Customer Case Study Improving Telecommunications Density and Efficiency

advertisement
Business-Critical Continuity™
for Telecommunications
Customer Case Study
Improving Telecommunications Density and Efficiency
Less Energy, Less Real Estate, More Bandwidth
The need to meet subscriber demand for sophisticated multimedia services and support a converging IP network while still reducing their cost per bit led this European
operator to seek out an expert infrastructure solution that would increase their central
office datacenter and core site density by 150%, power and cooling capacity by 100%,
and efficiency by more than 20%. The client wanted a formula that could be implemented and verified once, then replicated to rapidly consolidate their numerous
regional data centers.
Specific requirements were:
n Keep the site live without any service interruptions throughout implementation
n Design a solution to that could enable the operator to cut the number of their
data centers by 50%, without footprint expansion at the remaining sites
CLIENT BUSINESS
Global Telecommunications Provider
European Operating Company
CLIENT RELATIONSHIP
Over 20 years
THE NEED
In order to meet subscriber demand for
multimedia technologies, this service provider
needed 2X the power and cooling capacity of
their regional data centers in the same footprint.
THE SOLUTION
Emerson Network Power implemented IT and
power distribution racks, chilled water cooling
system with in-line cooling, and highly efficient
DC power systems with remote monitoring to
increase the power and cooling capacity of the
site, improve overall site efficiency and meet
the client’s demand for zero downtime.
THE BENEFIT
n Strategically reorganized layout for growth
n 150% density increase
n 27% PUE improvement
n Replicable model for other sites
n >100% power & cooling capacity
improvement
n 26% reduction in OpEx*
n 20% reduction in needed CapEx*
KEY COMPONENTS
nKnürr ® IT and power distribution racks
nLiebert® chilled water cooling system
n AC and DC battery backup systems
nNetSure™ DC power systems and inverters
nENEC ™ metering and remote monitoring
nNetPerform™ interdisciplinary project
management and consulting team
EN601CRA-EUOPCO / 0912
n Improve site PUE and density
n Increase power and cooling capacity from ~400W/m2 to 1000W/m2 average and
up to 2000W/m2 in dedicated high density sections
n Enhance equipment layout to minimize hot spot issues and conflicting air flows
n Redesign existing site layout to accommodate future network equipment
n Improve energy efficiency to reduce CO2 emissions and operating costs
A Holistic Approach to Improving Site Efficiency
Emerson Network Power determined that a holistic approach was required to achieve
the customer’s objectives. The operator needed to simplify the layout of their equipment while improving the integration of their DC and AC power systems, cooling and
battery backup, and leverage metering and remote monitoring as well.
A comprehensive site audit by Emerson Network Power’s team of expert engineers laid
the foundation for discussions and the ultimate execution plan. The telecom/ICT
equipment would be separated into high/low heat density zones to accommodate cold
aisle containment and the ICT rack infrastructure. The DC and AC power plants would
be upgraded to increase redundancy and moved to a dedicated power and battery
room, improving efficiency and allowing for future growth. Real time monitoring and
reporting were also identified as critical to long-term site health and optimization. The
operating company agreed and plan execution began.
Emerson Network Power rapidly assembled the project team to perform detailed site
assessments, design work and assist the customer with proper equipment selection.
The final package included:
nNetPerform™ site assessment and design engineering services
n Knürr Miracel® IT server racks with integrated Liebert® MPX A+B
monitored and controlled power distribution units
nLiebert® HPC and HPM chilled water cooling system
with >1MW capacity, n+1 redundancy, free cooling
operation, smart aisle control/regulation, high
performance room cooling units with EC fans
n In-the-aisle Liebert® CRV cooling units and intelligent
iCOM control loop for smart inter working of system
1
Customer Case Study
n Redundant (1+1) 48V NetSure™ DC power system of 336kW capacity
with NetSure™ DC distribution system and 1 hour battery backup
n 400/230V inverter system providing 2 x 225kVA of uninterruptible AC power with 1 hour battery backup
nKnürr® cold aisle containment for hot/cold air separation and vast efficiency boost
nENEC ™ energy management system to monitor utility AC supply, AC distribution (on each branch
level), NetSure™ DC power and distribution system, inverter and distribution system, cooling system,
individual PDUs and ambient site temperature
nNetPerform™ implementation, startup and commissioning services and equipment training
Moving forward, Emerson Network Power can easily perform advanced tuning and optimization services
as well as ongoing site maintenance and support to this customer.
High Density Site Solution
By implementing the recommended high density solution, all targeted KPIs were met by the operator:
elimination of hot spots, increased energy efficiency, reduction of floor space, and flexibility for future
expansion and consolidation of sites. In addition, the capital expenditure required to fulfill future expansion
was reduced by over 20% compared to the customer’s expected, traditional technologies.
KPIs Achieved
Metric
Annual Average PUE
Datacenter Density
(Power & Cooling Capacity)
Existing Site/Technologies
2.03
2
~400W/m
With Emerson Network Power
1.49 — 27% improvement
(with facility restrictions & critical legacy equipment)
1.3 proposed (if facility restrictions were eliminated)
1000W/m2 average, up to 2000W/m2
for high density — >100% improvement
Capital Expenditure
to Achieve Goals
$3.6M
$2.8M — 20% reduction
Payback Period
N/A
<2 Years*
*Compared to fulfilling network demands using existing site and technologies.
Emerson Network Power was able to improve overall site efficiency by 27%. Without disrupting service to
subscribers, the power and cooling capacity of the data center was nearly tripled. Floor space was strategically reorganized to accommodate future network equipment and growth. Finally, the site has provided a
blueprint for achieving the customer’s goal of 50% reduction in number of sites across their network.
Meeting the Telecom Energy Needs of Tomorrow
Emerson Network Power’s holistic site solution approach has helped solve similar challenges in other
central office and critical-node MSC/MTSO environments. Our engineering experts consolidate existing
equipment at the site, integrate high density network elements like blade servers, and improve overall
site efficiency to help telecommunications service providers keep pace with the growing energy needs
required by the multimedia technologies their customers demand. With Emerson Network Power, our
customers can Consider It Solved ™.
EmersonNetworkPower.com/EnergySystems (North America)
EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power Energy Systems North America 2012.
Business-Critical Continuity™, Emerson Network Power™, the Emerson Network Power logo, Emerson® and Consider it Solved are service marks and trademarks of Emerson Electric Co.
EnergyMaster™, eSure™, NetPerform™, NetReach™, NetSpan™, NetSure® and NetXtend™ are trademarks of Emerson Network Power Energy Systems North America.
2
EN601CRA-EUOPCO / 0912
Download