Liebert Hipluse U UPS;80 - 400kVA; 380/400/415V Detailed Specification Conformity And Standard Table 1-1 Conformity and standard Item Normative reference General safety requirements for UPS EN62040-1/IEC62040-1/AS62040-1 EMC requirements for UPS EN62040-2/IEC62040-2/AS62040-2 (C3) Method of specifying the performance and test requirements of UPS EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111) Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/ EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529) Environmental Requirements Table 1-2 Item Environmental requirements Power rating (kVA) Unit 80 ~ 500 Operating Temperature °C 0 ~ 40°C Maximal temperature for 8hr day °C 40°C (derate power by 1.5% per °C between 40°C and 50°C Mean Temperature for 24hr °C Maximum 35°C Relative humidity ≤95% at 20°C Altitude of operation m ≤1000m asl (derate power by 1% per 100m between 1000m and 2000m) Storage temperature and transport temperature °C -25°C to 70°C Over-voltage level Overvoltage level 2 Pollution level Pollution level 2 Grid system TN, TT, IT (4-pole switch configured) Mechanical Characteristics Table 1-3 Item Dimensions (W × D × H) Weight (kg) Unit Power rating (kVA) 80/100/120 (6P) 160 (12P) 200 (6P) 300 (6P) Without packaging 900 × 855 × 1900 1250 × 855 × 1900 1640 × 855 × 1900 1240 × 855 × 1900 1640 × 855 × 1900 With packaging 1028 × 998 × 2125 1366 × 996 × 2160 1768 × 998 × 2166 1356 × 996 × 2160 1768 × 998 × 2166 Without packaging 900 With packaging 1000 000 m3/h 1890 890 Ventilation Airflow Protection level Color Cable entry Mechanical characteristics 160 (6P) 1200 200 1200 200 1300 300 By internal intake fans 3180 180 IP20 ZP7021 Bottom (top optional) Item Dimensions (W × D × H) Unit Side cabinet Main cabinet Side cabinet Main cabinet Side cabinet Without packaging 900 × 855 × 1900 640 × 855 × 1900 1240 × 855 × 1900 500 × 855 × 1900 1640 × 855 × 1900 640 × 855 × 1900 With packaging 1028 × 998 × 2125 766 × 976 × 2116 1356 × 996 × 2160 706 × 966 × 2112 1768 × 998 × 2166 768 × 998 × 2116 1540 × 855 × 1900 Without packaging 900 With packaging 1000 000 Overall net weight Ventilation Airflow 300 (12P) Main cabinet Overall dimension Weight (kg) Power rating (kVA) 200 (12P) 120 (12P) 1740 × 855 × 1900 500 00 1 2280 × 855 × 1900 650 50 1 1300 300 700 1950 950 1400 400 m3/h h 2550 By internal intake fans 2910 22 Protection level 5350 IP20 Color ZP7021 Cable entry Bottom (top optional) Power rating (kVA) Item Dimensions (W × D × H) Unit 400 (6P) Side cabinet Without packaging 1640 × 855 × 1900 With packaging 1768 × 998 × 2166 Overall dimension Weight (kg) Ventilation Airflow 400 (12P) Main cabinet 500 (12P) Rectifier Inverter Rectifier Inverter 640 × 855 × 1900 1225 × 855 × 1900 1055 × 855 × 190 1595 × 855 × 1900 1045 × 855 × 1900 768 × 998 × 2116 1356 × 996 × 2160 1166 × 966 × 2145 2280 × 855 × 1900 1166 × 966 × 2145 2280 × 855 × 1900 2640 × 855 × 1900 Without packaging 1900 300 1200 200 1500 500 With packaging 2000 350 1300 300 1600 600 Overall net weight 2200 200 m3/h 6150 150 By internal intake fans Protection level IP20 IP21 (optional) Color ZP7021 Cable entry Bottom (top optional) Cabling top or bottom from Note: Tables show the standard weight, that is, any option is excluded. Electrical Characteristics (Input Rectifier) Table 1-4 Item Rated mains voltage Unit Vac Supply Electrical characteristics (input rectifier) Power rating (kVA) 80 (6P) 100 (6P) 120 (6P) 120 (12P) 380, 400, or 415 Three phase without neutral Input voltage tolerance 1 % ±15, (maxmally from 290Vac to 498Vac) Frequency Hz 50 or 60 Input frequency tolerance Hz 45 ~ 65 160 (6P) 160 (12P) 200 (6P) 200 (12P) Item Unit Power rating (kVA) 80 (6P) 100 (6P) 120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) Rated input power 2 kVA 95 119 143 140 191 186 239 233 Rated input current2 A 145 181 217 212 289 282 362 353 Maximal input Power3 kVA 110 137 165 161 220 214 274 268 Maximal input current3 A 166 208 249 244 333 325 416 406 Duration of progressive power walk-in4 s 5 ~ 300 Note: 1.. With mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge. 2.. IEC620 -3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery. 3.. IEC620 -3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current. 4.. Set y dedicated setting software Item Rated mains voltage Unit Vac Supply 300 (6P) 300 (12P) Power rating (kVA) 400 (6P) 500 (12P) 380, 400, or 415 Three phase without neutral Input voltage tolerance 1 % ±15, (maxmally from 290Vac to 498Vac) Frequency Hz 50 or 60 Hz 45 ~ 65 Input frequency tolerance Rated input power 2 400 (12P) kVA 365 65 586 A 551 51 885 Maximal input Power3 kVA 420 20 730 Maximal input current3 A 634 34 1106 Duration of progressive power walk-in4 s Rated input current2 5 ~ 300 Note: 1.. With mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge. 2.. IEC620 -3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery. 3.. IEC620 -3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current. 4.. Set y dedicated setting software Electrical Characteristics (DC Intermediate Circuit) Table 1-5 Electrical characteristics (DC intermediate circuit) Item Unit Power rating (kVA) 80 100 120 160 Voltage range for inverter operation Vdc 320 ~ 490 Recommended number of lead-acid cells 1,2 pcs 192 (380Vac) 198 (400Vac) 204 (415Vac) 200 300 400 Item Unit Power rating (kVA) 80 100 120 160 Recommended float charge voltage 2.25V/el.1 Vdc 432 (380Vac) 446 (400Vac) 459 (415Vac) Recommended boost charge voltage 2.35V/el.1 Vdc 451 (380Vac) 465 (400Vac) 479 (415Vac) Maximum voltage on manual charge 2.40 V/el.1 Vdc 461 (380Vac) 475 (400Vac) 490 (415Vac) End-of-discharge voltage 2.45V/el.1 Vdc 471 (380Vac) 485 (400Vac) 500 (415Vac) Max boost charge duration 3 min 480 ~ 1800 Freshening charge duration3 h 1 ~ 36 Boost-float threshold current 3 A 0.001C ~ 0.025C Ripple voltage superimposed 4 % ≤1 200 300 400 400 500 Note: 1.. (According to ated voltage). 2.. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software. 3.. Set y software. 4.. Batt y disconnected, RMS percentage value referred to DC voltage Item Power rating (kVA) Unit 500 Voltage range for inverter operation Vdc 400 ~ 625 Recommended number of lead-acid cells 1,2 pcs 240 (380Vac) 246 (400Vac) 252 (415Vac) Recommended float charge voltage 2.25V/el.1 Vdc 540 (380Vac) 553 (400Vac) 567 (415Vac) Recommended boost charge voltage 2.35V/el.1 Vdc 564 (380Vac) 578 (400Vac) 592 (415Vac) Maximum voltage on manual charge 2.40 V/el.1 Vdc 576 (380Vac) 590 (400Vac) 605 (415Vac) End-of-discharge voltage 2.45V/el.1 Vdc 588 (380Vac) 603 (400Vac) 617 (415Vac) Max boost charge duration 3 min 480 ~ 1800 Freshening charge duration3 h 1 ~ 36 Boost-float threshold current 3 A 0.001C10 ~ 0.025C10 Ripple voltage superimposed 4 % ≤1 Note: 1.. (According to ated voltage). 2.. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software. 3.. Set y software. 4.. Batt y disconnected, RMS percentage value referred to DC voltage Electrical Characteristics (Inverter Output) Table 1-6 Item Rated mains voltage1 Supply Unit Vac Electrical characteristics (inverter output) Power rating (kVA) 80 100 120 380, 400, or 415 Three phase with neutral 160 200 300 Item Power rating (kVA) Unit Frequency2 Hz 80 100 120 160 200 300 400 500 50 or 60 Rated Power at cos = 0.9 kVA 80 100 120 160 200 300 400 500 Rated Power at cos = 1 kW 72 90 108 144 180 270 360 450 Min, I/In 60, 1.10 10, 1.25 1, 1.5 Three-phase transient overload3 Maximal non linear load allowed4 100% Pn Voltage stability, steady State test3 % ±1 Voltage stability, transient test 5 % ±5 Hz/s 3 Maximum rate of change of frequency6 Note: 1. Factory set 380V, 400 or 415 voltages with software setting. 2. Factory set at 50Hz 60 Hz with software setting. 3. IEC62040-3 (5.3.2). 4. IEC62040-3 (ANNEX E). 5. IEC62040-3 (5.3.1), also for 0% ~ 100% ~ 0%, load transient, restore time 20ms to 1%. 6. Factory set at 0.1Hz/s; up to 3Hz/s with software setting Electrical Characteristics (Bypass Input Mains) Table 1-7 Item Unit Rated mains voltage1 Vac Supply Electrical characteristics (bypass input mains) Power rating (kVA) 80 100 120 160 200 300 400 500 759 380, 400, or 415 Three phase with neutral Rated current 380Vac 400Vac 415Vac A Bypass voltage tolerance2 % Default upper limit: 15%; default lower limit: -20% Delay time to recognise bypass voltage returned to window s 2 Inverter output voltage window % ±5 Frequency3 Hz 50 or 60 Input frequency tolerance 4 Hz 45 ~ 65 Maximum frequency slew rate Current rating of neutral cable Protection, bypass line 121 151 181 243 304 456 607 116 145 174 231 289 434 578 723 112 140 167 222 278 416 556 695 1.3In ms I/In The bypass line should be protected using an external device in the input distribution system. This device should be sized to discriminate with the load protection. 10 14.3 20 12.6 50 11.0 Note: 1. Factory set 380V. 400 or 415 voltages with software setting. 2. Other values in -20% ~ 15% with software setting. 3. Factory set at 50Hz 60 Hz with software setting. 4. Other values -5% ~ 5% with software setting 100 10.0 200 9.0 500 8.0 1000 7.1 2000 6.6 5000 5.7 Electrical Characteristics (System Performance) Table 1-8 Item Unit No load losses Electrical characteristics (system performance) Power rating (kVA) 80/100/120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) kW 2.17 2.48 2.75 3.30 3.50 4.15 Full load losses (100%) kW 8.24 8.92 9.63 11.89 11.12 13.91 Item Unit No load losses Full load losses (100%) Power rating (kVA) 300 (6P) 300 (12P) 400 (6P) 400 (12P) 500 (12P) kW 3.90 4.65 4.70 6.67 8.25 kW 19.33 21.8 28.2 31.6 39.6 Electrical Characteristics (ECO Mode) Table 1-9 Item Unit Full load losses (100%) kW Item Unit Full load losses (100%) kW Electrical characteristics (ECO mode) Power rating (kVA) 80/100/120 (6P) 120 (12P) 160 (6P) 160 (12P) 200 (6P) 200 (12P) 2.34 2.64 2.97 3.52 3.55 4.20 Power rating (kVA) 300 (6P) 300 (12P) 400 (6P) 400 (12P) 500 (12P) 5.23 5.91 7.10 8.96 9.32