Liebert® NX™ UPS GUIDE SPECIFICATIONS for a 250-800kVA Uninterruptible Power Supply System 1.0 GENERAL 1.1 SUMMARY These specifications describe requirements for an Uninterruptible Power Supply System (UPS). The UPS shall automatically maintain AC power within specified tolerances to the critical load, without interruption, during failure or deterioration of the normal power source. The manufacturer shall design and furnish all materials and equipment to be fully compatible with electrical, environmental and space conditions at the site. It shall include all equipment to properly interface the AC power source to the intended load and shall be designed for unattended operation. 1.2 STANDARDS The UPS and all associated equipment and components shall be manufactured in accordance with the following applicable standards: CE 2006/95/EC (Low Voltage Safety), CE 2004/108/EC (Electromagnetic Compatibility) European RoHS Directive 2011/65/EU IEC/EN/AS 60950-1 Information Technology Equipment IEC/EN/AS 61000 Electromagnetic Compatibility (EMC) IEC/EN AS 60146 Semiconductor Convertors IEC/EN/AS 60529 Degrees of Protection IEC/EN/AS 62040-1 General Safety Requirements for UPS IEC/EN/AS 62040-2 Electromagnetic Compatibility for UPS (as Class C3 UPS) IEC/EN/AS 62040-3 Design Performance and Tests for UPS (VFI SS 111) The UPS is CE marked in accordance with EEC directives 73/23 “Low Voltage” and 89/336 “Electromagnetic compatibility”. The quality system for the engineering and manufacturing facility shall be certified to conform to quality system standard ISO 9001 for the design and manufacture of power protection systems for computers and other sensitive electronics. Also, manufacturing systems shall conform to ISO 14001 for environmental management requirements. 1.3 SYSTEM DESCRIPTION 1.3.1 Design Requirements The UPS shall be sized to provide a minimum of ____ kVA/kW output (unity load power factor rating) The UPS shall be able to provide power at full rated output kVA loads with power factor between 0.9 lagging and 0.9 leading. Load voltage and bypass line voltage shall be 380/400/415VAC, three-phase, four-wire. Input voltage shall be 380/400/415VAC, three-phase, four-wire. The battery shall support the UPS at 100% rated kW load for at least _____ minutes at 25°C (77°F) at startup. The UPS shall have an active power factor corrected IGBT converter/rectifier, capable of maintaining input power factor and input THDi within specifications without an additional input filter. NX REV0_12-17-12 1 Guide Specifications Liebert NX UPS, 250-800kVA, Single-Module The UPS shall be of transformer-free design, requiring no internal transformer in the main power path for the basic operation of the module. Optional transformers in cabinets or otherwise external to the basic UPS module shall be permissible to provide isolation and/or voltage transformation. 1.3.2 Modes of Operation The UPS shall operate as an on-line reverse transfer system in the following modes: A. Normal: The critical AC load is continuously powered by the UPS inverter. The rectifier/charger derives power from the utility AC source and supplies DC power to the DC-DC booster, which in turn supplies the inverter while simultaneously float charging the battery. B. Energy Optimization Mode: The critical AC load is continuously powered by the bypass with the inverter available to power the load if the bypass source voltage or frequency exceeds adjustable parameters of power quality. C. Emergency: Upon failure of utility AC power, the critical AC load is powered by the inverter, which, without any switching, obtains its power from the battery plant via the DC booster. There shall be no interruption in power to the critical load upon failure or restoration of the utility AC source. D. Recharge: Upon restoration of the utility AC source, the rectifier supplies power to the DC-DC booster and the output inverter. The rectifier powers the inverter and simultaneously recharges the battery. This shall be an automatic function and shall cause no power interruption to the critical AC load. E. Bypass: If the UPS must be taken out of service for maintenance or repair, the static transfer switch shall transfer the critical load to the bypass source. The transfer process shall cause no interruption in power to the critical AC load. F. Off-Battery: If the battery only is taken out of service for maintenance, it is disconnected from the DC-DC booster by means of an external disconnect circuit breaker. The UPS shall continue to function and meet all of the specified steady-state performance criteria, except for the power outage backup time capability. 1.3.3 Performance Requirements The solid-state power components, magnetic, electronic devices and over-current protection devices shall operate within the manufacturer’s recommended temperature when the UPS is operating at 100% capacity, supporting critical load and maintain battery charging with the following conditions occurring simultaneously. Any altitude within the specified operating range up to 1000m (3300 ft) elevation Any ambient temperature within the specified operating range of 0°C to 40°C (32°F to 104°F). (Note: Battery life is halved for every 10°C increase above 20°C). Relative humidity (RH) within 0 to 95% , non-condensing. Environment pollution level 2 Any input voltage within the specified range, +10% to -15% of nominal 1.3.4 Input A. Voltage Range: +25%, -15% of nominal (minimum -15% at nominal load, below –15% with load derated. No battery charging with nominal load below -5%) B. Frequency Range: 40Hz to 70Hz C. Rectifier Walk-In: 0% to 100% of full rated load over 1-30 seconds (adjustable, for 600-800kVA only) D. Rectifier Start Delay: Programmable from 1-180 seconds before walk-in begins (for 600-800kVA only) E. Max Inrush Current : ≤1 In F. Power Factor: ≥0.99 at full load with nominal input voltage G. Generator Adaptability: UPS input current limit can be adjusted to suit generator power rating. Wide input frequency range is permissible. NX (APL)_REV0_12-17-1212 2 Guide Specifications Liebert NX UPS 250-800kVA, Single-Module H. Current Distortion: ≤ 3% THD at full load, UPS in double-conversion mode 1.3.5 AC Output A. Load Rating: 100% load rating at 104°F (40°C) for 8 hours for any combination of linear and non-linear loads; 100% of load rating continuous at 95°F (35°C) B. Voltage Regulation: <1% Steady State; <5% for 100% Transient State C. Manual Voltage Adjustment Range: ±5% for line drop compensation D. Frequency Regulation: Synchronized to bypass: ±1% (2, 3, 4 selectable) Synchronized to internal clock 0.1% E. Efficiency: Defined as output kW/input kW at rated lagging load power factor; not less than 95% (at 75% to 100% load). F. Phase Imbalance: Balanced loads 100% unbalanced loads 120° ±1° 120° ±1.5° G. Voltage Transients (average of all three phases): 100% Load Step ±5% H. Output Voltage Transients I. Voltage transients shall be limited to a maximum deviation from nominal system output volts of ± 5% with recovery to within 1% of the nominal output voltage within one electrical cycle (20 milliseconds) for each of the following conditions. Limits shall apply to any UPS load within the UPS rating, and frequency shall be maintained at 60 Hz ± 0.1 Hz. The system shall not transfer to bypass under these conditions (except item 3). 1. 100% load step 2. Loss or return of AC input power, momentary sags, surges or spikes on the input to the UPS (all three phases or single phase) 3. Uninterrupted transfer of the critical load to and from the UPS output and bypass power line (manually initiated or automatic) Voltage Harmonic Distortion: Maximum <2% (100% linear load) Maximum <5% (100% non-linear load, per IEC 62040-3) J. Overload at full Output Voltage with ±1% voltage regulation: 105% continuously 125% of full load for 10 minutes at 25°C (77°F) ambient 150% of full load for a minimum of 30 milliseconds at 25°C (77°F) ambient K. Current Limit: 300% nominal current L. Fault Clearing: Inverter only: 300% of normal full load current for 10 milliseconds or 150% of normal full load current for <5 seconds (when bypass is not available). Bypass available: 1000% for 100 milliseconds in inverter pulse-parallel operation when bypass is available. 1.3.6 Earthing The UPS chassis shall have an appropriate equipment earthing terminal. NX (APL)_REV0_12-17-12 3 Guide Specifications Liebert NX UPS, 250-800kVA, Single-Module 1.4 ENVIRONMENTAL CONDITIONS The UPS shall be able to withstand the following environmental conditions without damage or degradation of operating characteristics: A. Operating Ambient Temperature UPS: 0°C to 40°C (32°F to 104°F) Battery: 25°C (77°F), ±3°C (±5°F) B. Storage/Transport Ambient Temperature -15°C to 50°C (-4°F to 158°F) C. Relative Humidity 0 to 95%, non-condensing D. Altitude Operating: up to 1000m (3300 ft.) above Mean Sea Level without de-rating Consult factory for de-rating above 3300 ft. (1500m) elevation. Storage/Transport: To 50,000 ft. (15,000m) above Mean Sea Level 1.5 SUBMITTALS 1.5.1 Proposal Submittals Submittals with the proposal shall include: Functional relationship of equipment including weights, dimensions and heat dissipation. Descriptions of equipment to be furnished, including deviations from these specifications. Size and weight of shipping units to be handled by contractor. Detailed layouts of customer power and control connections. Descriptive list of site services and maintenance to be offered. 1.5.2 60 Day Submittals Submittals 60 days prior to UPS delivery shall include: Detailed installation drawings including all terminal locations. Interconnect wiring diagrams showing conduit wiring with terminal numbers for each wire. Descriptive list of site services and maintenance to be offered. 1.5.3 UPS Delivery Submittals Submittals upon UPS delivery shall include: A complete set of submittal drawings. Two (2) sets of instruction manuals. Manuals shall include a functional description of the equipment, safety precautions, instructions, step-by-step operating procedures and routine maintenance guidelines, including illustrations. Descriptive list of site services and maintenance to be offered. 1.6 WARRANTY 1.6.1 UPS Warranty The UPS manufacturer shall warrant the unit against defects in workmanship and materials for 12 months after initial startup or 18 months after the shipping date, whichever comes first. NX (APL)_REV0_12-17-1212 4 Guide Specifications Liebert NX UPS 250-800kVA, Single-Module 1.6.2 Warranty - End User Warranties associated with buyout items shall be passed through to the end user. 1.7 QUALITY ASSURANCE 1.7.1 Manufacturer Qualifications A minimum of 20 years’ experience in the design, manufacture and testing of solid-state UPS systems is required. 1.7.2 Factory Testing Before shipment, the manufacturer shall fully and completely test the system to ensure compliance with the specifications. These tests shall include operational discharge and recharge tests to ensure guaranteed rated performance. 2.0 PRODUCT 2.1 FABRICATION 2.1.1 Materials All materials of the UPS shall be new, of current manufacture, high grade and shall not have been in prior service except as required during factory testing. All active electronic devices shall be solid-state. All power semiconductors shall be sealed. Control logic and fuses shall be physically isolated from power train components to ensure operator safety and protection from heat. All electronic components shall be accessible from the front without removing sub-assemblies for service access. 2.1.2 Wiring Wiring practices, materials and coding shall be in accordance with the requirements of IEC and applicable local codes and standards. All electrical power connections shall be torqued to the required value and marked with a visual indicator (English tag). Provisions shall be made in the cabinets to permit installation of input, output and external control cabling using raceways or conduits. Provision shall be made for top and bottom access to input, output, bypass and DC connections. Provisions for adequate wires/cables bend radius. All copper busbars for customer power connections shall be tin-plated for connection integrity. 2.1.3 Construction and Mounting The UPS shall be in an IP20 enclosure, designed for floor mounting. The UPS shall be structurally adequate and shall have provisions for hoisting, jacking and forklift handling. Maximum cabinet height shall be 2145mm (85in.). 2.1.4 Cooling Adequate ventilation shall be provided to ensure that all components are operated well within temperature ratings. Temperature sensors shall be provided to monitor the UPS’s internal temperature. Upon detection of temperatures in excess of the manufacturer’s recommendations, the sensors shall cause audible and visual alarms to be sounded on the UPS control panel. A separate room ambient temperature sensor shall be provided to allow control of battery charging voltage with change of temperature. Air filters shall be located at the point of air inlet and shall be changeable. Recommended service and ventilation clearance of 500mm shall be required in the rear of the system. 2.2 EQUIPMENT 2.2.1 UPS System The UPS system shall consist of an IGBT power factor-corrected rectifier, DC-DC booster and three-phase transformer-free inverter, bypass static transfer switch, bypass synchronizing circuitry, protective devices and NX (APL)_REV0_12-17-12 5 Guide Specifications Liebert NX UPS, 250-800kVA, Single-Module accessories as specified. The specified system shall also include a battery disconnect breaker and battery system. 2.2.2 Configurations The UPS system shall consist of either a single module unit, or two, or more (up to a maximum of four) units of the same kVA rating. Systems greater than one module shall operate simultaneously in a parallel configuration with the load shared equally between the connected modules. With the exception of a single module configuration, the system shall be redundant or non-redundant as stated elsewhere in the specification. A. Non-redundant system: all the modules making up the UPS system shall supply the full rated load. If a module should malfunction, the load has to be transferred, automatically and uninterrupted, to the bypass line by the use of the static mains bypass switch. B. Redundant system: the UPS system shall have one or more module(s) than required to supply the full rated load. The malfunction of one of the modules shall cause that module to be disconnected from the critical load and the remaining module(s) shall continue to carry the load. Upon repair of the module, it shall be reconnected to the critical load to resume redundant operation. Any module shall also be capable of being taken off the critical load manually for maintenance without disturbing the critical load bus. Module redundancy level shall be a predefined number of modules that are required to supply the full rated load. With the number of connected modules equal to this value, a malfunction of another module shall cause the load to be transferred automatically and uninterrupted to the bypass line by the use of the static mains bypass switch. 2.2.3 System Protection The UPS shall have built-in protection against: surges, sags and over-current from the AC rectifier input source, over-voltage and voltage surges from output terminals of paralleled sources, and load switching as well as circuit breaker operation in the distribution system. The UPS shall be protected against sudden changes in output load and short circuits at the output terminals. The UPS shall have built-in protection against permanent damage to itself and the connected load for all predictable types of malfunctions. Fast-acting, current-limiting devices shall be used to protect against cascading failure of solid-state devices. Internal UPS malfunctions shall cause the module to trip off-line with minimum damage to the module and provide maximum information to maintenance personnel regarding the reason for tripping off-line. The load shall be automatically transferred to the bypass line uninterrupted, should there be an internal UPS malfunction or should the connected critical load exceed the capacity of the available on-line modules. The status of protective devices shall be indicated on a graphic display screen on the front of the unit. 2.3 COMPONENTS 2.3.1 Rectifier The term rectifier shall denote the solid-state equipment and controls necessary to convert alternating current (AC) to regulated direct current (DC) to simultaneously supply the inverter and charge the battery. The rectifier shall be of DSP (Digital Signal Processor) controlled design and utilize insulated gate bipolar transistors (IGBTs). The DC output of the rectifier will meet the input requirements of the inverter even without the battery being connected. A. Input Current Harmonic Distortion Input current THD shall be less than 3% at full rated UPS output load and 100% balance non-linear load (with input voltage THD ≤ 2%). B. Input Power factor correction: The rectifier also performs a PFC function; input power factor shall be a minimum 0.99 at 100% load and 0.98 at 50% load. C. AC Input Current Limiting: The maximum Input current limit can be reduced at 100% for generator operation. D. Input Power Walk-In: The rectifier/charger shall provide a feature that limits, during the transfer from NX (APL)_REV0_12-17-1212 6 Guide Specifications Liebert NX UPS 250-800kVA, Single-Module battery mode to line mode, the total initial power requirement at the input terminals to 0% of rated load and gradually increases power to 100% of full rating over the 30-second (adjustable) time interval (for 600-800kVA only). E. Fuse Protection Each AC phase shall be individually fused with fast-acting fuses so that loss of any semiconductor shall not cause cascading failures. 2.3.2 DC-DC Booster The term DC-DC Booster shall denote the equipment and controls to regulate the output of the rectifier to the levels appropriate for charging the battery and to boost the battery voltage to the level required and to operate the inverter. The DC-DC booster shall be solid-state, capable of providing rated output power, and for increased performance the inverter shall be a pulse width-modulated design and utilize insulated gate bipolar transistors (IGBTs). The DC-DC booster shall control charging of the battery. The batteries shall be VRLA (Valve Regulated Lead Acid), maintenance free type. A. Battery Recharge In addition to supplying power for the load, the rectifier/charger shall be capable of producing battery charging current sufficient to replace 95% of the battery discharge power within ten (10) times the discharge time. After the battery is recharged, the rectifier/charger shall maintain the battery at full charge until the next emergency operation. Ripple voltage at the battery terminal (RMS) should be less than 1%, and ripple current must not exceed 5% (of C-10 Ah rating) nominal discharging current. B. Discharging: The battery converter will supply power to the inverter when the rectifier is shut down or in joint mode, and also the rectifier is current limiting. C. Temperature-Compensated Charging The UPS shall adjust the battery charging voltage based on the battery temperature reported from external battery temperature sensors. Temperature sensors shall be monitored for faulty measurements and ignored if a fault is detected to prevent over or under changing the battery. When multiple sensors are used the voltage shall be based on the average temperature measured. Excessive difference in the temperature measurements shall be reported and the charging voltage adjusted to protect the batteries from excessive current. D. Battery Load Testing The UPS shall be capable of performing battery load testing under operator supervision. To accomplish this, the rectifier shall reduce charging voltage to force the batteries to carry the load for a short time. If the curve of battery voltage drop indicates diminished battery capacity, the UPS shall display an alarm message. If the voltage drop indicates battery failure, the UPS shall terminate the test immediately and annunciate the appropriate alarms. 2.3.3 Inverter The term inverter shall denote the equipment and controls to convert direct current (DC) from the rectifier or battery via the DC-DC booster to provide alternating current (AC) to power the load. The inverter shall be solidstate, capable of providing rated output power, and for increased performance, the inverter shall be a pulse-widthmodulated design, Vector controlled and utilize insulated gate bipolar transistors (IGBTs). With this patented Vector control, switching at high frequency can achieve minimum output voltage distortion. A. Overload Capability The inverter shall be able to sustain an overload across its output terminals as follows: 150% of UPS rated output for 30 milliseconds. 125% of UPS rated output with a resistive load for ten (10) minutes. NX (APL)_REV0_12-17-12 7 Guide Specifications Liebert NX UPS, 250-800kVA, Single-Module 105% of UPS rated output with a resistive load for long term. The UPS will achieve the overload mentioned above with 380/400/415V nominal input and output voltage and when the battery is fully charged. B. Output Frequency The inverter shall track the bypass continuously, providing the bypass source maintains a frequency of either 50Hz or 60Hz ±1%. The inverter shall change its frequency (slew rate) at less than 1Hz per second to maintain synchronous operation with the bypass. This shall allow make-before-break manual or automatic transfers. If the bypass fails to maintain proper frequency, the inverter shall revert to an internal oscillator, which shall be temperature compensated, and shall hold the inverter output frequency to 0.1% from the rated frequency for steady-state and transient conditions. Drift shall not exceed 0.1% during any 24-hour period. Total frequency deviation, including short time fluctuations and drift, shall not exceed 0.1% from the rated frequency. C. Phase-to-Phase Balance The inverter shall have system logic to provide individual phase voltage compensation to obtain phase balance of ±1% under all 100% linear conditions and ±1.5% under 100% unbalanced non-linear load. D. Fault Sensing and Isolation The UPS shall be provided with a means to detect a malfunctioning inverter and isolate it from the critical load bus to prevent disturbance of the critical load voltage beyond the specified limits. The inverter output static switch shall be switched off to isolate a malfunctioning module from the critical load. E. Battery Protection The inverter shall be provided with monitoring and control circuits to protect the battery system from damage due to excessive discharge. Inverter shutdown shall be initiated when the battery voltage has reached the end of discharge voltage. The battery end-of-discharge voltage shall be calculated and automatically adjusted for partial load conditions to allow extended operation without damaging the battery. 2.3.4 Static Bypass For times when maintenance is required or the inverter cannot maintain voltage to the load due to sustained overload or malfunction, a bypass circuit shall be provided to isolate the inverter output from the load and provide a path for power directly from an alternate AC (bypass) source. The UPS control system shall constantly monitor the availability of the inverter bypass circuit to perform a transfer. The inverter bypass circuit shall consist of a bypass static switch and an over-current protection device to isolate the inverter. The bypass static switch shall denote the solid-state device incorporating SCRs (silicon-controlled rectifiers) that can automatically and instantaneously connect the alternate AC source to the load. A. Manual Load Transfers A manual load transfer between the inverter output and the alternate AC source shall be initiated from the control panel. Manually initiated transfers shall be make-before-break utilizing the inverter and the bypass static switch. B. Automatic Load Transfers An automatic load transfer between the inverter output and the alternate AC source shall be initiated if an overload condition is sustained for a time period in excess of the inverter output capability or due to a malfunction that would affect the output voltage. Transfers caused by overloads shall initiate an automatic retransfer of the load to the inverter only after the load has returned to a level within the rating of the inverter source. C. Back-feed Protection Using another optional (customer-supplied) contactor located upstream of the UPS Bypass input and whose trip coil control voltage comes from the input bypass line voltage, the UPS shall provide a normally closed contact to be used for isolating the bypass source to protect the operator against back-feed of energy resulting from a shortcircuit of the bypass line SCRs. That is, in the event that the UPS works on Battery mode and no main input NX (APL)_REV0_12-17-1212 8 Guide Specifications Liebert NX UPS 250-800kVA, Single-Module (Rectifier and Bypass) is available, the contactor cannot be closed. So if the bypass line SCRs are short-circuited, the UPS will be still disconnected from the Bypass supply. 2.3.5 Internal Maintenance Bypass A fully rated bypass circuit shall be fitted on all single module UPS systems to provide an alternative path for power flow from the alternate AC supply to the critical load for the purpose of maintaining the UPS when it is completely powered down. A Maintenance Bypass protection shall be provided; it will be activated when the Maintenance Bypass Switch is closed before the inverter shutdown. 2.3.6 Man-Machine Interface (MMI) A. UPS Display and Control Panel Each UPS module shall be equipped with a 320 x 240 dot graphic LCD display. This shall automatically provide all information relating to the current status of the UPS as well as being capable of displaying metered values. The display shall be menu-driven, permitting the user to easily navigate through operator screens. B. Metered Values A microprocessor shall control the display and memory functions of the monitoring system. All three phases of three-phase parameters shall be displayed simultaneously. All voltage and current parameters shall be monitored using true RMS measurements for accuracy to ±1% of voltage, ±3% AC current. The following parameters shall be displayed: Main Input Voltage, line-to-line Main Input Voltage, line-to neutral Main Input current per phase Main Input frequency Three-phase Input Power Factor Bypass Voltage, line-to-line Bypass Voltage, line-to neutral Bypass Frequency Output Voltage, line-to-line Output Voltage, line-to neutral Output current per phase Output frequency Output Power factor per phase Battery bus voltage Battery current Forecasted Battery back-up time (remaining time) Battery temperature Parallel Active Power( kW), (for parallel system operation) Parallel Load Apparent Power ( kVA), (for parallel system operation) Parallel Reactive Power( kVAR), (for parallel system operation) C. Power Flow Indications Each UPS module shall be equipped with a mimic to indicate power flow to the critical load along with an indication of the availability of the rectifier/charger, battery, automatic bypass, inverter, load. The mimic shall provide a quick and easy indication of the load level (displayed on LCD), including for overload conditions (displayed on LCD). NX (APL)_REV0_12-17-12 9 Guide Specifications Liebert NX UPS, 250-800kVA, Single-Module D. Main Display Screen The main display screen of the UPS shall be the default screen and shall provide the following information: System Status Warning Indicator Fault Indicator Bypass Input Voltage Bypass Input Frequency Input Voltage Line to Line Input Frequency Output Voltage, Line to Line Output Current, Per Phase Output Frequency DC Source Voltage DC Source Current E. Control Buttons Buttons shall be provided to start and stop the inverter. A pop-up message requesting confirmation shall be displayed whenever a command is initiated that will change the status of the UPS. Other buttons shall be provided to reset faults and silence the alarm buzzer. F. Event Log This menu item displays the list of Events that have occurred recently while the UPS was in operation. G. Measures Menu A “measures menu” shall provide access to the full set of measurements for each functional block (rectifier, bypass, booster/charger, batteries, inverter and load). H. Battery Status Indicator A battery status indicator shall display DC alarm conditions, temperature, battery state of charge, the present battery voltage, total discharge time, status of last battery test and battery time remaining during discharge. A graphical representation of the battery voltage during the discharge shall be displayed. The graphical representation shall remain in the monitoring system memory until the next discharge occurs and shall be available for review of the battery performance. The UPS shall provide the operator with controls to perform the following functions: Configure and Manage Manual Battery Test. Modify Test Duration and Minimum Voltage Start Battery Test Monitor Test Status and Progression Stop Battery Test Battery Test Status I. Alarms The control panel shall report the system-level alarms listed below. An audible alarm shall be activated when any of the following alarms occurs. All alarms shall be displayed in text form. Placement into service or test mode Line power switch open Maintenance Bypass switch closed Inverter over-temperature warning Fan life exceeded DC under voltage NX (APL)_REV0_12-17-1212 10 Guide Specifications Liebert NX UPS 250-800kVA, Single-Module Synchronization system fault DIC Power-up System shutdown (DIC generated) Placement into service or test mode Maintenance Bypass switch closed Fan life exceeded Synchronization system fault DIC Power-up System shutdown (DIC generated) ID card missing Calibration started Input air high temperature Input air temp. out of range SBS output switch open SBS Bypass switch closed Do not insert battery switch Line power switch open Input air temp. out of range SBS output switch open SBS output switch closed Do not insert battery switch Overload warning Inverter Off warning Inverter Off pending command Current limit kW protection Inverter Off for shutdown command Bypass switch open Bypass line power failure Overload warning Bypass wrong phase rotation Bypass disabled for DC voltage low Bypass over-temperature warning Bypass switch open Imminent end of autonomy time Battery end of discharge High battery temperature Battery temp. out of range Temperature probe not responding Battery autonomy test High battery temperature Battery temperature out of range J. Controls System-level control functions shall be: Start Inverter (and transfer to inverter) Stop Inverter (after transferring to bypass) Startup Screen Battery Test Set-point Adjustment Configure Manual Battery Test Initiate Manual Battery Test Reset (Fault Cleared) System Settings (Time, Date, Language, LCD Brightness, Password, Audio Level) Audio Silence Command Alarm Reset Command K. Manual Procedures Load Transfers Two buttons (START INVERTER, STOP INVERTER) shall provide the means for the user to transfer the load to Bypass and back on UPS. A Sync-scope shall be provided to display the phasing between Bypass and Output in graphical representation. Shutdown NX (APL)_REV0_12-17-12 11 Guide Specifications Liebert NX UPS, 250-800kVA, Single-Module Two buttons (UPS, SYSTEM) shall provide the means for the user to shut down the inverter and transfer the load to bypass or shut down the entire system. 2.3.7 Self-Diagnostics A. Event Log File Event Log File The control system shall maintain a log of the event conditions that have occurred during system operation. Each log contains the event name, event time/date stamp, and a set/clear indicator. 2.3.8 Remote Monitoring Capability A. Communication Cards The UPS shall be equipped with slots for optional Liebert communication card. Optional additional dry contacts Optional Liebert SNMP Web Cards, providing SNMP, Telnet and Web-management capability Optional Liebert 485 Cards, for Modbus interfacing. B. Programmable Output Contacts Six output channels shall be provided for customer signaling. The activation for each alarm signal channel shall be customer-selected for a range of functions such as: EPO Environment parameter input interface User communication interface Intellislot intelligent card interface Temperature detection interface 2.3.9 Optional Accessories A. Battery Circuit Breaker (BCB) Each UPS module shall have a properly rated circuit breaker to isolate it from the battery. This Battery Circuit Breaker is to be housed in a separate enclosure for wall mounting, or mounted inside an optional battery cabinet and must be installed as close as possible to the battery systems and UPS. It shall contain a BCB and a BCB control board. It shall function as required by the E.P.O. button and the BCB shall trip once the E.P.O. button is pressed. B. External Battery Temperature Sensor To ensure temperature compensated charging to protect battery life, a battery temperature monitoring probe is necessary to monitor the battery enclosure temperature rise caused by the AC mains failure and of the battery’s internal resistance when operating. The probe system includes one battery temperature sensor and one temperature transport. C. Load Bus Synchronizer (LBS) Kit The Load Bus Synchronizer (LBS) kit shall enable independent UPS units or systems to stay in synchronous state when operating on battery or unsynchronized input sources. It will provide communication link between two redundant UPS systems on independent output bus (either two independent single units or two independent parallel systems each composed of up to six modules) to maintain synchronization. NX (APL)_REV0_12-17-1212 12 Guide Specifications Liebert NX UPS 250-800kVA, Single-Module NX (APL)_REV0_12-17-12 13 Guide Specifications