Liebert Hipluse U UPS;80 - 400kVA; 380/400/415V Conformity And Standard Detailed Specification

advertisement
Liebert Hipluse U UPS;80 - 400kVA; 380/400/415V
Detailed Specification
Conformity And Standard
Table 1-1
Conformity and standard
Item
Normative reference
General safety requirements for UPS
EN62040-1/IEC62040-1/AS62040-1
EMC requirements for UPS
EN62040-2/IEC62040-2/AS62040-2 (C3)
Method of specifying the performance and test requirements of UPS
EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
Note: The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/
EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and
60529)
Environmental Requirements
Table 1-2
Item
Environmental requirements
Power rating (kVA)
Unit
80 ~ 500
Operating Temperature
°C
0 ~ 40°C
Maximal temperature for 8hr day
°C
40°C (derate power by 1.5% per °C between 40°C and 50°C
Mean Temperature for 24hr
°C
Maximum 35°C
Relative humidity
≤95% at 20°C
Altitude of operation
m
≤1000m asl (derate power by 1% per 100m between 1000m and
2000m)
Storage temperature and transport
temperature
°C
-25°C to 70°C
Over-voltage level
Overvoltage level 2
Pollution level
Pollution level 2
Grid system
TN, TT, IT (4-pole switch configured)
Mechanical Characteristics
Table 1-3
Item
Dimensions
(W × D × H)
Weight (kg)
Unit
Power rating (kVA)
80/100/120 (6P)
160 (12P)
200 (6P)
300 (6P)
Without
packaging
900 × 855 ×
1900
1250 × 855 ×
1900
1640 × 855 ×
1900
1240 × 855 ×
1900
1640 × 855 ×
1900
With
packaging
1028 × 998 ×
2125
1366 × 996 ×
2160
1768 × 998 ×
2166
1356 × 996 ×
2160
1768 × 998 ×
2166
Without
packaging
900
With
packaging
1000
000
m3/h
1890
890
Ventilation
Airflow
Protection
level
Color
Cable entry
Mechanical characteristics
160 (6P)
1200
200
1200
200
1300
300
By internal intake fans
3180
180
IP20
ZP7021
Bottom (top optional)
Item
Dimensions
(W × D × H)
Unit
Side cabinet
Main cabinet
Side cabinet
Main cabinet
Side cabinet
Without
packaging
900 × 855 ×
1900
640 × 855 ×
1900
1240 × 855 ×
1900
500 × 855 ×
1900
1640 × 855 ×
1900
640 × 855 ×
1900
With
packaging
1028 × 998 ×
2125
766 × 976 ×
2116
1356 × 996 ×
2160
706 × 966 ×
2112
1768 × 998 ×
2166
768 × 998 ×
2116
1540 × 855 × 1900
Without
packaging
900
With
packaging
1000
000
Overall net
weight
Ventilation
Airflow
300 (12P)
Main cabinet
Overall
dimension
Weight (kg)
Power rating (kVA)
200 (12P)
120 (12P)
1740 × 855 × 1900
500
00
1
2280 × 855 × 1900
650
50
1
1300
300
700
1950
950
1400
400
m3/h
h
2550
By internal intake fans
2910
22
Protection
level
5350
IP20
Color
ZP7021
Cable entry
Bottom (top optional)
Power rating (kVA)
Item
Dimensions
(W × D × H)
Unit
400 (6P)
Side cabinet
Without
packaging
1640 × 855 ×
1900
With
packaging
1768 × 998 ×
2166
Overall
dimension
Weight (kg)
Ventilation
Airflow
400 (12P)
Main cabinet
500 (12P)
Rectifier
Inverter
Rectifier
Inverter
640 × 855 ×
1900
1225 × 855 ×
1900
1055 × 855 ×
190
1595 × 855 ×
1900
1045 × 855 ×
1900
768 × 998 ×
2116
1356 × 996 ×
2160
1166 × 966 ×
2145
2280 × 855 × 1900
1166 × 966 ×
2145
2280 × 855 × 1900
2640 × 855 × 1900
Without
packaging
1900
300
1200
200
1500
500
With
packaging
2000
350
1300
300
1600
600
Overall
net weight
2200
200
m3/h
6150
150
By internal intake fans
Protection
level
IP20
IP21 (optional)
Color
ZP7021
Cable entry
Bottom (top optional)
Cabling top or bottom from
Note: Tables show the standard weight, that is, any option is excluded.
Electrical Characteristics (Input Rectifier)
Table 1-4
Item
Rated mains
voltage
Unit
Vac
Supply
Electrical characteristics (input rectifier)
Power rating (kVA)
80 (6P)
100 (6P)
120 (6P)
120 (12P)
380, 400, or 415
Three phase without neutral
Input voltage
tolerance 1
%
±15, (maxmally from 290Vac to 498Vac)
Frequency
Hz
50 or 60
Input frequency
tolerance
Hz
45 ~ 65
160 (6P)
160 (12P)
200 (6P)
200 (12P)
Item
Unit
Power rating (kVA)
80 (6P)
100 (6P)
120 (6P)
120 (12P)
160 (6P)
160 (12P)
200 (6P)
200 (12P)
Rated input
power 2
kVA
95
119
143
140
191
186
239
233
Rated input
current2
A
145
181
217
212
289
282
362
353
Maximal input
Power3
kVA
110
137
165
161
220
214
274
268
Maximal input
current3
A
166
208
249
244
333
325
416
406
Duration of
progressive
power walk-in4
s
5 ~ 300
Note:
1.. With mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot
guarantee float charge to battery; the battery does not discharge.
2.. IEC620 -3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery.
3.. IEC620 -3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed
current.
4.. Set y dedicated setting software
Item
Rated mains
voltage
Unit
Vac
Supply
300 (6P)
300 (12P)
Power rating (kVA)
400 (6P)
500 (12P)
380, 400, or 415
Three phase without neutral
Input voltage
tolerance 1
%
±15, (maxmally from 290Vac to 498Vac)
Frequency
Hz
50 or 60
Hz
45 ~ 65
Input frequency
tolerance
Rated input
power 2
400 (12P)
kVA
365
65
586
A
551
51
885
Maximal input
Power3
kVA
420
20
730
Maximal input
current3
A
634
34
1106
Duration of
progressive
power walk-in4
s
Rated input
current2
5 ~ 300
Note:
1.. With mains at -15% nd suggested battery elements the UPS maintains the output rated voltage at rated load but cannot
guarantee float charge to battery; the battery does not discharge.
2.. IEC620 -3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery.
3.. IEC620 -3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed
current.
4.. Set y dedicated setting software
Electrical Characteristics (DC Intermediate Circuit)
Table 1-5
Electrical characteristics (DC intermediate circuit)
Item
Unit
Power rating (kVA)
80
100
120
160
Voltage range for inverter operation
Vdc
320 ~ 490
Recommended number of lead-acid cells 1,2
pcs
192 (380Vac)
198 (400Vac)
204 (415Vac)
200
300
400
Item
Unit
Power rating (kVA)
80
100
120
160
Recommended float charge voltage 2.25V/el.1
Vdc
432 (380Vac)
446 (400Vac)
459 (415Vac)
Recommended boost charge voltage
2.35V/el.1
Vdc
451 (380Vac)
465 (400Vac)
479 (415Vac)
Maximum voltage on manual charge 2.40
V/el.1
Vdc
461 (380Vac)
475 (400Vac)
490 (415Vac)
End-of-discharge voltage 2.45V/el.1
Vdc
471 (380Vac)
485 (400Vac)
500 (415Vac)
Max boost charge duration 3
min
480 ~ 1800
Freshening charge duration3
h
1 ~ 36
Boost-float threshold current 3
A
0.001C ~ 0.025C
Ripple voltage superimposed 4
%
≤1
200
300
400
400
500
Note:
1.. (According to ated voltage).
2.. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software.
3.. Set y software.
4.. Batt y disconnected, RMS percentage value referred to DC voltage
Item
Power rating (kVA)
Unit
500
Voltage range for inverter operation
Vdc
400 ~ 625
Recommended number of lead-acid cells 1,2
pcs
240 (380Vac)
246 (400Vac)
252 (415Vac)
Recommended float charge voltage 2.25V/el.1
Vdc
540 (380Vac)
553 (400Vac)
567 (415Vac)
Recommended boost charge voltage
2.35V/el.1
Vdc
564 (380Vac)
578 (400Vac)
592 (415Vac)
Maximum voltage on manual charge 2.40
V/el.1
Vdc
576 (380Vac)
590 (400Vac)
605 (415Vac)
End-of-discharge voltage 2.45V/el.1
Vdc
588 (380Vac)
603 (400Vac)
617 (415Vac)
Max boost charge duration 3
min
480 ~ 1800
Freshening charge duration3
h
1 ~ 36
Boost-float threshold current 3
A
0.001C10 ~ 0.025C10
Ripple voltage superimposed 4
%
≤1
Note:
1.. (According to ated voltage).
2.. Fact y set for rated 380V, different cells number and voltage per cell may be set by configuration software.
3.. Set y software.
4.. Batt y disconnected, RMS percentage value referred to DC voltage
Electrical Characteristics (Inverter Output)
Table 1-6
Item
Rated mains voltage1
Supply
Unit
Vac
Electrical characteristics (inverter output)
Power rating (kVA)
80
100
120
380, 400, or 415
Three phase with neutral
160
200
300
Item
Power rating (kVA)
Unit
Frequency2
Hz
80
100
120
160
200
300
400
500
50 or 60
Rated Power at cos = 0.9
kVA
80
100
120
160
200
300
400
500
Rated Power at cos = 1
kW
72
90
108
144
180
270
360
450
Min, I/In
60, 1.10
10, 1.25
1, 1.5
Three-phase transient overload3
Maximal non linear load allowed4
100% Pn
Voltage stability, steady State test3
%
±1
Voltage stability, transient test 5
%
±5
Hz/s
3
Maximum rate of change of
frequency6
Note:
1. Factory set 380V, 400 or 415 voltages with software setting.
2. Factory set at 50Hz 60 Hz with software setting.
3. IEC62040-3 (5.3.2).
4. IEC62040-3 (ANNEX E).
5. IEC62040-3 (5.3.1), also for 0% ~ 100% ~ 0%, load transient, restore time 20ms to 1%.
6. Factory set at 0.1Hz/s; up to 3Hz/s with software setting
Electrical Characteristics (Bypass Input Mains)
Table 1-7
Item
Unit
Rated mains voltage1
Vac
Supply
Electrical characteristics (bypass input mains)
Power rating (kVA)
80
100
120
160
200
300
400
500
759
380, 400, or 415
Three phase with neutral
Rated current
380Vac
400Vac
415Vac
A
Bypass voltage
tolerance2
%
Default upper limit: 15%; default lower limit: -20%
Delay time to
recognise bypass
voltage returned to
window
s
2
Inverter output voltage
window
%
±5
Frequency3
Hz
50 or 60
Input frequency
tolerance 4
Hz
45 ~ 65
Maximum frequency
slew rate
Current rating of
neutral cable
Protection, bypass
line
121
151
181
243
304
456
607
116
145
174
231
289
434
578
723
112
140
167
222
278
416
556
695
1.3In
ms
I/In
The bypass line should be protected using an external device in the input distribution system.
This device should be sized to discriminate with the load protection.
10
14.3
20
12.6
50
11.0
Note:
1. Factory set 380V. 400 or 415 voltages with software setting.
2. Other values in -20% ~ 15% with software setting.
3. Factory set at 50Hz 60 Hz with software setting.
4. Other values -5% ~ 5% with software setting
100
10.0
200
9.0
500
8.0
1000
7.1
2000
6.6
5000
5.7
Electrical Characteristics (System Performance)
Table 1-8
Item
Unit
No load losses
Electrical characteristics (system performance)
Power rating (kVA)
80/100/120 (6P)
120 (12P)
160 (6P)
160 (12P)
200 (6P)
200 (12P)
kW
2.17
2.48
2.75
3.30
3.50
4.15
Full load
losses (100%)
kW
8.24
8.92
9.63
11.89
11.12
13.91
Item
Unit
No load losses
Full load
losses (100%)
Power rating (kVA)
300 (6P)
300 (12P)
400 (6P)
400 (12P)
500 (12P)
kW
3.90
4.65
4.70
6.67
8.25
kW
19.33
21.8
28.2
31.6
39.6
Electrical Characteristics (ECO Mode)
Table 1-9
Item
Unit
Full load
losses (100%)
kW
Item
Unit
Full load
losses (100%)
kW
Electrical characteristics (ECO mode)
Power rating (kVA)
80/100/120 (6P)
120 (12P)
160 (6P)
160 (12P)
200 (6P)
200 (12P)
2.34
2.64
2.97
3.52
3.55
4.20
Power rating (kVA)
300 (6P)
300 (12P)
400 (6P)
400 (12P)
500 (12P)
5.23
5.91
7.10
8.96
9.32
Download