SPECIFICATION for ASCO PULSAR™ SERIES 451 SURGE PROTECTIVE DEVICES with NOISE FILTERING PART 1 GENERAL 1.1 Summary This specification describes the electrical and mechanical requirements for a high energy surge protective device (SPD) system with electrical line noise filtering. The specified system shall be connected in parallel with the facility's wiring system, shall provide effective high energy surge current diversion and high-frequency attenuation, and shall be suitable for application in ANSI/IEEE C62.41 Category A, B and C3 environments, as tested by ANSI/IEEE C62.11, C62.45. 1.2 Standards The specified system shall be designed, manufactured, tested and installed in compliance with the following codes and standards: A. American National Standards Institute and Institute of Electrical and Electronic Engineers (ANSI/IEEE C62.11. C62.41. C62.45) B. Canadian Standards Association (CSA) C. Federal Information Processing Standards Publication 94 (FIBS PUB 94) D. National Electrical Manufacturer Association (NEMA LS-1 1992) E. National Fire Protection Association (NFPA 20, 70 [National Electrical Code], 75 and 780) F. Underwriters Laboratories (UL 1449 2nd Ed. 2007 Rev. and UL 1283) G. International Electrotechnical Commission (IEC 801 -> IEC 1000) H. International Standards Organization (ISO) Company certified ISO 9001 for manufacturing, design and service I. MIL-STD-220A Page 1 of 7 ASCO Power Technologies, LP 10-2006 Florham Park, NJ 07932 Telephone: (800) 800 ASCO Pub 3200 The systems individual units shall be UL Listed and labeled under UL 1449 2nd Edition 2007 Revision, Standard for Transient Voltage Surge Suppressors and the surge ratings shall be permanently affixed to the SPD. The units shall also be listed to UL1283, Standard for Electromagnetic Interference Filters, and CSA Listed. 1.3 Electrical Requirements (Selection Required) A. Nominal system operating voltage shall be indicated as: ___ VAC, ______ Configuration: ___ Phase ____, ___ Wire Plus Ground B. Maximum Continuous Operating Voltage (MCOV): The Maximum Continuous Operating Voltage of the complete SPD, as well as all components in the suppression path shall be greater than 115% of the nominal system operating voltage to ensure the ability of the system to withstand temporary RMS overvoltage (swell conditions). C. Operating Frequency: The operating frequency range of the system shall be at least 47-63 Hz. D. Protection Modes: The SPD shall provide protection in all modes (L-N or L-L, L-G and N-G where applicable) Note: L = Line, G = Ground, N = Neutral E. UL 1449 Performance Ratings: The maximum UL 1449 listed surge ratings for each and/or all of the specified protection modes shall not exceed the following in any mode: System Voltage 120/208 or 120/240 208, 240, 277, 230/400, or 277/480 346, or 346/600 480 600 Rating Without Disconnect 400 Volts 800 Volts 1200 Volts 1500 Volts 2000 Volts Rating With Disconnect 800 Volts 1000 Volts 1500 Volts 1500 Volts 2000 Volts F. Noise Attenuation: The unit shall be UL 1283 Listed as an electromagnetic interference filter. The filter shall provide insertion loss with a maximum of 60 dB from 100 kHz to 100 MHz with data obtained utilizing the 50 ohm Insertion Loss Methodology from MIL-STD-220A. Page 2 of 7 ASCO Power Technologies, LP 10-2006 Florham Park, NJ 07932 Telephone: (800) 800 ASCO Pub 3200 G. Surge Current Capacity: The minimum SPD surge current capacity, per NEMA LS-1 1992 shall be as follows: Model 100 200 300 400 Surge Rating Per Mode 50 kA 100 kA 150 kA 200 kA Surge Rating Per Phase (L-N + L-G) 100 kA 200 kA 300 kA 400 kA H. Response Time: The typical response time of all suppression components shall be 0.5 ns. I. Joule Rating: The SP system shall provide a joule rating that meets or exceeds the requirements of ANSI/IEEE C62.41 Category C delivery capability. 1.4 Environmental Requirements A. Storage Temperature: -55 to +85° C (-67° to +187° F) B. Operating Temperature: -40° to +60° C (-40° to +140° F) C. Relative Humidity: 0% to 95% D. Audible Noise: Less than 45 dBa at 5 feet (1.5 m) E. Operating Altitude: 0 to 18,000 feet above sea level. F. Magnetic Fields: The unit shall not generate any appreciable magnetic fields, and shall be suitable for use directly inside computer rooms. PART 2 PRODUCT 2.1 System Description The system shall be constructed using multiple surge protection modules utilizing metal oxide varistors (MOVs) which have been tested and matched to assure surge current sharing. Use of other surge protective devices such as gas tubes, silicon avalanche diodes, or selenium cells are unacceptable since the failure of such devices could cause interruption of normal power to connected loads. Page 3 of 7 ASCO Power Technologies, LP 10-2006 Florham Park, NJ 07932 Telephone: (800) 800 ASCO Pub 3200 2.2 Enclosure The specified system shall be provided in a Type 12 enclosure with no ventilation openings. The cover of the enclosure shall be hinged on the left side and require a tool for access to internal components. Status monitoring for the unit must be visible without opening the door. The enclosure maximum dimensions shall be 30" high, 24" wide and 9" deep. 2.3 Connections Terminals shall be provided to accommodate wire sizes up to #4 AWG for units with surge current ratings up to 200 kA. Units over 200 kA shall be provided with terminals capable of accommodating wire size up to 1/0 AWG. 2.4 Internal Connections and Serviceability All internal unit connections for components in the suppression path shall be by way of low impedance copper plates. Surge current diversion modules shall use bolted connections to the plates to assure low impedance connections. The system shall be designed for simple change out of any or all SPD component modules by a qualified electrician. Designs that require factory service are not acceptable. 2.5 Performance A. Life Expectancy Testing: The unit shall be duty life cycle tested to survive repetitive 20 kV, 10 kA, IEEE C62.41 Category C3 surges. The minimum number of surges the unit must survive without failing or degrading the clamping voltage by more than 5% is as per the following table: Model 100 200 300 400 L-N 1.250 2,500 3,750 5,000 Number Of Life Cycle Surges Per Mode L-G N-G 1,250 1,250 2,500 2,500 3,750 3,750 5,000 5,000 Per Phase (L-N + L-G) 2,500 5,000 7,500 10,000 B. Overcurrent Protection (fusing): All components, including suppression, filtering, and monitoring components, shall be individually fused at the component level with the fuses rated so as not to impede maximum specified surge current capacity. The fuse shall be capable of opening in less than one millisecond and clear both high and low impedance faults. The fusing shall be capable of interrupting up to 200 kA symmetrical fault current with 600 VAC applied. Replaceable fusing is unacceptable. Overcurrent protection that limits specified surge currents is not acceptable. Page 4 of 7 ASCO Power Technologies, LP 10-2006 Florham Park, NJ 07932 Telephone: (800) 800 ASCO Pub 3200 2.6 Accessories A. Unit Status Indicators (Standard on all units) Red and green solid state indicators with printed labels shall be provided on the hinged front cover to indicate on-line unit. status of all modes of protection, including Neutral to Ground where applicable. B. Dry Contacts for remote monitoring (Standard on all units) Two sets of electrically isolated Form C dry contacts, one normally open and one normally closed for remote monitoring. C. Undervoltage detection (Standard on all units) Unit shall be equipped with 70% undervoltage detection capability. D. Phase Loss Monitoring (Standard on all units) Unit shall be equipped with phase loss monitoring. E. Power Loss Monitoring (Standard on all units) Unit shall be equipped with power loss monitoring. F. Audible Alarm (optional) The unit shall be equipped with an audible alarm that will activate when dry contacts are activated. The alarm shall be provided with an on/off switch to silence the alarm and an alarm push-to-test switch to test for proper alarm functioning. An LED will confirm whether alarm is on or disabled. Both switches, the LED, and the audible alarm shall be located on the unit's hinged front cover. G. Transient Counter (optional) A transient counter with adjustable sensitivity shall be available to totalize transient voltage surges in the common mode. The readout shall be at least a seven digit LCD display located on the unit's hinged front cover. The counter reset switches must be provided with a tamper-proof means for disabling to prevent unintentional reset. H. Integral Fused Disconnect Switch (optional) The specified system shall include a 200 KAIC integral fused disconnect switch located in-line with the SPD system enclosure with an external manual operator. The switch shall disconnect all ungrounded circuit conductors from the high energy surge current diversion modules. The switch shall be rated as follows: Model series 100 and 200: 40 amps; Model series 300: 80 amps; Model series 400: 100 amps. Page 5 of 7 ASCO Power Technologies, LP 10-2006 Florham Park, NJ 07932 Telephone: (800) 800 ASCO Pub 3200 2.7 Testing A. Component Testing and Monitoring: Unit shall include an on-line circuit which tests and redundantly monitors individual components in all protection modes including neutral to ground (where applicable). Units that require external test sets or equipment are unacceptable. B. External Test Capability: External testing demonstrating surge suppression capability and/or degradation shall be available. PART 3 DOCUMENTATION 3.1 Documentation These specifications are based on other manufacturers shall submit compliance or exception statements allow consideration. In addition, accompany any submittal. ASCO Series 451 SPD products. All for 10 day pre-approval, detailed to all provisions of this specification to the following documentation must A. Independent Test Data: Manufacturers shall submit independent test data from a nationally recognized testing laboratory verifying the following: life cycle testing, overcurrent protection, UL1449 2nd Edition 2007 Revision ratings, noise attenuation, and surge current capacity. B. Equipment Manual: The manufacturer shall furnish an installation manual with installation, start-up, spare parts lists, and operating instructions for the specified system. C. Drawings: Electrical and mechanical drawings shall be provided by the manufacturer that show unit dimensions, weights, component, and connection locations, mounting provisions, connection details, and wiring diagram. Failure to provide any of the documentation required by this section will result in product disapproval. Any deviation from the published specification will result in an applicable deduct applied. Page 6 of 7 ASCO Power Technologies, LP 10-2006 Florham Park, NJ 07932 Telephone: (800) 800 ASCO Pub 3200 PART 4 MANUFACTURER CERTIFICATIONS and PRODUCT WARRANTIES 4.1 Quality Assurance The manufacturer shall be ISO 9001 certified. The specified system shall be tested at the component and fully assembled level. Testing shall include but not be limited to quality control checks, dielectric voltage withstand test per UL and CSA requirements, UL ground continuity tests, and operational and calibration tests. 4.2 Warranty The manufacturer shall provide a full five year parts and labor warranty from date of shipment against any part failure when installed in compliance with manufacturer's written instructions, UL Listing requirements, and any applicable national, state or local electrical codes. A 24 hour 800 number must be available to support warranty. PART 5 EXECUTION 5.1 Installation The installing contractor shall install the parallel SPD with short and straight conductors as practically possible. The contractor shall twist the SPD input conductors together to reduce input conductor inductance. The contractor shall follow the SPD manufacturer's recommended installation practices as found in the installation, operation and maintenance manual and comply with all applicable codes. Page 7 of 7 ASCO Power Technologies, LP 10-2006 Florham Park, NJ 07932 Telephone: (800) 800 ASCO Pub 3200