Surge Arresters 3EL superior protection up to 550 kV Answers for energy.

Surge Arresters 3EL
superior protection up to 550 kV
Light weight. Strong performance.
Answers for energy.
Simply irresistible.
By resisting wear in any environment.
Our high voltage surge arresters with silicone housing are
leading the way with superior design and construction. Built
with silicone directly molded onto the metal oxide (MO)
blocks, all arresters simply resist discharge and moisture
ingress under nearly all physical or environmental
conditions.
The surge arresters 3EL provide superior protection for system
voltages from 3.6 up to 550 kV. Combine these advantages
with a lightweight Cage Design™ and high robustness, and you
have outstandingly cost-effective solutions for station arresters,
line surge arresters or equipment protection. What do we
call these irresistible surge arresters? Simply 3EL. Another
outstanding product family from Siemens.
Good reasons for the 3EL
Our 3EL arresters use the same MO blocks as our 3EP and 3EQ
arrester product lines resulting in the same excellent electrical
performance. The innovative cage design using silicone and
fibreglass-reinforced plastic (FRP) rods as housing material leads
to a lot of additional advantages.
Cage design: high mechanical strength and
safe overload performance
The MO blocks of the 3EL are enclosed by a cage of prestressed
fibreglass-reinforced plastic (FRP) rods. The high tensile
strength of the FRP rods is used to hold together tightly the
arrester‘s MO blocks. The result is the 3EL family having one of
the highest mechanical strengths of polymer arresters available
on the market – in very low weight. In case of an overload or
a short circuit of the arrester – an extremely rare event – it is
impossible that any high pressure is built up because the MO
blocks are not enclosed in a sealed mechanical shell or wrapped
by any hard material. This permits the arc to escape directly
through the soft silicone housing and makes it hardly possible
that any internal parts could be ejected damaging other
equipment even if it is installed very close.
Long service life
Silicone is the only polymeric material that maintains its
hydrophobicity throughout its lifetime. Other polymeric
materials may be hydrophobic too, but lose their hydrophobicity
after a short period. Additionally, the silicone used for our 3EL
arresters is highly fire-retardant and self-extinguishing and is
2
not subject to erosion or UV radiation, which guarantees
long-term stability of the housing material (unlike other
polymeric materials like e.g. EPDM). The aging resistance of
our 3EL arresters has been proven by accelerated aging tests
(1000/5000 h salt fog test).
A long service life of 3EL arresters is also ensured by its cage
design: silicone is directly molded onto the MO blocks ensuring
total enclosure of all components free of bubbles and gaps
and thus making impossible any partial discharges or moisture
ingress.
Light weight – flexible and easy installation
The use of FRP and silicone as housing materials leads to a low
weight of our 3EL arresters, allowing easy transport and flexible
installation at all mounting angles (e.g. horizontal, vertical,
hung from the transmission line as line surge arrester). The
strength and weight of arrester supports can be reduced
as well as the need of heavy installation equipment. The sheds
of the 3EL are resistant to damage arising from transport,
installation, storms, earthquakes or vandalism.
Silicone: best performance under pollution
conditions
The silicone material used for our 3EL arresters is highly
hydrophobic – water and pollution do not form a continuous
conductive film on the surface. Thus surface currents and the
risk of flashover are reduced, especially in polluted or coastal
environments.
Superior material and design leading to an outstanding price-performance ratio …
… during operation
… during transport and installation
safe overload performance and high
mechanical strength due to cage design
light weight, easy and flexible installation
at all mounting angles
excellent electrical performance
resistance to damage arising from transport,
installation or vandalism
long-term stable hydrophobicity of silicone
housing ensures best performance even under
extreme environmental conditions (industrial/
polluted, coastal, desert)
extended creepage distance
… throughout the entire life cycle
long service life, no moisture ingress due to
direct molding of silicone onto MO blocks
highly fire-retardant and self-extinguishing
Applications:
About IEC 60099-4
As a station arrester or line surge arrester for protection of
switchgear, transformers and other equipment in highvoltage systems up to Um = 550 kV against lightning and
switching overvoltages
For all arrester applications with high mechanical
requirements (up to 4 kNm, dynamic)
For erection at all mounting angles, e.g. hung from the
station structures, vertical installation, hung from the
transmission line (as line surge arrester)
For all applications where low weight and nonfragility of the
arrester are required
The IEC 60099-4 standard was extended in July 2006
by new rules for short-circuit tests of arresters. Whether
an arrester complies with the newly introduced
differentiation “Design A” or “Design B” depends on the
existence and size of the gas volume inside. While Design
A arresters are typically hollow (e.g. with porcelain or
composite housings), Design B arresters contain just a
small gas volume or none at all, so typically they are not
designed with pressure relief (e.g. „cage design“ or
„wrapped design“). Design B arresters are no longer
allowed to be tested with an internal fuse wire. Instead,
the so-called “pre-failing method” must be used before the
application of the high short-circuit current.
Our innovative “cage design” arresters – such as the 3EL2 –
are considered “Design B” according to the new standard.
Siemens was the first complete-range manufacturer
already fully in compliance with the new rules.
LD class Long duration current
impulse Max. value / A
3.6 7.2
4
3
3
2
2
2
1200
1200
1100
1100
750
550
12
24
36
52
Um
72.5 123 145 170 245 300 362 420 550
3EL2
3EL2
3EL2
3EL2
3EL1
3EL5
3
Matching to any requirement.
Electrical data.
Maximum values
3EL5
3EL1
3EL2
3EL2
3EL2
3EL2
Highest voltage for equipment Um
kV
145
362
362
420
420
550
Maximum rated voltage Ur
kV
126
288
288
360
360
468
Maximum nominal discharge current In
kA
10
10
10
10
10
20
2
2
2
3
3
4
Maximum line discharge class
Maximum energy absorption capability
Maximum long duration current impulse
Rated short circuit current
Maximum permissible service load
Highest
voltage
for equipment
Rated
voltage
Um
kV
Ur
kV
3.6
7.2
12
17.5
4
Continuous
Line
operating discharge
voltage
class
kJ/kVr
4.4
5
5
8
8
10
A
550
750
1100
1100
1200
1200
kA
20
65
65
65
65
65
kNm
0.5
1.2
4
4
4
4
Longduration
current
2 ms
Maximum values of the residual voltages at discharge
currents of the following impulses
30/60 μs
1 kA
kV
30/60 μs
2 kA
kV
8/20 μs
3 kA
kV
8/20 μs
5 kA
kV
8/20 μs
10 kA
kV
8/20 μs
15 kA
kV
8/20 μs
20 kA
kV
8/20 μs
40 kA
kV
30/60 μs
0.125 kA
kV
30/60 μs
0.5 kA
kV
Uc
kV
LD-CIass
I
3
2.4
2
550
6.8
7.2
7.4
8.0
8.6
9.2
9.8
11.4
6.2
6.6
3
2.4
2
750
6.1
6.4
6.7
7.1
7.7
8.2
8.6
9.8
5.6
5.9
6
4.8
2
750
12.2
12.9
13.3
14.2
15.3
16.4
17.1
19.6
11.2
11.8
6
4.8
2
550
13.7
14.4
14.9
15.9
17.1
18.5
19.7
22.7
12.5
13.2
6
4.8
2
750
12.2
12.9
13.3
14.2
15.3
16.4
17.1
19.6
11.2
11.8
9
7.2
2
550
20.5
21.5
22.3
23.9
25.7
27.7
29.5
34.1
18.7
19.8
9
7.2
2
750
18.4
19.3
20.0
21.3
23.0
24.6
25.7
29.4
16.8
17.7
9
7.2
2
1100
16.6
17.4
17.8
19.0
20.3
21.5
22.5
25.5
15.4
16.2
9
7.2
3
1100
17.3
18.2
18.6
19.9
21.2
22.9
24.0
27.2
16.4
17.3
9
7.2
3
1200
16.8
17.6
18.0
19.0
20.3
21.3
22.3
24.3
15.6
16.4
9
7.2
2
750
18.4
19.3
20.0
21.3
23.0
24.6
25.7
29.4
16.8
17.7
9
7.2
2
1100
16.6
17.4
17.8
19.0
20.3
21.5
22.5
25.5
15.4
16.2
9
7.2
3
1100
17.3
18.2
18.6
19.9
21.2
22.9
24.0
27.2
16.4
17.3
9
7.2
3
1200
16.8
17.6
18.0
19.0
20.3
21.3
22.3
24.3
15.6
16.4
12
9.6
2
550
27.4
28.7
29.8
31.8
34.2
36.9
39.3
45.5
25.0
26.3
15
12.0
2
750
30.6
32.1
33.3
35.6
38.3
40.9
42.8
49.0
27.9
29.5
15
12.0
2
1100
27.7
29.0
29.7
31.7
33.8
35.8
37.5
42.5
25.7
27.0
15
12.0
3
1100
28.9
30.3
31.0
33.1
35.3
38.2
40.0
45.4
27.4
28.8
15
12.0
3
1200
28.0
29.4
30.0
31.7
33.8
35.4
37.1
40.5
26.0
27.3
15
12.0
4
1200
29.9
31.3
32.0
33.8
36.0
37.8
39.6
43.2
27.7
29.2
15
12.0
2
550
34.2
35.9
37.2
39.8
42.8
46.2
49.2
56.9
31.2
32.9
15
12.0
2
750
30.6
32.1
33.3
35.6
38.3
40.9
42.8
49.0
27.9
29.5
15
12.0
2
1100
27.7
29.0
29.7
31.7
33.8
35.8
37.5
42.5
25.7
27.0
15
12.0
3
1100
28.9
30.3
31.0
33.1
35.3
38.2
40.0
45.4
27.4
28.8
15
12.0
3
1200
28.0
29.4
30.0
31.7
33.8
35.4
37.1
40.5
26.0
27.3
15
12.0
4
1200
29.9
31.3
32.0
33.8
36.0
37.8
39.6
43.2
27.7
29.2
18
14.4
2
750
36.7
38.6
39.9
42.7
45.9
49.1
51.4
58.8
33.5
35.3
18
14.4
2
1100
33.2
34.8
35.6
38.1
40.5
42.9
45.0
51.0
30.8
32.4
18
14.4
3
1100
34.7
36.4
37.2
39.8
42.3
45.8
48.0
54.4
32.8
34.6
Power frequency voltage versus time characteristic (TOV)
Condition:
Arrest er type
Number
of units
Housing
insulation
Specified
short-term
load SSL
(Fdyn)
Lightning impulse Power frequency
withstand voltage withstand voltage
1.2/50 μs
1 min. wet
kV
kV
Specified
long-term
load SLL
(Fstat)
Height
(H)
Creepage
distance
Flashover
distance
Weight
Figure
N
N
mm
mm
mm
kg
3EL5 003 - 0 P B 2 1 - 4 xxx
1
104
49
2940
2050
170
372
180
3.7
51
3EL1 003 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
6.4
11
3EL1 006 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
7.2
11
3EL5 006 - 0 P B 2 1 - 4 xxx
1
104
49
2940
2050
170
372
180
3.8
51
3EL1 006 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
7.2
11
3EL5 009 - 0 P C 2 1 - 4 xxx
1
122
57
2500
1750
200
485
210
4.2
51
3EL1 009 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
7.6
11
3EL2 009 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.3
21
3EL2 009 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.3
21
3EL2 009 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
17.3
21
3EL1 009 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
7.6
11
3EL2 009 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.3
21
3EL2 009 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.3
21
3EL2 009 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
17.3
21
3EL5 012 - 0 P D 2 1 - 4 xxx
1
144
67
2080
1450
240
605
248
4.6
51
3EL1 015 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
7.9
11
3EL2 015 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.8
21
3EL2 015 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.8
21
3EL2 015 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.0
21
3EL2 015 - 6 P C 4 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.0
21
3EL5 015 - 0 P D 2 1 - 4 xxx
1
144
67
2080
1450
240
605
248
4.7
51
3EL1 015 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
7.9
11
3EL2 015 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.8
21
3EL2 015 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.8
21
3EL2 015 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.0
21
3EL2 015 - 6 P C 4 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.0
21
3EL1 018 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
8.6
11
3EL2 018 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.8
21
3EL2 018 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.8
21
5
Highest
voltage
for equipment
Rated
voltage
Um
kV
Ur
kV
Uc
kV
LD-CIass
I
17.5
18
14.4
3
1200
33.6
35.2
36.0
38.1
40.5
42.5
44.6
48.6
31.2
32.8
18
14.4
4
1200
35.9
37.6
38.4
40.6
43.2
45.4
47.5
51.8
33.3
35.0
24
19.2
2
750
49.0
51.4
53.2
56.9
61.2
65.5
68.5
78.3
44.7
47.1
24
19.2
2
1100
44.3
46.4
47.5
50.8
54.0
57.2
59.9
68.0
41.0
43.2
24
19.2
3
1100
46.2
48.5
49.6
53.0
56.4
61.1
63.9
72.6
43.8
46.1
24
19.2
3
1200
44.8
47.0
48.1
50.8
54.0
56.7
59.4
64.8
41.6
43.7
24
19.2
4
1200
47.8
50.1
51.3
54.1
57.6
60.5
63.4
69.1
44.4
46.7
18
14.4
2
550
41.0
43.1
44.6
47.7
51.3
55.4
59.0
68.2
37.4
39.5
21
16.8
2
550
47.9
50.3
52.1
55.7
59.9
64.6
68.8
79.6
43.7
46.1
21
16.8
2
750
42.8
45.0
46.6
49.8
53.6
57.3
60.0
68.5
39.1
41.2
21
16.8
2
1100
38.7
40.6
41.6
44.4
47.3
50.1
52.4
59.5
35.9
37.8
21
16.8
3
1100
40.5
42.4
43.4
46.4
49.4
53.4
55.9
63.5
38.3
40.3
21
16.8
3
1200
39.2
41.1
42.1
44.4
47.3
49.6
52.0
56.7
36.4
38.3
21
16.8
4
1200
41.8
43.8
44.9
47.4
50.4
52.9
55.4
60.5
38.8
40.8
30
24.0
2
750
61.2
64.3
66.6
71.1
76.5
81.9
85.7
97.9
55.8
58.9
30
24.0
2
1100
55.4
58.1
59.4
63.5
67.5
71.6
74.9
85.1
51.3
54.0
30
24.0
3
1100
57.8
60.6
62.0
66.3
70.5
76.3
79.9
90.7
54.7
57.6
30
24.0
3
1200
56.0
58.7
60.1
63.5
67.5
70.9
74.3
81.0
52.0
54.7
30
24.0
4
1200
59.8
62.6
64.1
67.7
72.0
75.6
79.2
86.4
55.4
58.3
30
24
19.2
2
550
54.7
57.5
59.5
63.6
68.4
73.9
78.7
91.0
49.9
52.7
36
27
21.6
2
550
61.6
64.6
66.9
71.6
77.0
83.1
88.5
102
56.2
59.3
30
24.0
2
550
68.4
71.8
74.4
79.5
85.5
92.3
98.3
114
62.4
65.8
30
24.0
2
750
61.2
64.3
66.6
71.1
76.5
81.9
85.7
97.9
55.8
58.9
30
24.0
2
1100
55.4
58.1
59.4
63.5
67.5
71.6
74.9
85.1
51.3
54.0
30
24.0
3
1100
57.8
60.6
62.0
66.3
70.5
76.3
79.9
90.7
54.7
57.6
30
24.0
3
1200
56.0
58.7
60.1
63.5
67.5
70.9
74.3
81.0
52.0
54.7
30
24.0
4
1200
59.8
62.6
64.1
67.7
72.0
75.6
79.2
86.4
55.4
58.3
33
26.4
2
550
75.2
79.0
81.8
87.5
94.1
102
108
125
68.7
72.4
45
36
2
1100
83.0
87.1
89.1
95.2
101
107
112
128
77.0
81.0
45
36
3
1100
86.7
90.9
93.1
99.4
106
114
120
136
82.1
86.4
45
36
3
1200
84.0
88.1
90.1
95.2
101
106
111
122
78.0
82.0
45
36
4
1200
89.6
94.0
96.1
102
108
113
119
130
83.2
87.5
24
6
Continuous
Line
operating discharge
voltage
class
Longduration
current
2 ms
Maximum values of the residual voltages at discharge
currents of the following impulses
30/60 μs
1 kA
kV
30/60 μs
2 kA
kV
8/20 μs
3 kA
kV
8/20 μs
5 kA
kV
8/20 μs
10 kA
kV
8/20 μs
15 kA
kV
8/20 μs
20 kA
kV
8/20 μs
40 kA
kV
30/60 μs
0.125 kA
kV
30/60 μs
0.5 kA
kV
To find the right arrester
just follow the color codes
Long duration
LD
class current impulse
max. value / A
4
3
3
2
2
2
3EL2
3EL2
3EL2
3EL2
3EL1
3EL5
Arrest er type
Number
of units
Housing
insulation
Specified
short-term
load SSL
(Fdyn)
Lightning impulse Power frequency
withstand voltage withstand voltage
1.2/50 μs
1 min. wet
kV
kV
Specified
long-term
load SLL
(Fstat)
Height
(H)
Creepage
distance
Flashover
distance
1200
1200
1100
1100
750
550
Weight
Figure
N
N
mm
mm
mm
kg
3EL2 018 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
17.8
3EL2 018 - 6 P C 4 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
17.8
21
3EL1 024 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
9.4
11
3EL2 024 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.4
21
3EL2 024 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.4
21
3EL2 024 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.6
21
3EL2 024 - 6 P C 4 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.6
21
3EL5 018 - 0 P F 2 1 - 4 xxx
1
184
86
1660
1160
300
900
318
5.3
51
3EL5 021 - 0 P F 2 1 - 4 xxx
1
184
86
1660
1160
300
900
318
5.4
51
3EL1 021 - 1 P C 2 1 - 4 xxx
1
183
85
3930
2750
305
900
315
8.9
11
3EL2 021 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.4
21
3EL2 021 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.4
21
3EL2 021 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.6
21
3EL2 021 - 6 P C 4 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
18.6
21
3EL1 030 - 1 P E 2 1 - 4 xxx
1
264
123
2690
1880
445
1400
455
9.8
12
3EL2 030 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.9
21
3EL2 030 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.9
21
3EL2 030 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.3
21
3EL2 030 - 6 P C 4 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.9
21
3EL5 024 - 0 P H 2 1 - 4 xxx
1
242
113
1250
870
400
1230
418
6.3
52
3EL5 027 - 0 P H 2 1 - 4 xxx
1
242
113
1250
870
400
1230
418
6.4
52
3EL5 030 - 0 P H 2 1 - 4 xxx
1
242
113
1250
870
400
1230
418
6.5
52
3EL1 030 - 1 P E 2 1 - 4 xxx
1
264
123
2690
1880
445
1400
455
9.8
12
3EL2 030 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.9
21
3EL2 030 - 2 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.9
21
3EL2 030 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.3
21
3EL2 030 - 6 P C 4 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
19.9
21
3EL5 033 - 0 P K 2 1 - 4 xxx
1
302
140
980
680
510
1595
520
7.4
53
3EL2 045 - 2 P F 2 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
24.3
21
3EL2 045 - 2 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
24.3
21
3EL2 045 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
23.1
21
3EL2 045 - 6 P F 4 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
23.1
21
21
7
Highest
voltage
for equipment
Rated
voltage
Um
kV
Ur
kV
Uc
kV
LD-CIass
48
36
28.8
2
39
31.2
42
42
52
72.5
8
Continuous
Line
operating discharge
voltage
class
Longduration
current
2 ms
Maximum values of the residual voltages at discharge
currents of the following impulses
I
30/60 μs
1 kA
kV
30/60 μs
2 kA
kV
8/20 μs
3 kA
kV
8/20 μs
5 kA
kV
8/20 μs
10 kA
kV
8/20 μs
15 kA
kV
550
82.1
86.2
89.3
95.4
103
111
2
550
88.9
93.4
96.7
103
111
120
34
2
550
95.8
101
104
111
120
129
34
2
750
85.7
90.0
93.2
99.6
107
115
42
34
2
1100
77.5
81.3
83.2
88.8
94.5
42
34
3
1100
80.9
84.9
86.9
92.8
42
34
3
1200
78.4
82.2
84.1
42
34
4
1200
83.7
87.7
45
36
2
550
103
45
36
2
750
91.8
48
38
2
550
109
51
41
2
550
54
43
2
54
43
54
43
54
8/20 μs
20 kA
kV
8/20 μs
40 kA
kV
30/60 μs
0.125 kA
kV
30/60 μs
0.5 kA
kV
118
136
74.9
79.0
128
148
81.1
85.6
138
159
87.4
92.2
120
137
78.2
82.5
100
105
119
71.8
75.6
98.7
107
112
127
76.6
80.6
88.8
94.5
99.2
104
113
72.8
76.5
89.7
94.8
101
106
111
121
77.6
81.6
108
112
119
128
139
147
171
93.6
98.8
96.4
99.8
107
115
123
129
147
83.8
88.4
115
119
127
137
148
157
182
99.9
105
116
122
126
135
145
157
167
193
106
112
1100
99.6
104
107
114
122
129
135
153
92.3
97.2
3
1100
104
109
112
119
127
137
144
163
98.5
104
3
1200
101
106
108
114
122
128
134
146
93.6
98.4
43
4
1200
108
113
115
122
130
136
143
156
99.8
105
54
43
2
550
123
129
134
143
154
166
177
205
112
119
54
43
2
750
110
116
120
128
138
147
154
176
101
106
57
46
2
550
130
136
141
151
162
175
187
216
119
125
60
48
2
550
137
144
149
159
171
185
197
227
125
132
60
48
2
750
122
129
133
142
153
164
171
196
112
118
60
48
2
1100
111
116
119
127
135
143
150
170
103
108
60
48
3
1100
116
121
124
133
141
153
160
181
109
115
60
48
3
1200
112
117
120
127
135
142
149
162
104
109
60
48
4
1200
120
125
128
135
144
151
158
173
111
117
66
53
2
750
135
141
146
157
168
180
188
215
123
130
66
53
2
1100
122
128
131
140
149
157
165
187
113
119
66
53
3
1100
127
133
136
146
155
168
176
200
120
127
66
53
3
1200
123
129
132
140
149
156
163
178
114
120
66
53
4
1200
131
138
141
149
158
166
174
190
122
128
72
58
2
550
164
172
179
191
205
222
236
273
150
158
72
58
2
750
147
154
160
171
184
196
206
235
134
141
72
58
2
1100
133
139
143
152
162
172
180
204
123
130
72
58
3
1100
139
146
149
159
169
183
192
218
131
138
72
58
3
1200
134
141
144
152
162
170
178
194
125
131
72
58
4
1200
143
150
154
162
173
181
190
207
133
140
To find the right arrester
just follow the color codes
Long duration
LD
class current impulse
max. value / A
4
3
3
2
2
2
3EL2
3EL2
3EL2
3EL2
3EL1
3EL5
Arrest er type
Number
of units
Housing
insulation
Specified
short-term
load SSL
(Fdyn)
Lightning impulse Power frequency
withstand voltage withstand voltage
1.2/50 μs
1 min. wet
kV
kV
Specified
long-term
load SLL
(Fstat)
Height
(H)
1200
1200
1100
1100
750
550
Creepage
distance
Flashover
distance
Weight
Figure
N
N
mm
mm
mm
kg
3EL5 036 - 0 P K 2 1 - 4 xxx
1
302
140
980
680
510
1595
520
7.5
53
3EL5 039 - 0 P K 2 1 - 4 xxx
1
302
140
980
680
510
1595
520
7.6
53
3EL5 042 - 0 P K 2 1 - 4 xxx
1
302
140
980
680
510
1595
520
7.8
53
3EL1 042 - 1 P E 2 1 - 4 xxx
1
264
123
2690
1880
445
1400
455
10.3
12
3EL2 042 - 2 P C 2 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
21.0
21
3EL2 042 - 2 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
24.3
21
3EL2 042 - 6 P C 3 1 - 4 xxx
1
235
109
8290
5800
482
1470
405
20.5
21
3EL2 042 - 6 P F 4 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
23.1
21
3EL5 045 - 0 P H 2 2 - 4 xxx
2
484
226
620
430
800
2460
836
10.5
54
3EL1 045 - 2 P E 2 1 - 4 xxx
1
264
123
2690
1880
445
1400
455
10.9
12
3EL5 048 - 0 P H 2 2 - 4 xxx
2
484
226
620
430
800
2460
836
10.6
54
3EL5 051 - 0 P H 2 2 - 4 xxx
2
484
226
620
430
800
2460
836
10.7
54
3EL2 054 - 2 P F 2 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
24.8
21
3EL2 054 - 2 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.4
21
3EL2 054 - 6 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
23.8
21
3EL2 054 - 6 P F 4 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
24.4
21
3EL5 054 - 0 P H 2 2 - 4 xxx
2
484
226
620
430
800
2460
836
10.9
54
3EL1 054 - 1 P H 2 1 - 4 xxx
1
365
170
1930
1350
620
2050
630
11.4
13
3EL5 057 - 0 P H 2 2 - 4 xxx
2
484
226
620
430
800
2460
836
11.0
54
3EL5 060 - 0 P H 2 2 - 4 xxx
2
484
226
620
430
800
2460
836
11.1
54
3EL1 060 - 1 P H 2 1 - 4 xxx
1
365
170
1930
1350
620
2050
630
12.9
13
3EL2 060 - 2 P F 2 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.4
21
3EL2 060 - 2 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.4
21
3EL2 060 - 6 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
24.4
21
3EL2 060 - 6 P F 4 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.1
21
3EL1 066 - 1 P H 2 1 - 4 xxx
1
365
170
1930
1350
620
2050
630
12.9
13
3EL2 066 - 2 P F 2 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.9
21
3EL2 066 - 2 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.9
21
3EL2 066 - 6 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.1
21
3EL2 066 - 6 P F 4 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.7
21
3EL5 072 - 0 L K 2 2 - 4 xxx
2
604
280
490
340
1020
3190
1040
13.1
-
3EL1 072 - 1 P H 2 1 - 4 xxx
1
365
170
1930
1350
620
2050
630
13.2
13
3EL2 072 - 2 P F 2 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
26.5
21
3EL2 072 - 2 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
27.0
21
3EL2 072 - 6 P F 3 1 - 4 xxx
1
365
170
5670
3970
705
2340
630
25.7
21
3EL2 072 - 6 P J 4 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
26.3
22
9
Highest
voltage
for equipment
Rated
voltage
Um
kV
Ur
kV
123
145
10
Continuous
Line
operating discharge
voltage
class
Longduration
current
2 ms
Maximum values of the residual voltages at discharge
currents of the following impulses
LD-CIass
I
30/60 μs
1 kA
kV
96
77
2
550
219
230
238
254
274
295
315
364
200
211
96
77
2
750
196
206
213
228
245
262
274
313
179
188
96
77
2
1100
177
186
190
203
216
229
240
272
164
173
96
77
3
1100
185
194
199
212
226
244
256
290
175
184
96
77
3
1200
179
188
192
203
216
227
238
259
166
175
96
77
4
1200
191
200
205
217
230
242
253
276
177
187
102
82
2
550
233
244
253
270
291
314
334
387
212
224
102
82
2
750
208
218
226
242
260
278
291
333
190
200
102
82
2
1100
188
197
202
216
230
243
255
289
174
184
102
82
3
1100
197
206
211
225
240
259
272
308
186
196
102
82
3
1200
190
200
204
216
230
241
252
275
177
186
102
82
4
1200
203
213
218
230
245
257
269
294
188
198
108
86
2
550
246
259
268
286
308
332
354
409
225
237
108
86
2
750
220
231
240
256
275
295
308
353
201
212
108
86
2
1100
199
209
214
228
243
258
270
306
185
194
108
86
3
1100
208
218
223
239
254
275
288
327
197
207
108
86
3
1200
202
211
216
228
243
255
267
292
187
197
108
86
4
1200
215
226
231
244
259
272
285
311
200
210
111
89
2
750
226
238
246
263
283
303
317
362
207
218
120
96
2
750
245
257
266
285
306
327
343
392
223
236
120
96
2
1100
221
232
238
254
270
286
300
340
205
216
120
96
3
1100
231
243
248
265
282
305
320
363
219
230
120
96
3
1200
224
235
240
254
270
284
297
324
208
219
120
96
4
1200
239
251
256
271
288
302
317
346
222
233
126
101
2
550
287
302
312
334
359
388
413
478
262
277
132
106
2
750
269
283
293
313
337
360
377
431
246
259
132
106
2
1100
244
255
261
279
297
315
330
374
226
238
132
106
3
1100
254
267
273
292
310
336
352
399
241
253
132
106
3
1200
247
258
264
279
297
312
327
356
229
241
132
106
4
1200
263
276
282
298
317
333
348
380
244
257
144
115
2
750
294
308
319
341
367
393
411
470
268
283
144
115
2
1100
266
279
285
305
324
343
360
408
246
259
144
115
3
1100
277
291
298
318
338
366
384
435
263
276
144
115
3
1200
269
282
288
305
324
340
356
389
249
262
144
115
4
1200
287
301
308
325
346
363
380
415
266
280
Uc
kV
30/60 μs
2 kA
kV
8/20 μs
3 kA
kV
8/20 μs
5 kA
kV
8/20 μs
10 kA
kV
8/20 μs
15 kA
kV
8/20 μs
20 kA
kV
8/20 μs
40 kA
kV
30/60 μs
0.125 kA
kV
30/60 μs
0.5 kA
kV
To find the right arrester
just follow the color codes
Long duration
LD
class current impulse
max. value / A
4
3
3
2
2
2
3EL2
3EL2
3EL2
3EL2
3EL1
3EL5
Arrest er type
Number
of units
Housing
insulation
Specified
short-term
load SSL
(Fdyn)
Lightning impulse Power frequency
withstand voltage withstand voltage
1.2/50 μs
1 min. wet
kV
kV
Specified
long-term
load SLL
(Fstat)
Height
(H)
Creepage
distance
Flashover
distance
1200
1200
1100
1100
750
550
Weight
Figure
N
N
mm
mm
mm
kg
3EL5 096 - 0 L K 2 3 - 4 xxx
3
906
420
320
220
1530
4785
1560
18.2
-
3EL1 096 - 1 P K 2 1 - 4 xxx
1
528
246
1330
930
900
3075
910
16.8
13
3EL2 096 - 2 P J 2 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
32.9
22
3EL2 096 - 2 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
33.4
22
3EL2 096 - 6 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
31.3
22
3EL2 096 - 6 P J 4 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
32.6
22
3EL5 102 - 0 L K 2 3 - 4 xxx
3
906
420
320
220
1530
4785
1560
18.4
-
3EL1 102 - 1 P K 2 1 - 4 xxx
1
528
246
1330
930
900
3075
910
17.5
13
3EL2 102 - 2 P J 2 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
33.4
22
3EL2 102 - 2 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
34.0
22
3EL2 102 - 6 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
31.9
22
3EL2 102 - 6 P J 4 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
33.2
22
3EL5 108 - 0 L K 2 3 - 4 xxx
3
906
420
320
220
1530
4785
1560
18.7
-
3EL1 108 - 1 P K 2 1 - 4 xxx
1
528
246
1330
930
900
3075
910
18.3
13
3EL2 108 - 2 P J 2 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
34.0
22
3EL2 108 - 2 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
34.5
22
3EL2 108 - 6 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
32.6
22
3EL2 108 - 6 P J 4 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
33.9
22
3EL1 111 - 1 P K 2 1 - 4 xxx
1
528
246
1330
930
900
3075
910
19.0
13
3EL1 120 - 1 P H 2 2 - 4 xxx
2
731
340
960
670
1245
4100
1260
22.5
14
3EL2 120 - 2 P J 2 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
35.1
22
3EL2 120 - 2 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
35.6
22
3EL2 120 - 6 P J 3 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
34.5
22
3EL2 120 - 6 P J 4 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
35.2
22
3EL5 126 - 0 L K 2 3 - 4 xxx
3
906
420
320
220
1530
4785
1560
19.4
-
3EL1 132 - 1 P H 2 2 - 4 xxx
2
731
340
960
670
1245
4100
1260
25.7
14
3EL2 132 - 2 P J 2 1 - 4 xxx
1
571
266
3760
2630
1062
3820
985
36.2
22
3EL2 132 - 2 P M 3 1 - 4 xxx
1
676
315
3220
2250
1240
4495
1165
38.8
22
3EL2 132 - 6 P M 3 1 - 4 xxx
1
676
315
3220
2250
1240
4495
1165
37.3
22
3EL2 132 - 6 P M 4 1 - 4 xxx
1
676
315
3220
2250
1240
4495
1165
37.9
22
3EL1 144 - 1 P Q 2 2 - 4 xxx
2
893
340
780
550
1525
5125
1260
26.1
14
3EL2 144 - 2 P M 2 1 - 4 xxx
1
676
315
3220
2250
1240
4495
1165
39.4
22
3EL2 144 - 2 P M 3 1 - 4 xxx
1
676
315
3220
2250
1240
4495
1165
40.5
22
3EL2 144 - 6 P M 3 1 - 4 xxx
1
676
315
3220
2250
1240
4495
1165
38.6
22
3EL2 144 - 6 P M 4 1 - 4 xxx
1
676
315
3220
2250
1240
4495
1165
39.2
22
11
Highest
voltage
for equipment
Rated
voltage
Um
kV
Ur
kV
Uc
kV
LD-CIass
170
138
110
138
110
138
245
300
362
420
550
12
Continuous
Line
operating discharge
voltage
class
Longduration
current
2 ms
Maximum values of the residual voltages at discharge
currents of the following impulses
I
30/60 μs
1 kA
kV
30/60 μs
2 kA
kV
8/20 μs
3 kA
kV
8/20 μs
5 kA
kV
8/20 μs
10 kA
kV
8/20 μs
15 kA
kV
8/20 μs
20 kA
kV
8/20 μs
40 kA
kV
30/60 μs
0.125 kA
kV
30/60 μs
0.5 kA
kV
2
750
282
296
306
2
1100
255
267
273
327
352
377
394
292
311
329
345
450
257
271
391
236
110
3
1100
266
279
285
305
324
351
248
368
417
252
138
110
3
1200
258
270
276
292
311
265
326
342
373
239
138
110
4
1200
275
288
295
311
252
331
348
364
397
255
144
115
2
750
294
308
319
268
341
367
393
411
470
268
144
115
2
1100
266
279
283
285
305
324
343
360
408
246
144
115
3
1100
277
259
291
298
318
338
366
384
435
263
144
115
3
1200
276
269
282
288
305
324
340
356
389
249
144
115
4
262
1200
287
301
308
325
346
363
380
415
266
150
120
280
2
750
306
321
333
356
383
409
428
490
279
150
295
120
2
1100
277
290
297
317
338
358
375
425
257
270
156
125
3
1100
301
315
323
345
367
397
416
472
285
300
156
125
3
1200
291
305
312
330
351
369
386
421
270
284
156
125
4
1200
311
326
333
352
374
393
412
449
288
303
192
154
2
750
392
411
426
455
490
524
548
627
357
377
192
154
2
1100
354
372
380
406
432
458
480
544
328
346
192
154
3
1100
370
388
397
424
451
488
511
581
350
369
192
154
3
1200
359
376
384
406
432
454
475
518
333
350
192
154
4
1200
382
401
410
433
461
484
507
553
355
373
198
158
2
1100
365
383
392
419
446
472
495
561
339
356
198
158
3
1100
382
400
409
437
465
504
527
599
361
380
198
158
3
1200
370
388
396
419
446
468
490
535
343
361
198
158
4
1200
394
413
423
447
475
499
523
570
366
385
228
182
2
1100
421
441
451
482
513
544
569
646
390
410
228
182
3
1100
439
461
472
504
536
580
607
689
416
438
228
182
3
1200
426
446
457
482
513
539
564
616
395
416
228
182
4
1200
454
476
487
514
547
575
602
657
421
443
228
182
2
1100
421
441
451
482
513
544
569
646
390
410
228
182
3
1100
439
461
472
504
536
580
607
689
416
438
228
182
3
1200
426
446
457
482
513
539
564
616
395
416
228
182
4
1200
454
476
487
514
547
575
602
657
421
443
240
192
2
1100
443
464
475
508
540
572
599
680
410
432
240
192
3
1100
462
485
496
530
564
611
639
726
438
461
240
192
3
1200
448
470
481
508
540
567
594
648
416
437
240
192
4
1200
478
501
513
541
576
605
634
691
444
467
276
276
288
221
221
230
3
4
3
1200
1200
1200
515
550
538
540
576
564
553
590
577
584
623
609
621
662
648
652
696
680
683
729
713
745
795
778
478
510
499
503
537
525
288
230
4
1200
574
601
615
650
691
726
760
829
532
560
336
269
3
1100
647
679
695
742
790
855
895
1016
613
645
336
269
3
1200
627
658
673
711
756
794
832
907
582
612
336
269
4
1200
669
702
718
758
806
847
887
968
621
653
360
288
3
1100
694
728
744
795
846
916
959
1089
657
691
360
288
3
1200
672
705
721
761
810
851
891
972
624
656
360
288
4
1200
717
752
769
812
864
907
950
1037
665
700
420
336
4
1200
837
877
897
948
1008
1058
1109
1210
776
816
Arrest er type
Number
of units
Housing
insulation
Specified Specified Grading
short-term long-term ring diamload SSL load SLL
eter
(Fdyn)
(Fstat)
[D]
Lightning impulse Power frequency
withstand voltage withstand voltage
1.2/50 μs
1 min. wet
kV
kV
N
N
Height
(H)
Creepage Flashover
distance distance
Weight
mm
mm
mm
kg
Figure
3EL1 138 - 1 P Q 2 2 - 4 xxx
2
893
340
780
550
-
1525
5125
1260
25.9
14
3EL2 138 - 2 P M 2 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
38.8
22
3EL2 138 - 2 P M 3 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
39.4
22
3EL2 138 - 6 P M 3 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
37.9
22
3EL2 138 - 6 P M 4 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
38.6
22
3EL1 144 - 1 P Q 2 2 - 4 xxx
2
893
340
780
550
-
1525
5125
1260
26.1
14
3EL2 144 - 2 P M 2 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
39.4
22
3EL2 144 - 2 P M 3 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
40.5
22
3EL2 144 - 6 P M 3 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
38.6
22
3EL2 144 - 6 P M 4 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
39.2
22
3EL1 150 - 1 P Q 2 2 - 4 xxx
2
893
340
780
550
-
1525
5125
1260
26.5
14
3EL2 150 - 2 P M 2 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
39.9
22
3EL2 156 - 2 P M 3 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
41.6
22
3EL2 156 - 6 P M 3 1 - 4 xxx
1
676
315
3220
2250
-
1240
4495
1165
39.9
22
3EL2 156 - 6 P P 4 2 - 4 xxx
2
806
375
2590
1810
-
1544
5290
1390
48.4
-
3EL1 192 - 1 P K 2 2 - 4 xxx
2
1056
492
660
460
-
1805
6150
1519
30.9
14
3EL2 192 - 2 P Q 2 2 - 4 xxx
2
936
436
2260
1580
-
1767
6160
1615
54.8
-
3EL2 192 - 2 P Q 3 2 - 4 xxx
2
936
436
2260
1580
-
1767
6160
1615
55.4
-
3EL2 192 - 6 P Q 3 2 - 4 xxx
2
936
436
2260
1580
-
1767
6160
1615
52.9
-
3EL2 192 - 6 P Q 4 2 - 4 xxx
2
936
436
2260
1580
-
1767
6160
1615
54.2
-
3EL2 198 - 2 P Q 2 2 - 4 xxx
2
936
436
2260
1580
-
1767
6160
1615
55.4
-
3EL2 198 - 2 P Q 3 2 - 4 xxx
2
936
436
2260
1580
-
1767
6160
1615
55.9
-
3EL2 198 - 6 P Q 3 2 - 4 xxx
2
936
436
2260
1580
-
1767
6160
1615
53.6
-
3EL2 198 - 6 P J 4 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
58.5
23
3EL2 228 - 2 P J 2 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
62.3
23
3EL2 228 - 2 P J 3 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
63.4
23
3EL2 228 - 6 P J 3 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
60.5
23
3EL2 228 - 6 P W 4 2 - 4 xxx
2
1247
581
1730
1210
800
2302
8315
1750
63.2
23
3EL2 228 - 2 P J 2 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
62.3
23
3EL2 228 - 2 P J 3 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
63.4
23
3EL2 228 - 6 P J 3 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
60.5
23
3EL2 228 - 6 P W 4 2 - 4 xxx
2
1247
581
1730
1210
800
2302
8315
1750
63.2
23
3EL2 240 - 2 P J 2 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
63.4
23
3EL2 240 - 2 P J 3 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
64.5
23
3EL2 240 - 6 P J 3 2 - 4 xxx
2
1142
532
1880
1310
800
2124
7640
1585
61.7
23
3EL2 240 - 6 P W 4 2 - 4 xxx
2
1247
581
1730
1210
800
2302
8315
1750
65.2
23
3EL2 276 - 6 P W 3 2 - 4 xxx
3EL2 276 - 6 P M 4 2 - 4 xxx
3EL2 288 - 6 P M 3 2 - 4 xxx
2
2
2
1247
1352
1352
581
629
629
1730
1610
1610
1210
1120
1120
800
800
800
2302
2480
2480
8315
8990
8990
1750
1925
1925
67.1
70.5
69.9
23
23
23
3EL2 288 - 6 P M 4 2 - 4 xxx
2
1352
629
1610
1120
800
2480
8990
1925
71.8
23
3EL2 336 - 2 P J 3 3 - 4 xxx
3
1713
798
1250
870
1200
3186
11460
2506
90.7
24
3EL2 336 - 6 P J 3 3 - 4 xxx
3
1713
798
1250
870
1200
3186
11460
2506
86.4
24
3EL2 336 - 6 P J 4 3 - 4 xxx
3
1713
798
1250
870
1200
3186
11460
2506
88.3
24
3EL2 360 - 2 P J 3 3 - 4 xxx
3
1713
798
1250
870
1200
3186
11460
2506
93.4
24
3EL2 360 - 6 P J 3 3 - 4 xxx
3
1713
798
1250
870
1200
3186
11460
2506
89.0
24
3EL2 360 - 6 L M 4 3 - 4 xxx
3
2028
945
1070
750
1200
3720
13485
2960
96.1
-
3EL2 420 - 6 L M 4 3 - 4 xxx
3
2028
945
1070
750
1200
3720
13485
2960
116.0
13
Always the right housings.
3EL5
Fig. 51
3EL1
Fig. 52
Fig. 53
Fig. 54
Fig. 11
Fig. 12
Fig. 13
Fig. 14
3EL2
Fig. 21
14
Fig. 22
Fig. 23
Fig. 24
80
80
40
40
50
40
40
80
50
50
80
50
Line terminals
14
14
3EL5xxx-xxxxx-xYxx
DIN/NEMA Flat terminal
3EL1xxx-xxxxx-xYxx
DIN/NEMA Flat terminal
100
50
Ø30
114
80
M10
50
40
40
14
3EL2xxx-xxxxx-xAxx
Metal plate
(connection with cable eye)
3EL2xxx-xxxxx-xDxx
Terminal stud
3EL2xxx-xxxxx-xYxx
DIN/NEMA Flat terminal
Other line terminals on request
15
Installation and grounding
3EL5/1xxx-xxxxx-xxx1
60
44.5
Ø200-254
3 mounting holes (Ø 14 mm),
for 3 x M12 bolts,
bolt circle 200–254 mm,
(8.75”–10”)
for insulated installation
Ø13 (3x)
3EL5/1xxx-xxxxx-xxx5
60
Ø13 (3x)
44.5
Ø200-254
Ø13 (3x)
16
3 mounting holes (Ø 14 mm),
for 3 x M12 bolts,
bolt circle 200–254 mm,
(8.75”–10”)
for directly grounded installation
Installation and grounding
3EL2xxx-xxxxx-xxx0
99
4 mounting holes (Ø 12 mm),
for 4 x M10 bolts,
hole distance 99 mm x 99 mm
for directly grounded installation
M10 (4x)
Ø140
99
3EL2xxx-xxxxx-xxx1
3 mounting holes (Ø 14 mm),
for 3 x M12 bolts,
hole distance 200 mm–276 mm
circle
for insulated installation
120°
6
0
7
Ø2
0
Ø2
14
.5
44
60
M12
M12 (3x)
M12 (3x)
3EL2xxx-xxxxx-xxx2
260
60
4 mounting holes (Ø 18 mm),
for 4 x M16 bolts,
hole distance 200 mm x 200 mm
for insulated installation
30
10
70
44.5
200
M16 (4x)
200
M16 (4x)
260
3EL2xxx-xxxxx-xxx3
4 mounting holes (Ø 22 mm),
for 4 x M20 bolts,
hole distance 310 mm x 310 mm
for insulated installation
30
12
72
44.5
60
310
M20 (4x)
380
M12
310
M20 (4x)
380
3EL2xxx-xxxxx-xxx5
120°
00
Ø2
76
Ø2
M12
14
M12 (3x)
44
.5
3 mounting holes (Ø 14 mm),
for 3 x M12 bolts,
hole distance 200 mm–276 mm
circle (8.75”–10.85”)
for grounded installation
60
M12
17
Control devices for surge arresters
These control devices can be connected to all shown surge arresters in this catalogue.
ACM basic
ACM advanced
Arrester condition monitor (ACM) basic
Order Number: 3EX5080-0
Arrester condition monitor (ACM) advanced
Order Number: 3EX5080-1
Order Number: 3EX5085 (USB wireless module)
Arrester condition indicator (ACI)
The arrester condition indicator shows the
arrester status at a glance. Its easy-to-understand
“traffic light” visualization is based on a 3rdharmonic-evaluation of the leakage current.
Order Number: 3EX5070
Surge counter
Surge counter with
leakage current meter
Surge counter
Order Number: 3EX5030
Surge counter with leakage current meter
Order Number: 3EX5050
Sensor
Display
Sensor
Order Number: 3EX5060
Display
Order Number: 3EX5062
Up to 200 m
Connecting lead*
Order Number: 3EX5963-xx
Control spark gap
To estimate the current that flows through the
surge arrester in case of an overvoltage and to
count the surges.
Order Number: 3EX6040
LCM II
LCM II, system for live condition check of
metal oxide surge arresters
*Required for operation
Available in different lengths
18
Order Number (example)
Silicone rubber-housed surge arrester cage design
Surge arrester model
Bending moment 1.2 kNm
Bending moment 4 kNm
Bending moment 0.5 kNm
Rated voltage in kV
–
Long-duration current max. values
550 A
750 A
1100 A
1200 A
3 E L 2 120 – 2 P M 3 2 – 4 D A 1
3 E L
1
2
5
120
–
0
1
2
6
Application
Phase surge arrester
Neutral point surge arrester
Transmission line surge arrester
Housing size of single unit
Line discharge class
LD 2
LD 3
LD 4
P
S
L
M
2
3
4
Number of units
1 unit
2 units
3 units
–
Form of sheds
1
2
3
–
Alternating sheds
4
High-voltage terminal
Metal plate (connection with cable eye)
Bolt, 30 mm diameter, 80 mm long, stainless steel
DIN/NEMA Flat, 100 mm x 100 mm, stainless steel
A
D
Y
Name plate
German / English (IEC)
English (ANSI)
Other languages
A
H
Z
Mounting
Not insulated, 99 mm x 99 mm, M10 (only 3EL2)
3-hole, insulated, Ø 200–276 mm / Ø 8.75 “–10.85 “, M12 (3EL2) Ø 200–254 mm / Ø 8.75 “ – 10.00“, M12 (3EL1 / 3EL5)
4-hole, insulated, 200 mm x 200 mm, M16 (only 3EL2)
4-hole, insulated, 310 x 310 mm, M20 (only 3EL2)
Not insulated, Ø 200–276 mm / Ø 8.75 ”–10.85 ”, M12 (3EL2), Ø 200–254 mm / Ø 8.75 ”–10.00 ”, M12 (3EL1 / 3EL5)
0
1
2
3
5
The top row in table 3 shows an example of the
build-up of our order numbers.
Not all combinations are possible.
19
Published by and copyright © 2010:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Siemens AG
Energy Sector
Power Transmission Division
High Voltage Products
Nonnendammallee 104
13629 Berlin, Germany
www.siemens.com/energy/arrester
For more information, please
contact us at:
Phone: +49 30 386 33 222
Fax:
+49 30 386 26 721
E-Mail: arrester@siemens.de
Power Transmission Division
Order No. E50001-G630-A142-X-4A00
Printed in Germany
Dispo 30002
fb 2410 471303 WS 0610X.X
Printed on elementary chlorine-free
bleached paper.
All rights reserved.
Trademarks mentioned in this document
are the property of Siemens AG, its affiliates,
or their respective owners.
Subject to change without prior notice.
The information in this document contains
general descriptions of the technical options
available, which may not apply in all cases.
The required technical options should therefore
be specified in the contract.
www.siemens.com/energy