Liebert RDU-S ®

advertisement
®
Liebert RDU-S
GUIDE SPECIFICATIONS
1.0 GENERAL
1.1 Summary
This specification defines the monitoring requirements of an environmental monitoring panel for
notification of IT critical spaces. The primary communication feature of the monitoring panel shall be
HTTP access and SNMP Data communication. When an alarm occurs the monitoring panel shall
automatically display and report the alarm condition via Physical LED Display, Web GUI, SNMP TRAP,
Email Alarm, and SMS Alarm (Optional). The monitoring panel shall provide remote alarm
notification to all of the following: A PC using SNMP software, an Email Account, and a
hardware/software receiving SMS messages (Optional). The environmental monitoring panel shall
also provide data charting for temperature and/or humidity values.
1.2 Design Requirements
All materials and equipment used shall be standard components, regularly manufactured for this
and/or other systems.
1.3 Work By Others
x
100Vac ~ 240Vac to power up the Environmental Monitoring Device
1.4 Quality Assurance
x
x
x
The environmental monitoring panel shall be started up by factory-trained personnel.
The environmental monitoring panel shall be the catalogued product of manufacturers regularly
engaged in production and installation of critical IT space monitoring systems and shall be
manufacturer’s latest standard design that complies with the specification requirements.
Compatibility shall be defined as the ability to upgrade existing field panels to the current level
of technology via a firmware upgrade and not a complete circuit board replacement.
1.5 Warranty
The manufacturer shall warrant the monitoring panel from defects, including all parts, for a period of
(1) year from the date of shipment.
2.0 PRODUCT
2.1 Environmental Monitoring Panel
2.1.1
The environmental monitoring panel will consist of:
x
x
Input power plug
2 Digital Alarm Output Port
x
x
LED Status and Alarm display
Micro SD Slot
x
x
2 USB Ports
1 USB Configuration Port
x
x
x
x
x
1 Ethernet Port
3 Digital Inputs
1 TH_BUS Analog Input
2 1-Wire Sensor Input (Future Use)
2 COM Port serial inputs for supported equipments
2.1.2
x
x
The environmental monitoring panel shall have sufficient memory to support:
Historical alarm/event history with a maximum capacity of 10,000 logs
Data trend history with a maximum capacity of 8,000 logs
2.1.3
The environmental monitoring panel shall support firmware upgrades without
the need to replace the hardware.
2.1.4
The environmental monitoring panel shall have the capability to communicate
with Liebert Nform® Software.
2.1.5
The environmental monitoring panel shall have a USB CONFIG port that will
display the current IP Address and restore the default password.
2.1.6
The environmental monitoring panel shall have the ability to provide alarm
notification via Physical LED Display, WEB GUI, SNMP TRAP, EMAIL Alert, and
SMS ALERT (Optional).
2.1.7
The environmental monitoring panel shall have the capability to communicate
with a specific type of Liebert Power Distribution Unit.
2.2 Environmental Monitoring Panel Built-In Web Server and Internal Software Function
2.2.1
General
x
2.2.2
The web server specified in this section shall be provided as an internal
part of the monitoring panel that is used to configure the panel and
shall work with Microsoft Internet Explorer version 7 and 8. If needed,
optional upper level monitoring platform is available.
Web Server Functions
x
x
The web server shall be the main utility for the user to set logic on
different scenarios for alarm notification.
User also has different options for notification
2.2.3
The environmental monitoring panel shall have the capability to do trending
analysis for temperature and/or humidity values and has an optional feature to
export the data.
2.2.4
The environmental monitoring panel shall be able to execute custom, jobspecific processes defined by the use to perform special routines in lieu of the
software description features defined in 2.2.2.
3.0 POINT SCHEDULE MATRIX
3.1 The service engineer/installer shall collaborate with the owner to determine preference on
installation.
3.2 Optional sensors are available for purchase depending on the set-up that is required by the
client.
3.3 Attached I/O Schedule
4.0 START-UP AND COMMISSIONING
4.1 When installation is complete, configure sensor/equipment and verify remote access before
the module is placed on-line.
INPUT / OUTPUT SUMMARY
ANALOG INPUT
DIGITAL
OUTPUT
ALARM
X
ALARM
TEMPERATURE /
HUMIDITY
X
STATUS
TEMPERATURE
AREA, SYSTEM OR
POINT DESCRIPTION
DIGITAL INPUT
EVENT
TRIGGER
ALARM
END DEVICE
OR SENSOR
X
Yes
Temperature
Sensor
(02311725)
X
Yes
Temperature /
Humidity
Sensor
(02311720)
X
Yes
PROCESS CONTROL
AREA
Cabinet Internal
Temperature
Cabinet Internal
Humidity
X
Door Sensor
Cabinet Door Sensor
X
X
(33010342)
Yes
Temperature /
Humidity
Sensor
(02311720)
X
Yes
Leak Sensor
(33010326 /
33010328 /
33010322)
Camera
X
Yes
*USB Camera
(51060034 /
51060033)
PDU
X
Room Ambient
Temperature / Humidity
X
X
Leak Detected
X
X
X
*MPS PDU
TELECOM ROOM
Yes
Temperature
Sensor
(02311725)
Yes
Temperature /
Humidity
Sensor
(02311720)
X
Yes
Leak Sensor
(33010326 /
33010328 /
33010322)
Camera
X
Yes
*USB Camera
(51060034 /
51060033)
PDU
X
Room Temperature
Room Humidity
Leak Detected
X
X
X
X
X
X
X
*MPS PDU
Notes: USB Camera Max Input: 2; Temp & Temp/Humid Sensor max is 8; MPS PDU Max Input: 8, for part number
see MPS Guide Spec / Brochure.
INPUT / OUTPUT SUMMARY
ANALOG INPUT
DIGITAL
OUTPUT
ALARM
EVENT
TRIGGER
ALARM
END DEVICE
OR SENSOR
X
Yes
Temperature
Sensor
(02311725)
Yes
Leak Sensor
(33010326 /
33010328 /
33010322)
X
Yes
Door Sensor
(33010342)
Vibration
Sensor
(33010330 &
33010331)
Microwave
and infrared
sensor
(33040015)
Camera
X
Yes
*USB Camera
(51060034 /
51060033)
PDU
X
AREA, SYSTEM OR
POINT DESCRIPTION
ALARM
TEMPERA
TURE /
HUMIDITY
X
STATUS
TEMPERA
TURE
X
DIGITAL INPUT
REMOTE SHELTER
Room Temperature
Leak Detected
X
Intrusion Alarm
X
X
X
*MPS PDU
COMPUTER ROOM
X
Yes
Temperature
Sensor
(02311725)
X
Yes
Temperature /
Humidity
Sensor
(02311720)
X
Yes
Leak Sensor
(33010326 /
33010328 /
33010322)
Camera
X
Yes
*USB Camera
(51060034 /
51060033)
PDU
X
Room Temperature
X
Room Humidity
X
Leak Detected
X
X
*MPS PDU
Notes: USB Camera Max Input: 2; Temp & Temp/Humid Sensor max is 8; MPS PDU Max Input: 8, for part number
see MPS Guide Spec / Brochure.
INPUT / OUTPUT SUMMARY
ANALOG INPUT
DIGITAL
OUTPUT
ALARM
X
ALARM
TEMPERA
TURE /
HUMIDITY
X
STATUS
TEMPERA
TURE
AREA, SYSTEM OR
POINT DESCRIPTION
DIGITAL INPUT
EVENT
TRIGGER
ALARM
END DEVICE
OR SENSOR
X
Yes
Temperature
Sensor
(02311725)
X
Yes
Temperature /
Humidity
Sensor
(02311720)
X
Yes
Door Sensor
(33010342)
Microwave
and infrared
sensor
(33040015)
COMMUNICATION
CLOSET / IT RACK
Cabinet Internal
Temperature
Cabinet Internal
Humidity
Cabinet Door Ajar
X
X
X
Motion Sensor
X
X
X
Yes
Smoke Sensor
X
X
X
Yes
Vibration Sensor
X
X
X
Yes
Leak Detected
X
X
Camera
PDU
X
Smoke
Sensor
(33010441)
Vibration
Sensor
(33010330 &
33010331)
Yes
Leak Sensor
(33010326 /
33010328 /
33010322)
Yes
*USB Camera
(51060034 /
51060033)
*MPS PDU
Notes: USB Camera Max Input: 2; Temp & Temp/Humid Sensor max is 8; MPS PDU Max Input: 8, for part number
see MPS Guide Spec / Brochure.
Download