ECE421/521 POWER SYSTEM ANALYSIS Homework #4 total 3.2a 521(100’) 4 421(120’) 3.6a 521(100’) 5 421(120’) 3.2(a) 3.2b 1 3.2c 3 3.4a 5 3.4b 5 3.4c 3 3.5a 5 3.5b 5 3.5c 5 3.5d 5 3.6b 5 3.6c 5 3.6d 1 3.9 5 3.10 8 3.14 14 3.15a 5 3.15b 5 3.17 6 5’ The three-phase apparent power is, π3π = 60∠πππ −1 0.8 = 60∠36.87°πππ΄ = 48ππ + π36ππ£ππ (1’) The rated voltage per phase is, π= 69.3 √3 = 40∠0°ππ (1’) The rated current is, π∗ 3π πΌπ = 3π ∗ = (60∠−36.87°)103 3×40∠0° = 500∠ − 36.87°π΄ (1’) The excitation voltage per phase is, πΈ = 40000 + (π15)(500∠ − 36.87°) = 44500 + π6000π = 44903∠7.7°π (1’) The excitation voltage per phase is 44.9kV and the power angle δ is 7.7° (b) 1’ The maximum value of three-phase power that the generator can deliver before losing its synchronism is reached at πΏ = 90°, π3ππππ₯ = 3 (c) |πΈ||π| ππ π ππ90° = 3 3’ The power angle is, 36000×40000 15 = 288ππ (1’) πΏ = π ππ−1 π3π ππ 3|πΈ||π| = π ππ−1 48×15 3×46×40 = 7.5° (1’) The armature current is, πΌπ = πΈ−π πππ = 46000∠7.5°−40000∠0° π15 = 400 − π374π΄ = 548∠ − 43°π΄ (1’) The power factor is, ππΉ = cos(0° − (−43°)) = 0.73 (1’) The power factor is lagging. 3.4(a) 5’ (1’) Based on phasor diagram, |π|π πππΏ = ππ |πΌπ | (1’) Considering |πΌπ | = |πΌπ |cosβ‘(π + πΏ), |π|π πππΏ = ππ |πΌπ |cosβ‘(π + πΏ) Applying triangle function, |π|π πππΏ = ππ |πΌπ |(πππ ππππ πΏ − π ππππ πππΏ) (1’) Rearrange equation, |π|π πππΏ + ππ |πΌπ |π ππππ πππΏ = ππ |πΌπ |πππ ππππ πΏ Divide πππ πΏ on both sides of equation, |π|π‘πππΏ + ππ |πΌπ |π ππππ‘πππΏ = ππ |πΌπ |πππ π Rearrange it, (1’) ππ |πΌπ |πππ π π‘πππΏ = |π|+π π |πΌπ |π πππ (1’) We have, π |πΌ |πππ π π π πΏ = π‘ππ−1 (|π|+π |πΌ π π |π πππ (b) ) 5’ The three-phase apparent power is, π3π = 60∠πππ −1 0.8 = 60∠36.87°πππ΄ = 48ππ + π36ππ£ππ (1’) The rated voltage per phase is, π= 34.64 √3 = 20∠0°ππ (1’) The rated current is, ∗ π3π πΌπ = 3π ∗ = (60∠−36.87°)103 3×20∠0° = 1000∠ − 36.87°π΄ (1’) Power angle, π |πΌ |πππ π π π πΏ = π‘ππ−1 (|π|+π |πΌ π π |π πππ 9.333×1000×0.8 ) 20000+9.333×1000×0.6 ) = π‘ππ−1 ( = 16.3° (1’) Excitation voltage magnitude is, |πΈ| = |π|πππ πΏ + ππ πΌπ = 20000 × πππ 16.3° + 13.5 × 1000 × sin(36.87° + 16.3°) = 30ππ Excitation voltage is, πΈ = 30∠16.3°ππ (c) 3’ Run the following code, (1’) %Problem 3.4(c) delta = 0:0.05:180; delta = delta*pi/180; Xd = 13.5; Xq = 9.333; E = 30000; V = 20000; P = (3*E*V*sin(delta)/Xd+3*V^2*(Xd-Xq)*sin(2*delta)/(2*Xd*Xq))/10^6; (1’) delta = delta*180/pi; [Pmax,k] = max(P); dmax = delta(k); plot(delta,P); title('salient-pole synchronous generator power angle curve') xlabel('delta, degree'); ylabel('real power, MW'); we have the power angle curve, (1’) Read Pmax and dmax from workspace, we have, (1’) Steady-state maximum power Pmax=138.71MW The corresponding power angle dmax=75.05 degree 3.5(a) 5’ To determine the equivalent circuit to the primary side, π 2 π π1 = π 1 + (π1 ) π 2 = 0.2 + 102 × 0.002 = 0.4πΊ 2 π 2 ππ1 = π1 + (π1 ) π2 = 0.45 + 102 × 0.0045 = 0.9πΊ 2 ππ1 = π π1 + πππ1 = 0.4 + π0.9πΊ (1’) (2’) (2’) (b) 5’ The transformer is operating at full load 0.8 power factor lagging and 240V, π2′ = π1 π π2 2 = 10 × 240 = 2400π (1’) PF=0.8 lagging, π2 = 150 × 0.8 + π150 × 0.6 = 120 + π90πππ΄ π πΌ1 = (π2′ )∗ = 2 120000−π90000 2400 (1’) = 50 − π37.5π΄ = 62.5∠ − 36.87°π΄ (1’) The primary voltage, π1 = π2′ + πΌ1 ππ1 = 2400 + (50 − π37.5)(0.4 + π0.9) = 2453.8 + π30π = 2453.9∠0.7°π (1’) Voltage regulation, ππ = (c) |π1 |−|π2′ | |π2′ | × 100 = 2453.9−2400 × 2400 100 = 2.25% (1’) 5’ PF=0.8 leading, π2 = 150 × 0.8 − π150 × 0.6 = 120 − π90πππ΄ π πΌ1 = (π ′ )∗ = 50 + π37.5π΄ = 62.5∠36.87°π΄ 2 (0.5’) (0.5’) The primary voltage, π1 = π2′ + πΌ1 ππ1 = 2400 + (50 + π37.5)(0.4 + π0.9) = 2386.3 + π60π = 2387∠1.4°π Voltage regulation, (2’) ππ = (d) |π1 |−|π2′ | |π2′ | × 100 = 2387−2400 × 2400 100 = −0.54% (2’) 5’ Run trans.m, for the PF=0.8 lagging load, the result is, Shunt branch ref. to LV side Rc = Xm = (2’) Shunt branch ref. to HV side 10.000 ohm Rc = 15.000 ohm 1000.000 ohm Xm = Series branch ref. to LV side 1500.000 ohm Series branch ref. to HV side Ze = 0.004000 + j 0.009000 ohm Ze = 0.400000 + j 0.900000 ohm Enter load kVA, S2 = 150 Enter load power factor, pf = 0.8 Enter 'lg' within quotes for lagging pf or 'ld' within quotes for leading pf -> 'lg' Enter load terminal voltage in volt, V2 = 240 Secondary load voltage = 240.000 V Secondary load current = 625.000 A at -36.87 degrees Current ref. to primary = Primary no-load current = Primary input current = 62.500 A at -36.87 degrees 2.949 A at -33.69 degrees 65.445 A at -36.73 degrees Primary input voltage = 2453.933 V at 0.70 degrees Voltage regulation = Transformer efficiency = 2.247 percent 94.249 percent Maximum efficiency is 95.238 percent, occurs at 288.000 kVA with 0.80 pf The result agrees to the calculation. (1’) for the PF=0.8 leading load, the result is, (2’) Would you like the analysis for another load? Enter 'Y' or 'N' within quotes -> 'Y' Enter load kVA, S2 = 150 Enter load power factor, pf = 0.8 Enter 'lg' within quotes for lagging pf or 'ld' within quotes for leading pf -> 'ld' Enter load terminal voltage in volt, V2 = 240 Secondary load voltage = 240.000 V Secondary load current = 625.000 A at 36.87 degrees Current ref. to primary = Primary no-load current = Primary input current = 62.500 A at 36.87 degrees 2.869 A at -33.69 degrees 63.512 A at 34.43 degrees Primary input voltage = 2387.004 V at 1.44 degrees Voltage regulation = Transformer efficiency = -0.541 percent 94.249 percent Maximum efficiency is 95.238 percent, occurs at 288.000 kVA with 0.80 pf The result agrees to the calculation. (1’) 3.6(a) 5’ Open-circuit test π22 π0 π π2 = π = 24002 3456 2400 = 1666.7πΊ πΌπ = π 2 = 1666.7 = 1.44π΄ π2 (0.5’) (0.5’) πΌπ = √πΌ02 − πΌπ2 = √2.42 − 1.442 = 1.92π΄ (0.5’) π 2400 1.92 ππ2 = πΌ 2 = π = 1250πΊ (0.5’) Refer to the high voltage side, π 4800 π π1 = (π1 )2 π π2 = (2400)2 1666.7 = 6666.8πΊ 2 π π2 4800 2 ) 1250 2400 ππ1 = ( 1 )2 ππ2 = ( = 5000πΊ (0.5’) (0.5’) Short-circuit test ππ1 = ππ π πΌπ π π π1 = ππ π (πΌπ π )2 = 1250 12.5 = = 100πΊ 4375 12.52 = 28πΊ (1’) 2 2 ππ1 = √ππ1 − π π1 = √1002 − 282 = 96πΊ (b) (1’) 5’ Transformer is operating at full-load, 0.8 PF lagging, π = 60 × 0.8 + 60 × 0.6 = 48ππ + 36ππ£ππ = 60∠36.87°πππ΄ (0.5’) Calculate voltage regulation utilizing the equivalent circuit referred to the primary side, π πΌ2 = (π )∗ = 2 60000∠−36.87° 2400 = 25∠ − 36.87°π΄ (0.5’) π 2400 πΌ2′ = π2 πΌ2 = 4800 × 25∠ − 36.87° = 12.5∠ − 36.87°π΄ 1 π π2′ = π1 π2 = 4800π 2 (0.5’) (0.5’) π1 = π2′ + πΌ2′ ππ1 = 4800 + (12.5∠ − 36.87°)(28 + π96) = 5800 + π750π = 5848.3∠7.37°π ππ = |π1 |−|π2′ | × |π2′ | 100 = 5848.3−4800 × 100 4800 = 21.84% (0.5’) Efficiency, ππ = |π2′ |2 π π1 = 48002 6666.8 = 3456π (0.5’) π = |π2 ||πΌ2 | = 2400 × 25 = 60000ππ΄ πππ’ = π π1 |πΌ2′ |2 = 28 × 12.52 = 4375π π×π×ππΉ (0.5’) 1×60000×0.8 π = (π×π×ππΉ)+π2 ×π ππ’ +ππ (c) (0.5’) = (1×60000×0.8)+1×4375+3456 = 85.97% (0.5’) 5’ The maximum efficiency occurs when, ππ πππ’ π=√ 3456 4375 =√ = 0.89 (2’) The load for maximum efficiency is, |π| = π60 = 53.4πππ΄ (1’) The maximum efficiency at 0.8 PF lagging is, π×π×ππΉ π = (π×π×ππΉ)+π2 ×π ππ’ +ππ (d) 0.89×60000×0.8 = (0.89×60000×0.8)+0.892 ×4375+3456 = 86.06% (2’) 1’ Efficiency for 0.75 full-load, 0.8 PF lagging is, π×π×ππΉ π = (π×π×ππΉ)+π2 ×π ππ’ +ππ 0.75×60000×0.8 = (0.75×60000×0.8)+0.752 ×4375+3456 = 85.88% (1’) (0.5’) 3.9 5’ π2πΏ , line voltage of low voltage side π1πΏ , line voltage of high voltage side π2π , phase voltage of low voltage side π1π , phase voltage of high voltage side Low side is Δ connected, take π2πΏ as reference π2π = π2πΏ = 24∠0°ππ (0.5’) ′ π2πΏ = ππ2πΏ = 10 × 24 = 240∠0°ππ (0.5’) The complex power of low side, π3π = 400∠36.87°πππ΄ ′ πΌ1π = πΌ2π =( π3π ′ √3π2πΏ )∗ = ′ π1π = π2π + ππ1 πΌ1π = (0.5’) 400∠−36.87° × √3×240 240 + √3 1000 = 962.3∠ − 36.87°π΄ (0.5’) (1.2 + π6) × 0.9623∠ − 36.87° = 142.96 + π3.93ππ = 143.01∠1.57°ππ (0.5’) The line voltage at the high voltage side is, π1πΏ = √3∠30°π1π = 247.69∠31.57°ππ (1’) The voltage of the sending end of the feeder is, πππππππ = π1π + ππΌ1 = 143.01∠1.57° + (0.6 + π1.2) × 0.9623∠ − 36.87° = 144.18∠1.79°ππ ππππππππΏ = √3∠30°π1π = 249.72∠31.79°ππ 3.10 (1’) 8’ Take the transformer rated value 400MVA, 240kV as base quantities, ππ΅1 = 400πππ΄ ππ΅1 = 240ππ (0.5’) (0.5’) 24 ππ΅2 = 240 (240) = 24ππ ππ = 1.2 + π6πΊ (0.5’) (0.5’) (0.5’) π2 ππ΅1 = ππ΅1 = π΅1 2402 400 = 144πΊ ππππ’ = ππ ππ΅1 = π2ππ’ = 24 ππ΅2 = 1ππ’ πππ’ = 1.2+π6 144 400∠36.87° ππ΅1 (0.5’) = 0.0083 + π0.0417ππ’ (0.5’) (0.5’) = 1∠36.87°ππ’ (0.5’) πΌππ’ = (π ππ’ )∗ = 1∠ − 36.87°ππ’ (0.5’) π 2ππ’ π1ππ’ = π2ππ’ + ππππ’ πΌππ’ = 1 + (0.0083 + π0.0417)(1∠ − 36.87°) = 1.0317 + π0.0284 = 1.0321∠1.58°ππ’ (1’) High-voltage side line voltage is, π1πΏ = ππ΅1 π1ππ’ = 247.69∠1.58ππ (0.5’) Feeder voltage, π ππππ’ = π π = π΅1 0.6+π1.2 144 = 0.0042 + π0.083ππ’ (0.5’) ππππ’ = π1ππ’ + ππππ’ πΌ1ππ’ = 1.0317∠1.58° + π0.0284 + (0.0042 + π0.0083)(1∠ − 36.87°) = 1.04 + π0.03ππ’ = 1.04∠1.79°ππ’ (1’) ππ = ππππ’ ππ΅1 = 249.72∠1.79°ππ 3.14 (0.5’) 14’ ππ΅1 = 22ππ (0.5’) ππ΅ = 100πππ΄ (0.5’) 220 ππ΅2 = ππ΅3 = 22 ( 22 ) = 220ππ 22 ππ΅4 = 220 (220) = 22ππ (0.5’) 110 ππ΅5 = ππ΅6 = 22 ( 22 ) 110ππ 22 ππ΅π = 110 (110) = 22ππ 4 ππ΅πΏ = 110 (110) = 4ππ (0.5’) (0.5’) (0.5’) (0.5’) ππ΅2 = 2 ππ΅2 ππ΅ πππππ1 = ππ΅5 = 2202 100 π121 484 2 ππ΅5 ππ΅ πππππ2 = = = = 484πΊ = π0.25ππ’ 1102 100 π42.35 121 (0.5’) (0.5’) = 121πΊ (0.5’) = π0.35ππ’ (0.5’) 20 2 100 ππ = 0.225 (68.85) (22) = 0.27ππ’ (0.5’) Load is Δ-connected capacitors, πππππ = 42 10 ππ΅ππππ = πππππ = = 1.6πΊ π72 π 42 10 (0.5’) = 0.16πΊ = 10ππ’ 100 (0.5’) (0.5’) 22 ππΊ = 0.24( 80 )(22)2 = 0.3ππ’ 100 22 2 )( ) 50 22 ππ1 = 0.1( 100 = 0.2ππ’ (0.5’) (0.5’) 220 ππ2 = 0.06( 40 )(220)2 = 0.15ππ’ 100 (0.5’) 22 ππ3 = 0.064( 40 )(22)2 = 0.16ππ’ (0.5’) (0.5’) 100 110 2 )( ) 40 110 πππ = 0.096( = 0.24ππ’ (0.5’) πππ‘ = 0.072( 40 )(110)2 = 0.18ππ’ (0.5’) 100 100 110 22 ππ π‘ = 0.12( 40 )(22)2 = 0.3ππ’ ππ = πππ +πππ‘ −ππ π‘ 2 = (0.5’) π0.24+π0.18−π0.3 2 = π0.06ππ’ (0.5’) ππ = ππ‘ = πππ +ππ π‘ −πππ‘ 2 πππ‘ +ππ π‘ −πππ 2 = π0.24+π0.3−π0.18 2 = π0.18ππ’ (0.5’) = π0.18+π0.3−π0.24 2 = π0.12ππ’ (0.5’) (1’) 3.15(a) 5’ ππ΅π = 20ππ (0.5’) 200 ) 20 ππ΅1 = ππ΅2 = 20 ( = 200ππ 20 ππ΅π = 200 (200) = 20ππ 100 (0.5’) 20 ππΊ = 0.09( 60 )(20)2 = 0.15ππ’ 100 20 2 )( ) 50 20 ππ1 = 0.1( = 0.2ππ’ 100 200 2 )( ) 50 200 ππ2 = 0.1( 100 (0.5’) ππ = 0.08(43.2)(20)2 = 0.15ππ’ ππ΅ππππ = 2 ππ΅1 ππ΅ = π 2002 100 πππππ = π ππππ = π΅ππππ = 400πΊ 120+π200 400 (0.5’) (0.5’) = 0.2ππ’ 18 (0.5’) (0.5’) (0.5’) = 0.3 + π0.5ππ’ (0.5’) (0.5’) (b) 5’ 18 ππ = 20 = 0.9ππ’ (0.5’) 45 |ππ | = 100 = 0.45ππ’ (0.5’) ππ = 0.45 × 0.8 + π0.45 × 0.6 = 0.36 + π0.27ππ’ π πΌ = (ππ )∗ = π 0.36−π0.27 0.9 = 0.4 − π0.3ππ’ (0.5’) (0.5’) Terminal voltage of generator is, ππ = ππ + πΌ(π0.2 + π0.2 + 0.3 + π0.5) = 0.9 + (0.4 − π0.3)(0.3 + π0.9) = 1.29 + π0.27ππ’ = 1.318∠11.8°ππ’ (1’) ππ = 1.318∠11.8° × 20 = 26.36∠11.8°ππ (0.5’) πΈπ = ππ + πΌ(π0.15) = 1.29 + π0.27 + (0.4 − π0.3)(π0.15) = 1.335 + π0.33ππ’ = 1.38∠13.9°ππ’ ππ = 1.38∠13.9° × 20 = 27.5∠13.9°ππ 3.17 (0.5’) 6’ Choose ππ΅1 = 23ππ, ππ΅ = 100πππ΄ as common base, ππ = 0.2ππ’ 115 ) 23 ππ΅2 = ππ΅3 = 23 ( ππ΅ππππ = 2 ππ΅2 ππ΅ = 1152 100 = 115ππ = 132.25πΊ (0.5’) (1’) πππππ = π66.125 132.25 π3 = 115 ππ΅3 π2 = 184.8+π6.6 ππ΅ π3 = π20 ππ΅ = π0.5ππ’ = 1ππ’ (0.5’) = 1.848 + π0.066ππ’ = π0.2ππ’ π πΌ3 = (π3 )∗ = 3 (0.5’) −π0.2 1 (0.5’) (0.5’) = −π0.2ππ’ (0.5’) π2 = π3 + πΌ3 πππππ = 1 + (−π0.2)(π0.5) = 1.1ππ’ π πΌ2 = (π2 )∗ = 2 1.848−π0.066 1.1 = 1.68 − π0.06ππ’ (0.5’) (0.5’) πΌ1 = πΌ2 + πΌ3 = −π0.2 + 1.68 − π0.06 = 1.68 − π0.26ππ’ (0.5’) π1 = π2 + πΌ1 ππ = 1.1 + (1.68 − π0.26)(π0.2) = 1.15 + π0.34ππ’ = 1.2∠16.26°ππ’ In kV, π1 = 1.2ππ΅1 = 27.6ππ π2 = 1.1ππ΅2 = 126.5ππ (0.5’) (0.5’) (0.5’)