Figure 4 Connecting an NX Series or APM UPS to an NX Series or APM UPS . . . .. . . . . . . . . . . . . . . . . . . . . 2 ACRONYM NX series : NX product series comprises of NX, NXr, Nxc, Hipulse U, ITA(30/40 kVA) UPS Non NX series : Non NX product series comprises of Ul33, NXL, 80-net, and any other brand UPS General 1.0 GENERAL Load Bus Sync (LBS) Extender/Adapter for Dual Bus UPS is designed to extend the LBS function, up to 150m (492 ft.) between NX series or APM series uninterruptible power system (UPS) modules of a dual bus system (DBS). The adapter also enables an NX Series or APM UPS to synchronize with other UPS models. Figure 1 LBS Adapter dimensions (216.2mm) 1.8" (45.5mm) DY3-4ZPW POWER ON COM1 COM2 SWITCH LED1 Figure 2 5.25" (133.5mm) Horizontal installation DY3-4ZPW POWER?ON COM2 COM1 SWITCH LED1 Figure 3 Vertical installation 1 Installation 2.0 INSTALLATION 2.1 NX Series or APM UPS to NX Series or APM UPS ! WARNING Installation by qualified electrical personnel only - hazardous voltage may be present at the UPS output connectors. 1. Connect the power cables of the adapter to the Phase A, Neutral and Ground output of each UPS. 2. For NX Series UPS except for NXr, connect the LBS cable (with two DB9 ports) to COM1 of the LBS Signal Adapter; for NXr UPS and APM UPS, connect the end of the LBS cable (with a DB9 port and an RJ45 port) with DB9 port to COM1 of the LBS Signal Adapter. 3. For NX Series UPS except for NXr, connect the other end of the LBS cable (with two DB9 ports) to X4 on the parallel board (UHW241M3) in the UPS; for NXr UPS and APM UPS, connect the end of the LBS cable (with a DB9 port and an RJ45 port) with RJ45 port to the J4 port of the bypass module of the UPS. 4. Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal Adapter. 5. The switch of both LBS signal adapters should be in the right position (see Figure 4). Figure 4 Connecting an NX Series or APM UPS to an NX Series or APM UPS Power ON COM1 COM2 SWITCH Power ON LED1 Power Cable Connect to NX Series or APM UPS COM1 COM2 SWITCH LED1 LBS Cable Power Cable Connect to NX Series or APM UPS LBS Cable Communication Cable up to 492 ft. (150m) 2.2 NX Series or APM UPS to Non NX Series or non-APM UPS ! WARNING Installation by qualified electrical personnel only - hazardous voltage may be present at the UPS output connectors. 1. Connect the power cables of the adapter to the Phase A, Neutral and Ground Output of each UPS. 2. For NX Series UPS except for NXr, connect the LBS cable (with two DB9 ports) to COM1 of the LBS . Adapter connectedto the UPS; for NXr UPS and APM UPS, connect the end of the LBS cable Signal . (with a DB9 port and an RJ45 port) with DB9 port to COM1 of the LBS Signal Adapter. 3. For NX Series UPS except for NXr, connect the other end of the LBS cable (with two DB9 ports) to X4 on board the parallel (UHW241M3) in the UPS; for NXr UPS and APM UPS, connect the end of the LBS. cable (with a DB9 port and an RJ45 port) with RJ45 port to the J4 port of the bypass module of the UPS. 4. Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal Adapter. 5. The switches of LBS signal adapters connected to the NX Series or APM UPS should be in the right position and the switches of LBS signal adapters connected to the Non NX Series or non-APM UPS should be in the left position (see Figure 5). 2 Installation Figure 5 Connecting an NX Series or APM UPS to a Non NX Series or non-APM UPS Power ON COM1 COM2 SWITCH Power ON LED1 COM1 LED1 Power Cable Connect to NX Series or APM UPS Power Cable Connect to Non NX Series or non-APM UPS LBS Cable Communication Cable up to 492 ft. (150m) Table 1 Human interface - indicators and switches Item Description Power port Connect to Phase A, Neutral and Ground of output of UPS. LED1 (red) Power LED. It illuminates when the power is on, turns o ffwhen the power fails. COM1 LBS Signal interface. Connect to NX Series or APM UPS. COM2 RS485 interface. Connect to other Signal Adapter. Green LED: Communication Power is OK. Yellow LED: Adapter is connected to Non NX Series or non-APM UPS. Switch to left: Connect to Non NX Series or non-APM UPS. Switch to right: Connect to NX Seires or APM UPS. SWITCH Table 2 Electrical rating Description Rating Voltage 120V-277VAC Frequency 45-65HZ Current Table 3 1.5A Max. Part number description Description Part Number 150 Meter Kit NX150MLBSKIT 50 Meter Kit NX050MLBSKIT 3 COM2 SWITCH Emerson Network Power, a business of Emerson (NYSE:EMR),a global company that leads by applying a unique combination of industry expertise, technology, and resources to make the future of our customers' enterprises and networks possible. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network Power assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. All rights reserved throughout the world. Speci cations subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners 31011102-V1.3 www.EmersonNetworkPower.com