Liebert® IntelliSlot Unity Card Version 4.2.0.0_89131 Firmware Release Notes

advertisement
Liebert® IntelliSlotTM Unity Card
Version 4.2.0.0_89131 Firmware
Release Notes
November 26th, 2014
This document outlines:
1. Version and Compatibility Information
2. What‟s New
3. Upgrade Instructions
4. Known Issues
===================================================================================
1. Version and Compatibility
===================================================================================
This release contains the following firmware version:
IS-UNITY_4.2.0.0_89131
This release is compatible with the following Liebert IntelliSlot communication cards:
IS-UNITY-DP
IS-UNITY-LIFE
This release is compatible with the following Liebert power and thermal management equipment:
Liebert APM™
Liebert HPC-S,M,R,W,Generic
Liebert APS™
Liebert HPM™
Liebert CRV™
Liebert NXC™
Liebert CW™*
Liebert NXL™
Liebert Challenger™*
Liebert NXR™
Liebert Deluxe System/3™*
Liebert PCW™
Liebert DCP™
Liebert PDX™
Liebert DS™*
Liebert PeX™*
Liebert DSE™
Liebert XDC™ with iCOMTM Control
Liebert eXL™
Liebert XDP™ with iCOMTM Control
Liebert HPC™
Liebert XDP-Cray
*iCOM Firmware PA1.04.033.STD versions or later
1
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Em erson Electric Co.
©2014 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered tr ademarks or trademarks of
Mozilla Found ation Corporation . Safari, MacBook, and iPad ar e r egist ered trademar ks of Apple, Inc. All other tr ademar ks, brand nam es, and service m arks are
the property of their respective owners.
This release supports the following communication interfaces:
Communication Protocol
Communication HTTP/ Em erson
Card
HTTPS Protocol
Remote Serv ice
Deliv ery Protocol
IS-UNITY-DP



IS-UNITY-LIFE



Third-Party Protocols
Em ail
SMS
SNMP
v1,v2c,v3
BACnet
IP/MSTP
Modbus
TCP/RTU

-

-

-

-

-
YDN23
NXL &
PeX Only
-
This release supports the following browsers:
o
Microsoft Internet Explorer® - IE9, IE10, and IE11
o
Mozilla Firefox® - ver. 28.0 or later
o
Google ChromeTM - ver. 34.0.1847.116 m or later
o
Safari® (MacBook ®) - ver. 6.1.1
o
Safari® (iPad®) - ver. 7.1
===================================================================================
2. What’s New
===================================================================================
This release contains the following enhancements:

Support for the Liebert ® eXL UPS has been added.

Embedded LIFE TM Technology support for all iCOM V4 Thermal Management equipment has been
completed, to improve Remote Service Delivery support.

Images for various Thermal Management devices have been updated for their home w ebpages.
This release contains fixes for the following issues:
Component
Web Interface
Modbus
SNMP
Embedded
LIFETM
technology
IP Networking &
Communication
Description
Shellshock vulnerability patches for the bash shell have been applied.
Certain bezel w eb pages w ould sometimes trigger Javascript errors w hen displaying
“unavailable” parametric data values from an APM, NXR, or APS device. This w ill no
longer trigger the Javascript error messages.
Some thermal management units added enumerated values to some existing status
register data points. These needed to be changed from status register values to input
register values to accommodate the 5 possible enumerated values they can have.
APS & APM Scaling issues for output pow er and KVA w ere incorrectly reported in w atts
and VA respectively. These points now report properly in KW and kVA.
Corrections to some pow er measurements w ere made to improve the efficiency of the
analysis of UPS data.
Enhancements have been made to allow better behavior of the IP Netw orking features
w hen connected to an isolated netw ork that does not have a gatew ay.
2
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Em erson Electric Co.
©2014 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered tr ademarks or trademarks of
Mozilla Found ation Corporation . Safari, MacBook, and iPad ar e r egist ered trademar ks of Apple, Inc. All other tr ademar ks, brand nam es, and service m arks are
the property of their respective owners.
===================================================================================
3. Update Instructions
===================================================================================
The Unity cards may be updated to this firmware version using the web-based Firmware Upload feature.
Please refer to the Firmware Updates section of the Liebert IntelliSlot Unity Card User Manual (SL-52645).
===================================================================================
4. Known Issues
===================================================================================
Component
Description
Device Settings
When temperature settings are made on some thermal devices, there may be
some „round-off‟ error of one tenth of a degree between what was requested and
what the device shows after the change. This is a known limitation of some
thermal device firmware versions and will be corrected in future versions of the
device controller firmware.
When selecting the Reset Event(s) buttons on the Summary webpage for some
devices, the user will be guided through an extra login and confirmation
sequence before the Reset request is successful.
There are some minor data point mapping errors for PeX and NXL equipment
which will be corrected in the next maintenance release.
Events
YDN23
3
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Em erson Electric Co.
©2014 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered tr ademarks or trademarks of
Mozilla Found ation Corporation . Safari, MacBook, and iPad ar e r egist ered trademar ks of Apple, Inc. All other tr ademar ks, brand nam es, and service m arks are
the property of their respective owners.