between 9 and 54 inches from ³ ³ ³ ³ ³4.27.3 ³ ³the floor when the clear floor ³ ³ ³ ³ ³4.2.5 ³ ³space allows a parallel ³ ³ ³ ³ ³4.2.6 ³ ³approach? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are they between 15 and 48 ³ ³ ³ ³ ³ ³ ³inches from the floor when the ³ ³ ³ ³ ³ ³ ³clear floor space allows only a³ ³ ³ ³ ³ ³ ³forward approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are all electrical and ³ ³ ³ ³ ³ ³ ³communications receptacles used³ ³ ³ ³ ³ ³ ³by building occupants at least ³ ³ ³ ³ ³ ³ ³15 inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.27.4 ³ ³Are controls operable with one ³ ³ ³ ³ ³ ³ ³hand, and without tight ³ ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³ ³of the wrist? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³activate controls less than 5 ³ ³ ³ ³ ³ ³ ³lbf? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(14) ³Alarms ³Where alarms are provided, do ³ ³ ³ ³ ³4.28.1 ³ ³they comply with 4.28? (Use ³ ³ ³ ³ ³ ³ ³Form 21: Alarms) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(10) ³Drinking ³If drinking fountains are ³ ³ ³ ³ ³4.15.1 ³Fountains ³located in a room or space, do ³ ³ ³ ³ ³ ³ ³they comply with 4.15? (Use ³ ³ ³ ³ ³ ³ ³Form 5: Drinking Fountains) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(17) ³Public ³If public telephones are ³ ³ ³ ³ ³4.31.1 ³Telephones ³located in a room or space, do ³ ³ ³ ³ ³ ³ ³they comply with 4.31? (Use ³ ³ ³ ³ ³ ³ ³Form 6: Telephones) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 14-4 14-5 Clearances for Seating and Tables] 14-6 SURVEY FORM 15: ASSEMBLY AREAS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Assembly Room Location: See Minimum Requirements Sheets I and J for special exceptions or requirements which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Capacity of Seating Number of Required in Assembly Areas: Wheelchair Locations: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ 4 to 25 1 26 to 50 2 51 to 300 4 301 to 500 6 over 500 6, plus 1 additional space for each total seating capacity increase of 100 ÚÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(19)(a)³Wheelchair ³In assembly areas with fixed ³ ³ ³ ³ ³4.33.1 ³Seating ³seating, is the required number³ ³ ³ ³ ³ ³ ³of wheelchair locations ³ ³ ³ ³ ³ ³ ³provided (See Table above)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Aisle Seating ³In addition, are one percent ³ ³ ³ ³ ³ ³ ³(but not less than one) of all ³ ³ ³ ³ ³ ³ ³fixed seats, aisle seats with ³ ³ ³ ³ ³ ³ ³no armrests on the aisle side, ³ ³ ³ ³ ³ ³ ³or removable or folding ³ ³ ³ ³ ³ ³ ³armrests on the aisle side? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Identification ³Is each such aisle seat ³ ³ ³ ³ ³ ³ ³identified by a sign or marker?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there a sign posted at the ³ ³ ³ ³ ³ ³ ³ticket office notifying patrons³ ³ ³ ³ ³ ³ ³of such aisle seats? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the wheelchair locations ³ ³ ³ ³ ³ ³ ³comply with 4.33.2, 4.33.3 and ³ ³ ³ ³ ³ ³ ³4.33.4 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.33.2 ³Wheelchair ³Do paired wheelchair spaces ³ ³ ³ ³ ³ ³Seating ³total 66 inches in width? (It ³ ³ ³ ³ ³ ³Size - Width ³is not required that all ³ ³ ³ ³ ³ ³ ³wheelchair spaces be paired.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Depth ³If wheelchair users enter the ³ ³ ³ ³ ³ ³ ³space from the side, is the ³ ³ ³ ³ ³ ³ ³space at least 60 inches deep? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If wheelchair users enter the ³ ³ ³ ³ ³ ³ ³space from the front or back, ³ ³ ³ ³ ³ ³ ³is the space at least 48 inches³ ³ ³ ³ ³ ³ ³deep? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 15-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.33.3 ³Placement ³Are the wheelchair areas an ³ ³ ³ ³ ³ ³of ³integral part of the fixed ³ ³ ³ ³ ³ ³Wheelchair ³seating plan with a choice of ³ ³ ³ ³ ³ ³Areas ³admission prices and lines of ³ ³ ³ ³ ³ ³ ³sight comparable to those for ³ ³ ³ ³ ³ ³ ³the general public? (Readily ³ ³ ³ ³ ³ ³ ³removable seats may be ³ ³ ³ ³ ³ ³ ³installed in wheelchair spaces ³ ³ ³ ³ ³ ³ ³when the spaces are not ³ ³ ³ ³ ³ ³ ³required to accommodate ³ ³ ³ ³ ³ ³ ³wheelchair users.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Multiple ³If the seating capacity exceeds³ ³ ³ ³ ³ ³Locations ³300, are the wheelchair spaces ³ ³ ³ ³ ³ ³ ³provided in more than one ³ ³ ³ ³ ³ ³ ³location? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Accessible viewing ³ ³ ³ ³ ³ ³ ³positions may be clustered for ³ ³ ³ ³ ³ ³ ³bleachers, balconies, and other³ ³ ³ ³ ³ ³ ³areas having sight lines which ³ ³ ³ ³ ³ ³ ³require slopes greater than 5%.³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Companion ³Is there at least one companion³ ³ ³ ³ ³ ³Seating ³fixed seat provided next to ³ ³ ³ ³ ³ ³ ³each wheelchair seating area? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Accessible ³Do wheelchair spaces adjoin an ³ ³ ³ ³ ³ ³Route ³accessible route that also ³ ³ ³ ³ ³ ³ ³serves as a means of egress in ³ ³ ³ ³ ³ ³ ³an emergency? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.33.4 ³Surfaces ³Are the floor surfaces at ³ ³ ³ ³ ³4.5 ³ ³wheelchair areas level, stable,³ ³ ³ ³ ³ ³ ³firm, and slip-resistant? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(5) ³Level Changes ³Are ramps or elevators used for³ ³ ³ ³ ³4.3.8 ³ ³changes in level greater than ³ ³ ³ ³ ³4.5.2 ³ ³1/2 inch? (Lifts may only be ³ ³ ³ ³ ³ ³ ³used in certain limited ³ ³ ³ ³ ³ ³ ³situations in new construction.³ ³ ³ ³ ³ ³ ³See Minimum Requirements ³ ³ ³ ³ ³ ³ ³Summary Sheet D and ADAAG ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 4) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the ramps or elevators ³ ³ ³ ³ ³ ³ ³comply with 4.8 or 4.10? (Use ³ ³ ³ ³ ³ ³ ³Form 7: Ramps or Form 13: ³ ³ ³ ³ ³ ³ ³Elevators) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³When walkway levels change, is ³ ³ ³ ³ ³ ³ ³the vertical difference less ³ ³ ³ ³ ³ ³ ³than 1/4 inch? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are changes in level between ³ ³ ³ ³ ³ ³ ³1/4 and 1/2 inch beveled with a³ ³ ³ ³ ³ ³ ³maximum slope of 1:2? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where floor materials change, ³ ³ ³ ³ ³ ³ ³does the vertical difference ³ ³ ³ ³ ³ ³ ³between them meet the above ³ ³ ³ ³ ³ ³ ³requirements? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.5.3 ³Carpet ³If carpet or carpet tile is ³ ³ ³ ³ ³ ³ ³used on the floor, is it ³ ³ ³ ³ ³ ³ ³securely attached? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is it a low pile type of carpet³ ³ ³ ³ ³ ³ ³(1/2 inch thick or less) with a³ ³ ³ ³ ³ ³ ³firm pad or no pad underneath? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 15-2 ÚÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.33.5 ³Performing ³Is there an accessible route ³ ³ ³ ³ ³ ³Areas ³connecting wheelchair seating ³ ³ ³ ³ ³ ³ ³locations and performance areas³ ³ ³ ³ ³ ³ ³including stages, arena floors,³ ³ ³ ³ ³ ³ ³dressing rooms, locker rooms, ³ ³ ³ ³ ³ ³ ³and other spaces used by ³ ³ ³ ³ ³ ³ ³performers? (Use Form 12: ³ ³ ³ ³ ³ ³ ³Building Lobbies and Corridors)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(19)(b)³Assistive ³In assembly areas where audible³ ³ ³ ³ ³ ³Listening ³communications are integral to ³ ³ ³ ³ ³ ³Systems ³the use of the space, is there ³ ³ ³ ³ ³ ³Permanently ³a permanently installed ³ ³ ³ ³ ³ ³Installed ³assistive listening system if ³ ³ ³ ³ ³ ³ ³(1) the assembly area ³ ³ ³ ³ ³ ³ ³accommodates 50 or more persons³ ³ ³ ³ ³ ³ ³or has an audio- amplification ³ ³ ³ ³ ³ ³ ³system and (2) it has fixed ³ ³ ³ ³ ³ ³ ³seats? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Portable ³For other assembly areas, is ³ ³ ³ ³ ³ ³Systems ³there a permanently installed ³ ³ ³ ³ ³ ³ ³assistive listening system or ³ ³ ³ ³ ³ ³ ³adequate number of ³ ³ ³ ³ ³ ³ ³outlets/wiring to permit use of³ ³ ³ ³ ³ ³ ³a portable assistive listening ³ ³ ³ ³ ³ ³ ³system? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Receivers ³Is the minimum number of ³ ³ ³ ³ ³ ³ ³receivers provided equal to 4% ³ ³ ³ ³ ³ ³ ³of the total number of seats, ³ ³ ³ ³ ³ ³ ³but not less than two? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.7(4) ³Signage ³Where a permanently installed ³ ³ ³ ³ ³ ³ ³assistive listening system is ³ ³ ³ ³ ³ ³ ³provided, is there signage ³ ³ ³ ³ ³ ³ ³installed to notify patrons of ³ ³ ³ ³ ³ ³ ³the availability of such a ³ ³ ³ ³ ³ ³ ³system? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the signage include the ³ ³ ³ ³ ³ ³ ³International Symbol for ³ ³ ³ ³ ³ ³ ³hearing loss? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.33.6 ³Placement of ³If the assistive listening ³ ³ ³ ³ ³ ³Assistive ³system serves individual fixed ³ ³ ³ ³ ³ ³Listening ³seats, are these seats located ³ ³ ³ ³ ³ ³Systems ³within a 50-foot viewing ³ ³ ³ ³ ³ ³ ³distance of the stage or ³ ³ ³ ³ ³ ³ ³playing area? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do these seats have a complete ³ ³ ³ ³ ³ ³ ³view of the stage or playing ³ ³ ³ ³ ³ ³ ³area? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 15-3 SURVEY FORM 16: TOILET ROOMS AND BATHROOMS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special exceptions or requirements which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Toilet Room Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(6) ³Public and ³If toilet rooms are provided, ³ ³ ³ ³ ³4.1.3(11) ³Common Use ³does each public and common use³ ³ ³ ³ ³4.22.1 ³Toilet Rooms ³toilet room comply with 4.22 ³ ³ ³ ³ ³ ³ ³(See below)? (A common use ³ ³ ³ ³ ³ ³ ³toilet room is one used for a ³ ³ ³ ³ ³ ³ ³restricted group of people such³ ³ ³ ³ ³ ³ ³as occupants of a building or ³ ³ ³ ³ ³ ³ ³employees of a company.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Private Use ³If other toilet rooms are ³ ³ ³ ³ ³ ³Toilet Rooms ³provided for the use of an ³ ³ ³ ³ ³ ³ ³occupant of a specific space, ³ ³ ³ ³ ³ ³ ³(such as a private toilet room ³ ³ ³ ³ ³ ³ ³for a company president) is ³ ³ ³ ³ ³ ³ ³each toilet room adaptable ³ ³ ³ ³ ³ ³ ³(e.g., door clearance, clear ³ ³ ³ ³ ³ ³ ³floor space at fixtures and ³ ³ ³ ³ ³ ³ ³maneuvering space)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(6) ³Public and ³If bathrooms or bathing ³ ³ ³ ³ ³4.1.3(11) ³Common Use ³facilities are provided, does ³ ³ ³ ³ ³4.23.1 ³Bathing ³each public and common use ³ ³ ³ ³ ³ ³Facilities ³bathroom or bathing facility ³ ³ ³ ³ ³ ³ ³comply with 4.23 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(5) ³Toilet/Bath ³In buildings eligible for the ³ ³ ³ ³ ³Exception 1³Rooms in ³elevator exception, if ³ ³ ³ ³ ³ ³Buildings ³toilet/bath rooms are provided ³ ³ ³ ³ ³ ³Eligible for ³on a level not served by an ³ ³ ³ ³ ³ ³Elevator ³elevator, is a toilet/bath room³ ³ ³ ³ ³ ³Exemption ³complying with 4.22 or 4.23 ³ ³ ³ ³ ³ ³ ³provided on the accessible ³ ³ ³ ³ ³ ³ ³ground floor? If toilet or ³ ³ ³ ³ ³ ³ ³bathing facilities are also ³ ³ ³ ³ ³ ³ ³provided on floors above or ³ ³ ³ ³ ³ ³ ³below ground level, they must ³ ³ ³ ³ ³ ³ ³be accessible. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.22.1 ³Accessible ³Are the toilet/bath rooms ³ ³ ³ ³ ³ ³Route ³located on an accessible route?³ ³ ³ ³ ³ ³ ³(Use Form 12: Building Lobbies ³ ³ ³ ³ ³ ³ ³and Corridors) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.22.3 ³ ³If provided, are each of the ³ ³ ³ ³ ³4.23.3 ³ ³following accessible fixtures ³ ³ ³ ³ ³ ³ ³and controls located on an ³ ³ ³ ³ ³ ³ ³accessible route? (Use Form ³ ³ ³ ³ ³ ³ ³12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ³ ³ ³ Ä 4.22.4 & 4.23.4 Water ³ ³ ³ ³ ³ ³ ³ closets ³ ³ ³ ³ ³ ³ ³ Ä 4.22.5 & 4.23.5 Urinals ³ ³ ³ ³ ³ ³ ³ Ä 4.22.6 & 4.23.6 Lavatories ³ ³ ³ ³ ³ ³ ³ and Mirrors ³ ³ ³ ³ ³ ³ ³ Ä 4.22.7 & 4.23.7 Controls and³ ³ ³ ³ ³ ³ ³ Dispensers ³ ³ ³ ³ ³ ³ ³ Ä 4.23.8 Bathing and Shower ³ ³ ³ ³ ³ ³ ³ Facilities ³ ³ ³ ³ ³ ³ ³ Ä 4.23.9 Medicine Cabinets ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.22.3 ³Maneuvering ³Is there an unobstructed ³ ³ ³ ³ ³4.23.3 ³Space ³turning space (a 60-inch ³ ³ ³ ³ ³ ³ ³diameter circle or T-shaped ³ ³ ³ ³ ³ ³ ³space) in the toilet/bath room?³ ³ ³ ³ ³ ³ ³(See Figure 3.) (The clear ³ ³ ³ ³ ³ ³ ³floor space of fixtures and ³ ³ ³ ³ ³ ³ ³controls, the accessible route,³ ³ ³ ³ ³ ³ ³and the turning space may ³ ³ ³ ³ ³ ³ ³overlap.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.22.2 ³Doors ³Do the doors comply with 4.13? ³ ³ ³ ³ ³4.23.3 ³ ³(Use Form 11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the door swing not intrude³ ³ ³ ³ ³ ³ ³into the clear floor space at ³ ³ ³ ³ ³ ³ ³any fixture? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(16) ³Room ³Do signs which designate ³ ³ ³ ³ ³4.30.1 ³Identification ³toilet/bath rooms comply with ³ ³ ³ ³ ³ ³Signage ³4.30.4, 4.30.5, and 4.30.6? ³ ³ ³ ³ ³ ³ ³(Use Form 19: Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.22.4 ³Toilet Stalls - ³If toilet stalls are provided, ³ ³ ³ ³ ³4.23.4 ³Standard Stall ³is at least one a standard ³ ³ ³ ³ ³ ³ ³stall at least 60 inches wide ³ ³ ³ ³ ³ ³ ³complying with 4.17 (See ³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.17.3 ³Size and ³Does the size and arrangement ³ ³ ³ ³ ³ ³Arrangement ³of the standard toilet stall ³ ³ ³ ³ ³ ³ ³comply with Figure 30(a)? ³ ³ ³ ³ ³ ³ ³(Arrangements may be reversed.)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Stall Width ³Is the stall at least 60 inches³ ³ ³ ³ ³ ³ ³wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Stall Depth ³If the toilet is wall mounted, ³ ³ ³ ³ ³ ³ ³is the stall at least 56 inches³ ³ ³ ³ ³ ³ ³deep? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If the toilet is a floor ³ ³ ³ ³ ³ ³ ³mounted model, is the stall at ³ ³ ³ ³ ³ ³ ³least 59 inches deep? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Door Location ³Is the stall door located at ³ ³ ³ ³ ³ ³ ³the "open" side of the toilet ³ ³ ³ ³ ³ ³ ³stall? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.17.4 ³Toe Clearance ³If the stall is less than 60 ³ ³ ³ ³ ³ ³ ³inches deep, does the front ³ ³ ³ ³ ³ ³ ³partition and at least one side³ ³ ³ ³ ³ ³ ³partition have toe clearances ³ ³ ³ ³ ³ ³ ³of at least 9 inches above the ³ ³ ³ ³ ³ ³ ³floor? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 16-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.17.5 ³Stall Door ³When the stall door is open 90 ³ ³ ³ ³ ³4.13.5 ³Width ³degrees, is there a clear ³ ³ ³ ³ ³ ³ ³opening of at least 32 inches ³ ³ ³ ³ ³ ³ ³measured between the face of ³ ³ ³ ³ ³ ³ ³the door and the edge of the ³ ³ ³ ³ ³ ³ ³partition on the latch side? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Door Swing ³If the stall door swings into ³ ³ ³ ³ ³ ³ ³the stall, is there at least 36³ ³ ³ ³ ³ ³ ³inches additional depth in the ³ ³ ³ ³ ³ ³ ³stall so that it does not ³ ³ ³ ³ ³ ³ ³encroach on the clear floor ³ ³ ³ ³ ³ ³ ³space required at the toilet ³ ³ ³ ³ ³ ³ ³and is there at least 18 inches³ ³ ³ ³ ³ ³ ³of maneuvering space at the ³ ³ ³ ³ ³ ³ ³latch side of the door? (See ³ ³ ³ ³ ³ ³ ³Figure 30 (a-1)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Approach Aisle ³If the stall door swings out ³ ³ ³ ³ ³ ³ ³and the approach is from the ³ ³ ³ ³ ³ ³ ³latch side, is the aisle ³ ³ ³ ³ ³ ³ ³approaching the stall at least ³ ³ ³ ³ ³ ³ ³42 inches wide? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³If the stall door swings out ³ ³ ³ ³ ³ ³ ³and the approach is from the ³ ³ ³ ³ ³ ³ ³hinge side, is the aisle ³ ³ ³ ³ ³ ³ ³approaching the stall at least ³ ³ ³ ³ ³ ³ ³48 inches wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.17.5 ³Maneuvering ³If the stall door opens out at ³ ³ ³ ³ ³4.13.6 ³Space ³the end of an aisle, is there ³ ³ ³ ³ ³ ³ ³at least 18 inches of ³ ³ ³ ³ ³ ³ ³maneuvering space at the latch ³ ³ ³ ³ ³ ³ ³side of the stall door? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.17.6 ³Grab Bars ³Are the grab bars in the ³ ³ ³ ³ ³ ³In Standard ³standard stall placed as shown ³ ³ ³ ³ ³ ³Stall ³in Figure 30 (a), (c), and (d)?³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the grab bars comply with ³ ³ ³ ³ ³ ³ ³4.26.2, 4.26.3, 4.26.4 (See ³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.22.4 ³Additional ³Where 6 or more toilet stalls ³ ³ ³ ³ ³4.23.4 ³Toilet Stall ³are provided, in addition to ³ ³ ³ ³ ³ ³ ³the 60 inch wide standard ³ ³ ³ ³ ³ ³ ³stall, is at least one stall 36³ ³ ³ ³ ³ ³ ³inches wide with an outward ³ ³ ³ ³ ³ ³ ³swinging, self-closing door ³ ³ ³ ³ ³ ³ ³provided? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Grab Bars in ³Do the parallel grab bars in ³ ³ ³ ³ ³ ³Additional ³the 36 inch wide stall comply ³ ³ ³ ³ ³ ³Stall ³with Figure 30(d)? Do the grab³ ³ ³ ³ ³ ³ ³bars comply with 4.26.2, 4.26.3³ ³ ³ ³ ³ ³ ³and 4.26.4 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.16.2 ³Toilets Not ³If the toilet is not in a stall³ ³ ³ ³ ³ ³in Stalls ÄÄ ³and is approached from the ³ ³ ³ ³ ³ ³Front ³front and there is a lavatory ³ ³ ³ ³ ³ ³Approach ³alongside the toilet, is there ³ ³ ³ ³ ³ ³ ³a clear floor space at least 48³ ³ ³ ³ ³ ³ ³inches wide by 66 inches long? ³ ³ ³ ³ ³ ³ ³(See Figure 28) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 16-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Side ³If the toilet is not in a stall³ ³ ³ ³ ³ ³Approach ³and is approached from the side³ ³ ³ ³ ³ ³ ³and there is a lavatory ³ ³ ³ ³ ³ ³ ³alongside the toilet, is there ³ ³ ³ ³ ³ ³ ³a clear floor space at least 48³ ³ ³ ³ ³ ³ ³inches wide by 56 inches long? ³ ³ ³ ³ ³ ³ ³(See Figure 28) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Lateral ³If the toilet is not in a stall³ ³ ³ ³ ³ ³Transfer ³and there is provision for a ³ ³ ³ ³ ³ ³ ³lateral transfer (no lavatory ³ ³ ³ ³ ³ ³ ³alongside the toilet), is there³ ³ ³ ³ ³ ³ ³a clear floor space at least 60³ ³ ³ ³ ³ ³ ³inches wide by 56 inches long? ³ ³ ³ ³ ³ ³ ³(See Figure 28) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.16.4 ³Grab Bars for ³If the toilet is not in a ³ ³ ³ ³ ³ ³Toilets Not in ³stall, is the back grab bar at ³ ³ ³ ³ ³ ³Stalls ³least 36 inches long with the ³ ³ ³ ³ ³ ³ ³end closer to the side wall ³ ³ ³ ³ ³ ³ ³mounted at least 12 inches from³ ³ ³ ³ ³ ³ ³the centerline of the toilet? ³ ³ ³ ³ ³ ³ ³(See Figure 29) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the side grab bar at least ³ ³ ³ ³ ³ ³ ³42 inches long and mounted a ³ ³ ³ ³ ³ ³ ³maximum 12 inches from the back³ ³ ³ ³ ³ ³ ³wall? (See Figure 29) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the grab bars horizontal ³ ³ ³ ³ ³ ³ ³and mounted between 33 and 36 ³ ³ ³ ³ ³ ³ ³inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the grab bars comply with ³ ³ ³ ³ ³ ³ ³4.26.2, 4.26.3, or 4.26.4 (See ³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.2 ³Grab Bars for ³Is the outside diameter of the ³ ³ ³ ³ ³ ³All ³grab bar between 1-1/4 and ³ ³ ³ ³ ³ ³Accessible ³1-1/2 inch? ³ ³ ³ ³ ³ ³Toilets ³OR ³ ³ ³ ³ ³ ³Diameter ³Does the shape provide an ³ ³ ³ ³ ³ ³ ³equivalent gripping surface? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Standard pipe sizes ³ ³ ³ ³ ³ ³ ³designated by the industry as ³ ³ ³ ³ ³ ³ ³1-1/4 to 1-1/2 inches are ³ ³ ³ ³ ³ ³ ³acceptable for purposes of this³ ³ ³ ³ ³ ³ ³section. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.2 ³Wall ³Is the space between the grab ³ ³ ³ ³ ³ ³Clearance ³bar and the wall exactly 1-1/2 ³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.3(5) ³Fixed ³Are the grab bars secured so ³ ³ ³ ³ ³ ³ ³that they do not rotate within ³ ³ ³ ³ ³ ³ ³their fittings? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.2 ³Clearance in ³If a grab bar is located in a ³ ³ ³ ³ ³ ³Recess ³recess, is the recess a maximum³ ³ ³ ³ ³ ³ ³of 3 inches deep extending at ³ ³ ³ ³ ³ ³ ³least 18 inches above the rail?³ ³ ³ ³ ³ ³ ³(See Figure 39(d)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.3 ³Structural ³Do the grab bars meet the ³ ³ ³ ³ ³ ³Strength ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for bending stress³ ³ ³ ³ ³ ³ ³and shear stress? (See ³ ³ ³ ³ ³ ³ ³4.26.3(1) and (2)) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 16-4 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the fasteners meet ³ ³ ³ ³ ³ ³structural strength ³ ³ ³ ³ ³ ³requirements for shear force ³ ³ ³ ³ ³ ³and tensile force? (See ³ ³ ³ ³ ³ ³4.26.3(3) and (4)) ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.26.4 ³Hazards ³Are grab bars and adjacent ³ ³ ³ ³ ³ ³walls free of sharp or abrasive³ ³ ³ ³ ³ ³elements? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do grab bars have edges with a ³ ³ ³ ³ ³ ³minimum radius of 1/8 inch? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.22.4 ³Accessible ³Is the centerline of the toilet³ ³ ³ ³4.23.4 ³Toilets ³18 inches from a wall or ³ ³ ³ ³ ³ ³partition? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.16.3 ³Toilet Seat ³Is the top of the toilet seat ³ ³ ³ ³ ³ ³between 17 and 19 inches from ³ ³ ³ ³ ³ ³the floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the seat a type that does ³ ³ ³ ³ ³ ³not automatically spring back ³ ³ ³ ³ ³ ³to a lifted position? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.16.5 ³Toilet Flush ³Are flush controls automatic or³ ³ ³ ³4.27.4 ³Controls ³operable with one hand without ³ ³ ³ ³ ³ ³tight grasping, pinching or ³ ³ ³ ³ ³ ³twisting of the wrist? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³operate the controls no greater³ ³ ³ ³ ³ ³than 5 lbf? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are they mounted on the wide ³ ³ ³ ³ ³ ³side of the toilet where the ³ ³ ³ ³ ³ ³clear floor space is provided? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the controls no higher than³ ³ ³ ³ ³ ³44 inches above the floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.16.6 ³Toilet Paper ³Is the paper dispenser mounted ³ ³ ³ ³ ³Dispenser ³below the grab bar no more than³ ³ ³ ³ ³ ³36 inches from the back wall ³ ³ ³ ³ ³ ³and at least 19 inches from the³ ³ ³ ³ ³ ³floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the dispenser located so ³ ³ ³ ³ ³ ³that it does not obstruct the ³ ³ ³ ³ ³ ³use of the grab bar? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the dispenser allow ³ ³ ³ ³ ³ ³continuous paper delivery? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.22.5 ³Urinals ³Where urinals are provided, ³ ³ ³ ³4.23.5 ³ ³does at least one comply with ³ ³ ³ ³ ³ ³4.18 (See below)? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³Rim Height ³Does the urinal have an ³ ³ ³ ³ ³ ³elongated rim no more than 17 ³ ³ ³ ³ ³ ³inches above the floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.18.3 ³Clear Floor ³Is there a clear floor space at³ ³ ³ ³4.2.4 ³Space ³least 30 by 48 inches which ³ ³ ³ ³ ³ ³allows a forward approach to ³ ³ ³ ³ ³ ³the urinal? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the clear floor space ³ ³ ³ ³ ³ ³adjoin or overlap an accessible³ ³ ³ ³ ³ ³route? ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÙ 16-5 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.2.4.3 ³Surface ³Is the surface of the clear ³ ³ ³ ³ ³ ³floor space stable, firm and ³ ³ ³ ³ ³ ³slip resistant? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³Width ³If urinal shields are provided ³ ³ ³ ³ ³Between ³and they do not extend beyond ³ ³ ³ ³ ³Shields ³the front edge of the urinal ³ ³ ³ ³ ³ ³rim, is there at least 29 ³ ³ ³ ³ ³ ³inches between the two panels? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.18.4 ³Urinal Flush ³Are the flush controls ³ ³ ³ ³4.27.4 ³Controls ³automatic or operable with one ³ ³ ³ ³ ³ ³hand without tight grasping, ³ ³ ³ ³ ³ ³pinching, or twisting of the ³ ³ ³ ³ ³ ³wrist? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³operate the controls no greater³ ³ ³ ³ ³ ³than 5 lbf? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the controls mounted no ³ ³ ³ ³ ³ ³more than 44 inches above the ³ ³ ³ ³ ³ ³floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.22.6 ³Lavatories ³If lavatories are provided, ³ ³ ³ ³4.23.6 ³ ³does at least one lavatory meet³ ³ ³ ³ ³ ³the following requirements? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.19.2 ³Rim Height ³Is the lavatory rim or counter ³ ³ ³ ³ ³ ³surface no higher than 34 ³ ³ ³ ³ ³ ³inches above the finish floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³Knee ³Is there a clearance of at ³ ³ ³ ³ ³Clearance ³least 29 inches from the floor ³ ³ ³ ³ ³ ³to the bottom of the apron? ³ ³ ³ ³ ³ ³(See Figure 31) ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³Wall ³Does the front edge of the ³ ³ ³ ³ ³Projection ³lavatory project at least 17 ³ ³ ³ ³ ³ ³inches from the wall? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the toe and knee clearances ³ ³ ³ ³ ³ ³comply with Figure 31? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.19.3 ³Clear Floor ³Is there a clear floor space at³ ³ ³ ³4.2.4 ³Space ³least 30 by 48 inches in front ³ ³ ³ ³ ³ ³of the lavatory allowing a ³ ³ ³ ³ ³ ³forward approach? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is no more than 19 inches of ³ ³ ³ ³ ³ ³this clear floor space measured³ ³ ³ ³ ³ ³underneath the lavatory? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the clear floor space ³ ³ ³ ³ ³ ³adjoin or overlap an accessible³ ³ ³ ³ ³ ³route? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.2.4.3 ³Surface ³Is the surface of the clear ³ ³ ³ ³ ³ ³floor space stable, firm and ³ ³ ³ ³ ³ ³slip resistant? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.19.4 ³Pipe Shielding ³Are hot water pipes and drain ³ ³ ³ ³ ³ ³pipes insulated or otherwise ³ ³ ³ ³ ³ ³configured to protect against ³ ³ ³ ³ ³ ³contact? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³Smooth ³Is the area below the lavatory ³ ³ ³ ³ ³Surfaces ³free of sharp or abrasive ³ ³ ³ ³ ³ ³surfaces? ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÙ 16-6 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.19.5 ³Faucet ³Can the faucet be operated with³ ³ ³ ³4.27.4 ³Operation ³one hand without tight ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³of the wrist? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³operate controls no greater ³ ³ ³ ³ ³ ³than 5 lbf? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If the valve is self-closing, ³ ³ ³ ³ ³ ³does it remain open for at ³ ³ ³ ³ ³ ³least 10 seconds? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.22.6 ³Mirrors ³Where mirrors are provided, ³ ³ ³ ³4.23.6 ³ ³does at least one mirror have a³ ³ ³ ³4.19.6 ³ ³bottom edge of the reflecting ³ ³ ³ ³ ³ ³surface no higher than 40 ³ ³ ³ ³ ³ ³inches from the floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.22.7 ³Dispensers ³Is at least one of each ³ ³ ³ ³4.23.7 ³Location ³dispenser type accessible and ³ ³ ³ ³ ³ ³on an accessible route? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.27.2 ³Floor Space ³Is there a clear floor space at³ ³ ³ ³4.2.4 ³ ³least 30 by 48 inches in front ³ ³ ³ ³ ³ ³of the dispenser allowing ³ ³ ³ ³ ³ ³either a forward or a parallel ³ ³ ³ ³ ³ ³approach to the dispenser? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.2.4.3 ³Surface ³Is the surface of the clear ³ ³ ³ ³ ³ ³floor space stable, firm and ³ ³ ³ ³ ³ ³slip resistant? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.27.3 ³Dispenser ³If a forward approach is ³ ³ ³ ³ ³Height ³provided, is the highest ³ ³ ³ ³ ³ ³operable part no higher than 48³ ³ ³ ³ ³ ³inches? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If a parallel approach is ³ ³ ³ ³ ³ ³provided, is the highest ³ ³ ³ ³ ³ ³operable part no higher than 54³ ³ ³ ³ ³ ³inches? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.27.4 ³Dispenser ³Can the dispenser be operated ³ ³ ³ ³ ³Operation ³with one hand without tight ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³of the wrist? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.23.9 ³Medicine ³If medicine cabinets are ³ ³ ³ ³ ³Cabinet ³provided, does at least one ³ ³ ³ ³ ³ ³have a usable shelf no higher ³ ³ ³ ³ ³ ³than 44 inches from the floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.2.4 ³Clear Floor ³Is there a clear floor space at³ ³ ³ ³ ³Space ³least 30 by 48 inches in front ³ ³ ³ ³ ³ ³of the medicine cabinet ³ ³ ³ ³ ³ ³allowing either a forward or ³ ³ ³ ³ ³ ³parallel approach to the ³ ³ ³ ³ ³ ³medicine cabinet? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.2.4.3 ³Surface ³Is the surface of the clear ³ ³ ³ ³ ³ ³floor space stable, firm and ³ ³ ³ ³ ³ ³slip resistant? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.25.2 ³Storage ³If fixed or built-in storage ³ ³ ³ ³4.2.4 ³ ³facilities are provided, does ³ ³ ³ ³ ³ ³at least one of each type have ³ ³ ³ ³ ³ ³a clear floor space 30 by 48 ³ ³ ³ ³ ³ ³inches allowing either a ³ ³ ³ ³ ³ ³forward or parallel approach? ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÙ 16-7 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.25.3 ³ ³If a parallel approach is ³ ³ ³ ³4.2.5 ³ ³provided, are clothes rods and ³ ³ ³ ³4.2.6 ³ ³shelves between 9 and 54 inches³ ³ ³ ³ ³ ³from the floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.25.3 ³Shelf Height ³Where the distance between a ³ ³ ³ ³ ³ ³wheelchair and clothes rod or ³ ³ ³ ³ ³ ³shelf is between 10 - 21 inches³ ³ ³ ³ ³ ³(e.g., closets without ³ ³ ³ ³ ³ ³accessible doors) is the ³ ³ ³ ³ ³ ³accessible shelf no more than ³ ³ ³ ³ ³ ³48 inches from the floor and ³ ³ ³ ³ ³ ³the reach no more than 21 ³ ³ ³ ³ ³ ³inches? (See Figure 38) ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.25.3 ³ ³If a front approach is ³ ³ ³ ³ ³ ³provided, are clothes rods and ³ ³ ³ ³ ³ ³shelves between 15 and 48 ³ ³ ³ ³ ³ ³inches from the floor? ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.23.8 ³Bathtubs and ³Where bathtubs or showers are ³ ³ ³ ³ ³Showers ³provided, does at least one ³ ³ ³ ³ ³ ³comply with 4.20 or 4.21? (Use³ ³ ³ ³ ³ ³Form 17: Bathtubs and Showers) ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(14) ³Alarms ³Where alarms are provided, do ³ ³ ³ ³4.28.1 ³ ³they comply with 4.28? (Use ³ ³ ³ ³ ³ ³Form 20: Alarms) ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÙ 16-8 16-9 Bars at Water Closets, and Lavatory Clearances] 16-10 16-11 of Handrails and Grab Bars] 16-12 SURVEY FORM 17: BATHTUBS AND SHOWERS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Bathroom Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.23.1 ³Accessible ³Are the bathing facilities ³ ³ ³ ³ ³ ³Route ³located on an accessible route?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.23.2 ³Doors ³Do the doors comply with 4.13? ³ ³ ³ ³ ³ ³ ³(Use Form 11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the door swing not intrude³ ³ ³ ³ ³ ³ ³into the clear floor space at ³ ³ ³ ³ ³ ³ ³any fixture? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.23.8 ³Bathtubs ³Where bathtubs are provided, ³ ³ ³ ³ ³4.20.1 ³ ³does at least one comply with ³ ³ ³ ³ ³ ³ ³4.20 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.2 ³Clear Space ³Does the clear floor space ³ ³ ³ ³ ³ ³ ³comply with both the dimensions³ ³ ³ ³ ³ ³ ³and approach shown in Figure ³ ³ ³ ³ ³ ³ ³33? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.3 ³Seat ³Is a securely mounted in-tub ³ ³ ³ ³ ³ ³ ³seat or built-in seat provided ³ ³ ³ ³ ³ ³ ³at the head of the tub? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.4 ³Grab Bar ³Are grab bar dimensions and ³ ³ ³ ³ ³ ³Placement ³locations as shown in Figure ³ ³ ³ ³ ³ ³ ³34? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.5 ³Controls: ³Can faucets and other controls ³ ³ ³ ³ ³4.27.4 ³ ³be operated with one hand and ³ ³ ³ ³ ³ ³ ³without tight grasping, ³ ³ ³ ³ ³ ³ ³pinching, or twisting of the ³ ³ ³ ³ ³ ³ ³wrist? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³operate the controls no greater³ ³ ³ ³ ³ ³ ³than 5 lbf? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.5 ³ ³Are controls located within the³ ³ ³ ³ ³ ³ ³area shown in Figure 34? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.6 ³Spray Unit ³Is there a shower spray unit ³ ³ ³ ³ ³ ³ ³with a hose at least 60 inches ³ ³ ³ ³ ³ ³ ³long? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Can the shower spray unit be ³ ³ ³ ³ ³ ³ ³used both as a hand-held and as³ ³ ³ ³ ³ ³ ³a fixed shower head? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.7 ³Enclosures ³If provided, are bathtub ³ ³ ³ ³ ³ ³ ³enclosures designed so that ³ ³ ³ ³ ³ ³ ³they do not obstruct the ³ ³ ³ ³ ³ ³ ³controls or transfer from a ³ ³ ³ ³ ³ ³ ³wheelchair onto the bathtub ³ ³ ³ ³ ³ ³ ³seat or into the bathtub? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If an enclosure is provided on ³ ³ ³ ³ ³ ³ ³the bathtub, is there no track ³ ³ ³ ³ ³ ³ ³mounted on the bathtub rim? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 17-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.23.8 ³Showers ³Where showers are provided, ³ ³ ³ ³ ³4.21.1 ³ ³does at least one comply with ³ ³ ³ ³ ³ ³ ³4.21 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.2 ³ ³In public and common use ³ ³ ³ ³ ³9.1.2 ³ ³bathing facilities with ³ ³ ³ ³ ³ ³ ³showers, does the shower stall ³ ³ ³ ³ ³ ³ ³size and clear floor space ³ ³ ³ ³ ³ ³ ³comply with either Figure 35(a)³ ³ ³ ³ ³ ³ ³for a transfer type shower or ³ ³ ³ ³ ³ ³ ³Figure 35(b) for a roll-in ³ ³ ³ ³ ³ ³ ³shower? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³In guest rooms in transient ³ ³ ³ ³ ³ ³ ³lodging required to have ³ ³ ³ ³ ³ ³ ³roll-in showers, does the ³ ³ ³ ³ ³ ³ ³shower stall size and clear ³ ³ ³ ³ ³ ³ ³floor space comply with Figure ³ ³ ³ ³ ³ ³ ³57(a) or 57(b)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.2 ³Transfer ³If the shower stall is a ³ ³ ³ ³ ³ ³Type ³transfer type shown in Figure ³ ³ ³ ³ ³ ³Showers ³35(a), is it exactly 36 by 36 ³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Clear Floor ³In a transfer type shower, is ³ ³ ³ ³ ³ ³Space ³there a clear floor space at ³ ³ ³ ³ ³ ³ ³least 36 by 48 inches outside ³ ³ ³ ³ ³ ³ ³the stall with 12 inches ³ ³ ³ ³ ³ ³ ³extending beyond the seat wall?³ ³ ³ ³ ³ ³ ³(See Figure 35(a)) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.3 ³Seat ³In a transfer type shower, is ³ ³ ³ ³ ³ ³ ³there a seat mounted between 17³ ³ ³ ³ ³ ³ ³and 19 inches from the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the seat extend the full ³ ³ ³ ³ ³ ³ ³depth of the stall? Is the seat³ ³ ³ ³ ³ ³ ³L-shaped and as shown in Figure³ ³ ³ ³ ³ ³ ³36? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the seat on the wall ³ ³ ³ ³ ³ ³ ³opposite the controls? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.4 ³Grab Bars ³In a transfer type shower, are ³ ³ ³ ³ ³ ³ ³grab bars provided between 33 ³ ³ ³ ³ ³ ³ ³and 36 inches above the floor ³ ³ ³ ³ ³ ³ ³along the control wall and half³ ³ ³ ³ ³ ³ ³the back wall (but not behind ³ ³ ³ ³ ³ ³ ³the seat) as shown in Figure ³ ³ ³ ³ ³ ³ ³37(a)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.7 ³Curbs ³If curbs are provided in a ³ ³ ³ ³ ³ ³ ³transfer type shower, are they ³ ³ ³ ³ ³ ³ ³no higher than 1/2 inch? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.5 ³Faucets ³In a transfer type shower, are ³ ³ ³ ³ ³ ³ ³the faucets and other controls ³ ³ ³ ³ ³ ³ ³located within the area shown ³ ³ ³ ³ ³ ³ ³in Figure 37(a)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.2 ³Roll-in ³In public or common use bathing³ ³ ³ ³ ³ ³Showers ³facilities, if the shower stall³ ³ ³ ³ ³ ³Public and ³is a roll-in type shown in ³ ³ ³ ³ ³ ³Common ³Figure 35(b), is it at least 30³ ³ ³ ³ ³ ³Use ³by 60 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.2 ³ ³Is there at least a 36 by 60 ³ ³ ³ ³ ³ ³ ³inch clear floor space ³ ³ ³ ³ ³ ³ ³alongside the roll-in shower as³ ³ ³ ³ ³ ³ ³shown in Figure 35(b)? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 17-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.4 ³Grab Bars ³In a roll-in shower, does a ³ ³ ³ ³ ³ ³ ³grab bar extend around three ³ ³ ³ ³ ³ ³ ³sides as shown in Figures 35(b)³ ³ ³ ³ ³ ³ ³and 37(b)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.7 ³Curbs ³Is there no curb at the roll-in³ ³ ³ ³ ³ ³ ³shower? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.5 ³Faucets ³In a roll-in shower, are the ³ ³ ³ ³ ³ ³ ³faucets and other controls ³ ³ ³ ³ ³ ³ ³located on the back wall within³ ³ ³ ³ ³ ³ ³the area shown in Figure 37(b) ³ ³ ³ ³ ³ ³ ³or on a side wall as shown in ³ ³ ³ ³ ³ ³ ³Figure 37(a)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.1.2 ³Roll-in ³In accessible guest rooms in ³ ³ ³ ³ ³4.21.2 ³Showers ³transient lodging required to ³ ³ ³ ³ ³ ³Transient ³have roll-in showers, is there ³ ³ ³ ³ ³ ³Lodging ³a shower complying with Figure ³ ³ ³ ³ ³ ³ ³57(a)? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is there a shower complying ³ ³ ³ ³ ³ ³ ³with Figure 57(b)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.3 ³Seat ³In a roll-in shower required in³ ³ ³ ³ ³ ³ ³accessible guest rooms in ³ ³ ³ ³ ³ ³ ³transient lodging, is there a ³ ³ ³ ³ ³ ³ ³folding seat affixed to the ³ ³ ³ ³ ³ ³ ³wall adjacent to the controls ³ ³ ³ ³ ³ ³ ³as shown in Figure 57(a) or ³ ³ ³ ³ ³ ³ ³57(b)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.4 ³Grab Bars ³In a roll-in shower required in³ ³ ³ ³ ³ ³ ³accessible guest rooms in ³ ³ ³ ³ ³ ³ ³transient lodging, are grab ³ ³ ³ ³ ³ ³ ³bars provided between 33 and 36³ ³ ³ ³ ³ ³ ³inches above the floor around ³ ³ ³ ³ ³ ³ ³two sides as shown in Figure ³ ³ ³ ³ ³ ³ ³57(a) or 57(b)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.7 ³Curbs ³Is there no curb at the roll-in³ ³ ³ ³ ³ ³ ³shower? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.5 ³Faucets ³In a roll-in shower required in³ ³ ³ ³ ³ ³ ³accessible guest rooms in ³ ³ ³ ³ ³ ³ ³transient lodging, are the ³ ³ ³ ³ ³ ³ ³faucets and other controls ³ ³ ³ ³ ³ ³ ³located within the area shown ³ ³ ³ ³ ³ ³ ³in Figure 57(a) or 57(b)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.5 ³Faucets - All ³In all accessible showers, can ³ ³ ³ ³ ³4.27.4 ³Accessible ³faucets and other controls be ³ ³ ³ ³ ³ ³Showers ³operated with one hand and ³ ³ ³ ³ ³ ³ ³without tight grasping, ³ ³ ³ ³ ³ ³ ³pinching, or twisting of the ³ ³ ³ ³ ³ ³ ³wrist? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³operate the controls no greater³ ³ ³ ³ ³ ³ ³than 5 lbf? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.6 ³Spray Unit ³In all accessible showers, does³ ³ ³ ³ ³ ³All ³the shower spray unit have a ³ ³ ³ ³ ³ ³Accessible ³hose at least 60 inches long? ³ ³ ³ ³ ³ ³Showers ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: In unmonitored ³ ³ ³ ³ ³ ³ ³facilities where vandalism is a³ ³ ³ ³ ³ ³ ³consideration, a fixed shower ³ ³ ³ ³ ³ ³ ³head mounted at 48 inches above³ ³ ³ ³ ³ ³ ³the shower floor may be used in³ ³ ³ ³ ³ ³ ³lieu of a hand-held shower ³ ³ ³ ³ ³ ³ ³head. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Can the shower spray unit be ³ ³ ³ ³ ³ ³ ³used both as a hand-held and as³ ³ ³ ³ ³ ³ ³a fixed shower head? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 17-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.4 ³Grab Bars ³Do all grab bars for accessible³ ³ ³ ³ ³4.21.4 ³ ³bathtubs and showers comply ³ ³ ³ ³ ³4.26.1 ³ ³with 4.26 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.2 ³Diameter ³Is the outside diameter of the ³ ³ ³ ³ ³ ³ ³grab bar between 1-1/4 inch and³ ³ ³ ³ ³ ³ ³1-1/2 inch? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Does the shape provide an ³ ³ ³ ³ ³ ³ ³equivalent gripping surface? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Standard pipe sizes ³ ³ ³ ³ ³ ³ ³designated by the industry as ³ ³ ³ ³ ³ ³ ³1-1/4 to 1-1/2 inches are ³ ³ ³ ³ ³ ³ ³acceptable for purposes of this³ ³ ³ ³ ³ ³ ³section. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the space between grab bars ³ ³ ³ ³ ³ ³ ³and walls exactly 1-1/2 ³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.3 ³ ³Are the grab bars secured so ³ ³ ³ ³ ³ ³ ³that they do not rotate within ³ ³ ³ ³ ³ ³ ³the fittings? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.2 ³Clearance in ³If a grab bar is located in a ³ ³ ³ ³ ³ ³Recess ³recess, is the recess a maximum³ ³ ³ ³ ³ ³ ³of 3 inches deep extending at ³ ³ ³ ³ ³ ³ ³least 18 inches above the rail?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.3 ³Structural ³Do the grab bars meet the ³ ³ ³ ³ ³ ³Strength ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for bending stress³ ³ ³ ³ ³ ³ ³and shear stress in 4.26.3? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.3 ³ ³Do the fasteners meet the ³ ³ ³ ³ ³ ³ ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for shear force ³ ³ ³ ³ ³ ³ ³and tensile force in 4.26.3? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.26.4 ³Hazards ³Are the grab bar edges free of ³ ³ ³ ³ ³ ³ ³sharp or abrasive elements and ³ ³ ³ ³ ³ ³ ³do edges have a minimum radius ³ ³ ³ ³ ³ ³ ³of 1/8 inch? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.20.3 ³Seats ³Do all seats for accessible ³ ³ ³ ³ ³4.21.3 ³ ³bathtubs and showers meet the ³ ³ ³ ³ ³4.26.3 ³ ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for bending stress³ ³ ³ ³ ³ ³ ³and shear stress in 4.26.3? Do³ ³ ³ ³ ³ ³ ³the fasteners meet the ³ ³ ³ ³ ³ ³ ³structural strength ³ ³ ³ ³ ³ ³ ³requirements for shear force ³ ³ ³ ³ ³ ³ ³and tensile force in 4.26.3? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.21.8 ³Shower Stall ³If a shower stall enclosure is ³ ³ ³ ³ ³ ³Enclosures ³provided for an accessible ³ ³ ³ ³ ³ ³ ³shower, is it located so that ³ ³ ³ ³ ³ ³ ³it does not obstruct the ³ ³ ³ ³ ³ ³ ³controls or obstruct transfer ³ ³ ³ ³ ³ ³ ³from a wheelchair into the ³ ³ ³ ³ ³ ³ ³shower seat? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 17-4 Bathtubs] 17-5 Design] 17-6 with Folding Seat] 17-7 SURVEY FORM 18: DRESSING AND FITTING ROOMS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Dressing/Fitting Room Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(21) ³Dressing and ³Where dressing and fitting ³ ³ ³ ³ ³4.35.1 ³Fitting Rooms ³rooms are provided for use by ³ ³ ³ ³ ³ ³ ³the general public, patients, ³ ³ ³ ³ ³ ³ ³customers or employees, does 5 ³ ³ ³ ³ ³ ³ ³percent (but not less than one)³ ³ ³ ³ ³ ³ ³of dressing and fitting rooms ³ ³ ³ ³ ³ ³ ³for each type of use in each ³ ³ ³ ³ ³ ³ ³cluster of dressing and fitting³ ³ ³ ³ ³ ³ ³rooms comply with 4.35 (See ³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.35.1 ³Accessible ³Are dressing and fitting rooms ³ ³ ³ ³ ³ ³Route ³that are required to be ³ ³ ³ ³ ³ ³ ³accessible located on an ³ ³ ³ ³ ³ ³ ³accessible route? (Use Form ³ ³ ³ ³ ³ ³ ³12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.35.2 ³Clear Floor ³In a dressing or fitting room ³ ³ ³ ³ ³ ³Space ³with a swinging or sliding ³ ³ ³ ³ ³ ³ ³door, is there clear floor ³ ³ ³ ³ ³ ³ ³space at least 60 inches in ³ ³ ³ ³ ³ ³ ³diameter (or a 60 by 60 inch ³ ³ ³ ³ ³ ³ ³T-shape) allowing a wheelchair ³ ³ ³ ³ ³ ³ ³user to make a 180-degree turn?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Door Swing ³Is the clear turning space not ³ ³ ³ ³ ³ ³ ³obstructed by the door swing? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.35.3 ³Doors ³Do all doors to accessible ³ ³ ³ ³ ³4.13 ³ ³dressing and fitting rooms ³ ³ ³ ³ ³ ³ ³comply with 4.13? (Use Form 11:³ ³ ³ ³ ³ ³ ³Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Curtained ³If the dressing or fitting room³ ³ ³ ³ ³ ³Openings ³is private and entered through ³ ³ ³ ³ ³ ³ ³a curtained opening, is the ³ ³ ³ ³ ³ ³ ³opening at least 32 inches ³ ³ ³ ³ ³ ³ ³wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there adequate clear floor ³ ³ ³ ³ ³ ³ ³space in the dressing or ³ ³ ³ ³ ³ ³ ³fitting room and immediately ³ ³ ³ ³ ³ ³ ³adjacent to the curtained ³ ³ ³ ³ ³ ³ ³opening so that the dressing ³ ³ ³ ³ ³ ³ ³room is usable by a wheelchair ³ ³ ³ ³ ³ ³ ³user? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.35.4 ³Bench Affixed ³Does every accessible dressing ³ ³ ³ ³ ³ ³to Wall ³and fitting room have a 24 by ³ ³ ³ ³ ³ ³ ³48 inch (minimum) bench fixed ³ ³ ³ ³ ³ ³ ³to the wall along the longer ³ ³ ³ ³ ³ ³ ³dimension? (The bench may be a³ ³ ³ ³ ³ ³ ³folding type.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 18-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Bench Height ³Is the bench mounted 17 to 19 ³ ³ ³ ³ ³ ³ ³inches above the finish floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there clear floor space at ³ ³ ³ ³ ³ ³ ³least 30 by 48 inches provided ³ ³ ³ ³ ³ ³ ³alongside of the bench to allow³ ³ ³ ³ ³ ³ ³a person using a wheelchair to ³ ³ ³ ³ ³ ³ ³make a parallel transfer onto ³ ³ ³ ³ ³ ³ ³the bench? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.35.4 ³Bench Strength ³Does the structural strength of³ ³ ³ ³ ³4.26.3 ³ ³the bench and attachments ³ ³ ³ ³ ³ ³ ³comply with 4.26.3? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.35.4 ³Bench in Wet ³Where installed in conjunction ³ ³ ³ ³ ³ ³Areas ³with showers, swimming pools or³ ³ ³ ³ ³ ³ ³other wet locations, does the ³ ³ ³ ³ ³ ³ ³surface of the bench have a ³ ³ ³ ³ ³ ³ ³slip-resistant surface? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the bench in a wet location ³ ³ ³ ³ ³ ³ ³constructed so that water does ³ ³ ³ ³ ³ ³ ³not accumulate on the surface? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.35.5 ³Mirror ³If there is a mirror, is it a ³ ³ ³ ³ ³ ³ ³full-length mirror at least 18 ³ ³ ³ ³ ³ ³ ³inches wide by 54 inches high? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the mirror mounted in a ³ ³ ³ ³ ³ ³ ³position affording a view to a ³ ³ ³ ³ ³ ³ ³person on the bench as well as ³ ³ ³ ³ ³ ³ ³to a person in a standing ³ ³ ³ ³ ³ ³ ³position? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 18-2 SURVEY FORM 19: SIGNAGE Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Location: See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(7) ³Directional ³Do signs which provide ³ ³ ³ ³ ³4.1.3(16) ³and ³direction to, or information ³ ³ ³ ³ ³4.30.1 ³Informational ³about, functional spaces of the³ ³ ³ ³ ³ ³Signs: ³building comply with 4.30.2, ³ ³ ³ ³ ³ ³ ³4.30.3, and 4.30.5 (See below)?³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Building ³ ³ ³ ³ ³ ³ ³directories, menus, and all ³ ³ ³ ³ ³ ³ ³other signs which are temporary³ ³ ³ ³ ³ ³ ³are not required to comply. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.2 ³Character ³Do the letters and numbers on ³ ³ ³ ³ ³ ³Proportion ³such signs have a width to ³ ³ ³ ³ ³ ³ ³height ratio between 3:5 and ³ ³ ³ ³ ³ ³ ³1:1; and a stroke ³ ³ ³ ³ ³ ³ ³width-to-height ratio between ³ ³ ³ ³ ³ ³ ³1:5 and 1:10? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.3 ³Character Size ³Are the characters on such ³ ³ ³ ³ ³ ³ ³signs sized according to ³ ³ ³ ³ ³ ³ ³viewing distance with ³ ³ ³ ³ ³ ³ ³characters on overhead signs at³ ³ ³ ³ ³ ³ ³least 3 inches high? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.5 ³Finish ³Do the characters and ³ ³ ³ ³ ³ ³ ³backgrounds on such signs have ³ ³ ³ ³ ³ ³ ³a non-glare finish? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contrast ³Do the characters contrast with³ ³ ³ ³ ³ ³ ³their background (light-on-dark³ ³ ³ ³ ³ ³ ³or dark-on- light)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(7) ³Room and ³Do signs which designate ³ ³ ³ ³ ³4.1.3(16) ³Space ³permanent rooms and spaces ³ ³ ³ ³ ³4.30.1 ³Identification ³comply with 4.30.4, 4.30.5, and³ ³ ³ ³ ³ ³Signs: ³4.30.6 (See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.4 ³Raised and ³Are the characters on such ³ ³ ³ ³ ³ ³Braille ³signs raised and accompanied by³ ³ ³ ³ ³ ³Characters ³Grade II Braille? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 19-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Pictograms ³If a pictorial symbol ³ ³ ³ ³ ³ ³ ³(pictogram) is used to ³ ³ ³ ³ ³ ³ ³designate permanent rooms and ³ ³ ³ ³ ³ ³ ³spaces, is the pictogram ³ ³ ³ ³ ³ ³ ³accompanied by the equivalent ³ ³ ³ ³ ³ ³ ³verbal description placed ³ ³ ³ ³ ³ ³ ³directly below the pictogram? ³ ³ ³ ³ ³ ³ ³(The verbal description must be³ ³ ³ ³ ³ ³ ³in raised letters and ³ ³ ³ ³ ³ ³ ³accompanied by Grade II ³ ³ ³ ³ ³ ³ ³Braille.) (If the International³ ³ ³ ³ ³ ³ ³Symbol of Accessibility or ³ ³ ³ ³ ³ ³ ³other information in addition ³ ³ ³ ³ ³ ³ ³to room and space designation ³ ³ ³ ³ ³ ³ ³is included on the sign, it ³ ³ ³ ³ ³ ³ ³does not have to be raised and ³ ³ ³ ³ ³ ³ ³accompanied by Grade II ³ ³ ³ ³ ³ ³ ³Braille.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the border dimension of the ³ ³ ³ ³ ³ ³ ³pictogram at least 6 inches ³ ³ ³ ³ ³ ³ ³high? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Character Size ³Are the raised characters on ³ ³ ³ ³ ³ ³ ³such signs between 5/8 inch and³ ³ ³ ³ ³ ³ ³2 inches high and raised at ³ ³ ³ ³ ³ ³ ³least 1/32 inch? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Upper Case ³Are the raised characters on ³ ³ ³ ³ ³ ³ ³such signs upper case, and sans³ ³ ³ ³ ³ ³ ³serif or simple serif? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.5 ³Finish ³Do the characters and ³ ³ ³ ³ ³ ³ ³background on such signs have a³ ³ ³ ³ ³ ³ ³non-glare finish? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contrast ³Do the characters on such signs³ ³ ³ ³ ³ ³ ³contrast with their background ³ ³ ³ ³ ³ ³ ³(light-on-dark or ³ ³ ³ ³ ³ ³ ³dark-on-light)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.6 ³Mounting ³Are such signs mounted on the ³ ³ ³ ³ ³ ³Location ³wall adjacent to the latch side³ ³ ³ ³ ³ ³ ³of the door? (At double leaf ³ ³ ³ ³ ³ ³ ³doors, are the signs placed on ³ ³ ³ ³ ³ ³ ³the nearest adjacent wall?) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Mounting ³Are such signs mounted with ³ ³ ³ ³ ³ ³Height ³their centerline 60 inches ³ ³ ³ ³ ³ ³ ³above the ground surface? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Approach ³Can a person approach to within³ ³ ³ ³ ³ ³ ³3 inches of such signs without ³ ³ ³ ³ ³ ³ ³encountering protruding objects³ ³ ³ ³ ³ ³ ³or standing within the swing of³ ³ ³ ³ ³ ³ ³the door? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 19-2 SURVEY FORM 20: ALARMS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Alarm Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Note: Emergency warning systems in medical care facilities may be modified to suit standard health care alarm design practice. (4.1.3(14)) ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(14) ³Alarms ³Does the building or facility ³ ³ ³ ³ ³ ³ ³have a fire, evacuation or ³ ³ ³ ³ ³ ³ ³emergency alarm? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there a visual alarm (e.g., ³ ³ ³ ³ ³ ³ ³flashing light) which operates ³ ³ ³ ³ ³ ³ ³at the same time as an audible ³ ³ ³ ³ ³ ³ ³alarm? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.28.1 ³Visual Alarms - ³Are there visual alarms in ³ ³ ³ ³ ³ ³Areas Required ³public and common use ³ ³ ³ ³ ³ ³ ³restrooms? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are visual alarms provided in ³ ³ ³ ³ ³ ³ ³all general use areas of the ³ ³ ³ ³ ³ ³ ³building such as meeting rooms,³ ³ ³ ³ ³ ³ ³hallways, and lobbies? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.28.3 ³ ³Are the visual alarm signal ³ ³ ³ ³ ³ ³ ³appliances integrated into the ³ ³ ³ ³ ³ ³ ³building or facility alarm ³ ³ ³ ³ ³ ³ ³system? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If single-station audible ³ ³ ³ ³ ³ ³ ³alarms are provided, then are ³ ³ ³ ³ ³ ³ ³single-station visual alarm ³ ³ ³ ³ ³ ³ ³signals provided? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 20-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Photometric ³Do all required visual alarm ³ ³ ³ ³ ³ ³Requirements ³signals comply with the ³ ³ ³ ³ ³ ³ ³following minimum photometric ³ ³ ³ ³ ³ ³ ³requirements: ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Is the lamp a xenon strobe type³ ³ ³ ³ ³ ³ ³or equivalent? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Is the color clear or nominal ³ ³ ³ ³ ³ ³ ³white (i.e., unfiltered or ³ ³ ³ ³ ³ ³ ³clear filtered white light)? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Is the maximum pulse duration ³ ³ ³ ³ ³ ³ ³two-tenths of one second with a³ ³ ³ ³ ³ ³ ³maximum duty cycle of 40 ³ ³ ³ ³ ³ ³ ³percent? (The pulse duration ³ ³ ³ ³ ³ ³ ³is defined as the time interval³ ³ ³ ³ ³ ³ ³between initial and final ³ ³ ³ ³ ³ ³ ³points of 10 percent of maximum³ ³ ³ ³ ³ ³ ³signal.) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Is the intensity a minimum of ³ ³ ³ ³ ³ ³ ³75 candela? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the flash rate a minimum of ³ ³ ³ ³ ³ ³ ³1 Hz and a maximum of 3 Hz? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.28.3 ³Location ³Is the visual signal appliance ³ ³ ³ ³ ³ ³ ³placed 80 inches above the ³ ³ ³ ³ ³ ³ ³highest floor level within the ³ ³ ³ ³ ³ ³ ³space or 6 inches below the ³ ³ ³ ³ ³ ³ ³ceiling, whichever is lower? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are all portions of any room, ³ ³ ³ ³ ³ ³ ³space, corridor or hallway that³ ³ ³ ³ ³ ³ ³is required to have a visual ³ ³ ³ ³ ³ ³ ³signal appliance no more than ³ ³ ³ ³ ³ ³ ³50 feet from the signal (in the³ ³ ³ ³ ³ ³ ³horizontal plane)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³In large rooms and spaces ³ ³ ³ ³ ³ ³ ³exceeding 100 feet across which³ ³ ³ ³ ³ ³ ³do not have partitions or ³ ³ ³ ³ ³ ³ ³obstructions 6 feet or higher ³ ³ ³ ³ ³ ³ ³above the finish floor, are the³ ³ ³ ³ ³ ³ ³visual signal appliances spaced³ ³ ³ ³ ³ ³ ³around the perimeter no less ³ ³ ³ ³ ³ ³ ³than 100 feet apart or are they³ ³ ³ ³ ³ ³ ³suspended from the ceiling? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.28.2 ³Audible Alarms ³If provided, do audible alarms ³ ³ ³ ³ ³ ³ ³exceed the prevailing ³ ³ ³ ³ ³ ³ ³equivalent sound level in the ³ ³ ³ ³ ³ ³ ³room or space by at least 15 ³ ³ ³ ³ ³ ³ ³dbA, or do audible alarms ³ ³ ³ ³ ³ ³ ³exceed by 5 dbA any maximum ³ ³ ³ ³ ³ ³ ³sound level which has a ³ ³ ³ ³ ³ ³ ³duration of 60 seconds, ³ ³ ³ ³ ³ ³ ³whichever is louder? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³(In no case should sound levels³ ³ ³ ³ ³ ³ ³for alarm signals exceed 120 ³ ³ ³ ³ ³ ³ ³dbA.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 20-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.28.4 ³Auxiliary ³Do accessible dwelling units ³ ³ ³ ³ ³ ³Alarms ³and sleeping accommodations ³ ³ ³ ³ ³ ³Sleeping Rooms ³have a visual alarm connected ³ ³ ³ ³ ³ ³ ³to the building emergency alarm³ ³ ³ ³ ³ ³ ³system? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is there a standard 110-volt ³ ³ ³ ³ ³ ³ ³electrical receptacle into ³ ³ ³ ³ ³ ³ ³which an alarm can be connected³ ³ ³ ³ ³ ³ ³and a means by which the ³ ³ ³ ³ ³ ³ ³building alarm system will ³ ³ ³ ³ ³ ³ ³trigger such an alarm? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³When visual alarms are in ³ ³ ³ ³ ³ ³ ³place, is the signal visible in³ ³ ³ ³ ³ ³ ³all areas of the unit or room? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.28.4 ³Instructions ³Are instructions for using the ³ ³ ³ ³ ³ ³ ³auxiliary alarm provided? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 20-3 SURVEY FORM 21: DETECTABLE WARNINGS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Location of Detectable Warning: See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.7.7 ³Curb Ramps ³Do curb ramps on a site have a ³ ³ ³ ³ ³ ³ ³detectable warning complying ³ ³ ³ ³ ³ ³ ³with 4.29.2 (see below) ³ ³ ³ ³ ³ ³ ³extending the full width and ³ ³ ³ ³ ³ ³ ³depth of the curb ramp? ³ ³ ³ ³ ³ ³ ³(Detectable warnings are not ³ ³ ³ ³ ³ ³ ³required on the flared sides.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.5 ³Hazardous ³If a walk crosses or adjoins a ³ ³ ³ ³ ³ ³Vehicular ³vehicular way and the walking ³ ³ ³ ³ ³ ³Way ³surfaces are not separated by ³ ³ ³ ³ ³ ³ ³curbs, railings, or other ³ ³ ³ ³ ³ ³ ³elements between the pedestrian³ ³ ³ ³ ³ ³ ³areas and vehicular areas, is ³ ³ ³ ³ ³ ³ ³the boundary between the areas ³ ³ ³ ³ ³ ³ ³defined by a continuous ³ ³ ³ ³ ³ ³ ³detectable warning complying ³ ³ ³ ³ ³ ³ ³with 4.29.2 which is 36 inches ³ ³ ³ ³ ³ ³ ³wide on the edge of the ³ ³ ³ ³ ³ ³ ³pedestrian area? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.6 ³Reflecting ³Are the edges of reflecting ³ ³ ³ ³ ³ ³Pools ³pools protected by railings, ³ ³ ³ ³ ³ ³ ³walls, curbs, or detectable ³ ³ ³ ³ ³ ³ ³warnings complying with 4.29.2?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.2 ³Detectable ³Do detectable warnings consist ³ ³ ³ ³ ³ ³Warnings ³of raised truncated domes with ³ ³ ³ ³ ³ ³Pattern ³a nominal diameter of 0.9 ³ ³ ³ ³ ³ ³ ³inches, a nominal height of 0.2³ ³ ³ ³ ³ ³ ³inches, and a nominal ³ ³ ³ ³ ³ ³ ³center-to-center spacing of ³ ³ ³ ³ ³ ³ ³2.35 inches? (See Figure ³ ³ ³ ³ ³ ³ ³below) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contrast ³Do detectable warnings contrast³ ³ ³ ³ ³ ³ ³visually with adjoining ³ ³ ³ ³ ³ ³ ³surfaces (light-on- dark or ³ ³ ³ ³ ³ ³ ³dark-on-light)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the material used to provide³ ³ ³ ³ ³ ³ ³contrast an integral part of ³ ³ ³ ³ ³ ³ ³the walking surface? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Interior ³Do the detectable warnings used³ ³ ³ ³ ³ ³Resilience ³on interior surfaces differ ³ ³ ³ ³ ³ ³and Sound ³from adjoining walking surfaces³ ³ ³ ³ ³ ³ ³in resiliency or sound-on-cane ³ ³ ³ ³ ³ ³ ³contact? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 21-1 Section] SURVEY FORM 22: AUTOMATED TELLER MACHINES (ATMS) Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ATM Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ See Minimum Requirements Summary Sheets I and J for special requirements and exceptions which may be allowed in alterations and historic preservation. See also ADAAG 4.1.6 and 4.1.7. Note: The Access Board published a Notice of Proposed Rulemaking (NPRM) on September 8, 1992 (57 FR 41006) proposing to amend the reach range requirements for accessible automated teller machines. This rulemaking may result in a revision to ADAAG 4.34 (Automated Teller Machines). ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(20) ³ATMs ³If one or more ATMs are ³ ³ ³ ³ ³ ³ ³provided at a location, does at³ ³ ³ ³ ³ ³ ³least one comply with 4.34 (See³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Drive-up-only ³ ³ ³ ³ ³ ³ ³automated teller machines are ³ ³ ³ ³ ³ ³ ³not required to comply with the³ ³ ³ ³ ³ ³ ³reach and clear floor space ³ ³ ³ ³ ³ ³ ³requirements of 4.27.2, 4.27.3 ³ ³ ³ ³ ³ ³ ³and 4.34.3. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.34.1 ³Accessible ³Is each accessible ATM located ³ ³ ³ ³ ³ ³Route ³on an accessible route? (Use ³ ³ ³ ³ ³ ³ ³Form 12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.34.3 ³Clear Floor ³Is there clear floor space at ³ ³ ³ ³ ³4.27.2 ³Space ³least 30 by 48 inches, which ³ ³ ³ ³ ³ ³ ³allows a parallel approach by a³ ³ ³ ³ ³ ³ ³wheelchair user? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.34.2 ³Controls ³Is the highest operable part of³ ³ ³ ³ ³4.27.3 ³ ³the controls within both ³ ³ ³ ³ ³ ³ ³forward and side reach ranges ³ ³ ³ ³ ³ ³ ³for wheelchair users (48 ³ ³ ³ ³ ³ ³ ³inches)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the controls operable with ³ ³ ³ ³ ³ ³ ³one hand, and without tight ³ ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³ ³of the wrist? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the force required to ³ ³ ³ ³ ³ ³ ³activate the controls no ³ ³ ³ ³ ³ ³ ³greater than 5 lbf? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.34.4 ³Access for ³Are instructions and ³ ³ ³ ³ ³ ³Persons with ³information for use made ³ ³ ³ ³ ³ ³Visual ³accessible to and independently³ ³ ³ ³ ³ ³Impairments ³usable by people with visual ³ ³ ³ ³ ³ ³ ³impairments? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 22-1 SURVEY FORM 23: RESTAURANTS AND CAFETERIAS Use with the Minimum Requirements Summary Sheets and ADAAG. Restaurant Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Except as specified or modified in ADAAG 5, restaurants and cafeterias must comply with ADAAG 4.1 to 4.35. Restaurant Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.1 ³Accessible ³Does at least 5% (but not less ³ ³ ³ ³ ³4.1.3(18) ³Tables and ³than 1) of all fixed tables ³ ³ ³ ³ ³ ³Dining ³comply with 4.32 (See below)? ³ ³ ³ ³ ³ ³Counters ³OR ³ ³ ³ ³ ³ ³ ³Where food is consumed at a ³ ³ ³ ³ ³ ³ ³dining counter but there is no ³ ³ ³ ³ ³ ³ ³service, does a portion of the ³ ³ ³ ³ ³ ³ ³dining counter comply with 4.32³ ³ ³ ³ ³ ³ ³(See below)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.2 ³Clear Floor ³Do seating spaces provided for ³ ³ ³ ³ ³4.2.4 ³Space ³wheelchair users have at least ³ ³ ³ ³ ³ ³Seating ³a 30 by 48 inch clear floor ³ ³ ³ ³ ³ ³ ³space which adjoins or overlaps³ ³ ³ ³ ³ ³ ³an accessible route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is no more than 19 inches of ³ ³ ³ ³ ³ ³ ³the 30 by 48 inch clear space ³ ³ ³ ³ ³ ³ ³measured under the table? (See³ ³ ³ ³ ³ ³ ³Figure 45) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.3 ³Knee Space ³Is the knee space at least 27 ³ ³ ³ ³ ³ ³ ³inches high, 30 inches wide, ³ ³ ³ ³ ³ ³ ³and 19 inches deep? (See ³ ³ ³ ³ ³ ³ ³Figure 45) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.4 ³Table/Counter ³Is the top of the table or ³ ³ ³ ³ ³ ³Height ³counter between 28 and 34 ³ ³ ³ ³ ³ ³ ³inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.1 ³Distribution ³Where separate areas are ³ ³ ³ ³ ³ ³ ³designated for smoking and ³ ³ ³ ³ ³ ³ ³non-smoking patrons, are ³ ³ ³ ³ ³ ³ ³accessible tables or counters ³ ³ ³ ³ ³ ³ ³proportionally distributed ³ ³ ³ ³ ³ ³ ³between smoking and non-smoking³ ³ ³ ³ ³ ³ ³areas? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³In new construction, and where ³ ³ ³ ³ ³ ³ ³practicable in alterations, are³ ³ ³ ³ ³ ³ ³the accessible tables or ³ ³ ³ ³ ³ ³ ³counters distributed throughout³ ³ ³ ³ ³ ³ ³the space? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 23-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.2 ³Counters and ³Where counter service is ³ ³ ³ ³ ³4.32 ³Bars ³provided, is at least a 60 inch³ ³ ³ ³ ³ ³ ³wide portion of the main ³ ³ ³ ³ ³ ³ ³counter no more than 34 inches ³ ³ ³ ³ ³ ³ ³high with at least 27 inch high³ ³ ³ ³ ³ ³ ³knee space below? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is service available at ³ ³ ³ ³ ³ ³ ³accessible tables within the ³ ³ ³ ³ ³ ³ ³same area? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.3 ³Access Aisles ³Are all aisles between ³ ³ ³ ³ ³4.3.3 ³ ³accessible fixed tables at ³ ³ ³ ³ ³ ³ ³least 36 inches wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.4 ³Dining Areas - ³n new construction, are all ³ ³ ³ ³ ³ ³New ³dining areas, including raised ³ ³ ³ ³ ³ ³Construction ³or sunken areas and outdoor ³ ³ ³ ³ ³ ³ ³seating areas, accessible? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: An accessible ³ ³ ³ ³ ³ ³ ³means of vertical access to a ³ ³ ³ ³ ³ ³ ³mezzanine is not required in a ³ ³ ³ ³ ³ ³ ³building eligible for the ³ ³ ³ ³ ³ ³ ³elevator exception (See ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 1) where: ³ ³ ³ ³ ³ ³ ³(1) the area of mezzanine ³ ³ ³ ³ ³ ³ ³seating is not larger than 33% ³ ³ ³ ³ ³ ³ ³of the accessible seating area,³ ³ ³ ³ ³ ³ ³(2) the same services and ³ ³ ³ ³ ³ ³ ³decorative character are ³ ³ ³ ³ ³ ³ ³provided in the accessible ³ ³ ³ ³ ³ ³ ³space and, (3) the accessible ³ ³ ³ ³ ³ ³ ³areas are not restricted to use³ ³ ³ ³ ³ ³ ³by people with disabilities. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Alterations ³In alterations, are all raised ³ ³ ³ ³ ³ ³ ³or sunken dining areas and all ³ ³ ³ ³ ³ ³ ³parts of outdoor seating ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is accessible seating provided ³ ³ ³ ³ ³ ³ ³in an accessible space usable ³ ³ ³ ³ ³ ³ ³by the general public which ³ ³ ³ ³ ³ ³ ³provides the same services and ³ ³ ³ ³ ³ ³ ³decor as provided in ³ ³ ³ ³ ³ ³ ³inaccessible areas? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.5 ³Food Service ³Do food service lines have at ³ ³ ³ ³ ³ ³Lines ³least 36 inches of clear width?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Tray Slide ³Are tray slides no more than 34³ ³ ³ ³ ³ ³ ³inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.5 ³Self-Service ³Where self-service shelves are ³ ³ ³ ³ ³4.2.5 ³Shelves ³provided for food service, is ³ ³ ³ ³ ³4.2.6 ³Food Service ³at least 50 percent of each ³ ³ ³ ³ ³ ³ ³type no higher than 54 inches ³ ³ ³ ³ ³ ³ ³above the floor for a parallel ³ ³ ³ ³ ³ ³ ³approach and no higher than 48 ³ ³ ³ ³ ³ ³ ³inches for a front approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.6 ³Tableware and ³Are self-service shelves and ³ ³ ³ ³ ³ ³Condiment ³dispensing devices for ³ ³ ³ ³ ³ ³Areas ³tableware, dishware, ³ ³ ³ ³ ³ ³ ³condiments, food and beverages ³ ³ ³ ³ ³ ³ ³installed in accordance with ³ ³ ³ ³ ³ ³ ³Figure 54? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 23-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.7 ³Raised ³In banquet rooms or spaces ³ ³ ³ ³ ³ ³Platforms ³where a head table or speaker's³ ³ ³ ³ ³ ³ ³lectern is located on a raised ³ ³ ³ ³ ³ ³ ³platform, is the platform ³ ³ ³ ³ ³ ³ ³accessible by means of a ramp ³ ³ ³ ³ ³ ³ ³or platform lift complying with³ ³ ³ ³ ³ ³ ³4.8 or 4.11? (Use Form 7: ³ ³ ³ ³ ³ ³ ³Ramps or Form 9: Platform ³ ³ ³ ³ ³ ³ ³Lifts.) (Lifts may only be ³ ³ ³ ³ ³ ³ ³used in certain limited ³ ³ ³ ³ ³ ³ ³situations in new construction.³ ³ ³ ³ ³ ³ ³See Minimum Requirements ³ ³ ³ ³ ³ ³ ³Summary Sheets D and ADAAG ³ ³ ³ ³ ³ ³ ³4.1.3(5) Exception 4) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the open edges of a raised ³ ³ ³ ³ ³ ³ ³platform protected by placement³ ³ ³ ³ ³ ³ ³of tables or by a curb? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³5.8 ³Vending ³Are spaces for vending machines³ ³ ³ ³ ³4.2 ³Machines ³located on an accessible route?³ ³ ³ ³ ³ ³ ³(Use Form 12: Building Lobbies ³ ³ ³ ³ ³ ³ ³and Corridors) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 23-3 Tableware Areas] 23-4 SURVEY FORM 24: MEDICAL CARE FACILITIES Use with the Minimum Requirements Summary Sheets and ADAAG. 22, as applicable, as well as this form. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Use Forms 1 to In addition to the requirements of ADAAG 4.1 through 4.35, medical care facilities must comply with ADAAG 6. Medical care facilities covered by ADAAG 6 are those in which people receive physical or medical treatment or care and where persons may need assistance in responding to an emergency and where the period of stay may exceed twenty-four hours. ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(5)(d)³Parking ³If the unit or facility is an ³ ³ ³ ³ ³4.6 ³Outpatient ³outpatient facility, does 10 ³ ³ ³ ³ ³ ³Facilities ³percent of the total number of ³ ³ ³ ³ ³ ³ ³parking spaces serving such ³ ³ ³ ³ ³ ³ ³unit or facility comply with ³ ³ ³ ³ ³ ³ ³4.6? (Use Form 1: Parking) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Facilities ³If the unit or facility is one ³ ³ ³ ³ ³ ³Treating ³that specializes in treatment ³ ³ ³ ³ ³ ³Persons with ³or services for persons with ³ ³ ³ ³ ³ ³Mobility ³mobility impairments, does 20 ³ ³ ³ ³ ³ ³Impairments ³percent of the parking spaces ³ ³ ³ ³ ³ ³ ³serving such unit or facility ³ ³ ³ ³ ³ ³ ³comply with 4.6? (Use Form 1: ³ ³ ³ ³ ³ ³ ³Parking) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.2(5)(a)³ ³Do other facilities comply with³ ³ ³ ³ ³ ³ ³the table in 4.1.2(5)(a)? (Use³ ³ ³ ³ ³ ³ ³Form 1: Parking) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is one in every eight ³ ³ ³ ³ ³ ³ ³accessible parking spaces (but ³ ³ ³ ³ ³ ³ ³not less than one) designated ³ ³ ³ ³ ³ ³ ³"van accessible"? (Use Form 1:³ ³ ³ ³ ³ ³ ³Parking) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.2 ³Entrance ³Is there at least one ³ ³ ³ ³ ³ ³ ³accessible entrance covered by ³ ³ ³ ³ ³ ³ ³a canopy or overhang? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Passenger ³Is there an accessible ³ ³ ³ ³ ³ ³Loading Zone ³passenger loading zone at this ³ ³ ³ ³ ³ ³ ³entrance complying with 4.6.6? ³ ³ ³ ³ ³ ³ ³(Use Form 2: Passenger Loading ³ ³ ³ ³ ³ ³ ³Zones) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.1 ³Public and ³In all medical care facilities,³ ³ ³ ³ ³ ³Common Use ³are all public use and common ³ ³ ³ ³ ³ ³Areas ³use areas accessible? (Use ³ ³ ³ ³ ³ ³ ³Form 14: Rooms and Spaces and ³ ³ ³ ³ ³ ³ ³Form 16: Toilet Rooms and ³ ³ ³ ³ ³ ³ ³Bathrooms) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.1(1) ³Patient ³If the facility is a general ³ ³ ³ ³ ³ ³Bedrooms ³purpose hospital, are at least ³ ³ ³ ³ ³ ³and ³10 percent of patient bedrooms ³ ³ ³ ³ ³ ³Toilets ³and toilets accessible? ³ ³ ³ ³ ³ ³General ³ ³ ³ ³ ³ ³ ³Purpose ³Note: The distribution of ³ ³ ³ ³ ³ ³Hospitals ³accessible patient bedrooms can³ ³ ³ ³ ³ ³ ³vary based on the anticipated ³ ³ ³ ³ ³ ³ ³need in different specialized ³ ³ ³ ³ ³ ³ ³units (e.g., more than 10% may ³ ³ ³ ³ ³ ³ ³be needed in a general surgical³ ³ ³ ³ ³ ³ ³unit and less than 10% in ³ ³ ³ ³ ³ ³ ³obstetrics and pediatrics). ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 24-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.1(2) ³Facilities ³If the facility is a hospital ³ ³ ³ ³ ³ ³Treating ³or rehabilitation facility that³ ³ ³ ³ ³ ³Persons with ³specializes in treating ³ ³ ³ ³ ³ ³Mobility ³conditions that affect ³ ³ ³ ³ ³ ³Impairments ³mobility, or units within ³ ³ ³ ³ ³ ³ ³either that specialize in ³ ³ ³ ³ ³ ³ ³treating conditions that affect³ ³ ³ ³ ³ ³ ³mobility, are all patient ³ ³ ³ ³ ³ ³ ³bedrooms and toilets ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.1(3) ³Nursing ³If the facility is a long term ³ ³ ³ ³ ³ ³Homes ³care facility or nursing home, ³ ³ ³ ³ ³ ³ ³are at least 50 percent of ³ ³ ³ ³ ³ ³ ³patient bedrooms and toilets ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(1) ³Accessible ³Are accessible patient bedrooms³ ³ ³ ³ ³ ³Route ³located on an accessible route?³ ³ ³ ³ ³ ³ ³(Use Form 12: Building Lobbies ³ ³ ³ ³ ³ ³ ³and Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.3 ³Accessible ³Do accessible patient bedrooms ³ ³ ³ ³ ³ ³Patient ³comply with the following ³ ³ ³ ³ ³ ³Bedrooms ³provisions? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.3(1) ³Doors ³Does the door to each ³ ³ ³ ³ ³4.13 ³ ³accessible bedroom comply with ³ ³ ³ ³ ³ ³ ³4.13? (Use Form 11: Doors and ³ ³ ³ ³ ³ ³ ³Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.13.6 ³ ³If the door is not automatic or³ ³ ³ ³ ³ ³ ³power assisted, does it have ³ ³ ³ ³ ³ ³ ³maneuvering space relative to ³ ³ ³ ³ ³ ³ ³the direction of approach as ³ ³ ³ ³ ³ ³ ³shown in Figure 25? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Entry doors to ³ ³ ³ ³ ³ ³ ³acute care hospital bedrooms ³ ³ ³ ³ ³ ³ ³are exempt from the requirement³ ³ ³ ³ ³ ³ ³for the 18 inch space at the ³ ³ ³ ³ ³ ³ ³latch side of the door if the ³ ³ ³ ³ ³ ³ ³door is at least 44 inches ³ ³ ³ ³ ³ ³ ³wide. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.3(2) ³Floor Space ³Does each accessible bedroom ³ ³ ³ ³ ³ ³ ³have adequate space to provide ³ ³ ³ ³ ³ ³ ³a maneuvering space of 60 ³ ³ ³ ³ ³ ³ ³inches in diameter or a ³ ³ ³ ³ ³ ³ ³T-shaped space (See Figure 3)? ³ ³ ³ ³ ³ ³ ³(If the room has two beds, it ³ ³ ³ ³ ³ ³ ³is preferable that this space ³ ³ ³ ³ ³ ³ ³be located between the beds.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.3(3) ³ ³Does each accessible bedroom ³ ³ ³ ³ ³ ³ ³have adequate space to provide ³ ³ ³ ³ ³ ³ ³floor space at least 36 inches ³ ³ ³ ³ ³ ³ ³wide on each side of the bed? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³ Does each accessible bedroom ³ ³ ³ ³ ³ ³ ³have adequate space to provide ³ ³ ³ ³ ³ ³ ³an accessible route to each ³ ³ ³ ³ ³ ³ ³side of the bed? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.4 ³Patient ³If patient toilet/bath rooms ³ ³ ³ ³ ³4.22 ³Toilet/Bath ³are provided as part of a ³ ³ ³ ³ ³4.23 ³Rooms ³patient bedroom, does each ³ ³ ³ ³ ³ ³ ³accessible patient bedroom have³ ³ ³ ³ ³ ³ ³an accessible toilet/bath room ³ ³ ³ ³ ³ ³ ³complying with 4.22 or 4.23 ³ ³ ³ ³ ³ ³ ³located on an accessible route?³ ³ ³ ³ ³ ³ ³(Use Form 16: Toilet Rooms and³ ³ ³ ³ ³ ³ ³Bathrooms and Form 17: Bathtubs³ ³ ³ ³ ³ ³ ³and Showers) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 24-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.1(4)(a) ³Alterations ³Where patient bedrooms are ³ ³ ³ ³ ³ ³Patient ³added or altered as part of ³ ³ ³ ³ ³ ³Bedrooms in ³renovation to an entire wing, ³ ³ ³ ³ ³ ³Units, Wings ³department, or other discrete ³ ³ ³ ³ ³ ³or Discrete ³area, does the percentage of ³ ³ ³ ³ ³ ³Areas ³accessible rooms provided ³ ³ ³ ³ ³ ³ ³comply with 6.1(1), 6.1(2) or ³ ³ ³ ³ ³ ³ ³6.1(3) (See above)? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: No additional accessible³ ³ ³ ³ ³ ³ ³rooms are required in an ³ ³ ³ ³ ³ ³ ³alteration when the overall ³ ³ ³ ³ ³ ³ ³number of accessible bedrooms ³ ³ ³ ³ ³ ³ ³provided in the facility would ³ ³ ³ ³ ³ ³ ³meet or exceed the number ³ ³ ³ ³ ³ ³ ³required in new construction. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the altered patient bedrooms³ ³ ³ ³ ³ ³ ³and toilet/bath rooms which are³ ³ ³ ³ ³ ³ ³required to be accessible ³ ³ ³ ³ ³ ³ ³comply with 6.3 (See above)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³6.1(4)(b) ³Individual ³Where patient bedrooms are ³ ³ ³ ³ ³ ³Patient ³added or altered individually, ³ ³ ³ ³ ³ ³Bedrooms ³do they comply with 6.3 (See ³ ³ ³ ³ ³ ³ ³above)? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: No additional ³ ³ ³ ³ ³ ³ ³accessible patient bedrooms are³ ³ ³ ³ ³ ³ ³required in an alteration when ³ ³ ³ ³ ³ ³ ³either of the following occur: ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³The number of accessible ³ ³ ³ ³ ³ ³ ³bedrooms provided in the unit, ³ ³ ³ ³ ³ ³ ³department or area meet or ³ ³ ³ ³ ³ ³ ³exceed the percentage ³ ³ ³ ³ ³ ³ ³requirements of 6.1(1), 6.1(2),³ ³ ³ ³ ³ ³ ³or 6.1(3), ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³The number of accessible ³ ³ ³ ³ ³ ³ ³bedrooms provided in the ³ ³ ³ ³ ³ ³ ³facility equals the overall ³ ³ ³ ³ ³ ³ ³number that would be required ³ ³ ³ ³ ³ ³ ³if the facility were newly ³ ³ ³ ³ ³ ³ ³constructed. ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 24-3 25-5 SURVEY FORM 25: MERCANTILE FACILITIES Use with the Minimum Requirements Summary Sheets and ADAAG. Use Survey Forms 1 to 22, as applicable, as well as this form. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Location ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Check-out Aisles: Total Check-Out Aisles of Each Minimum Number of Accessible Design: Check-Out Aisles of Each Design ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ 1 - 4 1 5 - 8 2 9 - 15 3 over 15 3, plus 20% of additional aisles In addition to the requirements of ADAAG 4.1 through 4.35, mercantile buildings and facilities must comply with ADAAG 7. EXCEPTION: In new construction, where the selling space is under 5,000 square feet, only one check-out aisle is required to be accessible. EXCEPTION: In alterations, at least one check-out aisle shall be accessible in facilities under 5,000 square feet of selling space. In facilities of 5,000 or more square feet of selling space, at least one of each design of check-out aisle shall be made accessible when altered until the number of accessible check-out aisles of each design equals the number required in new construction. ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.1 ³General ³Are all areas used for business³ ³ ³ ³ ³ ³ ³transactions with the public ³ ³ ³ ³ ³ ³ ³accessible as required below? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.2(1) ³Sales/Service ³In department stores and ³ ³ ³ ³ ³ ³Counters³miscellaneous retail stores ³ ³ ³ ³ ³ ³With Cash ³where counters have cash ³ ³ ³ ³ ³ ³Registers ³registers, is there at least ³ ³ ³ ³ ³ ³ ³one of each type of counter ³ ³ ³ ³ ³ ³ ³where a portion of the counter ³ ³ ³ ³ ³ ³ ³is at least 36 inches long and ³ ³ ³ ³ ³ ³ ³no more than 36 inches high? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³In alterations, where it is ³ ³ ³ ³ ³ ³ ³technically infeasible to ³ ³ ³ ³ ³ ³ ³provide an accessible counter, ³ ³ ³ ³ ³ ³ ³is an auxiliary counter meeting³ ³ ³ ³ ³ ³ ³the above requirements ³ ³ ³ ³ ³ ³ ³provided? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the accessible counters ³ ³ ³ ³ ³ ³ ³dispersed throughout the ³ ³ ³ ³ ³ ³ ³building? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.2(2) ³Sales/Service ³At ticketing counters, teller ³ ³ ³ ³ ³ ³Counters ³stations, registration counters³ ³ ³ ³ ³ ³Without Cash ³and other counters which may ³ ³ ³ ³ ³ ³Registers ³not have cash registers, is ³ ³ ³ ³ ³ ³ ³there a portion of the main ³ ³ ³ ³ ³ ³ ³counter at least 36 inches long³ ³ ³ ³ ³ ³ ³and no more than 36 inches ³ ³ ³ ³ ³ ³ ³high? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 25-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is there an auxiliary counter ³ ³ ³ ³ ³ ³ ³at least 36 inches high near ³ ³ ³ ³ ³ ³ ³the main counter? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is equivalent facilitation ³ ³ ³ ³ ³ ³ ³provided? (e.g., at a hotel ³ ³ ³ ³ ³ ³ ³registration desk, equivalent ³ ³ ³ ³ ³ ³ ³facilitation might consist of: ³ ³ ³ ³ ³ ³ ³(1) the provision of a folding ³ ³ ³ ³ ³ ³ ³shelf attached to the main ³ ³ ³ ³ ³ ³ ³counter on which a person with ³ ³ ³ ³ ³ ³ ³a disability can write, and (2)³ ³ ³ ³ ³ ³ ³use of the space at the side of³ ³ ³ ³ ³ ³ ³the counter for handing ³ ³ ³ ³ ³ ³ ³materials back and forth.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do all accessible counters on ³ ³ ³ ³ ³ ³ ³an accessible route comply with³ ³ ³ ³ ³ ³ ³4.3? (Use Form 12: Building ³ ³ ³ ³ ³ ³ ³Corridors and Lobbies) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.3(1) ³Check-out ³In new construction, does the ³ ³ ³ ³ ³ ³Aisles - New ³number of accessible check-out ³ ³ ³ ³ ³ ³Construction ³aisles comply with the table ³ ³ ³ ³ ³ ³ ³above? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³In new construction where the ³ ³ ³ ³ ³ ³ ³selling space is under 5,000 ³ ³ ³ ³ ³ ³ ³square feet, is at least one ³ ³ ³ ³ ³ ³ ³check-out aisle accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Alterations ³In alterations, is at least one³ ³ ³ ³ ³ ³ ³check-out aisle of each design ³ ³ ³ ³ ³ ³ ³made accessible when altered ³ ³ ³ ³ ³ ³ ³until the number of accessible ³ ³ ³ ³ ³ ³ ³check-out aisles equals the ³ ³ ³ ³ ³ ³ ³number required in the table ³ ³ ³ ³ ³ ³ ³above? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³In alterations of facilities ³ ³ ³ ³ ³ ³ ³that have under 5,000 square ³ ³ ³ ³ ³ ³ ³feet of selling space, is there³ ³ ³ ³ ³ ³ ³at least one check-out aisle ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.3(2) ³Aisle Width ³Is the clear aisle width of ³ ³ ³ ³ ³4.2.1 ³ ³accessible check-out aisles at ³ ³ ³ ³ ³ ³ ³least 36 inches wide for ³ ³ ³ ³ ³ ³ ³lengths greater than 24 inches ³ ³ ³ ³ ³ ³ ³long and at least 32 inches ³ ³ ³ ³ ³ ³ ³wide for lengths 24 inches or ³ ³ ³ ³ ³ ³ ³less? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If there is a lip on the edge ³ ³ ³ ³ ³ ³ ³of the counter adjoining the ³ ³ ³ ³ ³ ³ ³aisle, is the top of the lip no³ ³ ³ ³ ³ ³ ³more than 40 inches above the ³ ³ ³ ³ ³ ³ ³floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Height ³Is the adjoining counter/belt ³ ³ ³ ³ ³ ³ ³height no more than 38 inches ³ ³ ³ ³ ³ ³ ³above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.3(3) ³Signs ³Is there a sign identifying ³ ³ ³ ³ ³ ³ ³each accessible check-out aisle³ ³ ³ ³ ³ ³ ³which is mounted above the ³ ³ ³ ³ ³ ³ ³check-out aisle? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the sign include the ³ ³ ³ ³ ³ ³ ³International Symbol of ³ ³ ³ ³ ³ ³ ³Accessibility? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 25-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.4 ³Security ³Are security bollards or other ³ ³ ³ ³ ³ ³Bollards ³such devices installed so that ³ ³ ³ ³ ³ ³ ³access and egress for ³ ³ ³ ³ ³ ³ ³wheelchair users is provided? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is there an alternate ³ ³ ³ ³ ³ ³ ³accessible entry that is ³ ³ ³ ³ ³ ³ ³equally convenient as that ³ ³ ³ ³ ³ ³ ³provided for the general ³ ³ ³ ³ ³ ³ ³public? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 25-3 SURVEY FORM 26: LIBRARIES Use with the Minimum Requirements Summary Sheets and ADAAG. Use Survey Forms 1 to 22 as applicable, as well as this form. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ In addition to the requirements of ADAAG 4.1 through 4.35, libraries must comply with ADAAG 8. Library Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³8.2 ³Reading and ³Do at least 5% (but not less ³ ³ ³ ³ ³ ³Study Areas ³than one) of fixed seating, ³ ³ ³ ³ ³ ³ ³tables, or study carrels comply³ ³ ³ ³ ³ ³ ³with 4.2 and 4.3.2 (See below)?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.2.4 ³Seating ³Do spaces provided for ³ ³ ³ ³ ³4.32.2 ³Clear Floor ³wheelchair users have a 30 by ³ ³ ³ ³ ³ ³Space ³48 inch clear space which ³ ³ ³ ³ ³ ³ ³overlaps an accessible route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is no more than 19 inches of ³ ³ ³ ³ ³ ³ ³the 30 by 48 inch clear space ³ ³ ³ ³ ³ ³ ³measured under the table? (See³ ³ ³ ³ ³ ³ ³Figure 45) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.3 ³Knee Space ³Is the knee space under the ³ ³ ³ ³ ³ ³ ³table at least 27 inches high, ³ ³ ³ ³ ³ ³ ³30 inches wide, and 19 inches ³ ³ ³ ³ ³ ³ ³deep? (See Figure 45) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.32.4 ³Height ³Is the top of the table between³ ³ ³ ³ ³ ³ ³28 and 34 inches from the ³ ³ ³ ³ ³ ³ ³floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.3.3 ³Aisles ³Are the aisles leading up to ³ ³ ³ ³ ³ ³ ³and between the tables or study³ ³ ³ ³ ³ ³ ³carrels at least 36 inches ³ ³ ³ ³ ³ ³ ³wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³8.3 ³Check-Out ³Is there at least one lane at ³ ³ ³ ³ ³7.2(1) ³Areas ³each check-out area where a ³ ³ ³ ³ ³ ³ ³portion of the counter is at ³ ³ ³ ³ ³ ³ ³least 36 inches long and no ³ ³ ³ ³ ³ ³ ³more than 36 inches high? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³8.3 ³Security ³Do security gates or turnstiles³ ³ ³ ³ ³4.13 ³Gates ³comply with 4.13? (Use Form ³ ³ ³ ³ ³ ³ ³10: Doors and Gates) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Is there an accessible gate or ³ ³ ³ ³ ³ ³ ³door next to a turnstile or ³ ³ ³ ³ ³ ³ ³security device? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³8.4 ³Card Catalogs ³Is the aisle between card ³ ³ ³ ³ ³ ³and Magazine ³catalogs and magazine displays ³ ³ ³ ³ ³ ³Displays ³at least 36 inches wide? (See ³ ³ ³ ³ ³ ³ ³Figure 55) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Reach ³Are the card catalogs between ³ ³ ³ ³ ³ ³ ³18 and 54 inches from the ³ ³ ³ ³ ³ ³ ³floor? (A height of 48 inches ³ ³ ³ ³ ³ ³ ³is preferred.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 26-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³8.5 ³Stacks ³Is the minimum clear aisle ³ ³ ³ ³ ³4.3 ³ ³width between the stacks at ³ ³ ³ ³ ³ ³ ³least 36 inches? (See Figure ³ ³ ³ ³ ³ ³ ³56) (A minimum clear aisle ³ ³ ³ ³ ³ ³ ³width of 42 inches is preferred³ ³ ³ ³ ³ ³ ³where possible. Shelf height ³ ³ ³ ³ ³ ³ ³in stack areas is ³ ³ ³ ³ ³ ³ ³unrestricted.) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 26-2 Card Catalog and Stacks] SURVEY FORM 27: TRANSIENT LODGING Ä HOTELS, MOTELS, INNS, BOARDING HOUSES, DORMITORIES, AND SIMILAR PLACES Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Except as specified in ADAAG 9.1, hotels, motels, inns, boarding houses, dormitories, and other similar places of transient lodging must comply with the applicable provisions of ADAAG 4.1 through 4.35. EXCEPTION: ADAAG 9.1 through 9.4 do not apply to an establishment located within a building that contains not more than five rooms for rent or hire and that is actually occupied by the proprietor of such establishment as the residence of such proprietor. Table A Number of Rooms Required to be Fully Accessible Table B Number of Rooms Required to be Accessible to People with Hearing Impairments ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Number of Accessible Rooms with Number of Rooms Accessible Rooms Rooms Rooms Roll-in Showers 1 to 25 1 1 to 25 1 26 to 50 2 26 to 50 2 51 to 75 3 1 51 to 75 3 76 to 100 4 1 76 to 100 4 101 to 150 5 2 101 to 150 5 151 to 200 6 2 151 to 200 6 201 to 300 7 3 201 to 300 7 301 to 400 8 4 301 to 400 8 401 to 500 9 4 plus one for 401 to 500 9 each additional 501 to 1000 2% of total 501 to 1000 2% of total 100 over 400 1001 and over 20 plus 1 for 1001 and over 20 plus 1 for each 100 over 1000 each 100 over 1000 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.1.1 ³Public/ ³Do all public use and common ³ ³ ³ ³ ³ ³Common Use ³use areas comply with 4.1 ³ ³ ³ ³ ³ ³Areas ³through 4.35? (Use Forms 1 to ³ ³ ³ ³ ³ ³ ³22 as applicable) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.1.2 ³Number of ³Does the number of accessible ³ ³ ³ ³ ³ ³Accessible ³sleeping rooms or suites comply³ ³ ³ ³ ³ ³Rooms ³with Table A? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.1.2 ³Number of ³In hotels of 51 or more ³ ³ ³ ³ ³ ³Rooms With ³sleeping rooms or suites, are ³ ³ ³ ³ ³ ³Roll-in ³additional accessible sleeping ³ ³ ³ ³ ³ ³Showers ³rooms with roll-in showers ³ ³ ³ ³ ³ ³ ³provided in compliance with ³ ³ ³ ³ ³ ³ ³Table A? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Roll-in ³Do the roll-in showers comply ³ ³ ³ ³ ³ ³Showers ³with requirements of 4.21 and ³ ³ ³ ³ ³ ³ ³Figure 57(a) or 57 (b)? (Use ³ ³ ³ ³ ³ ³ ³Form 17: Bathtubs and Showers) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 27-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.1.4 ³Classes of ³Are the accessible rooms and ³ ³ ³ ³ ³ ³Sleeping ³suites dispersed among various ³ ³ ³ ³ ³ ³Rooms ³classes of sleeping ³ ³ ³ ³ ³ ³ ³accommodations available to all³ ³ ³ ³ ³ ³ ³patrons? (Factors to be ³ ³ ³ ³ ³ ³ ³considered include room size, ³ ³ ³ ³ ³ ³ ³cost, amenities and number of ³ ³ ³ ³ ³ ³ ³beds provided.) ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is equivalent facilitation ³ ³ ³ ³ ³ ³ ³provided as follows: ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³For purposes of this section, ³ ³ ³ ³ ³ ³ ³the operator may choose to ³ ³ ³ ³ ³ ³ ³limit construction of ³ ³ ³ ³ ³ ³ ³accessible rooms to those ³ ³ ³ ³ ³ ³ ³designed for multiple ³ ³ ³ ³ ³ ³ ³occupancy rooms if the multiple³ ³ ³ ³ ³ ³ ³occupancy accessible rooms are ³ ³ ³ ³ ³ ³ ³made available at a ³ ³ ³ ³ ³ ³ ³single-occupancy rate to an ³ ³ ³ ³ ³ ³ ³individual with a disability ³ ³ ³ ³ ³ ³ ³who requests a single-occupancy³ ³ ³ ³ ³ ³ ³room. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2 ³Accessible ³Are the accessible rooms and ³ ³ ³ ³ ³ ³Rooms and ³suites on an accessible route ³ ³ ³ ³ ³ ³Suites Ä ³complying with 4.3? (Use Form ³ ³ ³ ³ ³ ³Accessible ³12: Building Lobbies and ³ ³ ³ ³ ³ ³Route ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(2) ³Accessible ³Does an accessible route ³ ³ ³ ³ ³ ³Route ³complying with 4.3 connect all ³ ³ ³ ³ ³ ³ ³accessible spaces and elements ³ ³ ³ ³ ³ ³ ³within the accessible units, ³ ³ ³ ³ ³ ³ ³including telephones? (Use Form³ ³ ³ ³ ³ ³ ³13: Building Corridors and ³ ³ ³ ³ ³ ³ ³Lobbies) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: An elevator is not ³ ³ ³ ³ ³ ³ ³required in a multi-story unit,³ ³ ³ ³ ³ ³ ³if the spaces identified in ³ ³ ³ ³ ³ ³ ³9.2.2(6) and (7) below are on ³ ³ ³ ³ ³ ³ ³an accessible level and the ³ ³ ³ ³ ³ ³ ³accessible sleeping area is ³ ³ ³ ³ ³ ³ ³suitable for dual occupancy. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(1) ³Maneuvering ³Do accessible sleeping rooms ³ ³ ³ ³ ³ ³Space at ³have a maneuvering space at ³ ³ ³ ³ ³ ³Beds ³least 36 inches wide located ³ ³ ³ ³ ³ ³ ³along both sides of a bed? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Where two beds are provided, is³ ³ ³ ³ ³ ³ ³there at least a 36 inch wide ³ ³ ³ ³ ³ ³ ³maneuvering space located ³ ³ ³ ³ ³ ³ ³between the two beds? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(3) ³Doors ³Do the doors into and within ³ ³ ³ ³ ³ ³ ³the accessible units comply ³ ³ ³ ³ ³ ³ ³with 4.13? (Use Form 11: Doors³ ³ ³ ³ ³ ³ ³and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(4) ³Storage ³If fixed or built-in storage ³ ³ ³ ³ ³ ³ ³facilities are provided, does ³ ³ ³ ³ ³ ³ ³at least one of each type ³ ³ ³ ³ ³ ³ ³provided comply with 4.25? (Use³ ³ ³ ³ ³ ³ ³Form 14: Rooms and Spaces) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Additional storage may be³ ³ ³ ³ ³ ³ ³provided outside the dimensions³ ³ ³ ³ ³ ³ ³required in 4.25. ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 27-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(5), ³Controls ³Do all controls in the ³ ³ ³ ³ ³9.2.2(7) ³ ³accessible units and on ³ ³ ³ ³ ³ ³ ³appliances or other built-in ³ ³ ³ ³ ³ ³ ³features comply with 4.27? (Use³ ³ ³ ³ ³ ³ ³Form 14: Rooms and Spaces) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(6) ³Accessible ³Where provided as part of an ³ ³ ³ ³ ³ ³Areas and ³accessible unit, are the living³ ³ ³ ³ ³ ³Spaces ³area; dining area; at least one³ ³ ³ ³ ³ ³ ³sleeping area; and patio, ³ ³ ³ ³ ³ ³ ³terrace or balcony accessible? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: The requirements of³ ³ ³ ³ ³ ³ ³4.13.8 (thresholds at doors) ³ ³ ³ ³ ³ ³ ³and 4.3.8 (changes in level) do³ ³ ³ ³ ³ ³ ³not apply where it is necessary³ ³ ³ ³ ³ ³ ³to utilize a higher door ³ ³ ³ ³ ³ ³ ³threshold or a change in level ³ ³ ³ ³ ³ ³ ³to protect the integrity of the³ ³ ³ ³ ³ ³ ³unit from wind/water damage. ³ ³ ³ ³ ³ ³ ³Where this exception results in³ ³ ³ ³ ³ ³ ³patios, terraces or balconies ³ ³ ³ ³ ³ ³ ³that are not at an accessible ³ ³ ³ ³ ³ ³ ³level, equivalent facilitation ³ ³ ³ ³ ³ ³ ³shall be provided. (e.g., ³ ³ ³ ³ ³ ³ ³equivalent facilitation at a ³ ³ ³ ³ ³ ³ ³hotel patio or balcony might ³ ³ ³ ³ ³ ³ ³consist of providing raised ³ ³ ³ ³ ³ ³ ³decking or a ramp to provide ³ ³ ³ ³ ³ ³ ³accessibility.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(6) ³Bathrooms ³Is at least one full bathroom ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³If only half-baths are ³ ³ ³ ³ ³ ³ ³provided, is at least one ³ ³ ³ ³ ³ ³ ³half-bath accessible? (Use ³ ³ ³ ³ ³ ³ ³Form 16: Toilet Rooms and ³ ³ ³ ³ ³ ³ ³Bathrooms, and Form 17: ³ ³ ³ ³ ³ ³ ³Bathtubs and Showers) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(6) ³Parking ³If parking is provided, is the ³ ³ ³ ³ ³ ³ ³carport, garage or parking ³ ³ ³ ³ ³ ³ ³space accessible? (Use Form 1: ³ ³ ³ ³ ³ ³ ³Parking) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(7) ³Kitchens ³If provided as part of an ³ ³ ³ ³ ³ ³ ³accessible unit, are kitchens, ³ ³ ³ ³ ³ ³ ³kitchenettes, or wet bars ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is clear floor space at least ³ ³ ³ ³ ³ ³ ³30 inches by 48 inches provided³ ³ ³ ³ ³ ³ ³for a front or parallel ³ ³ ³ ³ ³ ³ ³approach to cabinets, counters,³ ³ ³ ³ ³ ³ ³sinks, and appliances? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are countertops and sinks ³ ³ ³ ³ ³ ³ ³mounted no more than 34 inches ³ ³ ³ ³ ³ ³ ³above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is at least 50% of the shelf ³ ³ ³ ³ ³ ³ ³space in cabinets or ³ ³ ³ ³ ³ ³ ³refrigerator/freezers within ³ ³ ³ ³ ³ ³ ³the reach ranges of between 15 ³ ³ ³ ³ ³ ³ ³inches and 48 inches for a ³ ³ ³ ³ ³ ³ ³front approach and between 9 ³ ³ ³ ³ ³ ³ ³inches and 54 inches for a ³ ³ ³ ³ ³ ³ ³parallel approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.2.2(8) ³Accommodations ³In rooms and suites required to³ ³ ³ ³ ³ ³for Persons ³be accessible under Table A, ³ ³ ³ ³ ³ ³with Hearing ³are visual alarms, notification³ ³ ³ ³ ³ ³Impairments ³devices and telephones ³ ³ ³ ³ ³ ³ ³complying with 9.3 (see below) ³ ³ ³ ³ ³ ³ ³provided? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 27-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.1.3 ³Additional ³Are additional sleeping rooms ³ ³ ³ ³ ³ ³Rooms for ³or suites for persons with ³ ³ ³ ³ ³ ³Persons ³hearing impairments provided in³ ³ ³ ³ ³ ³with Hearing ³compliance with Table B? ³ ³ ³ ³ ³ ³Impairments ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.3 ³Visual Alarms ³Are auxiliary visual alarms ³ ³ ³ ³ ³ ³ ³complying with 4.28.4 provided ³ ³ ³ ³ ³ ³ ³in the accessible rooms or ³ ³ ³ ³ ³ ³ ³suites required in Tables A and³ ³ ³ ³ ³ ³ ³B? (Use Form 20: Alarms) ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are electrical outlets provided³ ³ ³ ³ ³ ³ ³(including one connected to the³ ³ ³ ³ ³ ³ ³facility's central alarm ³ ³ ³ ³ ³ ³ ³system) to enable room ³ ³ ³ ³ ³ ³ ³occupants to utilize portable ³ ³ ³ ³ ³ ³ ³devices provided by the ³ ³ ³ ³ ³ ³ ³operator of the facility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.3.1 ³Visual ³Are visual notification devices³ ³ ³ ³ ³9.3.2 ³Notification ³to alert room occupants of ³ ³ ³ ³ ³ ³Devices ³incoming telephone calls and a ³ ³ ³ ³ ³ ³ ³door knock or bell provided in ³ ³ ³ ³ ³ ³ ³the accessible sleeping rooms ³ ³ ³ ³ ³ ³ ³or suites required in Tables A ³ ³ ³ ³ ³ ³ ³and B? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are electrical outlets provided³ ³ ³ ³ ³ ³ ³to enable room occupants to ³ ³ ³ ³ ³ ³ ³utilize portable devices ³ ³ ³ ³ ³ ³ ³provided by the operator of the³ ³ ³ ³ ³ ³ ³facility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are visual notification devices³ ³ ³ ³ ³ ³ ³not connected to the auxiliary ³ ³ ³ ³ ³ ³ ³visual alarm signal devices? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.3.1 ³Telephones ³If the telephone is permanently³ ³ ³ ³ ³ ³ ³installed, does it have a ³ ³ ³ ³ ³ ³ ³volume control capable of a ³ ³ ³ ³ ³ ³ ³minimum of 12 dbA and a maximum³ ³ ³ ³ ³ ³ ³of 18 dbA above normal? (If an³ ³ ³ ³ ³ ³ ³automatic reset is provided, ³ ³ ³ ³ ³ ³ ³then 18 dbA may be exceeded.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there an accessible ³ ³ ³ ³ ³ ³ ³electrical outlet within 4 feet³ ³ ³ ³ ³ ³ ³of a telephone connection to ³ ³ ³ ³ ³ ³ ³facilitate the use of a text ³ ³ ³ ³ ³ ³ ³telephone? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.4 ³All Other ³Do doors and doorways designed ³ ³ ³ ³ ³ ³Rooms and ³to allow passage into and ³ ³ ³ ³ ³ ³Suites ³within all other sleeping ³ ³ ³ ³ ³ ³ ³rooms, suites, or other covered³ ³ ³ ³ ³ ³ ³units provide at least a 32 ³ ³ ³ ³ ³ ³ ³inch clear opening width? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.1.5 ³Alterations Ä ³When sleeping rooms or suites ³ ³ ³ ³ ³ ³Accessible ³are altered, is at least one ³ ³ ³ ³ ³ ³Rooms ³accessible room or suite ³ ³ ³ ³ ³ ³ ³complying with 9.1.2 and 9.2 ³ ³ ³ ³ ³ ³ ³(see above) provided for each ³ ³ ³ ³ ³ ³ ³25 altered rooms (or portion ³ ³ ³ ³ ³ ³ ³thereof) until the number ³ ³ ³ ³ ³ ³ ³equals that in Table A? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Rooms for ³In addition, when sleeping ³ ³ ³ ³ ³ ³Persons ³rooms or with suites are ³ ³ ³ ³ ³ ³Hearing ³altered, is at least one room ³ ³ ³ ³ ³ ³Impairments ³complying with 9.1.3 and 9.3 ³ ³ ³ ³ ³ ³ ³(see above) provided for each ³ ³ ³ ³ ³ ³ ³25 altered rooms (or portion ³ ³ ³ ³ ³ ³ ³thereof) until the number ³ ³ ³ ³ ³ ³ ³equals that in Table B? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 27-4 27-5 SURVEY FORM 28: TRANSIENT LODGING IN HOMELESS SHELTERS, HALFWAY HOUSES, TRANSIENT GROUP HOMES, AND OTHER SOCIAL SERVICES ESTABLISHMENTS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Except as specified in ADAAG 9.5, transient lodging in homeless shelters, halfway houses, transient group homes, and other social service establishments must comply with the applicable provisions of ADAAG 4.1 through 4.35. Facility Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Table A: Number of Rooms/Beds Required to be Fully Accessible Table B: Number of Rooms/Beds Required to be Accessible to People with Hearing Impairments Number of Accessible Number of Accessible Rooms/Beds Rooms/Beds Rooms/Beds Rooms/Beds ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ 1 to 25 1 1 to 25 1 26 to 50 2 26 to 50 2 51 to 75 3 51 to 75 3 76 to 100 4 76 to 100 4 101 to 150 5 101 to 150 5 151 to 200 6 151 to 200 6 201 to 300 7 201 to 300 7 301 to 400 8 301 to 400 8 401 to 500 9 401 to 500 9 501 to 1000 2% of total 501 to 1000 2% of total 1001 and over 20 plus 1 for 1001 and over 20 plus 1 for each 100 over each 100 over 1000 1000 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.1 ³Public/ ³In new construction, do all ³ ³ ³ ³ ³ ³Common Use ³public and common use areas ³ ³ ³ ³ ³ ³Areas Ä New ³comply with 4.1 through 4.35? ³ ³ ³ ³ ³ ³Construction ³(Use Forms 1 to 22 as ³ ³ ³ ³ ³ ³ ³applicable) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.1 ³Amenities ³Is at least one of each type of³ ³ ³ ³ ³ ³ ³amenity (e.g., washers, dryers,³ ³ ³ ³ ³ ³ ³and similar equipment) in each ³ ³ ³ ³ ³ ³ ³common area accessible and ³ ³ ³ ³ ³ ³ ³located on an accessible route ³ ³ ³ ³ ³ ³ ³to any accessible sleeping ³ ³ ³ ³ ³ ³ ³room? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Where a building is³ ³ ³ ³ ³ ³ ³exempt from the elevator ³ ³ ³ ³ ³ ³ ³requirement (see 4.1.3(5)), ³ ³ ³ ³ ³ ³ ³accessible amenities are not ³ ³ ³ ³ ³ ³ ³required on inaccessible floors³ ³ ³ ³ ³ ³ ³as long as one of each type is ³ ³ ³ ³ ³ ³ ³provided in common areas on ³ ³ ³ ³ ³ ³ ³accessible floors. ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 28-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3, ³Accessible ³In new construction, does the ³ ³ ³ ³ ³9.1.2 ³Sleeping ³number of accessible sleeping ³ ³ ³ ³ ³ ³Accommodations ³rooms comply with Table A? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³In facilities with multi-bed ³ ³ ³ ³ ³ ³ ³rooms or spaces, are accessible³ ³ ³ ³ ³ ³ ³beds complying with 9.2.2(1) ³ ³ ³ ³ ³ ³ ³(see below) provided in a ³ ³ ³ ³ ³ ³ ³number equal to Table A? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Accessible ³Do the accessible sleeping ³ ³ ³ ³ ³9.2.2 ³Route ³rooms on an accessible route ³ ³ ³ ³ ³ ³ ³comply with 4.3? (Use Form 12:³ ³ ³ ³ ³ ³ ³Building Lobbies and Corridors)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Accessible ³Does an accessible route ³ ³ ³ ³ ³9.2.2(2) ³Route ³complying with 4.3 connect all ³ ³ ³ ³ ³ ³ ³accessible spaces and elements ³ ³ ³ ³ ³ ³ ³within the accessible sleeping ³ ³ ³ ³ ³ ³ ³rooms, including telephones? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: An elevator is not ³ ³ ³ ³ ³ ³ ³required in a multi-story ³ ³ ³ ³ ³ ³ ³facility, if at least one of ³ ³ ³ ³ ³ ³ ³each type of space identified ³ ³ ³ ³ ³ ³ ³in 9.2.2(6) and (7) below is on³ ³ ³ ³ ³ ³ ³an accessible level. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Maneuvering ³Do accessible sleeping rooms ³ ³ ³ ³ ³9.2.2(1) ³Space at Beds ³have maneuvering space at least³ ³ ³ ³ ³ ³ ³36 inches wide located along ³ ³ ³ ³ ³ ³ ³both sides of a bed? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Where two beds are provided, is³ ³ ³ ³ ³ ³ ³there at least a 36 inch wide ³ ³ ³ ³ ³ ³ ³maneuvering space located ³ ³ ³ ³ ³ ³ ³between the two beds? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Doors ³Do the doors into and within ³ ³ ³ ³ ³9.2.2(3) ³ ³the accessible sleeping rooms ³ ³ ³ ³ ³ ³ ³comply with 4.13? (Use Form ³ ³ ³ ³ ³ ³ ³11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Storage ³If fixed or built-in storage ³ ³ ³ ³ ³9.2.2(4) ³ ³facilities are provided, does ³ ³ ³ ³ ³ ³ ³at least one of each type ³ ³ ³ ³ ³ ³ ³provided comply with 4.25? (Use³ ³ ³ ³ ³ ³ ³Form 14: Rooms and Spaces) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Additional storage may ³ ³ ³ ³ ³ ³ ³be provided outside the ³ ³ ³ ³ ³ ³ ³dimensions required by 4.25. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Controls ³Do all controls, including ³ ³ ³ ³ ³9.2.2(5) ³ ³those on amenities provided in ³ ³ ³ ³ ³9.2.2(7) ³ ³the accessible sleeping rooms ³ ³ ³ ³ ³ ³ ³comply with 4.27? (Use Form 14:³ ³ ³ ³ ³ ³ ³Rooms and Spaces) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Accessible ³If provided as part of an ³ ³ ³ ³ ³9.2.2(6) ³Areas and ³accessible unit, are the living³ ³ ³ ³ ³ ³Spaces ³area; dining area; at least one³ ³ ³ ³ ³ ³ ³sleeping area; and patio, ³ ³ ³ ³ ³ ³ ³terrace, or balcony accessible?³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: The requirements of³ ³ ³ ³ ³ ³ ³4.13.8 (thresholds at doors) ³ ³ ³ ³ ³ ³ ³and 4.3.8 (changes in level) do³ ³ ³ ³ ³ ³ ³not apply where it is necessary³ ³ ³ ³ ³ ³ ³to utilize a higher door ³ ³ ³ ³ ³ ³ ³threshold or a change in level ³ ³ ³ ³ ³ ³ ³to protect the integrity of the³ ³ ³ ³ ³ ³ ³unit from wind/water damage. ³ ³ ³ ³ ³ ³ ³Where this exception results in³ ³ ³ ³ ³ ³ ³patios, terraces or balconies ³ ³ ³ ³ ³ ³ ³that are not at an accessible ³ ³ ³ ³ ³ ³ ³level, equivalent facilitation ³ ³ ³ ³ ³ ³ ³shall be provided. (e.g., ³ ³ ³ ³ ³ ³ ³equivalent facilitation at a ³ ³ ³ ³ ³ ³ ³patio or balcony might consist ³ ³ ³ ³ ³ ³ ³of providing raised decking or ³ ³ ³ ³ ³ ³ ³a ramp to provide ³ ³ ³ ³ ³ ³ ³accessibility). ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Bathrooms ³Is at least one full bathroom ³ ³ ³ ³ ³9.2.2(6) ³ ³accessible? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³If only half baths are provided³ ³ ³ ³ ³ ³ ³is at least one half bath ³ ³ ³ ³ ³ ³ ³accessible? (Use Form 16: ³ ³ ³ ³ ³ ³ ³Toilet Rooms and Bathrooms and ³ ³ ³ ³ ³ ³ ³Form 17: Bathtubs and Showers) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Parking ³If parking is provided, is the ³ ³ ³ ³ ³9.2.2(6) ³ ³carport, garage or parking ³ ³ ³ ³ ³ ³ ³space accessible? (Use Form 1: ³ ³ ³ ³ ³ ³ ³Parking) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Kitchens ³If provided as part of an ³ ³ ³ ³ ³9.2.2(7) ³ ³accessible unit, are kitchens, ³ ³ ³ ³ ³ ³ ³kitchenettes, or wet bars ³ ³ ³ ³ ³ ³ ³accessible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is clear floor space at least ³ ³ ³ ³ ³ ³ ³30 inches by 48 inches provided³ ³ ³ ³ ³ ³ ³for a front or parallel ³ ³ ³ ³ ³ ³ ³approach to cabinets, counters,³ ³ ³ ³ ³ ³ ³sinks, and appliances? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are countertops and sinks ³ ³ ³ ³ ³ ³ ³mounted no more than 34 inches ³ ³ ³ ³ ³ ³ ³above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is at least 50% of the shelf ³ ³ ³ ³ ³ ³ ³space in cabinets or ³ ³ ³ ³ ³ ³ ³refrigerator/freezers within ³ ³ ³ ³ ³ ³ ³the reach ranges of between 15 ³ ³ ³ ³ ³ ³ ³inches and 48 inches for a ³ ³ ³ ³ ³ ³ ³front approach and between 9 ³ ³ ³ ³ ³ ³ ³inches and 54 inches for a ³ ³ ³ ³ ³ ³ ³parallel approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Accommodations ³In rooms required to be ³ ³ ³ ³ ³9.2.2(8) ³for Persons ³accessible under Table A, are ³ ³ ³ ³ ³ ³with Hearing ³visual alarms, notification ³ ³ ³ ³ ³ ³Impairments ³devices and telephones ³ ³ ³ ³ ³ ³ ³complying with 9.3 (see below) ³ ³ ³ ³ ³ ³ ³provided? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 28-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Additional ³Are additional sleeping rooms ³ ³ ³ ³ ³9.1.3 ³Rooms for ³for persons with hearing ³ ³ ³ ³ ³9.3 ³Persons with ³impairments provided in ³ ³ ³ ³ ³ ³Hearing ³compliance with Table B? ³ ³ ³ ³ ³ ³Impairments ³ ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Visual Alarms ³Are auxiliary visual alarms ³ ³ ³ ³ ³9.3 ³ ³complying with 4.28.4 provided ³ ³ ³ ³ ³ ³ ³in the accessible rooms ³ ³ ³ ³ ³ ³ ³required in Tables A and B? ³ ³ ³ ³ ³ ³ ³(Use Form 20: Alarms) ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are electrical outlets provided³ ³ ³ ³ ³ ³ ³(including one connected to the³ ³ ³ ³ ³ ³ ³facility's central alarm ³ ³ ³ ³ ³ ³ ³system) to enable room ³ ³ ³ ³ ³ ³ ³occupants to utilize portable ³ ³ ³ ³ ³ ³ ³devices provided by the ³ ³ ³ ³ ³ ³ ³operator of the facility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Visual ³Are visual notification devices³ ³ ³ ³ ³9.3.1 ³Notification ³to alert room occupants of ³ ³ ³ ³ ³9.3.2 ³Devices ³incoming telephone calls and a ³ ³ ³ ³ ³ ³ ³door knock or bell provided in ³ ³ ³ ³ ³ ³ ³the accessible sleeping rooms ³ ³ ³ ³ ³ ³ ³required in Tables A and B? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Are electrical outlets provided³ ³ ³ ³ ³ ³ ³to enable room occupants to ³ ³ ³ ³ ³ ³ ³utilize portable devices ³ ³ ³ ³ ³ ³ ³provided by the operator of the³ ³ ³ ³ ³ ³ ³facility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are visual notification ³ ³ ³ ³ ³ ³ ³devices not connected to the ³ ³ ³ ³ ³ ³ ³auxiliary visual alarm signal ³ ³ ³ ³ ³ ³ ³devices? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.3 ³Telephones ³If a permanently installed ³ ³ ³ ³ ³9.3.1 ³ ³telephone is provided in the ³ ³ ³ ³ ³ ³ ³accessible rooms, does it have ³ ³ ³ ³ ³ ³ ³a volume control capable of a ³ ³ ³ ³ ³ ³ ³minimum of 12 dbA and a maximum³ ³ ³ ³ ³ ³ ³of 18 dbA above normal? If an ³ ³ ³ ³ ³ ³ ³automatic reset is provided, ³ ³ ³ ³ ³ ³ ³then 18 dbA may be exceeded. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there an accessible ³ ³ ³ ³ ³ ³ ³electrical outlet within 4 feet³ ³ ³ ³ ³ ³ ³of a telephone connection to ³ ³ ³ ³ ³ ³ ³facilitate the use of a text ³ ³ ³ ³ ³ ³ ³telephone? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.2(1) ³Alterations in ³In alterations to social ³ ³ ³ ³ ³9.5.3 ³Social Service ³service establishments that are³ ³ ³ ³ ³9.5.1 ³Establishments ³not homeless shelters, are ³ ³ ³ ³ ³ ³(Excluding ³accessible sleeping rooms or ³ ³ ³ ³ ³ ³Homeless ³beds provided in a number ³ ³ ³ ³ ³ ³Shelters) ³consistent with Tables A and B ³ ³ ³ ³ ³ ³ ³above considering the total ³ ³ ³ ³ ³ ³ ³number of altered rooms? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are other altered areas ³ ³ ³ ³ ³ ³ ³consistent with 9.5.1 (See ³ ³ ³ ³ ³ ³ ³above)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³9.5.2(2) ³Alterations in ³In homeless shelters, if ³ ³ ³ ³ ³ ³Homeless ³altered, is at least one public³ ³ ³ ³ ³ ³Shelters ³entrance accessible to persons ³ ³ ³ ³ ³ ³ ³with mobility impairments so ³ ³ ³ ³ ³ ³ ³that they can approach, enter ³ ³ ³ ³ ³ ³ ³and exit? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 28-4 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Door Width ³Does the accessible public ³ ³ ³ ³ ³ ³ ³entrance(s) have a clear door ³ ³ ³ ³ ³ ³ ³opening of at least 32 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Sleeping Space ³If sleeping areas are altered, ³ ³ ³ ³ ³ ³ ³do the doors to the sleeping ³ ³ ³ ³ ³ ³ ³areas required to be accessible³ ³ ³ ³ ³ ³ ³in Table A have a clear door ³ ³ ³ ³ ³ ³ ³opening of at least 32 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Maneuvering ³If sleeping areas are altered, ³ ³ ³ ³ ³ ³Space at Beds ³does the maneuvering space ³ ³ ³ ³ ³ ³ ³around the beds required to be ³ ³ ³ ³ ³ ³ ³accessible in Table A comply ³ ³ ³ ³ ³ ³ ³with 9.2.2(1) (See above)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Toilet Rooms ³If toilet rooms are altered, is³ ³ ³ ³ ³ ³and Bathing ³there at least one toilet room ³ ³ ³ ³ ³ ³Areas ³for each gender, or one unisex ³ ³ ³ ³ ³ ³ ³toilet room that complies with ³ ³ ³ ³ ³ ³ ³the requirements below? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the altered toilet room ³ ³ ³ ³ ³ ³ ³have a clear door opening of at³ ³ ³ ³ ³ ³ ³least 32 inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the altered toilet room ³ ³ ³ ³ ³ ³ ³have an unobstructed turning ³ ³ ³ ³ ³ ³ ³space (a 60 inch diameter ³ ³ ³ ³ ³ ³ ³circle or T-shaped space)? (See³ ³ ³ ³ ³ ³ ³Figure 3(b) included in Form ³ ³ ³ ³ ³ ³ ³16: Toilet Rooms and Bathrooms)³ ³ ³ ³ ³ ³ ³(The clear floor space at ³ ³ ³ ³ ³ ³ ³fixtures and controls, the ³ ³ ³ ³ ³ ³ ³accessible route, and the ³ ³ ³ ³ ³ ³ ³turning space may overlap.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the altered toilet room ³ ³ ³ ³ ³ ³ ³have one water closet complying³ ³ ³ ³ ³ ³ ³with 4.16? (Use Form 16: ³ ³ ³ ³ ³ ³ ³Toilet Rooms and Bathrooms) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the altered toilet room ³ ³ ³ ³ ³ ³ ³have one lavatory complying ³ ³ ³ ³ ³ ³ ³with 4.19? (Use Form 16: ³ ³ ³ ³ ³ ³ ³Toilet Rooms and Bathrooms) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the door to the altered ³ ³ ³ ³ ³ ³ ³toilet room (without toilet ³ ³ ³ ³ ³ ³ ³stalls) have a privacy latch? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³If bathing facilities are ³ ³ ³ ³ ³ ³ ³provided in the altered toilet ³ ³ ³ ³ ³ ³ ³room, does at least one bathtub³ ³ ³ ³ ³ ³ ³or shower comply with 4.20 or ³ ³ ³ ³ ³ ³ ³4.21, respectively? (Use Form ³ ³ ³ ³ ³ ³ ³17: Bathtubs and Showers) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Common Areas ³If common areas (e.g., day ³ ³ ³ ³ ³ ³ ³rooms or lounges) are altered, ³ ³ ³ ³ ³ ³ ³is there at least one common ³ ³ ³ ³ ³ ³ ³area where persons with ³ ³ ³ ³ ³ ³ ³mobility impairments can ³ ³ ³ ³ ³ ³ ³approach, enter and exit, ³ ³ ³ ³ ³ ³ ³(including an opening of at ³ ³ ³ ³ ³ ³ ³least 32 inches wide)? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 28-5 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there at least one route ³ ³ ³ ³ ³ ³ ³connecting an accessible ³ ³ ³ ³ ³ ³ ³entrance with accessible ³ ³ ³ ³ ³ ³ ³sleeping rooms or beds, ³ ³ ³ ³ ³ ³ ³accessible toilet room(s), and ³ ³ ³ ³ ³ ³ ³accessible common area(s) that ³ ³ ³ ³ ³ ³ ³a person with a mobility ³ ³ ³ ³ ³ ³ ³impairment can use which ³ ³ ³ ³ ³ ³ ³includes minimum clear width of³ ³ ³ ³ ³ ³ ³36 inches, passing space ³ ³ ³ ³ ³ ³ ³complying with 4.3.4, turning ³ ³ ³ ³ ³ ³ ³space complying with 4.2.3 and ³ ³ ³ ³ ³ ³ ³changes in levels complying ³ ³ ³ ³ ³ ³ ³with 4.3.8? (Use Form 12: ³ ³ ³ ³ ³ ³ ³Building Corridors and Lobbies)³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Homeless shelters can ³ ³ ³ ³ ³ ³ ³comply with the provisions of ³ ³ ³ ³ ³ ³ ³9.5.2(2) (see above) by ³ ³ ³ ³ ³ ³ ³providing all elements on one ³ ³ ³ ³ ³ ³ ³accessible floor. ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 28-6 SURVEY FORM 29A: TRANSPORTATION FACILITIES Ä BUS STOPS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Every station, bus stop, bus stop pad, terminal, building or other transportation facility, must comply with the applicable provisions of ADAAG 4.1 through 4.35, ADAAG 5 through 9, and the applicable provisions of ADAAG 10. Note: The exception for elevators in 4.1.3(5) Exception 1 and 4.1.6(1)(k) do not apply to a terminal, depot, or other station used for specified public transportation, or an airport passenger terminal, or facilities subject to Title II. ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.2 ³Bus Stop ³If a bus stop pad has been ³ ³ ³ ³ ³10.2.1(1) ³Pad Ä ³newly constructed at a bus ³ ³ ³ ³ ³ ³Surface ³stop, bay or other area where a³ ³ ³ ³ ³ ³ ³lift or ramp is to be deployed,³ ³ ³ ³ ³ ³ ³does it have a surface that is ³ ³ ³ ³ ³ ³ ³stable and firm? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Clear ³Is there a clear length of at ³ ³ ³ ³ ³ ³Dimensions ³least 96 inches (measured from ³ ³ ³ ³ ³ ³ ³the curb or vehicle roadway) ³ ³ ³ ³ ³ ³ ³and a clear width of at least ³ ³ ³ ³ ³ ³ ³60 inches (parallel to the ³ ³ ³ ³ ³ ³ ³roadway) provided to the ³ ³ ³ ³ ³ ³ ³maximum extent allowed by legal³ ³ ³ ³ ³ ³ ³or site constraints? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Connection to ³Is the pad connected to ³ ³ ³ ³ ³ ³Pedestrian ³streets, sidewalks or ³ ³ ³ ³ ³ ³Way ³pedestrian paths by an ³ ³ ³ ³ ³ ³ ³accessible route complying with³ ³ ³ ³ ³ ³ ³4.3 and 4.4? (Use Form 3: ³ ³ ³ ³ ³ ³ ³Exterior Accessible Routes) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Slope ³Is the slope of the pad ³ ³ ³ ³ ³ ³ ³parallel to the roadway and, to³ ³ ³ ³ ³ ³ ³the extent practicable, the ³ ³ ³ ³ ³ ³ ³same as that of the roadway? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: A maximum slope of 1:50 ³ ³ ³ ³ ³ ³ ³(2%) perpendicular to the ³ ³ ³ ³ ³ ³ ³roadway is allowed for water ³ ³ ³ ³ ³ ³ ³drainage. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.2.1(2) ³Bus Shelter ³Where provided, are new or ³ ³ ³ ³ ³ ³Position ³replaced bus shelters installed³ ³ ³ ³ ³ ³ ³or positioned in such a way ³ ³ ³ ³ ³ ³ ³that a wheelchair or mobility ³ ³ ³ ³ ³ ³ ³aid user can enter from the ³ ³ ³ ³ ³ ³ ³public way and reach a location³ ³ ³ ³ ³ ³ ³having a minimum clear floor ³ ³ ³ ³ ³ ³ ³area of 30 inches by 48 inches,³ ³ ³ ³ ³ ³ ³entirely within the perimeter ³ ³ ³ ³ ³ ³ ³of the shelter? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Connection to ³Are such shelters connected by ³ ³ ³ ³ ³ ³Boarding Area ³an accessible route to the ³ ³ ³ ³ ³ ³ ³boarding area provided? (Use ³ ³ ³ ³ ³ ³ ³Form 3: Exterior Accessible ³ ³ ³ ³ ³ ³ ³Routes) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29a-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.2.1(3) ³New Route ³Where provided, do all new ³ ³ ³ ³ ³ ³Signs ³signs identifying bus routes ³ ³ ³ ³ ³ ³ ³comply with 4.30.5? Do such ³ ³ ³ ³ ³ ³ ³signs also comply with 4.30.2 ³ ³ ³ ³ ³ ³ ³and 4.30.3 to the maximum ³ ³ ³ ³ ³ ³ ³extent practicable? (Use Form ³ ³ ³ ³ ³ ³ ³19: Signage) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Signs that are sized to ³ ³ ³ ³ ³ ³ ³the maximum dimensions ³ ³ ³ ³ ³ ³ ³permitted under legitimate ³ ³ ³ ³ ³ ³ ³local, state or federal ³ ³ ³ ³ ³ ³ ³regulations or ordinances shall³ ³ ³ ³ ³ ³ ³be considered in compliance ³ ³ ³ ³ ³ ³ ³with 4.30.2 and 4.30.3 for ³ ³ ³ ³ ³ ³ ³purposes of this section. ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Bus schedules, ³ ³ ³ ³ ³ ³ ³timetables, or maps that are ³ ³ ³ ³ ³ ³ ³posted at the bus stop or bus ³ ³ ³ ³ ³ ³ ³bay are not required to comply ³ ³ ³ ³ ³ ³ ³with this provision. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅij10.2.2(1) ³Bus Stop ³Are bus stop sites chosen such ³ ³ ³Sites and ³that, to the maximum extent ³ ³ ³ ³ ³ ³Alterations ³practicable, the areas where ³ ³ ³ ³ ³ ³ ³lifts or ramps are to be ³ ³ ³ ³ ³ ³ ³deployed comply with section ³ ³ ³ ³ ³ ³ ³10.2.1(1) and (2) above? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.2.2(2) ³New Route ³When old route signs are ³ ³ ³ ³ ³ ³Signs ³replaced do the new signs ³ ³ ³ ³ ³ ³ ³comply with the requirements of³ ³ ³ ³ ³ ³ ³10.2.1(3) above? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29a-2 SURVEY FORM 29B: TRANSPORTATION FACILITIES Ä FIXED FACILITIES, TERMINALS AND STATIONS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Every station, bus stop, bus stop pad, terminal, building or other transportation facility, must comply with the applicable provisions of ADAAG 4.1 through 4.35, ADAAG 5 through 9, and the applicable provisions of ADAAG 10. Note: The exception for elevators in 4.1.3(5) Exception 1 and 4.1.6(1)(k) do not apply to a terminal, depot, or other station used for specified public transportation, or an airport passenger terminal, or facilities subject to Title II. ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1 ³Fixed ³Do new stations in rapid rail, ³ ³ ³ ³ ³ ³Facilities, ³light rail, commuter rail, ³ ³ ³ ³ ³ ³Terminals ³intercity bus, intercity rail, ³ ³ ³ ³ ³ ³and Stations ³high speed rail, and other ³ ³ ³ ³ ³ ³ ³fixed guideway systems (e.g., ³ ³ ³ ³ ³ ³ ³automated guideway transit, ³ ³ ³ ³ ³ ³ ³monorails, etc.) comply with ³ ³ ³ ³ ³ ³ ³the following provisions, as ³ ³ ³ ³ ³ ³ ³applicable? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(1) ³Circulation ³Are all elements, such as ³ ³ ³ ³ ³ ³Path Ä ³ramps, elevators or other ³ ³ ³ ³ ³ ³Vertical ³circulation devices, placed in³ ³ ³ ³ ³ ³Access ³such a way as to minimize the ³ ³ ³ ³ ³ ³ ³distance a wheelchair user and ³ ³ ³ ³ ³ ³ ³other persons who cannot ³ ³ ³ ³ ³ ³ ³negotiate steps must travel, as³ ³ ³ ³ ³ ³ ³compared to the general public?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Fare Areas ³Are fare vending, other ³ ³ ³ ³ ³ ³ ³ticketing areas, and fare ³ ³ ³ ³ ³ ³ ³collection areas placed in such³ ³ ³ ³ ³ ³ ³a way as to minimize the ³ ³ ³ ³ ³ ³ ³distance a wheelchair user and ³ ³ ³ ³ ³ ³ ³other persons who cannot ³ ³ ³ ³ ³ ³ ³negotiate steps must travel, as³ ³ ³ ³ ³ ³ ³compared to the general public?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Accessible ³Does the circulation path, ³ ³ ³ ³ ³ ³Entrance and ³(including an accessible ³ ³ ³ ³ ³ ³Route: ³entrance and accessible route) ³ ³ ³ ³ ³ ³ ³coincide with the circulation ³ ³ ³ ³ ³ ³ ³path for the general public, to³ ³ ³ ³ ³ ³ ³the maximum extent practicable?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(1) ³Directional ³If the circulation path is ³ ³ ³ ³ ³ ³Signage ³different from that for the ³ ³ ³ ³ ³ ³Where ³general public, are there signs³ ³ ³ ³ ³ ³Circulation ³provided to indicate direction ³ ³ ³ ³ ³ ³Path is ³to and that identify the ³ ³ ³ ³ ³ ³Different ³accessible entrance and ³ ³ ³ ³ ³ ³ ³accessible route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do these signs comply with ³ ³ ³ ³ ³ ³ ³4.30.2, 4.30.3, and 4.30.5? ³ ³ ³ ³ ³ ³ ³(Use Form 19: Signage) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.30.7 ³ ³Do the signs display the ³ ³ ³ ³ ³ ³ ³International Symbol of ³ ³ ³ ³ ³ ³ ³Accessibility? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(2) ³Entrances Ä ³Is at least one entrance ³ ³ ³ ³ ³4.14 ³Accessible ³connected by an accessible ³ ³ ³ ³ ³ ³Route ³route to public transportation ³ ³ ³ ³ ³ ³ ³stops, accessible parking, ³ ³ ³ ³ ³ ³ ³passenger loading zones, and ³ ³ ³ ³ ³ ³ ³public streets or sidewalks, if³ ³ ³ ³ ³ ³ ³available, and to all ³ ³ ³ ³ ³ ³ ³accessible spaces or elements ³ ³ ³ ³ ³ ³ ³within the building or ³ ³ ³ ³ ³ ³ ³facility? (Use Form 3: ³ ³ ³ ³ ³ ³ ³Exterior Accessible Routes and ³ ³ ³ ³ ³ ³ ³Form 12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Entrances ³If different entrances to the ³ ³ ³ ³ ³ ³Serving ³station serve different ³ ³ ³ ³ ³ ³Different ³transportation fixed routes or ³ ³ ³ ³ ³ ³Routes ³groups of fixed routes, does at³ ³ ³ ³ ³ ³ ³least one entrance serving each³ ³ ³ ³ ³ ³ ³group or route comply with the ³ ³ ³ ³ ³ ³ ³above provisions for entrances?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Public ³Do all accessible entrances ³ ³ ³ ³ ³ ³Entrances ³coincide with those used by the³ ³ ³ ³ ³ ³ ³majority of the general public,³ ³ ³ ³ ³ ³ ³to the maximum extent ³ ³ ³ ³ ³ ³ ³practicable? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(3) ³New Direct ³If there are direct connections³ ³ ³ ³ ³ ³Connections ³to commercial, retail or ³ ³ ³ ³ ³ ³ ³residential facilities, is ³ ³ ³ ³ ³ ³ ³there an accessible route from ³ ³ ³ ³ ³ ³ ³the point of connection to ³ ³ ³ ³ ³ ³ ³boarding platforms and all ³ ³ ³ ³ ³ ³ ³transportation system elements ³ ³ ³ ³ ³ ³ ³used by the public? (Use Form ³ ³ ³ ³ ³ ³ ³12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Future Direct ³Is there an accessible route ³ ³ ³ ³ ³ ³Connections ³connecting boarding platforms ³ ³ ³ ³ ³ ³ ³and all transportation system ³ ³ ³ ³ ³ ³ ³elements used by the public to ³ ³ ³ ³ ³ ³ ³all elements provided to ³ ³ ³ ³ ³ ³ ³facilitate future direct ³ ³ ³ ³ ³ ³ ³connections to commercial, ³ ³ ³ ³ ³ ³ ³retail or residential ³ ³ ³ ³ ³ ³ ³facilities? (Use Form 12: ³ ³ ³ ³ ³ ³ ³Building Lobbies and Corridors)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.1.3(7) ³Doors ³Does each door or gate that is ³ ³ ³ ³ ³ ³ ³part of an accessible route ³ ³ ³ ³ ³ ³ ³comply with 4.13? (Use Form 11:³ ³ ³ ³ ³ ³ ³Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(4) ³Entrance ³Where signs are provided at ³ ³ ³ ³ ³ ³Signs ³station entrances identifying ³ ³ ³ ³ ³ ³ ³the station or the entrance, or³ ³ ³ ³ ³ ³ ³both, does at least one sign ³ ³ ³ ³ ³ ³ ³comply with 4.30.4 and 4.30.6? ³ ³ ³ ³ ³ ³ ³(Use Form 19: Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are such signs placed in ³ ³ ³ ³ ³ ³ ³uniform locations at the ³ ³ ³ ³ ³ ³ ³entrances to the maximum extent³ ³ ³ ³ ³ ³ ³practicable? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Where the station ³ ³ ³ ³ ³ ³ ³has no defined entrance, but ³ ³ ³ ³ ³ ³ ³signage is provided, then the ³ ³ ³ ³ ³ ³ ³accessible signage shall be ³ ³ ³ ³ ³ ³ ³placed in a central location. ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-2 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(5) ³Station/ ³Do stations have identification³ ³ ³ ³ ³ ³Platform ³signs complying with 4.30.2, ³ ³ ³ ³ ³ ³Signs ³4.30.3, and 4.30.5 placed at ³ ³ ³ ³ ³ ³ ³frequent intervals and clearly ³ ³ ³ ³ ³ ³ ³visible from inside the vehicle³ ³ ³ ³ ³ ³ ³on both sides (when not ³ ³ ³ ³ ³ ³ ³obstructed by another train)? ³ ³ ³ ³ ³ ³ ³(Use Form 19: Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Sign Height ³When station identification ³ ³ ³ ³ ³ ³ ³signs are placed close to ³ ³ ³ ³ ³ ³ ³vehicle windows, is the top of ³ ³ ³ ³ ³ ³ ³the highest letter or symbol ³ ³ ³ ³ ³ ³ ³below the top of the vehicle ³ ³ ³ ³ ³ ³ ³window and the bottom of the ³ ³ ³ ³ ³ ³ ³lowest letter or symbol above ³ ³ ³ ³ ³ ³ ³the horizontal mid-line of the ³ ³ ³ ³ ³ ³ ³vehicle window? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(6) ³Route Signs ³Do lists of stations, routes, ³ ³ ³ ³ ³ ³Contrast and ³or destinations served by the ³ ³ ³ ³ ³ ³Letter ³station located on boarding ³ ³ ³ ³ ³ ³Characteristics ³areas, platforms, or mezzanines³ ³ ³ ³ ³ ³ ³comply with 4.30.2, 4.30.3, and³ ³ ³ ³ ³ ³ ³4.30.5? (Use Form 19: Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Braille and ³Does at least one sign on each ³ ³ ³ ³ ³ ³Raised Letters: ³platform or boarding area ³ ³ ³ ³ ³ ³ ³identifying the specific ³ ³ ³ ³ ³ ³ ³station comply with 4.30.4 and ³ ³ ³ ³ ³ ³ ³4.30.6? (Use Form 19: Signage) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Compliance with 4.30.5 is³ ³ ³ ³ ³ ³ ³not required. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Sign ³Are all signs that list ³ ³ ³ ³ ³ ³Placement ³stations, routes, or ³ ³ ³ ³ ³ ³ ³destinations served by the ³ ³ ³ ³ ³ ³ ³station placed in uniform ³ ³ ³ ³ ³ ³ ³locations within the transit ³ ³ ³ ³ ³ ³ ³system, to the maximum extent ³ ³ ³ ³ ³ ³ ³practicable? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(7) ³Automatic ³Do automatic fare vending, ³ ³ ³ ³ ³ ³Fare Vending ³collection and adjustment ³ ³ ³ ³ ³ ³Machines ³systems comply with 4.34.2, ³ ³ ³ ³ ³ ³ ³4.34.3, and 4.34.4? (Use Form ³ ³ ³ ³ ³ ³ ³21: Automated Teller Machines) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Location ³Are such automatic vending ³ ³ ³ ³ ³ ³ ³machines located at each ³ ³ ³ ³ ³ ³ ³accessible entrance and on an ³ ³ ³ ³ ³ ³ ³accessible route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Self-Service ³If self-service fare collection³ ³ ³ ³ ³ ³Fare ³devices are provided for the ³ ³ ³ ³ ³ ³Collection ³public, is there at least one ³ ³ ³ ³ ³ ³Machines ³accessible device for entering ³ ³ ³ ³ ³ ³ ³and exiting at each accessible ³ ³ ³ ³ ³ ³ ³point of entry or exit (unless ³ ³ ³ ³ ³ ³ ³one device serves both ³ ³ ³ ³ ³ ³ ³functions)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Width ³Does each accessible fare ³ ³ ³ ³ ³ ³ ³collection device have a ³ ³ ³ ³ ³ ³ ³minimum clear width of 32 ³ ³ ³ ³ ³ ³ ³inches to allow passage of a ³ ³ ³ ³ ³ ³ ³wheelchair? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Controls ³Where provided, are coin or ³ ³ ³ ³ ³ ³ ³card slots and controls ³ ³ ³ ³ ³ ³ ³necessary for operation in ³ ³ ³ ³ ³ ³ ³compliance with 4.27 (See ³ ³ ³ ³ ³ ³ ³below)? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-3 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.27.2 ³Clear Floor ³Is clear floor space at least ³ ³ ³ ³ ³ ³Space ³30 inches by 48 inches provided³ ³ ³ ³ ³ ³ ³at coin or card slots and ³ ³ ³ ³ ³ ³ ³controls that allows either a ³ ³ ³ ³ ³ ³ ³forward or parallel approach by³ ³ ³ ³ ³ ³ ³a person using a wheelchair? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.27.3 ³Forward Reach ³If the clear floor space allows³ ³ ³ ³ ³ ³ ³only a forward approach, then ³ ³ ³ ³ ³ ³ ³is the highest operable part no³ ³ ³ ³ ³ ³ ³more than 48 inches from the ³ ³ ³ ³ ³ ³ ³floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Side Reach ³If the clear floor space allows³ ³ ³ ³ ³ ³ ³only a parallel approach, then ³ ³ ³ ³ ³ ³ ³is the highest operable part no³ ³ ³ ³ ³ ³ ³more than 54 inches from the ³ ³ ³ ³ ³ ³ ³floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.27.4 ³Operation ³Are the controls operable with ³ ³ ³ ³ ³ ³ ³one hand and without tight ³ ³ ³ ³ ³ ³ ³grasping, pinching, or twisting³ ³ ³ ³ ³ ³ ³of the wrist? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(7) ³Fare Gates ³Do gates which must be pushed ³ ³ ³ ³ ³ ³ ³open by wheelchair or mobility ³ ³ ³ ³ ³ ³ ³aid users have a smooth ³ ³ ³ ³ ³ ³ ³continuous surface extending ³ ³ ³ ³ ³ ³ ³from 2 inches above the floor ³ ³ ³ ³ ³ ³ ³to 27 inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do such gates comply with 4.13?³ ³ ³ ³ ³ ³ ³(Use Form 11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Accessible ³Where the circulation path does³ ³ ³ ³ ³ ³Fare ³not coincide with that used by ³ ³ ³ ³ ³ ³Collection ³the general public, is the ³ ³ ³ ³ ³ ³Location ³accessible fare collection ³ ³ ³ ³ ³ ³ ³system located at or adjacent ³ ³ ³ ³ ³ ³ ³to the accessible point of ³ ³ ³ ³ ³ ³ ³entry or exit? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(8) ³Detectable ³Do platform edges bordering a ³ ³ ³ ³ ³ ³Warnings ³drop-off not protected by ³ ³ ³ ³ ³ ³ ³platform screens or guard rails³ ³ ³ ³ ³ ³ ³have a detectable warning? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Width ³Are the detectable warnings 24 ³ ³ ³ ³ ³ ³ ³inches wide running the full ³ ³ ³ ³ ³ ³ ³length of the platform ³ ³ ³ ³ ³ ³ ³drop-off? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.2 ³Pattern ³Does the detectable warning ³ ³ ³ ³ ³ ³ ³consist of raised truncated ³ ³ ³ ³ ³ ³ ³domes with a nominal diameter ³ ³ ³ ³ ³ ³ ³of 0.9 inches, a nominal height³ ³ ³ ³ ³ ³ ³of 0.2 inches, and a nominal ³ ³ ³ ³ ³ ³ ³center-to-center spacing of ³ ³ ³ ³ ³ ³ ³2.35 inches? (See figure below)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contrast ³Does the detectable warning ³ ³ ³ ³ ³ ³ ³contrast visually with ³ ³ ³ ³ ³ ³ ³adjoining surfaces ³ ³ ³ ³ ³ ³ ³(light-on-dark or ³ ³ ³ ³ ³ ³ ³dark-on-light)? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is the material used to provide³ ³ ³ ³ ³ ³ ³contrast an integral part of ³ ³ ³ ³ ³ ³ ³the walking surface? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-4 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Interior ³If the platform is in an ³ ³ ³ ³ ³ ³Resiliency ³interior location, does the ³ ³ ³ ³ ³ ³and Sound ³detectable warning differ from ³ ³ ³ ³ ³ ³ ³the adjoining walking surface ³ ³ ³ ³ ³ ³ ³in resiliency or sound-on-cane ³ ³ ³ ³ ³ ³ ³contact? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(9) ³Platform ³Is the rail-to-platform height ³ ³ ³ ³ ³ ³Height Ä ³coordinated with the floor ³ ³ ³ ³ ³ ³Vertical Gap ³height of new vehicles so that ³ ³ ³ ³ ³ ³ ³the vertical difference ³ ³ ³ ³ ³ ³ ³(measured when the vehicle is ³ ³ ³ ³ ³ ³ ³at rest) is within plus or ³ ³ ³ ³ ³ ³ ³minus 5/8 inch under normal ³ ³ ³ ³ ³ ³ ³passenger load conditions? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Existing vehicles ³ ³ ³ ³ ³ ³ ³operating in new stations may ³ ³ ³ ³ ³ ³ ³have a vertical difference with³ ³ ³ ³ ³ ³ ³respect to the new platform ³ ³ ³ ³ ³ ³ ³within plus or minus 1-1/2 ³ ³ ³ ³ ³ ³ ³inches. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Horizontal ³For rapid rail, light rail, ³ ³ ³ ³ ³ ³Gap ³commuter rail, high speed rail,³ ³ ³ ³ ³ ³Rail Systems ³and intercity rail systems in ³ ³ ³ ³ ³ ³ ³new stations, is the horizontal³ ³ ³ ³ ³ ³ ³gap (measured when the new ³ ³ ³ ³ ³ ³ ³vehicle is at rest) no greater ³ ³ ³ ³ ³ ³ ³than 3 inches? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: In light rail, ³ ³ ³ ³ ³ ³ ³commuter rail and intercity ³ ³ ³ ³ ³ ³ ³rail systems where it is not ³ ³ ³ ³ ³ ³ ³operationally or structurally ³ ³ ³ ³ ³ ³ ³feasible to meet the horizontal³ ³ ³ ³ ³ ³ ³gap or vertical difference ³ ³ ³ ³ ³ ³ ³requirements, mini-high ³ ³ ³ ³ ³ ³ ³platforms, car-borne or ³ ³ ³ ³ ³ ³ ³platform-mounted lifts, ramps ³ ³ ³ ³ ³ ³ ³or bridge plates, or similar ³ ³ ³ ³ ³ ³ ³manually deployed devices, ³ ³ ³ ³ ³ ³ ³meeting the applicable ³ ³ ³ ³ ³ ³ ³requirements of 36 CFR Part ³ ³ ³ ³ ³ ³ ³1192, or 49 CFR Part 38 shall ³ ³ ³ ³ ³ ³ ³suffice. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Horizontal ³For slow-moving automated ³ ³ ³ ³ ³ ³Gap ³guideway "people mover" transit³ ³ ³ ³ ³ ³People Movers ³systems, is the horizontal gap ³ ³ ³ ³ ³ ³ ³in new stations no greater than³ ³ ³ ³ ³ ³ ³1 inch? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(10) ³Boarding and ³Is the station designed so that³ ³ ³ ³ ³ ³Alighting ³persons with disabilities are ³ ³ ³ ³ ³ ³ ³able to board or alight from a ³ ³ ³ ³ ³ ³ ³vehicle at the same location as³ ³ ³ ³ ³ ³ ³used by the general public? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(11) ³Illumination ³Are illumination levels in the ³ ³ ³ ³ ³ ³ ³areas where signage is located ³ ³ ³ ³ ³ ³ ³uniform? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Glare ³Does the method of illumination³ ³ ³ ³ ³ ³ ³minimize glare on signs? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Circulation ³Is the lighting along ³ ³ ³ ³ ³ ³Route ³circulation routes of the type ³ ³ ³ ³ ³ ³ ³and configuration to provide ³ ³ ³ ³ ³ ³ ³uniform illumination? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-5 ÚÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(12)(a)³Text ³If an interior public pay ³ ³ ³ ³ ³4.31.9 ³Telephones - ³telephone is provided in a ³ ³ ³ ³ ³ ³Stations: ³transit facility, is at least ³ ³ ³ ³ ³ ³ ³one interior public text ³ ³ ³ ³ ³ ³ ³telephone provided? ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³Note: Transit facility is ³ ³ ³ ³ ³ ³ ³defined in 49 CFR 37.3 for ³ ³ ³ ³ ³ ³ ³purposes of applying ADAAG ³ ³ ³ ³ ³ ³ ³10.3.1(12) as a physical ³ ³ ³ ³ ³ ³ ³structure the primary function ³ ³ ³ ³ ³ ³ ³of which is to facilitate ³ ³ ³ ³ ³ ³ ³access to and from a ³ ³ ³ ³ ³ ³ ³transportation system which has³ ³ ³ ³ ³ ³ ³scheduled stops at the ³ ³ ³ ³ ³ ³ ³structure. It does not include³ ³ ³ ³ ³ ³ ³an open structure or a physical³ ³ ³ ³ ³ ³ ³structure the primary purpose ³ ³ ³ ³ ³ ³ ³of which is other than ³ ³ ³ ³ ³ ³ ³providing transportation ³ ³ ³ ³ ³ ³ ³services. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(12)(b)³Entrances ³If there are four or more ³ ³ ³ ³ ³ ³ ³public pay telephones serving a³ ³ ³ ³ ³ ³ ³particular entrance to a rail ³ ³ ³ ³ ³ ³ ³station and at least one is in ³ ³ ³ ³ ³ ³ ³an interior location, is at ³ ³ ³ ³ ³ ³ ³least one text telephone ³ ³ ³ ³ ³ ³ ³provided to serve that ³ ³ ³ ³ ³ ³ ³entrance? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the text telephones comply ³ ³ ³ ³ ³ ³ ³with 4.31.9? (Use Form 6: ³ ³ ³ ³ ³ ³ ³Telephones) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(13) ³Track ³Where it is necessary to cross ³ ³ ³ ³ ³ ³Crossings ³tracks to reach boarding ³ ³ ³ ³ ³ ³ ³platforms, is the surface of ³ ³ ³ ³ ³ ³ ³the route level and flush with ³ ³ ³ ³ ³ ³ ³the rail top at the outer edge ³ ³ ³ ³ ³ ³ ³and between the rails except ³ ³ ³ ³ ³ ³ ³for a maximum 2-1/2 inch gap on³ ³ ³ ³ ³ ³ ³the inner edge of each rail to ³ ³ ³ ³ ³ ³ ³permit passage of wheel ³ ³ ³ ³ ³ ³ ³flanges? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Where gap reduction is not ³ ³ ³ ³ ³ ³ ³practicable, is there an ³ ³ ³ ³ ³ ³ ³above-grade or below-grade ³ ³ ³ ³ ³ ³ ³accessible route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³4.29.5 ³ ³Where the walkway crosses the ³ ³ ³ ³ ³ ³ ³vehicular way, is the boundary ³ ³ ³ ³ ³ ³ ³between the areas defined by a ³ ³ ³ ³ ³ ³ ³continuous detectable warning ³ ³ ³ ³ ³ ³ ³which is 36 inches wide? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the detectable warning ³ ³ ³ ³ ³ ³ ³comply with 4.29.2 (See above)?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(14) ³Public ³Where public address systems ³ ³ ³ ³ ³ ³Address ³are provided to convey ³ ³ ³ ³ ³ ³Systems ³information to the public, is ³ ³ ³ ³ ³ ³ ³there a means of conveying the ³ ³ ³ ³ ³ ³ ³same or equivalent information ³ ³ ³ ³ ³ ³ ³to persons with hearing ³ ³ ³ ³ ³ ³ ³impairments? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(15) ³Clocks ³Where clocks are provided for ³ ³ ³ ³ ³ ³ ³use by the public, is the clock³ ³ ³ ³ ³ ³ ³face uncluttered so that its ³ ³ ³ ³ ³ ³ ³elements are clearly visible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contrast ³Do hands, numerals, and/or ³ ³ ³ ³ ³ ³ ³digits contrast with the ³ ³ ³ ³ ³ ³ ³background either ³ ³ ³ ³ ³ ³ ³light-on-dark, or ³ ³ ³ ³ ³ ³ ³dark-on-light? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-6 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where clocks are mounted ³ ³ ³ ³ ³ ³ ³overhead, are the numerals ³ ³ ³ ³ ³ ³ ³and/or digits 3 inches or ³ ³ ³ ³ ³ ³ ³greater in height? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are the clocks placed in a ³ ³ ³ ³ ³ ³ ³uniform location throughout the³ ³ ³ ³ ³ ³ ³facility to the maximum extent ³ ³ ³ ³ ³ ³ ³practicable? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(16) ³Escalators ³Where provided in below grade ³ ³ ³ ³ ³ ³Width ³stations, do escalators have a ³ ³ ³ ³ ³ ³ ³clear width of at least 32 ³ ³ ³ ³ ³ ³ ³inches? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contiguous ³At the top and bottom of each ³ ³ ³ ³ ³ ³Treads ³escalator run, are at least two³ ³ ³ ³ ³ ³ ³contiguous treads level beyond ³ ³ ³ ³ ³ ³ ³the comb plate before the ³ ³ ³ ³ ³ ³ ³risers begin to form? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contrast Step ³Are all escalator treads marked³ ³ ³ ³ ³ ³Edges ³by a strip of clearly ³ ³ ³ ³ ³ ³ ³contrasting color 2 inches ³ ³ ³ ³ ³ ³ ³wide, parallel to and on the ³ ³ ³ ³ ³ ³ ³nose of each step? (The edge ³ ³ ³ ³ ³ ³ ³of the tread must be apparent ³ ³ ³ ³ ³ ³ ³from both ascending and ³ ³ ³ ³ ³ ³ ³descending directions.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Slip ³Is the contrasting strip of a ³ ³ ³ ³ ³ ³Resistance ³material that is at least as ³ ³ ³ ³ ³ ³ ³slip resistant as the remainder³ ³ ³ ³ ³ ³ ³of the tread? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(17) ³levators ³Where provided, do elevators ³ ³ ³ ³ ³ ³Glazing ³have glass or transparent ³ ³ ³ ³ ³ ³ ³panels to allow an unobstructed³ ³ ³ ³ ³ ³ ³view both into and out of the ³ ³ ³ ³ ³ ³ ³car? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do elevators comply with 4.10? ³ ³ ³ ³ ³ ³ ³(Use Form 13: Elevators) ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Elevator cars with ³ ³ ³ ³ ³ ³ ³a clear floor area in which a ³ ³ ³ ³ ³ ³ ³60 inch diameter circle can be ³ ³ ³ ³ ³ ³ ³inscribed may be substituted ³ ³ ³ ³ ³ ³ ³for the minimum car dimensions ³ ³ ³ ³ ³ ³ ³of 4.10, Figure 22. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(18) ³Ticketing ³Where provided, do ticketing ³ ³ ³ ³ ³ ³and Baggage ³areas permit persons with ³ ³ ³ ³ ³ ³Claim Areas ³disabilities to obtain a ticket³ ³ ³ ³ ³ ³ ³and check baggage? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-7 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³7.2 ³Service ³Do such areas comply with 7.2 ³ ³ ³ ³ ³ ³Counters ³below: ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³At ticketing counters, is there³ ³ ³ ³ ³ ³ ³a portion of the main counter ³ ³ ³ ³ ³ ³ ³or auxiliary counter at least ³ ³ ³ ³ ³ ³ ³36 inches long and no more than³ ³ ³ ³ ³ ³ ³36 inches high? ³ ³ ³ ³ ³ ³ ³OR ³ ³ ³ ³ ³ ³ ³Is equivalent facilitation ³ ³ ³ ³ ³ ³ ³provided? (e.g., equivalent ³ ³ ³ ³ ³ ³ ³facilitation might consist of: ³ ³ ³ ³ ³ ³ ³1) the provision of a folding ³ ³ ³ ³ ³ ³ ³shelf attached to the main ³ ³ ³ ³ ³ ³ ³counter on which a person with ³ ³ ³ ³ ³ ³ ³a disability can write, and 2) ³ ³ ³ ³ ³ ³ ³use of the space at the side of³ ³ ³ ³ ³ ³ ³the counter for handing ³ ³ ³ ³ ³ ³ ³materials back and forth.) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are these counters on an ³ ³ ³ ³ ³ ³ ³accessible route? (Use Form 12:³ ³ ³ ³ ³ ³ ³Building Lobbies and Corridors)³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(19) ³Baggage ³Where provided, is the baggage ³ ³ ³ ³ ³ ³Check-in and ³check-in and retrieval system ³ ³ ³ ³ ³ ³Retrieval ³on an accessible route? (Use ³ ³ ³ ³ ³ ³ ³Form 12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there space immediately ³ ³ ³ ³ ³ ³ ³adjacent which is at least 30 ³ ³ ³ ³ ³ ³ ³inches by 48 inches to provide ³ ³ ³ ³ ³ ³ ³a parallel or forward ³ ³ ³ ³ ³ ³ ³approach? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(19) ³Security ³If unattended security barriers³ ³ ³ ³ ³ ³Barriers ³are provided, does at least one³ ³ ³ ³ ³ ³ ³gate comply with 4.13? (Use ³ ³ ³ ³ ³ ³ ³Form 11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.1(19) ³Gates ³Do gates that must be pushed ³ ³ ³ ³ ³ ³ ³open by wheelchair or mobility ³ ³ ³ ³ ³ ³ ³aids users have a smooth ³ ³ ³ ³ ³ ³ ³continuous surface extending ³ ³ ³ ³ ³ ³ ³from 2 inches above the floor ³ ³ ³ ³ ³ ³ ³to 27 inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.2(1) ³Existing ³Do rapid rail, light rail and ³ ³ ³ ³ ³ ³Facilities ³commuter rail key stations (as ³ ³ ³ ³ ³ ³Key Stations ³defined in 49 CFR Part 37) and ³ ³ ³ ³ ³ ³ ³existing intercity rail ³ ³ ³ ³ ³ ³ ³stations provide at least one ³ ³ ³ ³ ³ ³ ³accessible route from an ³ ³ ³ ³ ³ ³ ³accessible entrance to those ³ ³ ³ ³ ³ ³ ³areas necessary for use of the ³ ³ ³ ³ ³ ³ ³transportation system? (Use ³ ³ ³ ³ ³ ³ ³Form 12: Building Lobbies and ³ ³ ³ ³ ³ ³ ³Corridors) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.2(2) ³Accessible ³Does the accessible route ³ ³ ³ ³ ³ ³Route ³include the same features ³ ³ ³ ³ ³ ³ ³specified in 10.3.1(1), ³ ³ ³ ³ ³ ³ ³(4)-(9), (11)-(15), and ³ ³ ³ ³ ³ ³ ³(17)-(19) above? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-8 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.2(3) ³Fare ³If technical infeasibility in ³ ³ ³ ³ ³ ³Collection ³existing stations requires the ³ ³ ³ ³ ³ ³ ³accessible route to lead from ³ ³ ³ ³ ³ ³ ³the public way to a paid area ³ ³ ³ ³ ³ ³ ³of the transit system, is there³ ³ ³ ³ ³ ³ ³an accessible fare collection ³ ³ ³ ³ ³ ³ ³system provided along the ³ ³ ³ ³ ³ ³ ³accessible route? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Does the fare collection system³ ³ ³ ³ ³ ³ ³comply with 10.3.1(7) above? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.2(4) ³Platform ³In light rail, rapid rail and ³ ³ ³ ³ ³ ³Height ³commuter rail key stations, is ³ ³ ³ ³ ³ ³Vertical Gap: ³the platform or a portion ³ ³ ³ ³ ³ ³ ³thereof and the vehicle floor ³ ³ ³ ³ ³ ³ ³coordinated so that the ³ ³ ³ ³ ³ ³ ³vertical difference (measured ³ ³ ³ ³ ³ ³ ³when the vehicle is at rest) is³ ³ ³ ³ ³ ³ ³within plus or minus 1-1/2 ³ ³ ³ ³ ³ ³ ³inches under normal passenger ³ ³ ³ ³ ³ ³ ³load conditions? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Horizontal Gap ³Is the horizontal gap (measured³ ³ ³ ³ ³ ³ ³when the vehicle is at rest) no³ ³ ³ ³ ³ ³ ³greater than 3 inches for at ³ ³ ³ ³ ³ ³ ³least one door of each vehicle ³ ³ ³ ³ ³ ³ ³or car required to be ³ ³ ³ ³ ³ ³ ³accessible by 49 CFR Part 37? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Vertical Gap ³EXCEPTION: Existing vehicles ³ ³ ³ ³ ³ ³and Horizontal ³retrofitted to meet the ³ ³ ³ ³ ³ ³Gap ³requirements of 49 CFR 37.93 ³ ³ ³ ³ ³ ³Exceptions for ³(one-car-per-train rule) shall ³ ³ ³ ³ ³ ³Existing Cars ³be coordinated with the ³ ³ ³ ³ ³ ³or Where Not ³platform such that, for at ³ ³ ³ ³ ³ ³Feasible ³least one door, the vertical ³ ³ ³ ³ ³ ³ ³difference between the vehicle ³ ³ ³ ³ ³ ³ ³floor and the platform ³ ³ ³ ³ ³ ³ ³(measured when the vehicle is ³ ³ ³ ³ ³ ³ ³at rest with 50% normal ³ ³ ³ ³ ³ ³ ³passenger capacity) is within ³ ³ ³ ³ ³ ³ ³plus or minus 2 inches and the ³ ³ ³ ³ ³ ³ ³horizontal gap is no greater ³ ³ ³ ³ ³ ³ ³than 4 inches. ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³EXCEPTION: Where it is not ³ ³ ³ ³ ³ ³ ³structurally or operationally ³ ³ ³ ³ ³ ³ ³feasible to meet the horizontal³ ³ ³ ³ ³ ³ ³gap or vertical difference ³ ³ ³ ³ ³ ³ ³requirements, mini-high ³ ³ ³ ³ ³ ³ ³platforms, car-borne or ³ ³ ³ ³ ³ ³ ³platform mounted lifts, ramps ³ ³ ³ ³ ³ ³ ³or bridge plates, or similar ³ ³ ³ ³ ³ ³ ³manually deployed devices ³ ³ ³ ³ ³ ³ ³meeting the applicable ³ ³ ³ ³ ³ ³ ³requirements of 49 CFR Part 38 ³ ³ ³ ³ ³ ³ ³shall suffice. ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.2(5) ³New Direct ³Do new direct connections to ³ ³ ³ ³ ³ ³Connections ³commercial, retail, or ³ ³ ³ ³ ³ ³ ³residential facilities, to the ³ ³ ³ ³ ³ ³ ³maximum extent feasible, have ³ ³ ³ ³ ³ ³ ³an accessible route complying ³ ³ ³ ³ ³ ³ ³with 4.3 from the point of ³ ³ ³ ³ ³ ³ ³connection to boarding ³ ³ ³ ³ ³ ³ ³platforms and all ³ ³ ³ ³ ³ ³ ³transportation system elements ³ ³ ³ ³ ³ ³ ³used by the public? (Use Form ³ ³ ³ ³ ³ ³ ³12: Building Corridors and ³ ³ ³ ³ ³ ³ ³Lobbies) ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-9 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Future Direct ³If provided, are any elements ³ ³ ³ ³ ³ ³Connections ³provided to facilitate future ³ ³ ³ ³ ³ ³ ³direct connections on an ³ ³ ³ ³ ³ ³ ³accessible route connecting ³ ³ ³ ³ ³ ³ ³boarding platforms and all ³ ³ ³ ³ ³ ³ ³transportation system elements ³ ³ ³ ³ ³ ³ ³used by the public? (Use Form ³ ³ ³ ³ ³ ³ ³12: Building Corridors and ³ ³ ³ ³ ³ ³ ³Lobbies) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.3.3 ³Existing ³Are alterations that affect the³ ³ ³ ³ ³ ³Facilities ³usability of, or access to, an ³ ³ ³ ³ ³ ³Alterations ³area of a facility that ³ ³ ³ ³ ³ ³ ³contains a primary function ³ ³ ³ ³ ³ ³ ³made in such a way to ensure ³ ³ ³ ³ ³ ³ ³that the path of travel to the ³ ³ ³ ³ ³ ³ ³altered area and the restrooms,³ ³ ³ ³ ³ ³ ³telephones, and drinking ³ ³ ³ ³ ³ ³ ³fountains serving the altered ³ ³ ³ ³ ³ ³ ³area are accessible, to the ³ ³ ³ ³ ³ ³ ³maximum extent feasible in ³ ³ ³ ³ ³ ³ ³accordance with 49 CFR 37.43(c)³ ³ ³ ³ ³ ³ ³or 28 CFR 36.403, as ³ ³ ³ ³ ³ ³ ³applicable? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29b-10 Section] SURVEY FORM 29C: TRANSPORTATION FACILITIES Ä AIRPORTS Use with the Minimum Requirements Summary Sheets and ADAAG. Facility Name: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Facility Location: ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ Every Station, bus stop, bus stop pad, terminal, building or other transportation facility, must comply with the applicable provisions of ADAAG 4.1 through 4.35, ADAAG 5 through 9, and the applicable provisions of ADAAG 10. Note: The exception for elevators in 4.1.3(5) Exception 1 and 4.1.6(1)(k) do not apply to a terminal, depot, or other station used for specified public transportation, or an airport passenger terminal, or facilities subject to Title II. ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4 ³Airports Ä ³Are elements such as ramps, ³ ³ ³ ³ ³10.4.1(1) ³New ³elevators, or other circulation³ ³ ³ ³ ³ ³Construction ³devices, ticketing areas, ³ ³ ³ ³ ³ ³ ³security checkpoints, or ³ ³ ³ ³ ³ ³ ³passenger waiting areas placed ³ ³ ³ ³ ³ ³ ³so as to minimize the distance ³ ³ ³ ³ ³ ³ ³which wheelchair users and ³ ³ ³ ³ ³ ³ ³other persons who cannot ³ ³ ³ ³ ³ ³ ³negotiate steps may have to ³ ³ ³ ³ ³ ³ ³travel compared to the general ³ ³ ³ ³ ³ ³ ³public? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4.1(2) ³Circulation ³Does the circulation path, ³ ³ ³ ³ ³ ³Path ³including an accessible ³ ³ ³ ³ ³ ³ ³entrance and an accessible ³ ³ ³ ³ ³ ³ ³route, to the maximum extent ³ ³ ³ ³ ³ ³ ³practicable, coincide with the ³ ³ ³ ³ ³ ³ ³circulation path for the ³ ³ ³ ³ ³ ³ ³general public? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where the circulation path is ³ ³ ³ ³ ³ ³ ³different, is directional ³ ³ ³ ³ ³ ³ ³signage complying with 4.30.1, ³ ³ ³ ³ ³ ³ ³4.30.2, 4.30.3 and 4.30.5 ³ ³ ³ ³ ³ ³ ³provided which indicates the ³ ³ ³ ³ ³ ³ ³location of the nearest ³ ³ ³ ³ ³ ³ ³accessible entrance and ³ ³ ³ ³ ³ ³ ³accessible route? (Use Form 19:³ ³ ³ ³ ³ ³ ³Signage) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4.1(3) ³Ticketing ³Are ticketing areas designed in³ ³ ³ ³ ³ ³Areas ³such a way that persons with ³ ³ ³ ³ ³ ³ ³disabilities can obtain tickets³ ³ ³ ³ ³ ³ ³and check baggage? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do such areas comply with ³ ³ ³ ³ ³ ³ ³section 7.2? (See Section ³ ³ ³ ³ ³ ³ ³10.3.1(18) above) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4.1(4) ³Text ³Where public pay telephones are³ ³ ³ ³ ³ ³Telephones ³provided, and at least one is ³ ³ ³ ³ ³ ³(TDD)s ³at an interior location, is ³ ³ ³ ³ ³ ³ ³there a public text telephone ³ ³ ³ ³ ³ ³ ³provided? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29c-1 ÚÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÂÄÄÄÄ¿ ³Section ³Item ³Technical Requirements ³Comments ³ Yes ³ No ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³In addition, if there are four ³ ³ ³ ³ ³ ³ ³or more public pay telephones ³ ³ ³ ³ ³ ³ ³located in any of the following³ ³ ³ ³ ³ ³ ³locations, is at least one ³ ³ ³ ³ ³ ³ ³public text telephone provided ³ ³ ³ ³ ³ ³ ³in that location: ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(a) a main terminal outside the³ ³ ³ ³ ³ ³ ³security areas; ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(b) a concourse within the ³ ³ ³ ³ ³ ³ ³security areas; or ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³ ³(c) a baggage claim area in a ³ ³ ³ ³ ³ ³ ³terminal? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Do the text telephones comply ³ ³ ³ ³ ³ ³ ³with 4.31.9? (Use Form 6: ³ ³ ³ ³ ³ ³ ³Telephones) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4.1(5) ³Baggage ³Are baggage check-in and ³ ³ ³ ³ ³ ³Check-in and ³retrieval systems on an ³ ³ ³ ³ ³ ³Retrieval ³accessible route? (Use Form ³ ³ ³ ³ ³ ³ ³12: Building Corridors and ³ ³ ³ ³ ³ ³ ³Lobbies) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Is there space immediately ³ ³ ³ ³ ³ ³ ³adjacent which is at least 30 ³ ³ ³ ³ ³ ³ ³inches by 48 inches to provide ³ ³ ³ ³ ³ ³ ³a parallel or forward approach?³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4.1(5) ³Gates ³If unattended security barriers³ ³ ³ ³ ³ ³ ³are provided, does at least one³ ³ ³ ³ ³ ³ ³gate comply with 4.13? (Use ³ ³ ³ ³ ³ ³ ³Form 11: Doors and Gates) ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Smooth ³Do gates which must be pushed ³ ³ ³ ³ ³ ³Surface on ³open by wheelchair or mobility ³ ³ ³ ³ ³ ³Gates ³aid users have a smooth ³ ³ ³ ³ ³ ³ ³continuous surface extending ³ ³ ³ ³ ³ ³ ³from 2 inches above the floor ³ ³ ³ ³ ³ ³ ³to 27 inches above the floor? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4.1(6) ³Public ³If there are terminal ³ ³ ³ ³ ³ ³Address ³information systems which ³ ³ ³ ³ ³ ³Systems ³broadcast information to the ³ ³ ³ ³ ³ ³ ³general public through a public³ ³ ³ ³ ³ ³ ³address system, is there a way ³ ³ ³ ³ ³ ³ ³to provide the same or ³ ³ ³ ³ ³ ³ ³equivalent information to ³ ³ ³ ³ ³ ³ ³persons with hearing ³ ³ ³ ³ ³ ³ ³impairments, such as visual ³ ³ ³ ³ ³ ³ ³paging systems? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³10.4.1(7) ³Clocks ³If clocks are provided for use ³ ³ ³ ³ ³ ³ ³by the public, are the clock ³ ³ ³ ³ ³ ³ ³faces uncluttered so that the ³ ³ ³ ³ ³ ³ ³elements are clearly visible? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³Contrast ³Do hands, numerals, and/or ³ ³ ³ ³ ³ ³ ³digits contrast with the ³ ³ ³ ³ ³ ³ ³background either light-on-dark³ ³ ³ ³ ³ ³ ³or dark-on-light? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Where mounted overhead, are the³ ³ ³ ³ ³ ³ ³numerals and/or digits 3 inches³ ³ ³ ³ ³ ³ ³or greater in height? ³ ³ ³ ³ ÃÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÅÄÄÄÄ´ ³ ³ ³Are clocks placed in uniform ³ ³ ³ ³ ³ ³ ³locations throughout the ³ ³ ³ ³ ³ ³ ³facility to the maximum extent ³ ³ ³ ³ ³ ³ ³practicable? ³ ³ ³ ³ ÀÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÁÄÄÄÄÙ 29c-2