Intelligent static transfer switches - Insta switch, Mega switch - Ensures maximum reliability to critical
loads by eliminating system failures that are caused by power distribution problems.
INTRODUCTION
The INSTA & MEGA switches allows instantaneous
transfer of load between two power sources. It can be
used to ensure complete redundancy of power supply
upto the last piece of wire. It is useful in many applications,
where redundant power supply is available, either from
two UPS systems or one UPS and bypass source.
These switches are comprising of semiconductor
switches, they ensure continuity of power to the load in the
event of failure of one of the power sources. They have
different user selectable parameters and in-built
microprocessor. Typical applications include Data
centers, Call centers, Process control and Automation
etc.
FEATURES
Uses Power Semiconductors as Switching Element
Independent Micro-controller
Simple & Rugged design
Exceptional Performance
User friendly display & Control
BMS connectivity through MODBUS
for status monitoring
Ethernet Connectivity
Core Competence in Power Electronics
SPECIFICATIONS
ISW R21
Model
ISW R32
1 Pole (Ph)
No. of Switching Poles
2 Pole (Ph + N)
16 A
Nominal Output Current
32 A
16 A
32 A
63 A
Nominal Voltage
220 / 230 / 240 V, 1 Phase (110 / 230 V optional)
Voltage Tolerance
Low band : – 15% to +10% (Default), Medium band : – 10% to +10%, Narrow Band : – 5% to 10%
50 / 60 Hz, Normal band : 48 - 52 Hz, Wide band : 40 - 70 Hz (Default)
Nominal Frequency
Efficiency(1)
> 98 %
> 97 %
125 % for 10 min. 150% for 1 min. 1000% for 100 msec
Overload Capacity
Continuous
Duty
Input Under Voltage, Input Over Voltage, Output Overload, Output Short Circuit
Protections
< 5 ms for Sync. condition
Transfer / Re-transfer Time
< 5 ms / < 15 ms (selectable) for No Sync. Condition
Manual Bypass facility
Provided
Acoustic Noise Level(2)
< 45 dBA
Operating Temperature
0 to 40 C
0
up to 95 % (Non-condensing)
Relative Humidity
< 1000 meter, above sea level (without de-rating)
Altitude
IEC 62310-3
Testing standard
IP 20
Enclosure Protection
Natural Cooling
Cooling
422 x 385 x 85
440 x 450 x 132
19" Rack mountable, 2U Height
19" Rack mountable, 3U Height
Dimension (in mm)
WxDxH
12 kg
Weight (Approx)
12 kg
15 kg
15 kg
15 kg
Rear Side
Cable Entry
Source 1 Healthy
Source 2 Healthy
Sensitivity Low
Sensitivity Medium
Sensitivity High
Load on Manual Bypass - Source 1
LED Indications
Communication Interface
(optional)
Source 1 Feeding
Source 2 Feeding
No Sync
Overload
Source 1 Priority
Source 2 Priority
(3)
Source 1 Fuse Fail
(3)
Source 2 Fuse Fail
Load on Manual Bypass - Source 2
Load on Static Switch
RS 485 MODBUS, Ethernet Connectivity(3), PFCs
(1) For tolerance see IEC 60146-1-1 (2) Acoustic Noise measured @ 1.0 meter as per ISO 3746 (3) Applicable for ISW R32 model
FRONT VIEW (2U size)
FRONT VIEW (3U size)
LOAD ON
MANUAL BYPASS SWITCH
RS232
Low
Source1 Source2
Healthy
Medium
High
Sensitivity
Priority
No Sync
Feeding
Overload
Manual
Retransfer
1
2
3
4
5
6
7
8
SOURCES
S1 STSW S2
SW 1
Off
On
1
Source
2
SENSITIVITY SW
LOW MEDIUM HIGH OFF
SOURCE 1- FUSE FAIL
HEALTHY
1
PRIORITY
NO SYNC
SOURCE2- FUSE FAIL
FEEDING
0
OVERLOAD MANUAL
RETRANSFER
ON
1
2
3
4
5
6
7
8
INSTA
MON
0
2
PFC
INSTA SWITCH 3000
1
SW2
ETHERNET SLOT
(OPTIONAL)
2
MANUAL BYPASS SWITCH
REAR VIEW (2U size)
INPUT TB
PFC CONNECTOR
F1
REAR VIEW (3U size)
#
#
XM3
XM2
N.PLATE
F2
X3
XM1
N O/P
XM15
P N E P N P N
XM1
OUTPUT SOCKET
INPUT 1
S1 S2
P
N
E
P
N
N
P
#
Source 1 Phase
Source 1 Neutral
Earth
Source 2 Phase
Inter connection
INPUT 2
Source 2 Neutral
Connector
OUTPUT NEUTRAL
OUTPUT PHASE
#
n 16 A ISW : 3 sockets of 5 Amp
Output Socket (optional)
n
32 A ISW : 6 sockets of 5 Amp (As per IEC 320-C13)
Output
Source 1 Input
Source 2 Input
SPECIFICATIONS
MSW 1100
Model
MSW 360 /
MSW 3100
MSW 3200
MSW 3300
MSW 3400
MSW 360 N /
MSW 3100 N
MSW 3200 N
1 Phase
3 Phase
3 Phase
No. of Switching Poles
1 Pole (Ph)
3 Pole (Ph)
4 Pole (Ph+N)
Nominal Output Current
100 A
Input / Output
60 / 100 A
200 A
300 A
400 A
60 / 100 A
MSW 3300 N
200 A
300 A
Nominal Voltage
MSW 1100 : 220 / 230 / 240 V, 1 Phase (110 / 230 V optional)
Voltage Tolerance
MSW 1100 : Low band : – 15% to +10% (Default), Medium band : – 10% to +10%, Narrow Band : – 5% to +10%
MSW 3xxx : 400 / 415 V (3 Ph + N )
MSW 3xxx : Low band : – 30% to +15% (Default), Medium band : – 25% to +15%, Narrow Band : – 15% to +15%
Normal : 48 - 52 Hz , Wide 40 - 70 Hz (Default)
Nominal Frequency
Efficiency(1)
> 98 %
MSW 1100 : 125 % for 10 min. 150% for 1 min 1000% for 100 ms
Overload Capacity
MSW 3xxx : 110 % for 1 hour, 150 % for 1 min, 1000 % for 100 ms
Continuous
Duty
Input Under Voltage, Input Over Voltage, Output Overload, Output Short Circuit
Protections
MSW 1100 : < 5 ms for sync condition & < 5 ms / < 15 ms (selectable) for No sync. condition
MSW 3xxx : Low Sensitivity : < 8 ms, Medium Sensitivity : < 5 ms (Default), High Sensitivity : < 3 ms
Transfer /
Retransfer Time
Manual Bypass facility
Provided
(2)
< 45 dBA
Acoustic Noise Level
0 to 400 C
Operating Temperature
up to 90 % (Non-condensing)
Relative Humidity
< 1000 meter, above sea level (without de-rating)
Altitude
IEC 62310 - 3
Testing Standard
IP 20
Enclosure Protection
Forced Cooling
Cooling
Dimension (in mm) - Width
800
800
800
1000
1000
800
800
- Depth
600
600
600
600
600
600
600
600
- Height
1750
1750
1750
1950
1950
1750
1750
1950
225
225
225
275
350
225
225
275
Weight in kg (approx)
1000
RAL 7035
Color
Bottom
Cable Entry
LED Indications
Source 1 Healthy
Source 1 Feeding
Source 1 Priority
Source 2 Healthy
Source 2 Feeding
Source 2 Priority
Sensitivity Low
Sensitivity Medium
Sensitivity High
SPP, Overload
Fault Indications
RS 485 MODBUS
Ethernet connectivity (Applicable for MSW 1100)
Communication Interface
(optional)
(1) For tolerance see IEC 60146-1-1 (2) Acoustic Noise measured @ 1.0 meter as per ISO 3746
MSW
3300
H
Front Facia with Sensitivity Control
150
W
FRONT VIEW
D
SIDE VIEW
FEATURES
Uses Power Semiconductors as Switching Element
It acts like protective barrier to the load. When power supply
feeding to the load goes beyond the preset limits (Frequency
or voltage) the switch instantly disconnects from load and
protects it.
Independent Micro-controller
Makes it independent of source functioning and its control
scheme. The smart control enables user to select the
priority of source.
Simple & Rugged design
Low component count, giving high level of reliability.
User friendly display & Control
Display provides status of incoming power source and the
condition of static switch.
Exceptional Performance
It is tailored to suit the requirements of different operating
conditions. It tracks the Input Voltage, Phase & Frequency,
Distortion levels at the terminal points. If these parameters
are within the limits then depending upon the priority selection,
it activates the respective switch. This ensures the power
availability to the load
FUNCTION
In a typical connection (see diagram) two different power
sources (UPS, Stabiliser, Power conditioner etc.) are
connected to the critical load through INSTA / MEGA
switch, which will intelligently monitor the power from the
sources. Depending upon the preset limits, it will allow the
power to be passed to the critical load & thus making it as
the best solution for mission critical applications.
MODBUS RS 232 / 485 Interface (optional)
To connect your building Management System (BMS) for
monitoring of all status & alarms
Potential Free contacts (optional)
For remote monitoring of the switch activity
SINGLE LINE DIAGRAM
S3
FROM
SOURCE 1
F1
VTT1 - VTT 3
VTT1
INPUT
Make
before
switch
A3
1
A2
A1
F2
VTT2
S1
FROM
SOURCE 1
Output
to Load
INPUT
S5
VTT4 - VTT6
S2
Output
to Load
FROM
SOURCE 2
FROM
SOURCE 2
S4
Mega Switch
Insta Switch
SÜD
ISO 9001 : 2000
Western Region • Mumbai • Nagpur • Aurangabad • Goa • Kolhapur • Nashik • Indore • Bhopal • Vadodara • Ahmedabad • Surat • Silvasa • Jamnagar
Southern Region • Hyderabad • Vizag • Vijayawada • Chennai • Madurai • Coimbatore • Bengaluru • Mangalore • Cochin • Trichy
Eastern Region • Kolkata • Patna • Bhubaneshwar • Jamshedpur • Raipur • Raigarh • Guwahati • Siliguri
Northern Region • New Delhi • Mohali • Gurgaon • Noida • Lucknow • Jaipur
Overseas Partners • Italy • France • UK • Sri Lanka • Nepal • Bangladesh • Saudi Arabia
www.dbups.com
R&D being continuous process, the specifications are subject to change without prior notice.