20 YEAR MAX GUARANTEE DIAGRAM #1 CUT-IN REGLETS 1" MIN. DEEP SEALED WITH M-BOND ADHESIVE ON BOTH SIDES PRESATURATE EDGE OF TOPCOAT R FLASHING FABRIC IN MAJORSEALTM LIQUID FLASHING AND TUCK INTO JOINT COUNTERFLASHINGS BY OTHERS TOPCOAT R FLASHING FABRIC TARGET APPLIED OVER SCUPPER FABRIC ON BOTH SIDES. SEE DIAGRAM 1 TOPCOAT R FLASHING FABRIC INSIDE SCUPPER TO EXTEND OUT OPENING ON BOTH ENDS. SEE DIAGRAM 1 OVERLAP TOPCOAT R FLASHING FABRIC 2" MIN. INSIDE SCUPPER SURFACE GRANULES APPLIED TO TOP LAYER OF MAJORSEALTM LIQUID FLASHING TOPCOAT R FLASHING FABRIC BASE LAYER OF MAJORSEALTM LIQUID FLASHING GAF SBS MODIFIED BITUMEN OR BUILT-UP GRANULE SHEET. 2" MIN. 2" MIN. NOTE: 1. IF GAF GRANULE MEMBRANE IS LEFT EXPOSED OVERNIGHT BEFORE INSTALLING MAJORSEAL TMLIQUID FLASHING, A TEMPORARY NIGHT SEAL MUST BE INSTALLED. THE NIGHT SEAL MUST BE COMPLETELY REMOVED BEFORE INSTALLING THE FLASHING. R TM MAJORSEAL LIQUID FLASHING 1 Campus Drive. Parsippany, NJ 07054 WALL & CURB SERIES FIELD FABRICATED THRU WALL SCUPPER FLASHING DETAIL DRAWING # SYSTEM 323 MM SCALE N.T.S. ISSUE/ REVISION DATE 1-1-16