® Liebert RDU-SIC GUIDE SPECIFICATIONS 1.0 GENERAL 1.1 Summary This specification defines the monitoring requirements of an SNMP/Web card for monitoring and notification of UPS and IT critical spaces. The primary communication feature of the card shall be HTTP access and SNMP Data Access. When an alarm occurs, the monitoring panel shall automatically display and report the alarm condition via Web GUI, SNMP TRAP, Email, and SMS Alarm (Optional). The monitoring panel shall provide remote alarm notification to all of the following: a PC displaying the web GUI of the device, a PC using SNMP software, an Email client, and a hardware/software receiving SMS messages (Optional). 1.2 Design Requirements All materials and equipment used shall be standard components, regularly manufactured for this and/or other systems. 1.3 Work By Others x x UPS IntelliSlot installation Local Area Network Connection 1.4 Quality Assurance x x The SNMP/Web Card shall be the catalogued product of manufacturers regularly engaged in production and installation of critical IT space monitoring systems and shall be manufacturer’s latest standard design that complies with the specification requirements. Compatibility shall be defined as the ability to upgrade existing field panels to the current level of technology via a firmware upgrade and not a complete circuit board replacement. 1.5 Warranty The manufacturer shall warrant the monitoring panel from defects, including all parts, for a period of (1) year from the date of shipment. 2.0 PRODUCT 2.1 SNMP/ Web Card 2.1.1 The SNMP/Web Card will consist of: x x 1 LAN Port 1 USB Port x x 1 1-Wire Input Port (FUTURE USE) 1 COM Port for Supported Equipments 2.1.2 x The environmental monitoring panel shall have sufficient memory to support: Historical alarm/event history with a maximum capacity of 10,000 logs 2.1.3 The environmental monitoring panel shall support firmware upgrades without the need to replace the hardware. 2.1.4 The environmental monitoring panel shall have the capability to communicate with Liebert Nform® Software and/or SiteMonitor Software. 2.1.5 The environmental monitoring panel shall have a USB port that can be used to connect to a USB Modem for SMS (OPTIONAL) and can also be used as a configuration port. 2.1.6 The environmental monitoring panel shall have the ability to provide alarm notification via WEB GUI, SNMP TRAP, Email alert, and SMS Alert (Optional). 2.2 SNMP/Web card Built-In Web Server 2.2.1 General x The web server specified in this section shall be provided as an internal part of the monitoring panel that is used to configure the panel and shall work with Microsoft Internet Explorer version 6 and above. If needed, optional upper level monitoring platform is available. 2.2.2 Web Server Functions x x 2.2.3 The web server shall be the main utility for the user to set logic on different scenarios for alarm notification. User also has different options for notification The SNMP/Web card shall be able to execute custom, job-specific processes defined by the use to perform special routines in lieu of the software description features defined in 2.2.2. 3.0 POINT SCHEDULE MATRIX 3.1 The service engineer/installer shall collaborate with the owner to determine preference on installation. 3.2 Optional sensors are available for purchase depending on the set-up that is required by the client. 3.3 Attached I/O Schedule 4.0 START-UP AND COMMISSIONING 4.1 When installation is complete, configure sensor/equipment and verify remote access before the module is placed on-line. INPUT / OUTPUT SUMMARY ANALOG INPUT DIGITAL OUTPUT ALARM ALARM STATUS TEMPERATURE / HUMIDITY TEMPERATURE AREA, SYSTEM OR POINT DESCRIPTION DIGITAL INPUT EVENT TRIGGER ALARM END DEVICE OR SENSOR Yes RDU-SIC PROCESS CONTROL AREA UPS Monitoring Cabinet Internal Temperature X Cabinet Internal Humidity Room Ambient Temperature / Humidity X X X Yes Temperature Sensor (02311725) X X Yes Temperature / Humidity Sensor (02311720) X X Yes Temperature / Humidity Sensor (02311720) PDU X *MPS PDU TELECOM ROOM UPS Monitoring Room Temperature Room Humidity X Yes RDU-SIC X X Yes Temperature Sensor (02311725) X X Yes Temperature / Humidity Sensor (02311720) Notes: Max COM Port input is 4 (4 Temp/Humid Sensor or 4 PDU Sensor or a combination of both), for part number see MPS Guide Spec / Brochure INPUT / OUTPUT SUMMARY ANALOG INPUT DIGITAL OUTPUT ALARM ALARM STATUS TEMPERATURE / HUMIDITY TEMPERATURE AREA, SYSTEM OR POINT DESCRIPTION DIGITAL INPUT EVENT TRIGGER ALARM END DEVICE OR SENSOR Yes RDU-SIC Yes Temperature Sensor (02311725) REMOTE SHELTER UPS Monitoring Room Temperature X X PDU X X *MPS PDU COMPUTER ROOM UPS Monitoring Room Temperature Room Humidity PDU X X X X X X Yes RDU-SIC Yes Temperature Sensor (02311725) Yes Temperature / Humidity Sensor (02311720) *MPS PDU Notes: Max COM Port input is 4 (4 Temp/Humid Sensor or 4 PDU Sensor or a combination of both), for part number see MPS Guide Spec / Brochure INPUT / OUTPUT SUMMARY ANALOG INPUT DIGITAL OUTPUT ALARM ALARM STATUS TEMPERATURE / HUMIDITY TEMPERATURE AREA, SYSTEM OR POINT DESCRIPTION DIGITAL INPUT EVENT TRIGGER ALARM END DEVICE OR SENSOR Yes RDU-SIC Yes Temperature Sensor (02311725) Yes Temperature / Humidity Sensor (02311720) COMMUNICATION CLOSET / IT RACK UPS Monitoring Cabinet Internal Temperature Cabinet Internal Humidity PDU X X X X X X *MPS PDU Notes: Max COM Port input is 4 (4 Temp/Humid Sensor or 4 PDU Sensor or a combination of both), for part number see MPS Guide Spec / Brochure