Liebert RDU-SIC ®

advertisement
®
Liebert RDU-SIC
GUIDE SPECIFICATIONS
1.0 GENERAL
1.1 Summary
This specification defines the monitoring requirements of an SNMP/Web card for monitoring and
notification of UPS and IT critical spaces. The primary communication feature of the card shall be
HTTP access and SNMP Data Access. When an alarm occurs, the monitoring panel shall automatically
display and report the alarm condition via Web GUI, SNMP TRAP, Email, and SMS Alarm (Optional).
The monitoring panel shall provide remote alarm notification to all of the following: a PC displaying
the web GUI of the device, a PC using SNMP software, an Email client, and a hardware/software
receiving SMS messages (Optional).
1.2 Design Requirements
All materials and equipment used shall be standard components, regularly manufactured for this
and/or other systems.
1.3 Work By Others
x
x
UPS IntelliSlot installation
Local Area Network Connection
1.4 Quality Assurance
x
x
The SNMP/Web Card shall be the catalogued product of manufacturers regularly engaged in
production and installation of critical IT space monitoring systems and shall be manufacturer’s
latest standard design that complies with the specification requirements.
Compatibility shall be defined as the ability to upgrade existing field panels to the current level
of technology via a firmware upgrade and not a complete circuit board replacement.
1.5 Warranty
The manufacturer shall warrant the monitoring panel from defects, including all parts, for a period of
(1) year from the date of shipment.
2.0 PRODUCT
2.1 SNMP/ Web Card
2.1.1
The SNMP/Web Card will consist of:
x
x
1 LAN Port
1 USB Port
x
x
1 1-Wire Input Port (FUTURE USE)
1 COM Port for Supported Equipments
2.1.2
x
The environmental monitoring panel shall have sufficient memory to support:
Historical alarm/event history with a maximum capacity of 10,000 logs
2.1.3
The environmental monitoring panel shall support firmware upgrades without
the need to replace the hardware.
2.1.4
The environmental monitoring panel shall have the capability to communicate
with Liebert Nform® Software and/or SiteMonitor Software.
2.1.5
The environmental monitoring panel shall have a USB port that can be used to
connect to a USB Modem for SMS (OPTIONAL) and can also be used as a
configuration port.
2.1.6
The environmental monitoring panel shall have the ability to provide alarm
notification via WEB GUI, SNMP TRAP, Email alert, and SMS Alert (Optional).
2.2 SNMP/Web card Built-In Web Server
2.2.1
General
x
The web server specified in this section shall be provided as an internal
part of the monitoring panel that is used to configure the panel and
shall work with Microsoft Internet Explorer version 6 and above. If
needed, optional upper level monitoring platform is available.
2.2.2
Web Server Functions
x
x
2.2.3
The web server shall be the main utility for the user to set logic on
different scenarios for alarm notification.
User also has different options for notification
The SNMP/Web card shall be able to execute custom, job-specific processes
defined by the use to perform special routines in lieu of the software description
features defined in 2.2.2.
3.0 POINT SCHEDULE MATRIX
3.1 The service engineer/installer shall collaborate with the owner to determine preference on
installation.
3.2 Optional sensors are available for purchase depending on the set-up that is required by the
client.
3.3 Attached I/O Schedule
4.0 START-UP AND COMMISSIONING
4.1 When installation is complete, configure sensor/equipment and verify remote access before
the module is placed on-line.
INPUT / OUTPUT SUMMARY
ANALOG INPUT
DIGITAL
OUTPUT
ALARM
ALARM
STATUS
TEMPERATURE /
HUMIDITY
TEMPERATURE
AREA, SYSTEM OR
POINT DESCRIPTION
DIGITAL INPUT
EVENT
TRIGGER
ALARM
END DEVICE
OR SENSOR
Yes
RDU-SIC
PROCESS CONTROL
AREA
UPS Monitoring
Cabinet Internal
Temperature
X
Cabinet Internal Humidity
Room Ambient
Temperature / Humidity
X
X
X
Yes
Temperature
Sensor
(02311725)
X
X
Yes
Temperature /
Humidity Sensor
(02311720)
X
X
Yes
Temperature /
Humidity Sensor
(02311720)
PDU
X
*MPS PDU
TELECOM ROOM
UPS Monitoring
Room Temperature
Room Humidity
X
Yes
RDU-SIC
X
X
Yes
Temperature
Sensor
(02311725)
X
X
Yes
Temperature /
Humidity Sensor
(02311720)
Notes: Max COM Port input is 4 (4 Temp/Humid Sensor or 4 PDU Sensor or a combination of both), for part number
see MPS Guide Spec / Brochure
INPUT / OUTPUT SUMMARY
ANALOG INPUT
DIGITAL
OUTPUT
ALARM
ALARM
STATUS
TEMPERATURE /
HUMIDITY
TEMPERATURE
AREA, SYSTEM OR
POINT DESCRIPTION
DIGITAL INPUT
EVENT
TRIGGER
ALARM
END DEVICE
OR SENSOR
Yes
RDU-SIC
Yes
Temperature
Sensor
(02311725)
REMOTE SHELTER
UPS Monitoring
Room Temperature
X
X
PDU
X
X
*MPS PDU
COMPUTER ROOM
UPS Monitoring
Room Temperature
Room Humidity
PDU
X
X
X
X
X
X
Yes
RDU-SIC
Yes
Temperature
Sensor
(02311725)
Yes
Temperature /
Humidity
Sensor
(02311720)
*MPS PDU
Notes: Max COM Port input is 4 (4 Temp/Humid Sensor or 4 PDU Sensor or a combination of both), for part number
see MPS Guide Spec / Brochure
INPUT / OUTPUT SUMMARY
ANALOG INPUT
DIGITAL
OUTPUT
ALARM
ALARM
STATUS
TEMPERATURE /
HUMIDITY
TEMPERATURE
AREA, SYSTEM OR
POINT DESCRIPTION
DIGITAL INPUT
EVENT
TRIGGER
ALARM
END DEVICE
OR SENSOR
Yes
RDU-SIC
Yes
Temperature
Sensor
(02311725)
Yes
Temperature /
Humidity
Sensor
(02311720)
COMMUNICATION
CLOSET / IT RACK
UPS Monitoring
Cabinet Internal
Temperature
Cabinet Internal Humidity
PDU
X
X
X
X
X
X
*MPS PDU
Notes: Max COM Port input is 4 (4 Temp/Humid Sensor or 4 PDU Sensor or a combination of both), for part number
see MPS Guide Spec / Brochure