SPECIFICATION for ASCO PULSAR™ SERIES 451 SURGE PROTECTIVE DEVICES

advertisement
SPECIFICATION
for
ASCO PULSAR™ SERIES 451
SURGE PROTECTIVE DEVICES
with NOISE FILTERING
PART 1 GENERAL
1.1
Summary
This specification describes the electrical and mechanical requirements for
a high energy surge protective device (SPD) system with electrical line noise
filtering. The specified system shall be connected in parallel with the facility's
wiring system, shall provide effective high energy surge current diversion
and high-frequency attenuation, and shall be suitable for application in
ANSI/IEEE C62.41 Category A, B and C3 environments, as tested by
ANSI/IEEE C62.11, C62.45.
1.2
Standards
The specified system shall be designed, manufactured, tested and installed
in compliance with the following codes and standards:
A. American National Standards Institute and Institute of Electrical and
Electronic Engineers (ANSI/IEEE C62.11. C62.41. C62.45)
B. Canadian Standards Association (CSA)
C. Federal Information Processing Standards Publication 94 (FIBS PUB 94)
D. National Electrical Manufacturer Association (NEMA LS-1 1992)
E. National Fire Protection Association (NFPA 20, 70 [National Electrical
Code], 75 and 780)
F. Underwriters Laboratories (UL 1449 2nd Ed. 2007 Rev. and UL 1283)
G. International Electrotechnical Commission (IEC 801 -> IEC 1000)
H. International Standards Organization (ISO) Company certified ISO
9001 for manufacturing, design and service
I. MIL-STD-220A
Page 1 of 7
ASCO Power Technologies, LP
10-2006
Florham Park, NJ 07932 Telephone: (800) 800 ASCO
Pub 3200
The systems individual units shall be UL Listed and labeled under UL 1449 2nd
Edition 2007 Revision, Standard for Transient Voltage Surge Suppressors and the
surge ratings shall be permanently affixed to the SPD. The units shall also be listed
to UL1283, Standard for Electromagnetic Interference Filters, and CSA Listed.
1.3 Electrical Requirements (Selection Required)
A. Nominal system operating voltage shall be indicated as:
___ VAC, ______ Configuration: ___ Phase ____, ___ Wire Plus Ground
B. Maximum Continuous Operating Voltage (MCOV):
The Maximum Continuous Operating Voltage of the complete SPD, as well
as all components in the suppression path shall be greater than 115% of
the nominal system operating voltage to ensure the ability of the system to
withstand temporary RMS overvoltage (swell conditions).
C. Operating Frequency:
The operating frequency range of the system shall be at least 47-63 Hz.
D. Protection Modes:
The SPD shall provide protection in all modes (L-N or L-L, L-G and N-G
where applicable)
Note: L = Line, G = Ground, N = Neutral
E. UL 1449 Performance Ratings:
The maximum UL 1449 listed surge ratings for each and/or all of the
specified protection modes shall not exceed the following in any mode:
System Voltage
120/208 or 120/240
208, 240, 277, 230/400, or 277/480
346, or 346/600
480
600
Rating Without
Disconnect
400 Volts
800 Volts
1200 Volts
1500 Volts
2000 Volts
Rating With
Disconnect
800 Volts
1000 Volts
1500 Volts
1500 Volts
2000 Volts
F. Noise Attenuation:
The unit shall be UL 1283 Listed as an electromagnetic interference filter.
The filter shall provide insertion loss with a maximum of 60 dB from 100 kHz
to 100 MHz with data obtained utilizing the 50 ohm Insertion Loss
Methodology from MIL-STD-220A.
Page 2 of 7
ASCO Power Technologies, LP
10-2006
Florham Park, NJ 07932 Telephone: (800) 800 ASCO
Pub 3200
G. Surge Current Capacity:
The minimum SPD surge current capacity, per NEMA LS-1 1992 shall be
as follows:
Model
100
200
300
400
Surge Rating
Per Mode
50 kA
100 kA
150 kA
200 kA
Surge Rating Per Phase
(L-N + L-G)
100 kA
200 kA
300 kA
400 kA
H. Response Time:
The typical response time of all suppression components shall be 0.5 ns.
I. Joule Rating:
The SP system shall provide a joule rating that meets or exceeds the
requirements of ANSI/IEEE C62.41 Category C delivery capability.
1.4 Environmental Requirements
A. Storage Temperature:
-55 to +85° C (-67° to +187° F)
B. Operating Temperature:
-40° to +60° C (-40° to +140° F)
C. Relative Humidity:
0% to 95%
D. Audible Noise:
Less than 45 dBa at 5 feet (1.5 m)
E. Operating Altitude:
0 to 18,000 feet above sea level.
F. Magnetic Fields:
The unit shall not generate any appreciable
magnetic fields, and shall be suitable for
use directly inside computer rooms.
PART 2 PRODUCT
2.1
System Description
The system shall be constructed using multiple surge protection modules
utilizing metal oxide varistors (MOVs) which have been tested and matched
to assure surge current sharing. Use of other surge protective devices such
as gas tubes, silicon avalanche diodes, or selenium cells are unacceptable
since the failure of such devices could cause interruption of normal power to
connected loads.
Page 3 of 7
ASCO Power Technologies, LP
10-2006
Florham Park, NJ 07932 Telephone: (800) 800 ASCO
Pub 3200
2.2
Enclosure
The specified system shall be provided in a Type 12 enclosure with no
ventilation openings. The cover of the enclosure shall be hinged on the left
side and require a tool for access to internal components. Status monitoring
for the unit must be visible without opening the door. The enclosure
maximum dimensions shall be 30" high, 24" wide and 9" deep.
2.3
Connections
Terminals shall be provided to accommodate wire sizes up to #4 AWG for
units with surge current ratings up to 200 kA. Units over 200 kA shall be
provided with terminals capable of accommodating wire size up to 1/0 AWG.
2.4
Internal Connections and Serviceability
All internal unit connections for components in the suppression path shall be
by way of low impedance copper plates. Surge current diversion modules
shall use bolted connections to the plates to assure low impedance
connections. The system shall be designed for simple change out of any or
all SPD component modules by a qualified electrician. Designs that require
factory service are not acceptable.
2.5
Performance
A. Life Expectancy Testing:
The unit shall be duty life cycle tested to survive repetitive 20 kV, 10 kA,
IEEE C62.41 Category C3 surges. The minimum number of surges the
unit must survive without failing or degrading the clamping voltage by
more than 5% is as per the following table:
Model
100
200
300
400
L-N
1.250
2,500
3,750
5,000
Number Of Life Cycle Surges
Per Mode
L-G
N-G
1,250
1,250
2,500
2,500
3,750
3,750
5,000
5,000
Per Phase
(L-N + L-G)
2,500
5,000
7,500
10,000
B. Overcurrent Protection (fusing):
All components, including suppression, filtering, and monitoring
components, shall be individually fused at the component level with the
fuses rated so as not to impede maximum specified surge current
capacity. The fuse shall be capable of opening in less than one
millisecond and clear both high and low impedance faults. The fusing
shall be capable of interrupting up to 200 kA symmetrical fault current
with 600 VAC applied. Replaceable fusing is unacceptable. Overcurrent
protection that limits specified surge currents is not acceptable.
Page 4 of 7
ASCO Power Technologies, LP
10-2006
Florham Park, NJ 07932 Telephone: (800) 800 ASCO
Pub 3200
2.6
Accessories
A. Unit Status Indicators (Standard on all units)
Red and green solid state indicators with printed labels shall be provided
on the hinged front cover to indicate on-line unit. status of all modes of
protection, including Neutral to Ground where applicable.
B. Dry Contacts for remote monitoring (Standard on all units)
Two sets of electrically isolated Form C dry contacts, one normally open
and one normally closed for remote monitoring.
C. Undervoltage detection (Standard on all units)
Unit shall be equipped with 70% undervoltage detection capability.
D. Phase Loss Monitoring (Standard on all units)
Unit shall be equipped with phase loss monitoring.
E. Power Loss Monitoring (Standard on all units)
Unit shall be equipped with power loss monitoring.
F. Audible Alarm (optional)
The unit shall be equipped with an audible alarm that will activate when
dry contacts are activated. The alarm shall be provided with an on/off
switch to silence the alarm and an alarm push-to-test switch to test for
proper alarm functioning. An LED will confirm whether alarm is on or
disabled. Both switches, the LED, and the audible alarm shall be located
on the unit's hinged front cover.
G. Transient Counter (optional)
A transient counter with adjustable sensitivity shall be available to totalize
transient voltage surges in the common mode. The readout shall be at
least a seven digit LCD display located on the unit's hinged front cover.
The counter reset switches must be provided with a tamper-proof means
for disabling to prevent unintentional reset.
H. Integral Fused Disconnect Switch (optional)
The specified system shall include a 200 KAIC integral fused disconnect
switch located in-line with the SPD system enclosure with an external
manual operator. The switch shall disconnect all ungrounded circuit
conductors from the high energy surge current diversion modules. The
switch shall be rated as follows: Model series 100 and 200: 40 amps;
Model series 300: 80 amps; Model series 400: 100 amps.
Page 5 of 7
ASCO Power Technologies, LP
10-2006
Florham Park, NJ 07932 Telephone: (800) 800 ASCO
Pub 3200
2.7 Testing
A. Component Testing and Monitoring:
Unit shall include an on-line circuit which tests and redundantly monitors
individual components in all protection modes including neutral to ground
(where applicable). Units that require external test sets or equipment are
unacceptable.
B. External Test Capability:
External testing demonstrating surge suppression capability and/or
degradation shall be available.
PART 3 DOCUMENTATION
3.1
Documentation
These specifications are based on
other manufacturers shall submit
compliance or exception statements
allow consideration. In addition,
accompany any submittal.
ASCO Series 451 SPD products. All
for 10 day pre-approval, detailed
to all provisions of this specification to
the following documentation must
A. Independent Test Data:
Manufacturers shall submit independent test data from a nationally
recognized testing laboratory verifying the following: life cycle testing,
overcurrent protection, UL1449 2nd Edition 2007 Revision ratings, noise
attenuation, and surge current capacity.
B. Equipment Manual:
The manufacturer shall furnish an installation manual with installation,
start-up, spare parts lists, and operating instructions for the specified
system.
C. Drawings:
Electrical and mechanical drawings shall be provided by the
manufacturer that show unit dimensions, weights, component, and
connection locations, mounting provisions, connection details, and wiring
diagram.
Failure to provide any of the documentation required by this section will
result in product disapproval. Any deviation from the published
specification will result in an applicable deduct applied.
Page 6 of 7
ASCO Power Technologies, LP
10-2006
Florham Park, NJ 07932 Telephone: (800) 800 ASCO
Pub 3200
PART 4 MANUFACTURER CERTIFICATIONS and PRODUCT WARRANTIES
4.1
Quality Assurance
The manufacturer shall be ISO 9001 certified. The specified system shall be
tested at the component and fully assembled level. Testing shall include but
not be limited to quality control checks, dielectric voltage withstand test per
UL and CSA requirements, UL ground continuity tests, and operational and
calibration tests.
4.2
Warranty
The manufacturer shall provide a full five year parts and labor warranty from
date of shipment against any part failure when installed in compliance with
manufacturer's written instructions, UL Listing requirements, and any
applicable national, state or local electrical codes. A 24 hour 800 number
must be available to support warranty.
PART 5 EXECUTION
5.1
Installation
The installing contractor shall install the parallel SPD with short and straight
conductors as practically possible. The contractor shall twist the SPD input
conductors together to reduce input conductor inductance. The contractor
shall follow the SPD manufacturer's recommended installation practices as
found in the installation, operation and maintenance manual and comply
with all applicable codes.
Page 7 of 7
ASCO Power Technologies, LP
10-2006
Florham Park, NJ 07932 Telephone: (800) 800 ASCO
Pub 3200