Liebert Hipluse U 80-500kVA ; 380/400/415 Vac ; 50/60 Hz Connectivity Solution Liebert Hipluse U supports SNMP communication, Modbus protocol communication and dry contact communication. This notes provides information relevant to these types of communication. SNMP Protocol Communication In Order to monitor the UPS through web network, you may need to select the SIC card . This card supports SNMP protocol. This SIC card is a network management card. It can also be connected to the IRM series sensor to provide environment monitoring function. When the intelligent equipment generates an alarm, the SIC card can notify the user by recording the log, sending trap information, and sending a mail. The SIC card provides three approaches for you to monitor your intelligent equipment and equipment room environment: Web browser. You can use Web browser to monitor your intelligent equipment and equipment room environment through the Web server function provided by the SIC card → NMS. You can use NMS to monitor your intelligent equipment and equipment room environment through the SNMP function provided by the SIC card → SiteMonitor, a network management software for equipment room power and environment. You can use SiteMonitor to monitor your intelligent equipment and equipment room environment through the TCP/IP interface provided by the SIC card For the installation and setting information of the SIC card, refer to the Site Interface Web/SNMP Agent Card User Manual. Modbus Protocol Communication The UPS achieves the Modbus protocol communication through Modbus card (option). The Modbus card of the 80kVA ~ 500kVA UPS should be installed in the option box of the main cabinet. For details, see UPS JBUS/MODBUS Adapter Card User Manual. Dry Contact Communication The UPS provides the following three dry contact communication approaches: Low voltage dry contact card (option) Dry contact board (option) Monitoring board ports Communication Through Dry Contact Card The UPS provides low voltage dry contact card (option), to facilitate user monitor the UPS through dry contact signal. The dry contact card of the 80kVA ~ 500kVA UPS should be installed in the dry contact card box in the main cabinet. For details, see UPS Relay Card User Manual. Communication Through Dry Contact Board Relay Card Assembly (Dry Contact Board) for details. HIPULSE U series UPS supports the ULC366SA1 board (see Figure Figure ULC366SA1 board ). The ULC366SA1 dry contact board provides five dry contacts (phenix terminal): J4, J5, J6, J7 and J8. See Table 8-11 for details. Figure ULC366SA1 board Table Dry contact port Dry contact port Definition J4 4 General alarm J5 Battery low voltage J6 Can set via setting software. Default: UPS fault. Settable: 0-Undefined, 1-UPS fault, 2-Input switch open, 3-Parallel cables connection error, 4-Battery need to maintained, 5-Fan fault, 6-Battery temperature too high, 7-On bypass, 8-On battery, 9 ~ 10-Reserved J7 Can set via setting software. Default: On bypass. Settable: 0-Undefined, 1-On bypass, 2-Single output overload, 3-Parallel overlaod, 4-Output switch open, 5-Bypass (voltage/frequency) exceeds limits, 6-Input filter not connected, 7-UPS fault, 8-On battery, 9 ~ 10-Reserved J8 Can set via setting software. Default: On battery. Settable: 0-Undefined, 1-On battery, 2-Battery ground fault, 3-BCB open, 4-Input current unbalance, 5-Maintenance bypass closed, 6-Overtemperature, 7-UPS fault, 8-On bypass, 9 ~ 10-Reserved When routing cables, use a flat cable (34 pin) to connect the port J1 (34 pin socket) on ULC366SA1 dry contact board and any Intellislot port on monitoring board. There are five relays on ULC366SA1 dry contact board, and the rated specification of the relay is: 250V, 2A. Communication Through Monitoring Board Ports For on-site specific needs, the UPS may need auxiliary connection to achieve functions like acquiring external equipment status information, providing alarm signals to external devices, and remote EPO. These functions are realized through the following interfaces on the external interface board (EIB) of the main cabinet. Input dry contact port Output dry contact port EPO input port