Liebert® IntelliSlot Unity Card Version 6.0.1.0_95786 Firmware Release Notes

Liebert® IntelliSlotTM Unity Card
Version 6.0.1.0_95786 Firmware
Release Notes
December 18th, 2015
This document outlines:
1. Version and Compatibility Information
2. What’s New
3. Security Issues Addressed
4. Upgrade Instructions
5. Known Issues
===================================================================================
1. Version and Compatibility
===================================================================================
This release contains the following firmware version:
IS-UNITY_6.0.1.0_95786
This release is compatible with the following Liebert IntelliSlot communication cards:
IS-UNITY-DP
IS-UNITY-LIFE
This release is compatible with the following Liebert power and thermal management equipment:
Alber BDSU-50™
Liebert HPC™
Liebert APM™
Liebert HPC-S,M,R,W,Generic
Liebert APS™
Liebert HPM™
Liebert CRV™
Liebert NX™ 225-600kVA
Liebert CW™*
Liebert NXC™
Liebert Challenger™*
Liebert NXL™
Liebert Deluxe System/3™*
Liebert NXR™
Liebert DCP™
Liebert PCW™
Liebert DS™*
Liebert PDX™
Liebert DSE™
Liebert PeX™*
Liebert EXC™
Liebert PPC™
Liebert eXL™
Liebert RDC™
Liebert eXM™
Liebert RX™
Liebert FDC™
Liebert XDC™ with iCOMTM Control
Liebert FPC™
Liebert XDP™ with iCOMTM Control
Liebert GXT3™
Liebert XDP-Cray
Liebert GXT4™
*iCOM Firmware PA1.04.033.STD versions or later
1
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.
This release is compatible with the following sensors:
Liebert SN-2D
Liebert SN-T
Liebert SN-Z02
Liebert SN-3C
Liebert SN-TH
Liebert SN-Z03
Liebert SN-L
Liebert SN-Z01
This release supports the following communication interfaces:
Communication Protocol
Third-Party Protocols
Communication
Card
LIFE™
Services
Support
HTTP/
HTTPS
Emerson
Protocol
Email
SMS
SNMP
v1,v2c,v3
BACnet
IP/MSTP
Modbus
TCP/RTU
YDN23
IS-UNITY-DP








NXL &
PeX Only
IS-UNITY-LIFE



-
-
-
-
-
-
This release supports the following browsers:
o
Microsoft Internet Explorer® - IE9, IE10, and IE11
o
Mozilla Firefox® - ver. 28.0 or later
o
Google ChromeTM - ver. 34.0.1847.116 m or later
o
Safari® (MacBook®) - ver. 6.1.1 and 8.0.5
o
Safari® (iPad®) - ver. 5.1.1 and 7.1
===================================================================================
2. What’s New
===================================================================================
This release contains the following enhancements:
•
Support for the Liebert EXC, FDC, FPC, PPC, RDC and RX power distribution units that provides a
form, fit, and functional replacement of the IS-WEBS, IS-485S, and IS-IPBMS cards in these units for
SNMP and Modbus communications to building management systems. In addition, BACnet MSTP/IP,
SNMPv3, and environmental sensor support is now available for these PDUs. Available protocols for
these units are now
o
o
o
o
•
•
Web (HTTP/HTTPS)
SNMP v1/v2c/v3
BACnet MSTP/IP
Modbus RTU/TCP
o
o
o
Emerson Protocol
Email
SMS
Support for Alber BDSU-50 battery monitoring systems that provides a form, fit, and functional
replacement of the IS-WEBX, IS-485X, and IS-IPBMX cards in these units for SNMP and Modbus
communications to building management systems. In addition, BACnet MSTP/IP, SNMPv3, and
environmental sensor support are now available for these battery monitoring systems. Available
protocols for these systems are now
o Web (HTTP/HTTPS)
o Emerson Protocol
o SNMP v1/v2c/v3
o Email
o BACnet MSTP/IP
o SMS
o Modbus RTU/TCP
Support for Liebert eXM™ 480V units which provides all protocol support similar to those supported for
the Liebert eXM 208V units, including LIFE Services support.
2
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.
•
•
BTL Certification – The BACnet protocol support
in this release has been tested by the BACnet
Testing Laboratories (BTL) with 100% testing
completed and no issues found in conformance to
the BACnet protocol standards. The
BTLCertification listing for the Unity card on the
BACnet International website can be found here.
Improved Static Pressure Monitoring by supporting the Inches of Water Column (inWC) unit of
measure for static pressure measurements and set points via BACnet, Modbus, and SNMP interfaces.
Previously these have only been supported in Pascals for our thermal management units.
This release contains fixes for the following issues:
Component
Description
Web Interface
When using a recent version of the Firefox browser, some cookie settings would
cause the initialization page to get stuck. This has been corrected.
Additional security vulnerabilities have been addressed.
Corrected unit of measure conversions that used floating point factors.
BACnet MSTP
SNMP
LIFE Services
Added support for BACnet MSTP 76800 bps data rate.
A timing and load problem was causing loss of communications between
building management systems and thermal management devices at a few
customer sites. This problem has been corrected.
When Sensors are reordered on the Sensor webpage, the SNMP tables
reflecting the new order were not made until the card was restarted. This has
been corrected. After a little delay the sensors will appear in the SNMP tables
in the correct order without restarting the card.
Sensor data is now visible during a LIFE online session.
Increased transmission buffer size so more data can be transmitted in a single
call.
Persisted event status across card restart and communication recovery intervals
to eliminate misleading event state transitions.
===================================================================================
3. Security Issues Addressed
===================================================================================
The following highly publicized security vulnerabilities have already been addressed in a previous release:
Name
Description
“ShellShock”
Updated bash version to fix this in release 4.2
“Poodle”
SSLv3 was disabled in release 5.0
Cross-Scripting
Cross-Scripting entries via the Web user Interface were
restricted in release 5.1
3
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.
===================================================================================
4. Update Instructions
===================================================================================
The Unity cards may be updated to this firmware version using the web-based Firmware Upload feature.
Please refer to the Firmware Updates section of the Liebert IntelliSlot Unity Card User Manual (SL-52645).
===================================================================================
5. Known Issues
===================================================================================
Component
Description
Device Settings
When temperature settings are made on some thermal devices, there may be
some ‘round-off’ error of one tenth of a degree between what was requested and
what the device shows after the change. This is a known limitation of some
thermal device firmware versions and will be corrected in future versions of the
device controller firmware.
The IP address of the Unity card may be displayed on the local display of the
Liebert GXT4 UPS unit. The IP address is pushed to the GXT4 when the card
starts up. If the address changes (for example, if it is changed by the DHCP
server when the DHCP lease runs out), the local GXT4 display will continue to
show the old address until the card is restarted.
While the SNMP OIDS for the GXT are backward compatible with those from the
IS-WEBCARD, the text values in some SNMP varbinds and email/SMS
notifications have changed slightly to use the Unity card equivalent.
The preferred way to change the display order for multiple sensors is through the
Web user interface. If the order is changed using one of the supported protocols
then the entire list of sensors should be set in the correct order (including slots
that should become blank) to ensure all sensors are still included.
SNMP getnext requests may fail on some tables if there are multiple varbinds in
the request. If this occurs, use single-varbind requests.
Liebert GXT3/4
UPS Support
Sensor Support
SNMP
4
Emerson. Consider it Solved., Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2015 Emerson Electric Co. All rights reserved. Microsoft and Internet Explorer are either registered trademarks or trademarks of Microsoft Corporation.
Google and Chrome are either registered trademarks or trademarks of Google, Inc. Mozilla and Firefox are either registered trademarks or trademarks of
Mozilla Foundation Corporation. Safari, MacBook, and iPad are registered trademarks of Apple, Inc. All other trademarks, brand names, and service marks are
the property of their respective owners.