NetSure 701 Retrofit -48V DC Power Systems Description

advertisement
DC Power for
Business-Critical Continuity™
NetSure™ 701 Retrofit
-48V DC Power Systems
Key Features
Description
nCost effective way to add new
technology and increase
reliability without replacing the
entire system
NetSure™ systems for retrofit applications offer a cost efficient way to upgrade and
expand an existing power system while keeping the present infrastructure (cabinet
and mechanics) intact. Old rectifiers are replaced with new NetSure™ rectifiers,
substantially improving both system power efficiency and reliability. Also included
in this solution is an advanced control unit for site monitoring.
nIncreased system efficiency,
up to 96%
These NetSure™ systems can be installed on live systems with no interruption of
service. Compared to replacing the entire system, this type of upgrade significantly
reduces risk and installation time.
nCan be installed on live systems
nIncreased power in existing
footprint
nHigh efficiency rectifiers with
lower power losses reduce the
site’s cooling needs
nEliminates rectifier legacy
support issues
nEnables connection to remote
monitoring (ENEC, SNMP
and web)
An upgrade of a legacy system using a NetSure™ system increases both reliability
and efficiency. By using Emerson’s high-efficiency eSure™ rectifiers, the upgraded
system can reach 96% system efficiency. In addition to this, Emerson’s advanced
control unit enables supervision, comprehensive monitoring and maintenance with
remote management connectivity.
NetSure™ retrofit systems currently exist for Emerson, Ericsson, Nortel and other
legacy DC power systems. Additionally, we can easily adapt the solution to your
power plant needs.
Application
Designed for existing -48Vdc power plants with requirement for replacement and
expansion of power plant capacity.
nAdvanced control unit enables
use of hybrid energy sources
Controller (ACU+)
Example of an Ericsson system retrofitted with a
NetSure™ 701 DC power solution
R48-3500e
High-Efficiency Rectifier
EN291RF-NSRetrofit / 0712
1
NetSure™ 701 Retrofit
Technical Specifications – System
System Characteristics
Nominal System Voltage
Adjustable Output Voltage Range
Rated Output Capacity
Active Load Sharing
Approvals
Examples of Solutions
Robust, Fenix, Typhoon, etc.
Blue Power
ACTURA Optima 24350
ACTURA Flex 48800
-48V
-42.0 to -58.5 Vdc
Up to 31,5 kW per sub-rack assembly
Yes
CE , EN 60 950-1
BMK 447 902/30
BMK 447 902/31
BMK 447 902/32
BMK 447 902/33
BMK 447 902/25
BMK 447 902/26
14000/xx
BMK 447 9025/9
BMK 447 9025/10
BMK 447 9025/11
Main
Extension
Main
Extension
Main
Extension
Main
Main
Extension
Extension
9,6kW/Cab -48Vdc
9,6kW/Cab -48Vdc
28,8kW/Cab -48Vdc
28,8kW/Cab -48Vdc
28,8kW/Cab -48Vdc
28,8kW/Cab -48Vdc
16kW@48Vdc/3kW@+24Vdc
10,5kW/shelf -48Vdc
10,5kW/shelf -48Vdc
10,5kW/shelf -48Vdc
Technical Specifications – Rectifiers
AC Input
Input Voltage, Nominal
Input Voltage, Permitted Variation
Line Frequency
Max Input Current
Power Factor
THD, Total Harmonic Distortion
200 to 250 Vac
85 to 300 Vac
45 to 65 Hz
18.5 A
0.99
<5% from 50 to 100% of rated load
DC Output
Output Voltage, Adjustment Range
Output Power
Output Current
Output Current Limit Set Point
Efficiency
Psophometric Noise (system)
-42 to –58Vdc
3500 W @ Vout >48Vdc
73 A
0 to 73 A
96.7%
<2mV typical; <32 dBrnc typical
Environmental
Temperature Range, Operating
Temperature Range, Storage
Relative Humidity
Altitude
EMC
Safety
-40 to +75°C, -40 to +167°F
-40 to +75°C, -40 to +167°F
0 to 95%
2000 m (6560 ft.) at full power
EN 300 386:2001 class B, FCC part 15 class B
IEC 60950, EN 60950, UL 60950
Mechanics
Dimensions (H x W x D)
Weight
Emerson Network Power.
The global leader in enabling Business-Critical Continuity™.
132 x 85.3 x 287 mm (5.20 x 3.36 x 11.3 inches)
3,1 kg (6,8 lbs)
For further details, see separate rectifier datasheet.
Ordering Information
Part Number
BML 440 066/1
BML 440 062/1
Actura Flex 48800
Model Number
R48-3500e
R48-3200
Description
High efficiency rectifier (eSure™)
Standard rectifier
Controller
Description
Menu operated and user friendly control of rectifiers and batteries
Prepared for remote site monitoring through GSM, PSTN, ISDN,TCP/IP
Temperature compensated battery charging
Remote monitoring Low voltage disconnection (LVD)
Advanced alarm management and alarms history
Advanced battery management
Web & SNMP functions
Configurable relays for control of external units
For further details, see separate controller datasheet.
nAC Power
nConnectivity
nDC Power
nEmbedded Computing
nEmbedded Power
nIndustrial Power
nInfrastructure Management & Monitoring
nOutside Plant
nPower Switching & Controls
nPrecision Cooling
nRacks & Integrated Cabinets
nServices
Business-Critical Continuity™, Emerson Network Power™,
the Emerson Network Power logo, Emerson® and Consider it
Solved are service marks and trademarks of Emerson Electric Co.
EnergyMaster ™, eSure™, NetPerform™, NetReach™, NetSpan™,
NetSure® and NetXtend™ are trademarks of Emerson Network
Power Energy Systems North America.
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2012.
2
EN291RF-NSRetrofit / 0712
Download