® Liebert RDU-S GUIDE SPECIFICATIONS 1.0 GENERAL 1.1 Summary This specification defines the monitoring requirements of an environmental monitoring panel for notification of IT critical spaces. The primary communication feature of the monitoring panel shall be HTTP access and SNMP Data communication. When an alarm occurs the monitoring panel shall automatically display and report the alarm condition via Physical LED Display, Web GUI, SNMP TRAP, Email Alarm, and SMS Alarm (Optional). The monitoring panel shall provide remote alarm notification to all of the following: A PC using SNMP software, an Email Account, and a hardware/software receiving SMS messages (Optional). The environmental monitoring panel shall also provide data charting for temperature and/or humidity values. 1.2 Design Requirements All materials and equipment used shall be standard components, regularly manufactured for this and/or other systems. 1.3 Work By Others x 100Vac ~ 240Vac to power up the Environmental Monitoring Device 1.4 Quality Assurance x x x The environmental monitoring panel shall be started up by factory-trained personnel. The environmental monitoring panel shall be the catalogued product of manufacturers regularly engaged in production and installation of critical IT space monitoring systems and shall be manufacturer’s latest standard design that complies with the specification requirements. Compatibility shall be defined as the ability to upgrade existing field panels to the current level of technology via a firmware upgrade and not a complete circuit board replacement. 1.5 Warranty The manufacturer shall warrant the monitoring panel from defects, including all parts, for a period of (1) year from the date of shipment. 2.0 PRODUCT 2.1 Environmental Monitoring Panel 2.1.1 The environmental monitoring panel will consist of: x x Input power plug 2 Digital Alarm Output Port x x LED Status and Alarm display Micro SD Slot x x 2 USB Ports 1 USB Configuration Port x x x x x 1 Ethernet Port 3 Digital Inputs 1 TH_BUS Analog Input 2 1-Wire Sensor Input (Future Use) 2 COM Port serial inputs for supported equipments 2.1.2 x x The environmental monitoring panel shall have sufficient memory to support: Historical alarm/event history with a maximum capacity of 10,000 logs Data trend history with a maximum capacity of 8,000 logs 2.1.3 The environmental monitoring panel shall support firmware upgrades without the need to replace the hardware. 2.1.4 The environmental monitoring panel shall have the capability to communicate with Liebert Nform® Software. 2.1.5 The environmental monitoring panel shall have a USB CONFIG port that will display the current IP Address and restore the default password. 2.1.6 The environmental monitoring panel shall have the ability to provide alarm notification via Physical LED Display, WEB GUI, SNMP TRAP, EMAIL Alert, and SMS ALERT (Optional). 2.1.7 The environmental monitoring panel shall have the capability to communicate with a specific type of Liebert Power Distribution Unit. 2.2 Environmental Monitoring Panel Built-In Web Server and Internal Software Function 2.2.1 General x 2.2.2 The web server specified in this section shall be provided as an internal part of the monitoring panel that is used to configure the panel and shall work with Microsoft Internet Explorer version 7 and 8. If needed, optional upper level monitoring platform is available. Web Server Functions x x The web server shall be the main utility for the user to set logic on different scenarios for alarm notification. User also has different options for notification 2.2.3 The environmental monitoring panel shall have the capability to do trending analysis for temperature and/or humidity values and has an optional feature to export the data. 2.2.4 The environmental monitoring panel shall be able to execute custom, jobspecific processes defined by the use to perform special routines in lieu of the software description features defined in 2.2.2. 3.0 POINT SCHEDULE MATRIX 3.1 The service engineer/installer shall collaborate with the owner to determine preference on installation. 3.2 Optional sensors are available for purchase depending on the set-up that is required by the client. 3.3 Attached I/O Schedule 4.0 START-UP AND COMMISSIONING 4.1 When installation is complete, configure sensor/equipment and verify remote access before the module is placed on-line. INPUT / OUTPUT SUMMARY ANALOG INPUT DIGITAL OUTPUT ALARM X ALARM TEMPERATURE / HUMIDITY X STATUS TEMPERATURE AREA, SYSTEM OR POINT DESCRIPTION DIGITAL INPUT EVENT TRIGGER ALARM END DEVICE OR SENSOR X Yes Temperature Sensor (02311725) X Yes Temperature / Humidity Sensor (02311720) X Yes PROCESS CONTROL AREA Cabinet Internal Temperature Cabinet Internal Humidity X Door Sensor Cabinet Door Sensor X X (33010342) Yes Temperature / Humidity Sensor (02311720) X Yes Leak Sensor (33010326 / 33010328 / 33010322) Camera X Yes *USB Camera (51060034 / 51060033) PDU X Room Ambient Temperature / Humidity X X Leak Detected X X X *MPS PDU TELECOM ROOM Yes Temperature Sensor (02311725) Yes Temperature / Humidity Sensor (02311720) X Yes Leak Sensor (33010326 / 33010328 / 33010322) Camera X Yes *USB Camera (51060034 / 51060033) PDU X Room Temperature Room Humidity Leak Detected X X X X X X X *MPS PDU Notes: USB Camera Max Input: 2; Temp & Temp/Humid Sensor max is 8; MPS PDU Max Input: 8, for part number see MPS Guide Spec / Brochure. INPUT / OUTPUT SUMMARY ANALOG INPUT DIGITAL OUTPUT ALARM EVENT TRIGGER ALARM END DEVICE OR SENSOR X Yes Temperature Sensor (02311725) Yes Leak Sensor (33010326 / 33010328 / 33010322) X Yes Door Sensor (33010342) Vibration Sensor (33010330 & 33010331) Microwave and infrared sensor (33040015) Camera X Yes *USB Camera (51060034 / 51060033) PDU X AREA, SYSTEM OR POINT DESCRIPTION ALARM TEMPERA TURE / HUMIDITY X STATUS TEMPERA TURE X DIGITAL INPUT REMOTE SHELTER Room Temperature Leak Detected X Intrusion Alarm X X X *MPS PDU COMPUTER ROOM X Yes Temperature Sensor (02311725) X Yes Temperature / Humidity Sensor (02311720) X Yes Leak Sensor (33010326 / 33010328 / 33010322) Camera X Yes *USB Camera (51060034 / 51060033) PDU X Room Temperature X Room Humidity X Leak Detected X X *MPS PDU Notes: USB Camera Max Input: 2; Temp & Temp/Humid Sensor max is 8; MPS PDU Max Input: 8, for part number see MPS Guide Spec / Brochure. INPUT / OUTPUT SUMMARY ANALOG INPUT DIGITAL OUTPUT ALARM X ALARM TEMPERA TURE / HUMIDITY X STATUS TEMPERA TURE AREA, SYSTEM OR POINT DESCRIPTION DIGITAL INPUT EVENT TRIGGER ALARM END DEVICE OR SENSOR X Yes Temperature Sensor (02311725) X Yes Temperature / Humidity Sensor (02311720) X Yes Door Sensor (33010342) Microwave and infrared sensor (33040015) COMMUNICATION CLOSET / IT RACK Cabinet Internal Temperature Cabinet Internal Humidity Cabinet Door Ajar X X X Motion Sensor X X X Yes Smoke Sensor X X X Yes Vibration Sensor X X X Yes Leak Detected X X Camera PDU X Smoke Sensor (33010441) Vibration Sensor (33010330 & 33010331) Yes Leak Sensor (33010326 / 33010328 / 33010322) Yes *USB Camera (51060034 / 51060033) *MPS PDU Notes: USB Camera Max Input: 2; Temp & Temp/Humid Sensor max is 8; MPS PDU Max Input: 8, for part number see MPS Guide Spec / Brochure.